PHASE 4B - FIRST FLOOR -
SPECIAL SYSTEMS COVER SHEET
1
GENERAL NOTES
1. ELECTRICAL AND VOICE/DATA OUTLETS SHALL NOT BE INSTALLED IN THE SAME STUB SPACE AS
OUTLETS SERVING AN ADJACENT OFFICE OR SPACE.
2. EQUIPMENT GROUNDING SYSTEM SHALL NOT RELY ON METAL CONDUIT FOR EQUIPMENT GROUND.
A GROUND CONDUCTOR (SIZED PER CODE) SHALL BE INSTALLED IN ALL BRANCH AND FEEDER
CONDUITS U.O.N..
3. ALL WIRING DEVICES SHALL BE WHITE WITH MATCHING DEVICE PLATES, U.O.N. VERIFY OUTLET
MOUNTING HEIGHTS AND LOCATIONS WITH ELECTRICAL DETAILS (WHERE PROVIDED) AND
ARCHITECT'S PLANS AND DETAILS.
4. VERIFY THICKNESS OF WALL FOR ALL OUTLET AND SWITCH BOX LOCATIONS. INSTALL BOX FLUSH
WITH FINISHED WALL MATERIAL - VERIFY ALL ARCH. WALL FINISHES. REFER ALSO TO APPROVED
CABINET SHOP DRAWINGS.
5. ALL OVERHEAD MOUNTED SYSTEMS WEIGHING 14 KILOGRAMS (31 POUNDS) OR MORE (EXCLUDING
DISTRIBUTION SYSTEMS SUCH AS POWER CONDUITS NETWORKS THAT COLLECTIVELY EXCEED
THAT WEIGHT) MUST BE MOUNTED TO MINIMIZE THE LIKELIHOOD THAT THEY WILL FALL AND
INJURE BUILDING OCCUPANTS. MOUNT ALL SUCH SYSTEMS SO THAT THEY RESIST FORCES OF 0.5
TIMES THE COMPONENT WEIGHT IN ANY DIRECTION AND 1.5 TIMES THE COMPONENT WEIGHT IN
THE DOWNWARD DIRECTION.
6. CONDUIT INSTALLATIONS SHALL BE IN STRICT COMPLIANCE WITH TIA/EIA 569. CABLE INSTALLATION
SHALL BE IN STRICT COMPLIANCE WITH ANSI/TIA 568-C.
7. TELECOMMUNICATION GROUNDING SYSTEM SHALL CONFORM TO TIA/EIA 607.
8. ALL CABLING, PATHWAY, GROUND BUSES AND TERMINATION HARDWARE, RACKS AND CABINETS
SHALL BE PROVIDED WITH IDENTIFICATION (LABELING) IN ACCORDANCE WITH THE TIA/EIA 606.
9. ELECTRICAL CONTRACTOR SHALL PROVIDE LISTED FIRESTOPPING FOR ALL TELECOMM/LOW
VOLTAGE CONDUITS AND CABLES, REFER TO SPECIFICATIONS.
10. ALL TELEPHONE TERMINAL BACKBOARDS SHALL BE 3/4"D x 8'H) VOID FREE FIRE RETARDANT AC
PLYWOOD. LENGTH SHALL BE AS INDICATED ON PLAN.
11. CONDUIT/PATHWAY ROUTING INDICATED ON DRAWINGS IS FOR GENERAL REFERENCE ONLY.
12. ELECTRICAL CONTRACTOR SHALL FIELD COORDINATE AND VERIFY EXACT ROUTING AS REQUIRED.
13. CONTRACTOR SHALL MAINTAIN SEPARATION FROM ELECTRICAL FEEDERS, ELECTRONIC
BALLASTS, TRANSFORMERS, ETC. TO MINIMIZE ELECTRO-MAGNETIC COMPATIBILITY ISSUES.
14. ALL CONDUIT INDICATED ON THE TELECOMMUNICATION DRAWINGS SHALL BE PROVIDED BY THE
ELECTRICAL CONTRACTOR. TELECOMMUNICATIONS CONTRACTOR SHALL COORDINATE WITH
ELECTRICAL CONTRACTOR FOR ROUTING AT CONDUITS TO ENSURE TIA/EIA DISTANCE STANDARDS
ARE NOT EXCEEDED.
15. FIELD COORDINATE WITH ELECTRICAL CONTRACTOR TO ENSURE CONDUIT ROUTING FOR
TELEPHONE AND DATA DOES NOT RESULT IN CABLE LENGTHS IN EXCESS OF 300 FEET.
