EE0214 Acoustic Noise Measurements of Air Source Heat Pumps Building Performance Centre Analysis of Measurements: 418 Central Buchan Institute for Sustainable Construction, Edinburgh Napier University Page 62 Directivity 5.3.15. Table 5-3 shows the directivity in noise emissions from the unit by comparing the noise levels at the different microphones, for a typical period of ASHP operation. Table 5-3: Directivity Analysis of the ASHP Noise Emissions L Aeq(1min) dB 418 Central Buchan, normal operation Microphone Location Front Left Right Above Typical Microphone Level 57 55 56 54 Change from front microphone - -2 -1 -3 5.3.16. It is seen that the ASHP is slightly directional to the front of the unit. Frequency analysis 5.3.17. For the frequency analysis, a Fast Fourier Transform (FFT) of the signal was performed, averaged over a representative one minute period at a frequency resolution of 2 Hz. The resulting frequency spectrum for the ASHP operating under normal conditions is given in Figure 5-22, with that for the defrost cycle presented in Figure 5-23.

Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 418 Central Buchan Institute for Sustainable Construction, Edinburgh Napier University Page 62

Directivity

5.3.15. Table 5-3 shows the directivity in noise emissions from the unit by comparing

the noise levels at the different microphones, for a typical period of ASHP

operation.

Table 5-3: Directivity Analysis of the ASHP Noise Emissions LAeq(1min) dB 418 Central Buchan, normal operation

Microphone Location Front Left Right Above

Typical Microphone Level 57 55 56 54

Change from front microphone - -2 -1 -3

5.3.16. It is seen that the ASHP is slightly directional to the front of the unit.

Frequency analysis

5.3.17. For the frequency analysis, a Fast Fourier Transform (FFT) of the signal was

performed, averaged over a representative one minute period at a frequency

resolution of 2 Hz. The resulting frequency spectrum for the ASHP operating

under normal conditions is given in Figure 5-22, with that for the defrost cycle

presented in Figure 5-23.

Page 2: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 418 Central Buchan Institute for Sustainable Construction, Edinburgh Napier University Page 63

Figure 5-22. 418 Central Buchan, Sound Pressure Level Spectrum (Normal Operation)

Figure 5-23. 418 Central Buchan, Sound Pressure Level Spectrum (Defrost Cycle)

10

20

30

40

50

60

70

20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500

Soun

d Pr

esuu

re L

evel

(dB)

Frequency (Hz)

Figure X: FFT - normal operation, New Pitsligo

10

20

30

40

50

60

70

20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500

Soun

d Pr

esuu

re L

evel

(dB)

Frequency (Hz)

Figure X: FFT - defrost cycle, North Pitblae 1

Page 3: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 418 Central Buchan Institute for Sustainable Construction, Edinburgh Napier University Page 64

5.3.18. Tonal analysis of the frequency spectra shown in Figure 5-22 and Figure 5-23

has been undertaken in accordance with the Joint Nordic Method (v2). The

resulting tonal assessments are presented in Figure 5-23 and Figure 5-24,

showing that the tones identified within the spectrum for normal operation would

lead to a 2 dB tonal penalty. During the defrost cycle, the tonal assessment

indicates that a 6 dB tonal penalty would be appropriate.

104 158 210 262 294 390

0

10

20

30

40

50

60

70

20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500

A-w

eigh

ted

Soun

d Pr

esuu

re L

evel

(dB

A)

Frequency (Hz)

Figure X:Tonal assessment (JNM2)normal operation, New Pitsligo

Critical bandNoiseNoise PauseTones

Tone level, Lpt =Masking noise level, Lpn =

Tone audibility, ΔLta =

Tone penalty, k =

dBAdBAdBA

dBA

42.438.46.1

2.1

Overall level, Lpa =

Tone corrected level =

dBA

dBA

57.0

59.1

Figure 5-24. 418 Central Buchan Tonal Assessment (Normal Operation)

Page 4: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 418 Central Buchan Institute for Sustainable Construction, Edinburgh Napier University Page 65

Sound Power Level calculations

5.3.19. Figure 5-8 presents a statistical analysis plot of the percentage of time that a

specific sound power level would be recorded, when the ASHP is under

operation. This assumes that the ASHP is located in the common mounting

scenario as detailed in Section 3.42, which is not necessarily representative of

the actual measured condition.

50 100 148 198 246 296 344 394 444 492

0

10

20

30

40

50

60

70

20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500

A-w

eigh

ted

Soun

d Pr

esuu

re L

evel

(dB

A)

Frequency (Hz)

Figure X:Tonal assessment (JNM2)defrost cycle, New Pitsligo

Critical bandNoiseNoise PauseTones

Tone level, Lpt =Masking noise level, Lpn =

Tone audibility, ΔLta =

Tone penalty, k =

dBAdBAdBA

dBA

43.331.813.6

6.0

Overall level, Lpa =

Tone corrected level =

dBA

dBA

52.0

58.0

Figure 5-25. 418 Central Buchan Tonal Assessment (Defrost Cycle)

Page 5: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 418 Central Buchan Institute for Sustainable Construction, Edinburgh Napier University Page 66

Figure 5-26. 418 Central Buchan, Sound Power Level Statistical Analysis

5.3.20. The chart indicates that noise from the ASHP during operation will have a 90%

certainty of being within around 1 dB of LWA 68 dB.

5.3.21. Use of Equation 1 leads to an estimation that noise levels from the unit

operating normally would drop to LAeq 42 dB at a distance separation of

approximately 11 m. If a tonal penalty were to be included, then this distance

would rise to around 14 m.

Discussion

5.3.22. Whilst the manufacturer has not provided us with detailed information on the fan

and compressor speeds, analysis of the ASHP noise data suggests that the fan

speed was 790 rpm, and included four fan blades. The fan configuration

corresponds with a blade passing frequency of 53 Hz, with second, third and

fourth harmonics at 104, 158 and 210 Hz respectively. The compressor was of

a scroll type with an unknown speed. Analysis of the defrost cycle frequency

0

10

20

30

40

50

60

70

80

90

100

60 62 64 66 68 70 72 74 76

Perc

entil

e, %

LWA (dB)

Page 6: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 418 Central Buchan Institute for Sustainable Construction, Edinburgh Napier University Page 67

spectrum suggests however that the primary tone is at around 50Hz, which

corresponds with a rotational speed of 3000 rpm, typical for this type of

compressor. Harmonics of this tone are seen at multiple frequencies in the

spectrum, as displayed in the FFT analysis charts for the defrost cycle.

5.3.23. During normal operation, the fan contributes a greater amount of noise than the

compressor, although tonal content provided by the compressor is audible.