16. CONDUIT GREATER THAN 1-1/4" WILL REQUIRE J-BOX SIZED PER NEC SECTION 370-28.
17. BEND RADIUS OF CONDUIT LESS THAN 2" = 6 TIMES INTERNAL CONDUIT DIAMETER, GREATER THAN
2" = 10 TIMES INTERNAL CONDUIT DIAMETER.
18. ANY RUN WITH MORE THAN 2 90 DEGREE BENDS REQUIRES A PULL BOX PER 2 BENDS.
19. PULL BOXES MAY NOT BE USED IN PLACE OF BEND.
20. CABLING SHALL BE COMPLETE, OPERABLE, TESTED (END TO END) AND LABELED.
21. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE SATISFACTION OF THE
CONTRACTING OFFICER.
22. ALL TELECOMMUNICATION CABLING SHALL MAINTAIN A MINIMUM 47" BUFFER FROM ELECTRICAL
MOTORS AND TRANSFORMERS GREATER THAN 5KVA.
SYMBOL LEGEND
ABBREVIATIONS
AFF ABOVE FINISHED FLOOR
C CAMERA COAX CABLE (SIEMES CABLE)
CU UNDERGROUND RATED COAX CABLE
ER EXISTING DEVICE TO BE RELOCATED
PB PULL BOX
PU UNDERGROUND 24VDC POWER CABLE
T TELEPHONE CABLE
TC TERMINAL CAN
UT OUTSIDE PLANT MULTI-PAIR COOPER CABLE
TBB TELECOMMUNICATIONS BONDING BACKBONE
TGB TELECOMMUNICATIONS GROUNDING BUSBAR
TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR
UON UNLESS OTHERWISE NOTED
UTP UNTWISTED PAIR
DATA OUTLET
4S BOX WITH SINGLE GANG RING 18" AFF WITH
(1) BLUE CAT6 CABLE, (1) WHITE CAT6 CABLE AND (1) GREY CAT6 CABLE TO PATCH PANEL IN IDF ROOM
ANALOG PHONE
ANALOG VOICE UTP CAT6 </=2625 FEET </=800 METERS
DATA
DATA UTP CAT6 </=295 FEET </=90 METERS
MAXIMUM COPPER CABLE LENGTHS
24 AWG UTP EMT CONDUIT CAPACITY
AREA @ 40% CAPACITY (in<)CONDUIT (EMT) CABLE QTY. (OSP)
1" [25mm]
3/4" [19mm] 0.213
0.346
NOT USED
4
CABLE QTY. (ISP)
NOT USED
9
1-1/4" [32mm] 0.598 815
1-1/2" [38mm] 0.814 1121
2" [51mm] 1.342 1935
2-1/2" [64mm] 2.343 3361
3" [76mm] 3.538 5093
NOTES:
1. MAX. ISP CABLE QUANTITIES BASED ON NON-PLENUM 4-PAIR CAT6 UTP (.22" [6mm]
OD.) AND MAX OSP CABLE QUANTITIES BASED ON 4-PAIR CAT6 UTP (.30" [7mm] OD.).
ADJUST FOR OTHER CONDUIT AND CABLE TYPES.