Page 7: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Original) Institute for Sustainable Construction, Edinburgh Napier University Page 68

5.4 422 Fraserburgh (Original ASHP)

Site description

5.4.1. The property is located in a rural area off a quiet road. The ASHP is located to

the side of the brick built single story detached property. The unit is seated on

concrete paving slab footings.

5.4.2. This section details the results for the original ASHP that was subsequently

replaced, the results of which will be presented separately.

5.4.3. Subjectively the unit appeared to be operating normally with no audible rattle,

resonance or fault.

Equipment set up

5.4.4. The 9 Channel PULSE system was used at this site.

5.4.5. The ASHP was located on reflective ground, and in front of a reflective wall.

5.4.6. Accelerometers were fixed to the footings and to the wall surface immediately

behind the unit, as shown in Picture 5-10. The accelerometers were fixed to the

surfaces using cyanoacrylate cement.

Page 8: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Original) Institute for Sustainable Construction, Edinburgh Napier University Page 69

Picture 5-10. 422 Fraserburgh (Original), Footing and Wall-mounted Accelerometers

5.4.7. The microphones were mounted on heavy-duty tripods as shown in Picture 5-11

and Picture 5-12. All microphones were positioned 1 m from the ASHP casing.

Picture 5-11. 422 Fraserburgh, Original ASHP and Microphone Arrangement

Page 9: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Original) Institute for Sustainable Construction, Edinburgh Napier University Page 70

Picture 5-12. 422 Fraserburgh, Original ASHP and Microphone Arrangement

Measurement Results

5.4.8. The results given by the energy measurements were found to be erroneous for

the per-minute logging. The logging data has therefore been used from the

alternative per-five-minute logging system.

5.4.9. Figure 5-27 presents the LAeq(1min) measured noise levels at the microphone 1m

in front of the unit set against time, along with the per-five-minute logged ASHP

power consumption.

Page 10: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Original) Institute for Sustainable Construction, Edinburgh Napier University Page 71

Figure 5-27. 422 Fraserburgh (Original ASHP), Sound Pressure Level and Power Consumption vs Time

5.4.10. The PULSE system stopped recording on two occasions and had to be reset.

5.4.11. The data highlights that the ASHP is cycling on and off approximately every two

hours, consistently throughout the day and night-time periods. Throughout the

measurement period, the ASHP was operational for approximately 29% of the

time.

5.4.12. The trace clearly shows the increase in measured noise level during periods

when the ASHP is operating.

Measurement Analysis

5.4.13. Figure 5-28 presents a scatter diagram showing the noise levels against the

power consumption, for the periods when the ASHP was operating. It is seen

that the sound pressure level has no dependence on the power output of the

ASHP.

0

1000

2000

3000

4000

5000

6000

7000

8000

0

10

20

30

40

50

60

70

80

11/02/11 11/02/11 12/02/11 12/02/11 13/02/11 13/02/11 14/02/11 14/02/11 15/02/11 15/02/11 16/02/11

Pow

er (W

)

L Aeq

(1m

in)

(dB)

Date/Time

SPL

Power

Page 11: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Original) Institute for Sustainable Construction, Edinburgh Napier University Page 72

Figure 5-28. 422 Fraserburgh (Original ASHP), Sound Pressure Level vs Power Consumption

5.4.14. Figure 5-29 presents a statistical analysis plot of the percentage of time that a

specific noise level would be recorded, when the ASHP is under operation.

From this confidence intervals can be presented for the typical noise levels.

48

50

52

54

56

58

60

62

0 500 1000 1500 2000 2500 3000 3500 4000 4500

L Aeq

(1m

in)(

dB)

Power (W)

Page 12: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Original) Institute for Sustainable Construction, Edinburgh Napier University Page 73

Figure 5-29. 422 Fraserburgh (Original ASHP), Sound Pressure Level Statistical Analysis

5.4.15. The chart indicates that noise from the ASHP during operation will have a 90%

certainty of being within around 1.5 dB of LAeq(1min) 56 dB. The corresponding

total ASHP noise dose over the whole assessment period is calculated as

LAeq(1week) 51 dB.

Defrost Cycle

5.4.16. Analysis of the measurements revealed that defrost cycles are part of the ASHP

operation. During these periods, which can last for 3 to 4 minutes, the

compressor is operating in reverse, without the fan. The average sound

pressure level during a typical defrost cycle is around LAeq(1min) 54 dB.

0

10

20

30

40

50

60

70

80

90

100

48 50 52 54 56 58 60 62 64

Perc

entil

e, %

LAeq(1min) (dB)

Page 13: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Original) Institute for Sustainable Construction, Edinburgh Napier University Page 74

Directivity

5.4.17. Table 5-4 shows the directivity in noise emissions from the unit by comparing

the noise levels at the different microphones, for a typical period of ASHP

operation.

Table 5-4: Directivity Analysis of the ASHP Noise Emissions LAeq(1min) dB 422 Fraserburgh (Original ASHP), normal operation

Microphone Location Front Left Right Above

Typical Microphone Level 56 54 56 52

Change from front microphone - -2 0 -4

5.4.18. It is seen that the ASHP exhibits a slight directivity, such that noise is greater in

line with the fan, and on the side nearest the compressor (i.e. the right hand

side for this ASHP).

Frequency analysis

5.4.19. For the frequency analysis, a Fast Fourier Transform (FFT) of the signal was

performed, averaged over a representative one minute period at a frequency

resolution of 2 Hz. The resulting frequency spectrum for the ASHP operating

under normal conditions is given in Figure 5-30, with that for the defrost cycle

presented in Figure 5-31.

Page 14: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Original) Institute for Sustainable Construction, Edinburgh Napier University Page 75

Figure 5-30. 422 Fraserburgh (Original ASHP), Sound Pressure Level Spectrum (Normal Operation)

Figure 5-31. 418 Fraserburgh (Original ASHP), Sound Pressure Level Spectrum (Defrost Cycle)

10

20

30

40

50

60

70

20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500

Soun

d Pr

esuu

re L

evel

(dB)

Frequency (Hz)

g p ,

10

20

30

40

50

60

70

20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500

Soun

d Pr

esuu

re L

evel

(dB)

Frequency (Hz)

Page 15: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Original) Institute for Sustainable Construction, Edinburgh Napier University Page 76

5.4.20. Tonal analysis of the frequency spectra shown in Figure 5-30 and Figure 5-31

has been undertaken in accordance with the Joint Nordic Method (v2). The

resulting tonal assessments are presented in Figure 5-31 and Figure 5-32,

showing that the tones identified within the spectrum for normal operation would

lead to a 5 dB tonal penalty. During the defrost cycle, the tonal assessment

indicates that a 6 dB tonal penalty would be appropriate.

68 100108 162 216 392 442

0

10

20

30

40

50

60

70

20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500

A-w

eigh

ted

Soun

d Pr

esuu

re L

evel

(dBA

)

Frequency (Hz)

Figure X:Tonal assessment (JNM2)normal operation, North Pitblae 1

Critical bandNoiseNoise PauseTones

Tone level, Lpt =Masking noise level, Lpn =

Tone audibility, ΔLta =

Tone penalty, k =

dBAdBAdBA

dBA

43.536.29.3

5.3

Overall level, Lpa =

Tone corrected level =

dBA

dBA

56.0

61.3

Figure 5-32. 422 Fraserburgh Tonal Assessment, Original ASHP (Normal Operation)

Page 16: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Original) Institute for Sustainable Construction, Edinburgh Napier University Page 77

Sound Power Level calculations

5.4.21. Figure 5-34 presents a statistical analysis plot of the percentage of time that a

specific sound power level would be recorded, when the ASHP is under

operation.

50 100 148 198 246 300 324 350 396 446 496

0

10

20

30

40

50

60

70

20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500

A-w

eigh

ted

Soun

d Pr

esuu

re L

evel

(dBA

)

Frequency (Hz)

Figure X:Tonal assessment (JNM2)defrost cycle, North Pitblae 1

Critical bandNoiseNoise PauseTones

Tone level, Lpt =Masking noise level, Lpn =

Tone audibility, ΔLta =

Tone penalty, k =

dBAdBAdBA

dBA

47.527.022.5

6.0

Overall level, Lpa =

Tone corrected level =

dBA

dBA

54.0

60.0

Figure 5-33. 422 Fraserburgh Tonal Assessment, Original ASHP (Defrost Cycle)

Page 17: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Original) Institute for Sustainable Construction, Edinburgh Napier University Page 78

Figure 5-34. 422 Fraserburgh (Original ASHP), Sound Power Level Statistical Analysis

5.4.22. The chart indicates that noise from the ASHP during operation will have a 90%

certainty of being within around 2 dB of LWA 67 dB.

5.4.23. Use of Equation 1 leads to an estimation that noise levels from the unit

operating normally would drop to LAeq 42 dB at a distance separation of

approximately 10 m. If a tonal penalty were to be included, then this distance

would rise to around 18 m. This assumes that the ASHP is located in the

common mounting scenario as detailed in Section 3.42, which is not necessarily

representative of the actual measured condition.

Vibration

5.4.24. An FFT analysis of the vibration levels recorded for normal operation of the

ASHP is shown in Figure 5-35. The overall weighted peak vibration level at the

wall surface was 0.0035 ms-2, significantly below the average perception

threshold for whole-body vibration.

0

10

20

30

40

50

60

70

80

90

100

60 62 64 66 68 70 72 74 76

Perc

entil

e, %

LWA (dB)

Page 18: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Original) Institute for Sustainable Construction, Edinburgh Napier University Page 79

Figure 5-35. 422 Fraserburgh (Original ASHP), Vibration Levels

Discussion

5.4.25. Whilst the manufacturer has not provided us with detailed information on the fan

and compressor speeds, inspection of the results and experience of similar

units suggest that the fan speed was around 810 rpm, and included four fan

blades. This fan configuration corresponds with a blade passing frequency of

54 Hz, with second and third harmonics at 108 and 162 Hz respectively. These

effects are seen prominently in the frequency spectrum for normal operation.

The compressor was of a scroll type with an unknown speed. Analysis of the

defrost cycle frequency spectrum suggests however that the primary tone is at

around 50Hz, which corresponds with a rotational speed of 3000 rpm, typical for

this type of compressor. Harmonics of this tone are seen at multiple

frequencies in the spectrum.

0

20

40

60

80

100

120

0 20 40 60 80 100 120 140 160 180 200 220 240

RMS

Vibr

atio

n Le

vel (

dB r

e 10

-6m

s-2 )

Frequency (Hz)

Footings

Wall

Background

Page 19: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Original) Institute for Sustainable Construction, Edinburgh Napier University Page 80

5.4.26. During normal operation, the fan contributes a greater amount of noise than the

compressor, although the tonal content provided by compressor is audible.

5.4.27. The vibration data shows that the compressor contributes greatest to the

vibration emissions, with a small amount of vibration caused by the fan.

Page 20: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Replacement ASHP) Institute for Sustainable Construction, Edinburgh Napier University Page 81

5.5 422 Fraserburgh, Aberdeenshire (Replacement ASHP)

Site description

5.5.1. The site is identical to that detailed above.

5.5.2. This section details the results for the replacement ASHP.

5.5.3. Subjectively the unit appeared to be operating normally with no audible rattle,

resonance or fault.

Equipment set up

5.5.4. The 5 Channel PULSE system was used at this site.

5.5.5. The ASHP was located on reflective ground, and in front of a reflective wall.

5.5.6. An accelerometer was fixed to the casing of the ASHP, as shown in Picture

5-13. The accelerometer was fixed to the surface using cyanoacrylate cement.

Picture 5-13. 422 Fraserburgh (Replacement), Casing-mounted Accelerometer

5.5.7. The microphones were mounted on heavy-duty tripods as shown in Picture

5-14. All microphones were positioned 1 m from the ASHP casing.

Page 21: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Replacement ASHP) Institute for Sustainable Construction, Edinburgh Napier University Page 82

Picture 5-14. 422 Fraserburgh, Replacement ASHP and Microphone Arrangement

Measurement Results

5.5.8. Figure 5-36 presents the LAeq(1min) measured noise levels at the microphone 1m

in front of the unit set against time, along with the ASHP power consumption.

Page 22: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Replacement ASHP) Institute for Sustainable Construction, Edinburgh Napier University Page 83

Figure 5-36. 422 Fraserburgh (Replacement), SPL and Power Consumption vs Time

5.5.9. The data highlights that the ASHP is cycling on and off approximately every two

and a half hours, consistently throughout the day and night-time periods.

Throughout the measurement period, the ASHP was operational for

approximately 30% of the time.

5.5.10. The trace clearly shows the increase in measured noise level during periods

when the ASHP is operating.

5.5.11. Due to high winds on the 8th and 9th March, these periods have been excluded

from the analysis.

Measurement Analysis

5.5.12. Figure 5-37 presents a scatter diagram showing the noise levels against the

power consumption, for the periods when the ASHP was operating. It is seen

that the sound pressure level has no dependence on the power output of the

ASHP.

0

1000

2000

3000

4000

5000

6000

7000

8000

0

10

20

30

40

50

60

70

80

03/03/11 04/03/11 05/03/11 06/03/11 07/03/11 08/03/11 09/03/11 10/03/11

Pow

er (W

)

L Aeq

(1m

in)

(dB)

Date/Time

SPL

Power

Page 23: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Replacement ASHP) Institute for Sustainable Construction, Edinburgh Napier University Page 84

Figure 5-37. 422 Fraserburgh (Replacement), SPL vs Power Consumption

5.5.13. Figure 5-38 presents a statistical analysis plot of the percentage of time that a

specific noise level would be recorded, when the ASHP is under operation.