2. MINIMUM OF 1" CONDUIT MUST BE USED FOR ALL VOICE AND DATA CABLES.
3. MAXIMUM OF TWO WORKSTATIONS CAN SHARE A SINGLE HOMERUN CONDUIT.
WIRE LEGEND
DESCRIPTIONDESIGNATION COLORCABLE TYPE
D DATA CABLE VARIESCAT6
B SOUND CABLE BLACK18/2
WIRELESS ACCESS POINT
(1) CAT6 BLUE CABLE TO DATA PATCH PANEL IN IDF ROOM 5234A
WAP
S
PUBLIC ADDRESS SPEAKER
(1) 18/2 CABLE TIED INTO EXISTING PA SYSTEM
CR
PROXIMITY CARD READER WITH SCRAMBLE PAD AND LINE
MODULE
DOOR CONTACT
S SECURITY CABLE YELLOWCOMPOSITE CABLE
DC
SHEET INDEX
SHEET NUMBER
T.1 SPECIAL SYSTEMS COVER SHEET
DESCRIPTION
TELECOM & CCTV FLOOR PLANT.2
PUBLIC ADDRESS & ACCESS CONTROL FLOOR PLAN T.3
RISER DIAGRAMT.4
WIRING DETAILST.5
DETAILST.6
6
CCTV FIXED CAMERA
(1) CAT6 BLUE CABLE TO SIGNAL ROOM 1079
C CCTV CABLE BLUECAT6
439 El Cajon Blvd.
El Cajon, CA. 92020
Phone: (619) 588-7730
Fax: (619) 588-2932
Cell: (619) 302-7730 [email protected]
www.mannixarch.com
Department of
Veterans Affairs
Electronic Control Systems, LLC
D.B.A. Albireo Energy
12575 Kirkham Court, Suite #1
Poway, California 92064 USA
858-513-1911 Main
858-513-1907 Fax
www.albireoenergy.com
License - C-10 #999079
Albireo EnergyPartnering for Success
REQUEST TO EXIT SENSORREX
WAITINGROOMSW300
POLICESW303
FAMILYTOILET
PATIENTTOILETSW305
TRIAGE-1
TRIAGE-2
TRIAGE-3SW302D
BLUESW330
BLUESW328
EXAMSW326
TRIAGESW302
TRIAGE WAITINGSW301
CLEANROOM
EXAMSW348
HALLSW349
HALLSW417
HALLSW325
OFFICESW322
OFFICESW324
OFFICESW332
OFFICESW336
VESTIBULE1128A
CORRIDOR1128
CLINIC WAITINGSW200
SW304
SOILEDROOM
SW319
TRASH
BREAK ROOMSW418
HALL ESW417
ELECTRICALSW402EXAM
SW412EXAMSW408
EXAMSW404
SIGNALCLOSETSW416
TABLE W/
HYDRAULIC
BASE
ILLUM.
BOX
EXAM
LIGHT
A
SHELF
INSTURMENT
CAB.
STOOL
COAT
HOOKS
BLTN.
BD.
O
V
PROCEDUREROOMSW206
177 SQ. FT.
INTAKE COUNSELING(FUTURE EXAM)
SW202119 SQ. FT.
FAMILYTOILETSW26487 SQ. FT.
FAMILYTOILETSW26687 SQ. FT.
DECON1185
TOILET1184 EXAM /
TREATMENT1177
EXAM /TREATMENT
1178
OFFICE1179
EXAM1183
EXAM1182
EXAM1181
EXAM1180
PHASE 4A LINE
NURSE STATIONSW308
SW302A
SW302B
SW302C
EXAMSW350 EXAMSW352 HOUSEKEEPINGSW354
EXAM
SW356SW346
STAFFTOILETSW334 PHASE 4B LINE
EXAM
EXAMSW426
MEDICATION ROOMSW434
SOILED UTILITY RM.
SW414
EXAMSW424
NURSE STATIONCOMMUNICATION CENTER
SW406
EXAMSW420
MDWORKROOM
SW422
EVSSW410
STOR.SW445
HALL ASW409
HALL BSW407
HALL CSW435
HALL DSW425
CLINICCOORD.SW438
I.T.CLOSETSW450
STAFF TLT.SW446
PUBLICTOILETSW401
STAFFTOILETSW140
INTAKE / COUNSELINGEXIT INTERVIEW
SW142
GURNEYWAITING
CLOSETSW139
NIC
NIC
WAP
WAP WAP
WAP
WAP
WAP
WAP
WAP
W
W
3
2
PHASE 4A LINEPHASE 4B LINE
PHASE 4A LINEPHASE 4B LINE
2
T.2
1
4 TYP.
2
T.3
EX
EX
6
Scale: 1/4"=1'-0"Scale: 1/2"=1'-0"Scale: 3/8"=1'-0"Scale: 3/4"=1'-0"Scale: 1"=20'-0"Scale: 3/16"=1'-0"Scale: 3/32"=1'-0"Scale: 1"=1'-0"Scale: 1/16"=1'-0"
439 El Cajon Blvd.
El Cajon, CA. 92020
Phone: (619) 588-7730
Fax: (619) 588-2932
Cell: (619) 302-7730 [email protected]
www.mannixarch.com
Department of
Veterans Affairs
Electronic Control Systems, LLC
D.B.A. Albireo Energy
12575 Kirkham Court, Suite #1
Poway, California 92064 USA
858-513-1911 Main
858-513-1907 Fax
www.albireoenergy.com
License - C-10 #999079
Albireo EnergyPartnering for Success
SCALE: 1/8" = 1'-0"
TELECOM & CCTV FLOOR PLAN
N
KEY PLAN
PHASE 4B - FIRST FLOOR -
TELECOM & CCTV FLOOR PLAN
2
SCALE: 1/2" = 1'-0"
I.T. CLOSET 1053 - ENLARGED FLOOR PLAN
T.2
6
21
KEY NOTES
1
TERMINATE IN SIGNAL CLOSET 1079. SEE
ENLARGED FLOOR PLAN ON SHEET T.3
2
TERMINATE IN I.T. CLOSET 1053. SEE ENLARGED
FLOOR PLAN ON SHEET T.2
3
ELECTRICAL CONTRACTOR TO PROVIDE MINIMUM
(1) NEW 3/4" CONDUIT TO ABOVE CEILING SPACE
THEN PROVIDE J-HOOKS TO HOME RUN CABLES
TO SIGNAL CLOSET 1079.