From this confidence intervals can be presented for the typical noise levels.

42

44

46

48

50

52

54

56

58

60

62

0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000

L Aeq

(1m

in)(

dB)

Power (W)

Page 24: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Replacement ASHP) Institute for Sustainable Construction, Edinburgh Napier University Page 85

Figure 5-38. 422 Fraserburgh (Replacement), Sound Pressure Level Statistical Analysis

5.5.14. The chart indicates that noise from the ASHP during operation will have a 90%

certainty of being within around 2 dB of LAeq(1min) 47 dB. The corresponding

total ASHP noise dose over the whole assessment period is calculated as

LAeq(1week) 42 dB.

Defrost Cycle

5.5.15. Analysis of the measurements revealed that defrost cycles are part of the ASHP

operation. During these periods, which can last for 1 to 2 minutes, the

compressor is operating in reverse, without the fan. The average sound

pressure level during a typical defrost cycle is around LAeq(1min) 50 dB.

0

10

20

30

40

50

60

70

80

90

100

44 46 48 50 52 54 56 58 60

Perc

entil

e, %

LAeq(1min) (dB)

Page 25: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Replacement ASHP) Institute for Sustainable Construction, Edinburgh Napier University Page 86

Directivity

5.5.16. Table 5-5 shows the directivity in noise emissions from the unit by comparing

the noise levels at the different microphones, for a typical period of ASHP

operation.

Table 5-5: Directivity Analysis of the ASHP Noise Emissions LAeq(1min) dB 422 Fraserburgh (Replacement), normal operation

Microphone Location Front Left Right Above

Typical Microphone Level 47 44 45 45

Change from front microphone - -3 -2 -2

5.5.17. It is seen that the ASHP exhibits a slight directivity, such that noise is greater in

line with the fan.

Frequency analysis

5.5.18. For the frequency analysis, a Fast Fourier Transform (FFT) of the signal was

performed, averaged over a representative one minute period at a frequency

resolution of 2 Hz. The resulting frequency spectrum for the ASHP operating

under normal conditions is given in Figure 5-39, with that for the defrost cycle

presented in Figure 5-40.

Page 26: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Replacement ASHP) Institute for Sustainable Construction, Edinburgh Napier University Page 87

Figure 5-39. 422 Fraserburgh (Replacement), SPL Spectrum (Normal Operation)

Figure 5-40. 418 Fraserburgh (Replacement), SPL Spectrum (Defrost Cycle)

10

20

30

40

50

60

70

20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500

Soun

d Pr

esuu

re L

evel

(dB)

Frequency (Hz)

g p ,

10

20

30

40

50

60

70

20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500

Soun

d Pr

esuu

re L

evel

(dB)

Frequency (Hz)

Page 27: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Replacement ASHP) Institute for Sustainable Construction, Edinburgh Napier University Page 88

5.5.19. Tonal analysis of the frequency spectra shown in Figure 5-39 and Figure 5-40

has been undertaken in accordance with the Joint Nordic Method (v2). The

resulting tonal assessments are presented in Figure 5-40 and Figure 5-41,

showing that the tones identified within the spectrum for normal operation would

lead to a 6 dB tonal penalty. During the defrost cycle, the tonal assessment

indicates that a 6 dB tonal penalty would also be appropriate.

100108 162 200 246

0

10

20

30

40

50

60

70

20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500

A-w

eigh

ted

Soun

d Pr

esuu

re L

evel

(dBA

)

Frequency (Hz)

Figure X:Tonal assessment (JNM2)normal operation, North Pitblae 2

Critical bandNoiseNoise PauseTones

Tone level, Lpt =Masking noise level, Lpn =

Tone audibility, ΔLta =

Tone penalty, k =

dBAdBAdBA

dBA

42.531.612.9

6.0

Overall level, Lpa =

Tone corrected level =

dBA

dBA

47.0

53.0

Figure 5-41. 422 Fraserburgh Tonal Assessment, Replacement (Normal Operation)

Page 28: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Replacement ASHP) Institute for Sustainable Construction, Edinburgh Napier University Page 89

Sound Power Level calculations

5.5.20. Figure 5-43 presents a statistical analysis plot of the percentage of time that a

specific sound power level would be recorded, when the ASHP is under

operation.

42 50 68 100 148 200 248 296 346 396 446 496

0

10

20

30

40

50

60

70

20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500

A-w

eigh

ted

Soun

d Pr

esuu

re L

evel

(dBA

)

Frequency (Hz)

Figure X:Tonal assessment (JNM2)defrost cycle, North Pitblae 2

Critical bandNoiseNoise PauseTones

Tone level, Lpt =Masking noise level, Lpn =

Tone audibility, ΔLta =

Tone penalty, k =

dBAdBAdBA

dBA

42.327.416.9

6.0

Overall level, Lpa =

Tone corrected level =

dBA

dBA

50.0

56.0

Figure 5-42. 422 Fraserburgh Tonal Assessment, Replacement (Defrost Cycle)

Page 29: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Replacement ASHP) Institute for Sustainable Construction, Edinburgh Napier University Page 90

Figure 5-43. 422 Fraserburgh (Replacement), Sound Power Level Statistical Analysis

5.5.21. The chart indicates that noise from the ASHP during operation will have a 90%

certainty of being within around 2 dB of LWA 59 dB.

5.5.22. Use of Equation 1 leads to an estimation that noise levels from the unit

operating normally would drop to LAeq 42 dB at a distance separation of

approximately 4 m. If a tonal penalty were to be included, then this distance

would rise to around 8 m. This assumes that the ASHP is located in the

common mounting scenario as detailed in Section 3.42, which is not necessarily

representative of the actual measured condition.

Vibration

5.5.23. An FFT analysis of the vibration levels recorded for normal operation of the

ASHP is shown in Figure 5-44. The peaks in the background spectrum at 100

and 200 Hz are deemed to be due to an electrical component within the ASHP.

0

10

20

30

40

50

60

70

80

90

100

56 58 60 62 64 66 68 70 72

Perc

entil

e, %

LWA (dB)

Page 30: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Replacement ASHP) Institute for Sustainable Construction, Edinburgh Napier University Page 91

Figure 5-44. 422 Fraserburgh (Replacement), Vibration Levels

Discussion

5.5.24. Whilst the manufacturer has not provided us with detailed information on the fan

and compressor speeds, inspection of the results and experience of similar

units suggest that the fan speed was around 810 rpm, and included four fan

blades. This fan configuration corresponds with a blade passing frequency of

54 Hz, with second and third harmonics at 108 and 162 Hz respectively. These

effects are seen in the frequency spectrum for normal operation. The

compressor was of a scroll type with an unknown speed. Analysis of the defrost

cycle frequency spectrum suggests however that the primary tone is at around

50Hz, which corresponds with a rotational speed of 3000 rpm, typical for this

type of compressor. Harmonics of this tone are seen at multiple frequencies in

the spectrum.