4
ELECTRICAL CONTRACTOR TO PROVIDE MINIMUM
(1) NEW 3/4" CONDUIT TO ABOVE CEILING SPACE
THEN PROVIDE J-HOOKS TO HOME RUN CABLES
TO I.T. CLOSET 1053.
5
NEW TELECOM RACK. SEE RISER DIAGRAM ON
SHEET T.5
VITAL SIGN STATION
WAITINGROOMSW300
POLICESW303
FAMILYTOILET
PATIENTTOILETSW305
TRIAGE-1
TRIAGE-2
TRIAGE-3SW302D
BLUESW330
BLUESW328
EXAMSW326
TRIAGESW302
TRIAGE WAITINGSW301
CLEANROOM
EXAMSW348
HALLSW349
HALLSW417
HALLSW325
OFFICESW322
OFFICESW324
OFFICESW332
OFFICESW336
VESTIBULE1128A
CORRIDOR1128
CLINIC WAITINGSW200
BAY 5BAY 6 BAY 4 BAY 3 BAY 2 BAY 1BAY 7
SW304
SOILEDROOM
SW319
TRASH
BREAK ROOMSW418
HALL ESW417
ELECTRICALSW402EXAM
SW412EXAMSW408
EXAMSW404
SIGNALCLOSETSW416
TABLE W/
HYDRAULIC
BASE
ILLUM.
BOX
EXAM
LIGHT
A
SHELF
INSTURMENT
CAB.
STOOL
COAT
HOOKS
BLTN.
BD.
O
V
PROCEDUREROOMSW206
177 SQ. FT.
INTAKE COUNSELING(FUTURE EXAM)
SW202119 SQ. FT.
FAMILYTOILETSW26487 SQ. FT.
FAMILYTOILETSW26687 SQ. FT.
DECON1185
TOILET1184 EXAM /
TREATMENT1177
EXAM /TREATMENT
1178
OFFICE1179
EXAM1183
EXAM1182
EXAM1181
EXAM1180
PHASE 4A LINE
NURSE STATIONSW308
SW302A
SW302B
SW302C
EXAMSW350 EXAMSW352 HOUSEKEEPINGSW354
EXAM
SW356SW346
STAFFTOILETSW334 PHASE 4B LINE
PHASE 2A
PHASE 4A
PHASE 4B
SUPPLY ALCOVE
NIC
NIC
S SS
S
S SS
S
S
S
S
S
S
S
S
S
CR
CR
CR
CR
CR
CR
S
S
S
PHASE 4A LINEPHASE 4B LINE
PHASE 4A LINEPHASE 4B LINE
1 3
D2
1 2
D1
1 2
D1
1 3
D2
21
D1
D1
21
4
2
T.3
SE
C
6
PA
7
CC
TV
8
Scale: 1/4"=1'-0"Scale: 1/2"=1'-0"Scale: 3/8"=1'-0"Scale: 3/4"=1'-0"Scale: 1"=20'-0"Scale: 3/16"=1'-0"Scale: 3/32"=1'-0"Scale: 1"=1'-0"Scale: 1/16"=1'-0"
439 El Cajon Blvd.
El Cajon, CA. 92020
Phone: (619) 588-7730
Fax: (619) 588-2932
Cell: (619) 302-7730 [email protected]
www.mannixarch.com
Department of
Veterans Affairs
Electronic Control Systems, LLC
D.B.A. Albireo Energy
12575 Kirkham Court, Suite #1
Poway, California 92064 USA
858-513-1911 Main
858-513-1907 Fax
www.albireoenergy.com
License - C-10 #999079
Albireo EnergyPartnering for Success
SCALE: 1/8" = 1'-0"
ACCESS CONTROL & PA FLOOR PLAN
N
KEY PLAN
PHASE 4B - FIRST FLOOR -
PUBLIC ADDRESS & ACCESS
CONTROL FLOOR PLAN
3
SCALE: 1/2" = 1'-0"
SIGNAL ROOM 1079 - ENLARGED FLOOR PLAN
KEY NOTES
1
TERMINATE IN SIGNAL CLOSET 1079. SEE
ENLARGED FLOOR PLAN
2REFER TO WIRING DETAIL "D1" ON SHEET T.5
3REFER TO WIRING DETAIL "D2" ON SHEET T.5
4
CONNECT NEW SPEAKERS TO EXISTING PA
SYSTEM.
5
ELECTRICAL CONTRACTOR TO PROVIDE MINIMUM
(1) NEW 3/4" CONDUIT TO ABOVE CEILING SPACE
THEN PROVIDE J-HOOKS TO HOME RUN CABLES
TO HIRSCH CONTROLLER IN SIGNAL CLOSET 1079.
6EXISTING HIRSCH CONTROLLER
7 EXISTING PUBLIC ADRESS EQUIPMENT
8
EXISTING CCTV TERMINAL CABINET. FIELD VERIFY
EXACT LOCATION
T.3
6
21
Scale: 1/4"=1'-0"Scale: 1/2"=1'-0"Scale: 3/8"=1'-0"Scale: 3/4"=1'-0"Scale: 1"=20'-0"Scale: 3/16"=1'-0"Scale: 3/32"=1'-0"Scale: 1"=1'-0"Scale: 1/16"=1'-0"
439 El Cajon Blvd.
El Cajon, CA. 92020
Phone: (619) 588-7730
Fax: (619) 588-2932
Cell: (619) 302-7730 [email protected]
www.mannixarch.com
Department of
Veterans Affairs
Electronic Control Systems, LLC
D.B.A. Albireo Energy
12575 Kirkham Court, Suite #1
Poway, California 92064 USA
858-513-1911 Main
858-513-1907 Fax
www.albireoenergy.com
License - C-10 #999079
Albireo EnergyPartnering for Success
KEY PLAN
PHASE 4B - FIRST FLOOR -
TELECOM RISER DIAGRAM
4
(TYPICAL)
15
7
17
9
T.4
6
77
EXISTING
IDF RACK
EXISTING
IDF RACK
KEY NOTES
1
(1) 100 PAIR COPPER CABLE
2
(1) 24 STRAND SINGLE MODE FIBER WITH SC CONNECTORS
(1) 24 STRAND MULTI MODE FIBER WITH SC CONNECTORS &
(1) 1" INNERDUCT
3 NOT USED
4 4 POST RACK
5 2RU HORIZONTAL CABLE MANAGERS
6 VERTICAL CABLE MANAGER
7
EXISTING LADDER RACK. EXTEND AS NEEDED TO NEW TELECOM
RACK
8
1U FIBER ENCLOSURE WITH (2)12 PORT FIBER HOUSING WITH SC
CONNECTORS.
9
4" SLEEVE. PROVIDE FIRE STOPPING MATERIAL IN ALL PENETRATIONS
OF RATED WALLS.
10 48 PORT CAT 6 PATCH PANEL
11
(1) WHITE CAT6 FOR DATA
12
(1) BLUE CAT6 FOR DATA
13
(1) GREY CAT6 FOR DATA
14
120V OUTLET FOR TELECOMMUNICATIONS RACK (PROVIDED AND
INSTALLED BY ELECTRICAL CONTRACTOR)
15 TBB CONDUCTOR BY ELECTRICAL
16 J-HOOKS
17 TMGB BY ELECTRICAL
18 EXISTING IDF RACK
19
1" CONDUIT STUB UP TO CEILING. ROUTE CABLE VIA J-HOOKS TO IDF
ROOM
8
14
18
18
16" A.F.F.
16
12 13 19
1
TO EXISTING MDF IN
BASEMENT ROOM
BB102
2
8
6
5
5
10
5
10
5
10
5
10
5
6
4
11
Scale: 1/4"=1'-0"Scale: 1/2"=1'-0"Scale: 3/8"=1'-0"Scale: 3/4"=1'-0"Scale: 1"=20'-0"Scale: 3/16"=1'-0"Scale: 3/32"=1'-0"Scale: 1"=1'-0"Scale: 1/16"=1'-0"