0

20

40

60

80

100

120

0 20 40 60 80 100 120 140 160 180 200 220 240

RMS

Vibr

atio

n Le

vel (

dB r

e 10

-6m

s-2 )

Frequency (Hz)

Casing

Background

Page 31: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 422 Fraserburgh (Replacement ASHP) Institute for Sustainable Construction, Edinburgh Napier University Page 92

5.5.25. During normal operation, the compressor contributes a greater amount of noise

than the fan, and also provides the majority of the tonal content.

5.5.26. This replacement 6.0 kW ASHP measured 9 dB quieter than the initial 8.0 kW

ASHP. The manufacturer’s data suggested a reduction in noise by 7 dB would

have been achievable.

5.5.27. The vibration data shows that both the compressor and fan contribute to the

vibration emissions.

Page 32: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 443 Cheshire West Institute for Sustainable Construction, Edinburgh Napier University Page 93

5.6 443 Cheshire West

Site description

5.6.1. The property is located in a small village off a quiet road. The ASHP is located

to the rear of the brick built single story semi-detached property. The unit is

mounted onto the wall surface, supported from a metal frame fixed to the

brickwork. Vibration isolation couplings were used between the unit and the

framework.

5.6.2. Subjectively the unit appeared to be operating normally with no audible rattle,

resonance or fault.

Equipment set up

5.6.3. The 9 Channel PULSE system was used at this site.

5.6.4. The unit was mounted above a mixed ground surface of soil and paving slabs.

5.6.5. Accelerometers were fixed to the unit casing and to the wall surface

immediately behind the unit. The accelerometers were fixed to the surfaces

using cyanoacrylate cement.

5.6.6. The microphones were mounted on a temporary scaffolding framework as

shown in Picture 5-15 and Picture 5-16. All microphones were positioned 1 m

from the ASHP casing.

Page 33: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 443 Cheshire West Institute for Sustainable Construction, Edinburgh Napier University Page 94

Picture 5-15. 443 Cheshire West, ASHP and Microphone Arrangement

Picture 5-16. 443 Cheshire West, ASHP and Microphone Arrangement

Page 34: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 443 Cheshire West Institute for Sustainable Construction, Edinburgh Napier University Page 95

Measurement Results

5.6.7. Figure 5-45 presents the LAeq(1min) measured noise levels at the microphone 1m

in front of the unit set against time, along with the per-minute logged ASHP

power consumption.

Figure 5-45. 443 Cheshire West, Sound Pressure Level and Power Consumption vs Time

5.6.8. The chart highlights that the ASHP is cycling on and off very frequently,

approximately every twenty minutes, throughout the day and night time periods.

When the unit is operational, it is on for approximately four minutes.

Throughout the measurement period, the ASHP was operational for

approximately 22% of the time.

5.6.9. The data shows an increase in measured noise level during periods when the

ASHP is operating.

0

1000

2000

3000

4000

5000

6000

7000

8000

0

10

20

30

40

50

60

70

80

16/02/11 17/02/11 18/02/11 19/02/11 20/02/11 21/02/11 22/02/11 23/02/11

Pow

er (W

)

L Aeq

(1m

in)

(dB)

Date/Time

SPL

Energy

Page 35: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 443 Cheshire West Institute for Sustainable Construction, Edinburgh Napier University Page 96

Measurement Analysis

5.6.10. Figure 5-2 presents a scatter diagram showing the noise levels against the

power consumption, for the periods when the ASHP was operating. The chart

trend line indicates a slight increase in noise level with ASHP power level,

although the fit is not conclusive, with a regression coefficient (r2) of 23%.

Figure 5-46. 443 Cheshire West, Sound Pressure Level vs Power Consumption

5.6.11. Figure 5-47 presents a statistical analysis plot of the percentage of time that a

specific noise level would be recorded, when the ASHP is under operation.

From this confidence intervals can be presented for the typical noise levels.

52

54

56

58

60

62

64

66

68

70

72

0 500 1000 1500 2000 2500 3000 3500 4000

L Aeq

(1m

in)(

dB)

Power (W)

Page 36: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 443 Cheshire West Institute for Sustainable Construction, Edinburgh Napier University Page 97

Figure 5-47. 443 Cheshire West, Sound Pressure Level Statistical Analysis

5.6.12. The chart indicates that noise from the ASHP during operation will have a 90%

certainty of being within around 4 dB of LAeq(1min) 64 dB. The corresponding

total ASHP noise dose over the whole assessment period is calculated as

LAeq(1week) 58 dB.

Defrost Cycle

5.6.13. Analysis of the measurements revealed that defrost cycles are part of the ASHP

operation. During these periods, which can last for 2 to 3 minutes, the

compressor is operating in reverse, without the fan. The average sound

pressure level during a typical defrost cycle is around LAeq(1min) 57 dB.

0

10

20

30

40

50

60

70

80

90

100

54 56 58 60 62 64 66 68 70

Perc

entil

e, %

LAeq(1min) (dB)

Page 37: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 443 Cheshire West Institute for Sustainable Construction, Edinburgh Napier University Page 98

Directivity

5.6.14. Table 5-6 shows the directivity in noise emissions from the unit by comparing

the noise levels at the different microphones, for a typical period of ASHP

operation.

Table 5-6: Directivity Analysis of the ASHP Noise Emissions LAeq(1min) dB 443 Cheshire West, normal operation

Microphone Location Front Left Right Above

Typical Microphone Level 64 63 62 59

Change from front microphone - -1 -2 -5

5.6.15. It is seen that the ASHP exhibits a slight directivity, such that noise is greatest in

line with the fan, whilst there is a reduction in noise above the ASHP.

Frequency analysis

5.6.16. For the frequency analysis, a Fast Fourier Transform (FFT) of the signal was

performed, averaged over a representative one minute period at a frequency

resolution of 2 Hz. The resulting frequency spectrum for the ASHP operating

under normal conditions is given in Figure 5-48, with that for the defrost cycle

given in Figure 5-49.

Page 38: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 443 Cheshire West Institute for Sustainable Construction, Edinburgh Napier University Page 99

Figure 5-48. 443 Cheshire West, Sound Pressure Level Frequency Spectrum (Normal Operation)

Figure 5-49. 443 Cheshire West, Sound Pressure Level Frequency Spectrum (Defrost cycle)

10

20

30

40

50

60

70

20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500

Soun

d Pr

esuu

re L

evel

(dB)

Frequency (Hz)

10

20

30

40

50

60

70

20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500

Soun

d Pr

esuu

re L

evel

(dB)

Frequency (Hz)

Page 39: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 443 Cheshire West Institute for Sustainable Construction, Edinburgh Napier University Page 100

5.6.17. Tonal analysis of the frequency spectra shown in Figure 5-48 and Figure 5-49

has been undertaken in accordance with the Joint Nordic Method (v2). The

resulting tonal assessments are presented in Figure 5-49 and Figure 5-50,

showing that the tones identified within the spectrum would lead to a 4 dB tonal penalty for normal operation and a 6 dB tonal penalty for the defrost cycle.