439 El Cajon Blvd.
El Cajon, CA. 92020
Phone: (619) 588-7730
Fax: (619) 588-2932
Cell: (619) 302-7730 [email protected]
www.mannixarch.com
Department of
Veterans Affairs
Electronic Control Systems, LLC
D.B.A. Albireo Energy
12575 Kirkham Court, Suite #1
Poway, California 92064 USA
858-513-1911 Main
858-513-1907 Fax
www.albireoenergy.com
License - C-10 #999079
Albireo EnergyPartnering for Success
KEY PLAN
PHASE 4B - FIRST FLOOR -
WIRING DETAILS
5
SCALE: NONE
ACCESS CONTROL WIRING DETAIL
SCALE: NONE
CCTV SYSTEM WIRING DETAIL
SCALE: NONE
PUBLIC ADDRESS SYSTEM MOUNTING DETAIL
T.5
6
*24 VDC
POWER
SUPPLY
M8N2
CONTROLLER
CRCARD READER - WAITING SW300
DTLM C
REQUEST TO EXIT DEVICE - WAITING SW300RQE
ELECTRIFIED PANIC - WAITING SW300L
CRCARD READER - HALL SW349
DOOR CONTACT - HALL SW349DTLM C
REQUEST TO EXIT DEVICE - HALL SW349RQE
ELECTRIC LOCKSET - HALL SW349L
CRCARD READER - N. HALL SW325
DTLMC
REQUEST TO EXIT DEVICE - N. HALL SW325 RQE
ELECTRIFIED PANIC - N. HALL SW325L
CRCARD READER - TRIAGE WAITING SW301
DOOR CONTACT - TRIAGE WAITING SW301DTLMC
REQUEST TO EXIT DEVICE - TRIAGE WAITING SW301RQE
ELECTRIFIED PANIC - TRIAGE WAITING SW301L
EXISTING
PANEL
SLOT 3 SLOT 4
SLOT 6
3/4" CO. TO
MOUNTING HARDWARE
CEILING
CCTV CAMERA
BACKBOX HOUSING
CCTV P/T/Z CAMERA
1-1/2" C.O. TO DIGI*TRAC ACCESS &
SECURITY SYSTEM CONTROLLER
AND 24V POWER SUPPLY
DOOR CONTACT
3/4" CO. TO CARD
READER
KEYPAD CARD READER @ OUTSIDE
(UNSECURE SPACE) WITH
HIRSCH MB2SL MOUNTING BOX
3/4" CO.
SINGLE DOOR
ELECTRIC STRIKE
SINGLE DOOR MORTISE LOCKSET WITH ELECTRIC STRIKE
AND DOOR CONTACTS
PROVIDE MOUNTING BOX TO SECURE LINE
MODULE AT SECURE SIDE
56" - 58"
TO CENTER
AFF
REX (REQUEST TO EXIT)
MOUNT TO 4S BOX
3/4" CO.
DOUBLE DOOR WITH PANIC HARDWARE
AND DOOR CONTACTS
PROVIDE MOUNTING BOX TO SECURE LINE
MODULE AT SECURE SIDE
DOOR CONTACT3/4" CO. TO CARD
READER
3/4" CO.
KEYPAD CARD READER @ OUTSIDE
(UNSECURE SPACE) WITH
HIRSCH MB2SL MOUNTING BOX
TERMINATE CONDUIT AT
CENTER HINGE
56" - 58"
TO CENTER
AFF
REX (REQUEST TO EXIT)
MOUNT TO 4S BOX
3/4" CO.
1-1/2" C.O. TO DIGI*TRAC ACCESS &
SECURITY SYSTEM CONTROLLER
AND 24V POWER SUPPLY
ABOVE CEILINGABOVE CEILING
NON-RATED CEILING
9.75"
CEILING TILE
CUT TILE HOLE
4.5"
TILE BRIDGE
BAFFLE
SPEAKER/BAFFLE
ASSEMBLY
SUPPORT TO BUILDING
STRUCTURE AS
REQUIRED
PROVIDE SEISMIC SUPPORT OF
SPEAKER ROUGH-IN ASSEMBLY AS
REQUIRED BY SPECIFICATION.
SPEAKER
C 10A-T70
OR EQUAL
SPEAKER BACKBOX
CS 95-8
OR EQUAL
SCALE: NONE
TYPICAL SINGLE DOOR DETAIL
SCALE: NONE
TYPICAL DOUBLE DOOR DETAIL
1 2
3
4 5
CRCARD READER - TRIAGE SW302
DOOR CONTACT - TRIAGE SW302DTLMC
REQUEST TO EXIT DEVICE - TRIAGE SW302RQE
ELECTRIFIED PANIC - TRIAGE SW302L
C
SLOT 1
SLOT 5
DOOR CONTACT - WAITING SW300DOOR CONTACT - N. HALL SW325
CRCARD READER - S. HALL SW325
DTLM C
REQUEST TO EXIT DEVICE - S. HALL SW325RQE
ELECTRIFIED PANIC - S. HALL SW325L
SLOT 2
DOOR CONTACT - S. HALL SW325
C
BLDG NUMBER-ROOM NUMBER-JACK NUMBER
TELECOM RM. NUMBER-RACK NUMBER-PATCH PANEL
BLUE
CAT6
JACK
D1
BLDG NUMBER-ROOM NUMBER-JACK NUMBER
TELECOM RM. NUMBER-RACK NUMBER-PATCH PANEL
GRAY
CAT6
JACK
V1
BLDG NUMBER-ROOM NUMBER-JACK NUMBER
TELECOM RM. NUMBER-RACK NUMBER-PATCH PANEL
V1
D2D1
GRAY
VOICE
JACK
WHITE
CAT6
JACK
BLUE
CAT6
JACK
BLANK
Scale: 1/4"=1'-0"Scale: 1/2"=1'-0"Scale: 3/8"=1'-0"Scale: 3/4"=1'-0"Scale: 1"=20'-0"Scale: 3/16"=1'-0"Scale: 3/32"=1'-0"Scale: 1"=1'-0"Scale: 1/16"=1'-0"
439 El Cajon Blvd.
El Cajon, CA. 92020
Phone: (619) 588-7730
Fax: (619) 588-2932
Cell: (619) 302-7730 [email protected]
www.mannixarch.com
Department of
Veterans Affairs
Electronic Control Systems, LLC
D.B.A. Albireo Energy
12575 Kirkham Court, Suite #1
Poway, California 92064 USA
858-513-1911 Main
858-513-1907 Fax
www.albireoenergy.com
License - C-10 #999079
Albireo EnergyPartnering for Success
KEY PLAN
PHASE 4B - FIRST FLOOR -
TELECOM DETAILS
6
T.6
6
NOTES
1. EQUIPMENT RACKS AND CABINETS SHALL BE PROVIDED
WITH VERTICAL GROUND STRIPS.
2. LOCAL ELECTRICAL CODES SHALL BE COMPLIED WITH.
3. THE GROUNDING/EARTHING SYSTEM SHALL COMPLY WITH
J-STD-607-A.
4. ALL GROUNDING/EARTHING CONDUCTORS SHALL BE
COPPER.
5. LUGS, TAPS, GROUNDING STRIPS, AND BUSBARS SHALL BE
UL LISTED AND MADE OF PREMIUM QUALITY TIN-PLATED
ELECTROLYTIC COPPER THAT PROVIDES LOW ELECTRICAL
RESISTANCE WHILE INHIBITING CORROSION. ANTIOXIDANT
SHALL BE USED WHEN MAKING BONDING CONNECTIONS.
6. TWO-HOLE LUGS SHALL BE USED BECAUSE THEY RESIST
LOOSENING WHEN TWISTED (BUMPED) OR EXPOSED TO
VIBRATION. ALL LUGS SHALL BE IRREVERSIBLE
COMPRESSION AND MEET THE REQUIREMENTS OF NRTL.
LUGS WITH INSPECTION WINDOWS SHALL BE USED IN ALL
NON-CORROSIVE ENVIRONMENTS SO THAT CONNECTIONS
MAY BE INSPECTED FOR FULL CONDUCTOR INSERTION.
7. DIE INDEX NUMBERS SHALL BE EMBOSSED ON ALL
COMPRESSION CONNECTIONS TO ALLOW CRIMP
INSPECTION.
8. CABLE ASSEMBLIES SHALL BE UL LISTED AND CSA
CERTIFIED. GROUND CABLES SHALL BE A DISTINCTIVE
GREEN OR GREEN/YELLOW IN COLOR TO SIGNIFY THAT
THEY ARE GROUNDING CONDUCTORS, AND ALL JACKETS
SHALL BE UL, VW-1 FLAME RATED.
9. A TELECOMMUNICATIONS MAIN GROUNDING BUSBAR
(TMGB) SHALL BE LOCATED IN EACH BUILDING MDF. A
TELECOMMUNICATIONS GROUNDING BUSBAR (TGB) SHALL
BE LOCATED IN EACH TELECOMMUNICATIONS SPACE. THE
TGB SHALL BE GROUNDED/EARTHED TO THE
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR (TMGB).
10.THE TMGB SHALL BE BONDED TO THE BUILDING STEEL AND
GROUNDED/EARTHED TO THE ELECTRICAL SERVICE
GROUND ACCORDING TO J-STD-607-A GUIDELINES. EACH
TGB SHALL BE BONDED TO BUILDING STEEL AND THE
ELECTRICAL PANEL SERVING EQUIPMENT IN THE
TELECOMMUNICATIONS SPACE.
11.THE GAUGE OF THE CONNECTING GROUND/EARTH CABLE
(TELECOMMUNICATIONS BONDING BACKBONE (TBB)) WILL
FOLLOW J-STD-607-A GUIDELINES, AS IS SHOWN IN THE
TABLE "TBB CONDUCTOR SIZING"
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR (TMGB)
SCALE: N.T.S.