60 100 120 300 490500

0

10

20

30

40

50

60

70

20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500

A-w

eigh

ted

Soun

d Pr

esuu

re L

evel

(dBA

)

Frequency (Hz)

Figure X:Tonal assessment (JNM2)normal operation, Northwich

Critical bandNoiseNoise PauseTones

Tone level, Lpt =Masking noise level, Lpn =

Tone audibility, ΔLta =

Tone penalty, k =

dBAdBAdBA

dBA

52.647.07.6

3.6

Overall level, Lpa =

Tone corrected level =

dBA

dBA

64.0

67.6

Figure 5-50. 443 Cheshire West Tonal Assessment (Normal Operation)

Page 40: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 443 Cheshire West Institute for Sustainable Construction, Edinburgh Napier University Page 101

Sound Power Level calculations

5.6.18. Figure 5-8 presents a statistical analysis plot of the percentage of time that a

specific sound power level would be recorded, when the ASHP is under

operation.

50 100 150 200 250 300 348 400 450 500

0

10

20

30

40

50

60

70

20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500

A-w

eigh

ted

Soun

d Pr

esuu

re L

evel

(dBA

)

Frequency (Hz)

Figure X:Tonal assessment (JNM2)defrost cycle, Northwich

Critical bandNoiseNoise PauseTones

Tone level, Lpt =Masking noise level, Lpn =

Tone audibility, ΔLta =

Tone penalty, k =

dBAdBAdBA

dBA

54.012.044.0

6.0

Overall level, Lpa =

Tone corrected level =

dBA

dBA

57.0

63.0

Figure 5-51. 443 Cheshire West Tonal Assessment (Defrost Cycle)

Page 41: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 443 Cheshire West Institute for Sustainable Construction, Edinburgh Napier University Page 102

Figure 5-52. 443 Cheshire West, Sound Power Level Statistical Analysis

5.6.19. The chart indicates that noise from the ASHP during operation will have a 90%

certainty of being within around 3 dB of LWA 76 dB.

5.6.20. Use of Equation 1 leads to an estimation that noise levels from the unit

operating normally would drop to LAeq 42 dB at a distance separation of

approximately 28 m. If a tonal penalty were to be included, then this distance

would rise to around 45 m. This assumes that the ASHP is located in the

common mounting scenario as detailed in Section 3.42, which is not necessarily

representative of the actual measured condition.

Vibration

5.6.21. An FFT analysis of the vibration levels recorded for normal operation of the

ASHP is shown in Figure 5-53. The overall weighted peak vibration level at the

wall surface was 0.017 ms-2, just above the average perception threshold for

whole-body vibration.

0

10

20

30

40

50

60

70

80

90

100

66 68 70 72 74 76 78 80

Perc

entil

e, %

LWA (dB)

Page 42: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 443 Cheshire West Institute for Sustainable Construction, Edinburgh Napier University Page 103

Figure 5-53. 443 Cheshire West, Vibration Levels

Discussion

5.6.22. The manufacturer has stated that the fan for ASHP rotates at a nominal speed

of 903 rpm, with a compressor speed of 2900 rpm. With four fan blades, the

blade passing frequency is around 60 Hz, with harmonics around 120 and

180 Hz. These are identified in the frequency spectrum for normal operation.

The compressor speed corresponds to a frequency of around 50 Hz, with

harmonics observed throughout the frequency range.

5.6.23. During normal operation, the fan provides a greater amount of noise than the

compressor, although some tonal content from the compressor is audible.

5.6.24. The vibration data shows that both the compressor and fan contribute to the

vibration levels, and there is good vibration attenuation between the casing and

wall surface, due to the presence of the isolation mounts. It should be noted

that the vibration level around 100 Hz is likely to cause some structure-borne

noise to the inhabitants of the property.

0

20

40

60

80

100

120

0 20 40 60 80 100 120 140 160 180 200 220 240

RMS

Vibr

atio

n Le

vel (

dB r

e 10

-6m

s-2 )

Frequency (Hz)

Casing

Wall

Background

Page 43: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 474 West Berkshire (Site 1) Institute for Sustainable Construction, Edinburgh Napier University Page 104

5.7 474 West Berkshire (Site 1)

Site description

5.7.1. The property is located in a rural village off a quiet road. The ASHP is located

to the rear of a modern brick built two story semi-detached property. The unit is

seated on concrete footings, in front of the property wall.

5.7.2. Subjectively the unit appeared to be operating normally with no audible rattle,

resonance or fault.

Equipment set up

5.7.3. The 5 Channel PULSE system was used at this site.

5.7.4. The ASHP was located on hard, reflective ground, with a fence panel situated

close by, to the right of the unit.

5.7.5. An accelerometer was fixed to the unit casing, as shown in Picture 5-17, using

cyanoacrylate cement.

Page 44: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 474 West Berkshire (Site 1) Institute for Sustainable Construction, Edinburgh Napier University Page 105

Picture 5-17. 474 West Berkshire (Site 1), Casing-mounted Accelerometer

5.7.6. Three microphones were used, two mounted on scaffolding and one mounted

on a tripod as shown in Picture 5-18. All microphones were positioned 1 m from

the ASHP casing, with the exception of the position to the right of the ASHP,

which was situated slightly closer (60 cm) due to the presence of a walkway.

Page 45: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 474 West Berkshire (Site 1) Institute for Sustainable Construction, Edinburgh Napier University Page 106

Picture 5-18. 474 West Berkshire (Site 1), ASHP and Microphone Arrangement

Measurement Results

5.7.7. Figure 5-54 presents the LAeq(1min) measured noise levels at the microphone 1m

in front of the unit set against time, along with the per-minute logged ASHP

power consumption.

Page 46: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 474 West Berkshire (Site 1) Institute for Sustainable Construction, Edinburgh Napier University Page 107

Figure 5-54. 474 West Berkshire (Site 1), Sound Pressure Level and Power Consumption vs Time

5.7.8. The chart highlights that the ASHP operates mainly over a morning period and

an afternoon period. During these periods, the ASHP cycles on and off every

hour or so; when the ASHP is operating, it does so for periods of 10-20 minutes.

Throughout the measurement period, the ASHP was operating for

approximately 15% of the time.

5.7.9. The trace shows an increase in measured noise level during periods when the

ASHP is operating.

Measurement Analysis

5.7.10. Figure 5-55 presents a scatter diagram showing the noise levels against the

power consumption, for the periods when the ASHP was operating. The chart

trend line indicates a slight increase in noise level with ASHP power level,

although the fit is not conclusive, with a regression coefficient (r2) of just 4%.

0

1000

2000

3000

4000

5000

6000

7000

8000

0

10

20

30

40

50

60

70

80

23/02/11 24/02/11 25/02/11 26/02/11 27/02/11 28/02/11 01/03/11 02/03/11

Pow

er (W

)

L Aeq

(1m

in)

(dB)

Date/Time

SPL

Power

Page 47: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 474 West Berkshire (Site 1) Institute for Sustainable Construction, Edinburgh Napier University Page 108

Figure 5-55. 474 West Berkshire (Site 1), Sound Pressure Level vs Power Consumption

5.7.11. Figure 5-56 presents a statistical analysis plot of the percentage of time that a

specific noise level would be recorded, when the ASHP is under operation.

From this confidence intervals can be presented for the typical noise levels.

52

54

56

58

60

62

64

66

0 1000 2000 3000 4000 5000 6000

L Aeq

(1m

in)(

dB)

Power (W)

Page 48: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 474 West Berkshire (Site 1) Institute for Sustainable Construction, Edinburgh Napier University Page 109

Figure 5-56. 474 West Berkshire (Site 1), Sound Pressure Level Statistical Analysis

5.7.12. The chart indicates that noise from the ASHP during operation will have a 90%

certainty of being within around 2 dB of LAeq(1min) 60 dB. The corresponding

total ASHP noise dose over the whole assessment period is calculated as

LAeq(1week) 52 dB.

Defrost Cycle

5.7.13. Analysis of the measurements revealed that defrost cycles are part of the ASHP

operation. During these periods, which can last for 1 to 2 minutes, the

compressor is operating in reverse, without the fan. The average sound

pressure level during a typical defrost cycle is around LAeq(1min) 51 dB.

0

10

20

30

40

50

60

70

80

90

100

52 54 56 58 60 62 64

Perc

entil

e, %

LAeq(1min) (dB)

Page 49: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 474 West Berkshire (Site 1) Institute for Sustainable Construction, Edinburgh Napier University Page 110

Directivity

5.7.14. Table 5-7 shows the directivity in noise emissions from the unit by comparing

the noise levels at the different microphones, for a typical period of ASHP

operation.

Table 5-7: Directivity Analysis of the ASHP Noise Emissions LAeq(1min) dB 474 West Berkshire (Site 1), normal operation

Microphone Location Front Left Above

Typical Microphone Level 60 61 58

Change from front microphone - +1 -2

5.7.15. It is seen that the ASHP is not significantly directional, which is likely to be due

to the nearby acoustically reflective surfaces.

Frequency analysis

5.7.16. For the frequency analysis, a Fast Fourier Transform (FFT) of the signal was

performed, averaged over a representative one minute period at a frequency

resolution of 2 Hz. The resulting frequency spectrum for the ASHP operating

under normal conditions is given in Figure 5-57, with that for the defrost cycle

presented in Figure 5-58.

Page 50: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 474 West Berkshire (Site 1) Institute for Sustainable Construction, Edinburgh Napier University Page 111

Figure 5-57. 474 West Berkshire (Site 1), SPL Spectrum (Normal Operation)

Figure 5-58. 474 West Berkshire (Site 1), SPL Spectrum (Defrost Cycle)

10

20

30

40

50

60

70

Soun

d Pr

esuu

re L

evel

(dB)

Frequency (Hz)

Figure X: FFT - normal operation, Westfields

10

20

30

40

50

60

70

Soun

d Pr

esuu

re L

evel

(dB)

Frequency (Hz)

Figure X: FFT - defrost cycle, Westfields

Page 51: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 474 West Berkshire (Site 1) Institute for Sustainable Construction, Edinburgh Napier University Page 112

5.7.17. Tonal analysis of the frequency spectra shown in Figure 5-57 and Figure 5-58

has been undertaken in accordance with the Joint Nordic Method (v2). The

resulting tonal assessments are presented in Figure 5-58 and Figure 5-59,

showing that the tones identified within the spectrum for normal operation would

lead to a 0 dB tonal penalty. During the defrost cycle, the tonal assessment

indicates that a 6 dB tonal penalty would be appropriate.

50 536 682

0

10

20

30

40

50

60

70

A-w

eigh

ted

Soun

d Pr

esuu

re L

evel

(dBA

)

Frequency (Hz)

Figure X:Tonal assessment (JNM2)normal operation, Westfields

Critical bandNoiseNoise PauseTones

Tone level, Lpt =Masking noise level, Lpn =

Tone audibility, ΔLta =

Tone penalty, k =

dBAdBAdBA

dBA

44.348.0-1.4

0.0

Overall level, Lpa =

Tone corrected level =

dBA

dBA

60.0

60.0

Figure 5-59. 474 West Berkshire Tonal Assessment (Normal Operation)

Page 52: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 474 West Berkshire (Site 1) Institute for Sustainable Construction, Edinburgh Napier University Page 113

Sound Power Level calculations

5.7.18. Figure 5-61 presents a statistical analysis plot of the percentage of time that a

specific sound power level would be recorded, when the ASHP is under

operation.

50 86100 148 196 246 274294 320 344 438 492 542 588 638 736 780 838 888

0

10

20

30

40

50

60

70

A-w

eigh

ted

Soun

d Pr

esuu

re L

evel

(dBA

)

Frequency (Hz)

Figure X:Tonal assessment (JNM2)defrost cycle, Westfields

Critical bandNoiseNoise PauseTones

Tone level, Lpt =Masking noise level, Lpn =

Tone audibility, ΔLta =

Tone penalty, k =

dBAdBAdBA

dBA

40.326.116.2

6.0

Overall level, Lpa =

Tone corrected level =

dBA

dBA

51.0

57.0

Figure 5-60. 474 West Berkshire Tonal Assessment (Defrost Cycle)

Page 53: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 474 West Berkshire (Site 1) Institute for Sustainable Construction, Edinburgh Napier University Page 114

Figure 5-61. 474 West Berkshire (Site 1), Sound Power Level Statistical Analysis

5.7.19. The chart indicates that noise from the ASHP during operation will have a 90%

certainty of being within around 2 dB of LWA 71 dB.

5.7.20. Use of Equation 1 leads to an estimation that noise levels from the unit

operating normally would drop to LAeq 42 dB at a distance separation of

approximately 16 m. This assumes that the ASHP is located in the common

mounting scenario as detailed in Section 3.42, which is not necessarily

representative of the actual measured condition.

Vibration

5.7.21. An FFT analysis of the vibration levels recorded for normal operation of the

ASHP is shown in Figure 5-62. The peaks in the background spectrum at 100

and 200 Hz are deemed to be due to an electrical component within the ASHP.

0

10

20

30

40

50

60

70

80

90

100

64 66 68 70 72 74 76

Perc

entil

e, %

LWA (dB)

Page 54: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 474 West Berkshire (Site 1) Institute for Sustainable Construction, Edinburgh Napier University Page 115

Figure 5-62. 474 West Berkshire (Site 1), Vibration Levels

Discussion

5.7.22. The manufacturer has indicated that the speed rating of the fan is nominally

770 rpm, and the compressor speed is 2850 rpm. With four fan blades, the

passing frequency would correspond to around 51 Hz, with upper harmonics

around 102 and 153 Hz. These are seen in the frequency spectrum results of

normal operation. The compressor speed corresponds with a rotation

frequency of around 48 Hz, upper harmonics are clearly visible in the defrost

cycle frequency spectrum.

5.7.23. During normal operation, the fan contributes a greater amount of noise than the

compressor, although tonal content provided by the compressor is audible.

5.7.24. The vibration data shows that both the compressor and fan contribute to the

vibration emissions.

0

20

40

60

80

100

120

0 20 40 60 80 100 120 140 160 180 200 220 240

RMS

Vibr

atio

n Le

vel (

dB r

e 10

-6m

s-2 )

Frequency (Hz)

Casing

Background

Page 55: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 475 West Berkshire (Site 2) Institute for Sustainable Construction, Edinburgh Napier University Page 116

5.8 475 West Berkshire (Site 2)

Site description

5.8.1. The property is located in a small village off a quiet road. The ASHP is located

to the rear of the brick built two story end of terrace property. The unit is

mounted onto concrete paving slab footings.

5.8.2. Subjectively the unit appeared to be operating normally although a prominent

rattle was heard at times.

Equipment set up

5.8.3. The 9 Channel PULSE system was used at this site.

5.8.4. The unit was mounted above a mixed ground surface of soil, gravel and paving

slabs. A garden storage unit was located to the right of the unit, preventing the

installation of a microphone to the right of the ASHP. A fence was located to

the left of the unit, which limited the distance at which the microphone could be

placed at this location.

5.8.5. Accelerometers were fixed to the unit casing and to the wall surface

immediately behind the unit as shown in Picture 5-19 and Picture 5-20. The

accelerometers were fixed to the surfaces using cyanoacrylate cement.

Page 56: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 475 West Berkshire (Site 2) Institute for Sustainable Construction, Edinburgh Napier University Page 117

Picture 5-19. 475 West Berkshire (Site 2), Casing-mounted Accelerometer

Picture 5-20. 475 West Berkshire (Site 2), Wall-mounted Accelerometer

5.8.6. The microphones were mounted on tripods as shown in Picture 5-21. All

microphones were positioned 1 m from the ASHP casing, with the exception of

the microphone to the left, which had a separation of 60 cm.

Page 57: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 475 West Berkshire (Site 2) Institute for Sustainable Construction, Edinburgh Napier University Page 118

Picture 5-21. 475 West Berkshire (Site 2), ASHP and Microphone Arrangement

Measurement Results

5.8.7. Figure 5-63 presents the LAeq(1min) measured noise levels at the microphone 1m

in front of the unit set against time, along with the per-minute logged ASHP

power consumption.

Page 58: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 475 West Berkshire (Site 2) Institute for Sustainable Construction, Edinburgh Napier University Page 119

Figure 5-63. 475 West Berkshire (Site 2), Sound Pressure Level and Power Consumption vs Time

5.8.8. The chart highlights that the ASHP is cycling on and off very frequently,

approximately every ten minutes, throughout the day and night time periods.

When the unit is operational, it is usually on for approximately three to four

minutes. Throughout the measurement period, the ASHP was operational for

approximately 33% of the time.

5.8.9. The data shows an increase in measured noise level during periods when the

ASHP is operating.

Measurement Analysis

5.8.10. Figure 5-64 presents a scatter diagram showing the noise levels against the

power consumption, for the periods when the ASHP was operating. The chart

shows no apparent link between power and noise level.

0

1000

2000

3000

4000

5000

6000

7000

8000

0

10

20

30

40

50

60

70

80

23/02/11 24/02/11 25/02/11 26/02/11 27/02/11 28/02/11 01/03/11 02/03/11

Pow

er (W

)

L Aeq

(1m

in)

(dB)

Date/Time

SPL

Energy

Page 59: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 475 West Berkshire (Site 2) Institute for Sustainable Construction, Edinburgh Napier University Page 120

Figure 5-64. 475 West Berkshire (Site 2), Sound Pressure Level vs Power Consumption

5.8.11. Figure 5-65 presents a statistical analysis plot of the percentage of time that a

specific noise level would be recorded, when the ASHP is under operation.

From this confidence intervals can be presented for the typical noise levels.

52

54

56

58

60

62

64

66

0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000

L Aeq

(1m

in)(

dB)

Power (W)

Page 60: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 475 West Berkshire (Site 2) Institute for Sustainable Construction, Edinburgh Napier University Page 121

Figure 5-65. 475 West Berkshire (Site 2), Sound Pressure Level Statistical Analysis

5.8.12. The chart indicates that noise from the ASHP during operation will have a 90%

certainty of being within around 3 dB of LAeq(1min) 62 dB. The corresponding

total ASHP noise dose over the whole assessment period is calculated as

LAeq(1week) 57 dB.

Defrost Cycle

5.8.13. Analysis of the measurements revealed that defrost cycles are part of the ASHP

operation. During these periods, which can last for 2 to 3 minutes, the

compressor is operating in reverse, without the fan. The average sound

pressure level during a typical defrost cycle is around LAeq(1min) 63 dB.

0

10

20

30

40

50

60

70

80

90

100

52 54 56 58 60 62 64 66 68

Perc

entil

e, %

LAeq(1min) (dB)

Page 61: Table 5-3: Directivity Analysis of the ASHP Noise ... · The PULSE system stopped recording on two occasions and had to be reset. 5.4.11. The data highlights that the ASHP is cycling

EE0214 Acoustic Noise Measurements of Air Source Heat Pumps

Building Performance Centre Analysis of Measurements: 475 West Berkshire (Site 2) Institute for Sustainable Construction, Edinburgh Napier University Page 122

Directivity

5.8.14. Table 5-8 shows the directivity in noise emissions from the unit by comparing

the noise levels at the different microphones, for a typical period of ASHP

operation.

Table 5-8: Directivity Analysis of the ASHP Noise Emissions LAeq(1min) dB 475 West Berkshire (Site 2), normal operation

Microphone Location Front Left Above

Typical Microphone Level 62 62 62

Change from front microphone - 0 0

5.8.15. It is seen that the ASHP does not exhibit significant directivity, which is likely to

be due in part to the acoustically reflective nature of the nearby fence and

garden storage unit.