THE TMGB SHALL BE PREDRILLED COPPER BUSBAR WITH
HOLES FOR USE WITH STANDARD-SIZED LUGS, HAVE MINIMUM
DIMENSIONS OF 1/4 INCH THICK BY 4 INCHES WIDE BY A
MINIMUM OF 12 INCHES LONG (SCOPE AND STANDARD
DICTATES ACTUAL LENGTH) AND SHALL BE LISTED BY A
NATIONALLY RECOGNIZED TESTING LIBRARY.
TELECOMMUNICATIONS GROUNDING BUSBAR (TGB)
SCALE: N.T.S.
THE TGB SHALL BE PREDRILLED COPPER BUSBAR WITH HOLES
FOR USE WITH STANDARD-SIZED LUGS, HAVE MINIMUM
DIMENSIONS OF 1/4 INCH THICK BY 2 INCHES WIDE BY A
MINIMUM OF 10 INCHES LONG (SCOPE AND STANDARD
DICTATES ACTUAL LENGTH) AND SHALL BE LISTED BY AN
NRTL.
COPPER COMPRESSION TWO-HOLE LUG
SCALE: N.T.S.
ONLY TWO-HOLE LUGS SHALL BE USED. LUGS SHALL BE
IRREVERSIBLE COMPRESSION AND MEET REQUIREMENTS OF
NRTL. LUGS WITH INSPECTION WINDOWS SHALL BE USED IN
ALL NON-CORROSIVE ENVIRONMENTS SO THAT CONNECTIONS
MAY BE INSPECTED FOR FULL CONDUCTOR INSERTION. DIE
INDEX NUMBERS SHALL BE EMBOSSED ON ALL COMPRESSION
CONNECTIONS TO ALLOW CRIMP INSPECTION.
ROUTE THE TBB TO EACH TGB IN AS STRAIGHT A PATH AS POSSIBLE. THE TBB SHOULD
BE INSTALLED AS A CONTINUOUS CONDUCTOR, AVOIDING SPLICES WHERE POSSIBLE
XXXXX-YYYY-ZZZ
XXX-X-XX
PATCH PANEL #
VOICE
RACK #
BUIDLING # JACK #
ROOM #
PRE-PRINTED UNIQUE
ADHESIVE WRAPAROUND LABEL
PRE-PRINTED UNIQUE WRAPAROUND ADHESIVE
LABELS 6 INCHES FROM TERMINATION, BOTH
ENDS OF ALL LOW VOLTAGE CABLE
PRE-PRINTED UNIQUE
ADHESIVE WRAPAROUND LABEL
EACH CONDUIT SHALL BE IDENTIFIED WITH:
1. BASIC AREA RUN TO
2. J-BOX # OR
3. FAR END TERMINATION POINT
CEILING
FLOOR
JACK POSITIONS
1
W-G
2
G
3
W-O
4
BL
5
W-BL
6
O
7
W-BR
8
BR
PAIR-2 PAIR-1 PAIR-4
PAIR-3
THE ILLUSTRATIONS ARE FRONT VIEWS OF THE CONNNECTOR.
THE WIRE COLORS INDICATED ARE ASSOCIATED WITH THE
STATION DISTRIBUTION CABLE.
GENERAL NOTES:
1. WIRE ALL UTP CABLES
TO T568A WIRING
SCHEEME.
2. PROVIDE NON
PROPRIETARY KEYSTONE
JACKS AND FACEPLATES
FOR ALL UTP
TERMINATION
LOCATIONS.
3. TEST ALL TERMINATIONS
IN ACCORDANCE WITH
EIA/TIE 568.
4. LABEL ALL DEVICES IN
ACCORDANCE WITH
ANSI/TIA/EIA-606-A
GREY
CAT6
JACK
TELECOM ROOM #
TBB CONDUCTOR SIZING
LENGTH IN LINEAR M (FT) SIZE (AWG)
LESS THAN 4 (13)
6
4 - 6 (14 - 20)
3
6 - 8 (21 - 26)
3
8 - 10 (27 - 33)
2
10 - 13 (34 - 41)
1
13 - 16 (42 - 52)
1/0
16 - 20 (53 - 66)
2/0
GREATHER THAN 20 (66)
3/0
SCALE: NOT TO SCALE
DATA OUTLET
3
SCALE: NOT TO SCALE
VOICE/DATA MODULAR DETAIL
4
SCALE: NOT TO SCALE
TYPICAL CONDUIT LABELING
5
SCALE: NOT TO SCALE
USOC T568A WIRING DETAIL
6
SCALE: NOT TO SCALE
TYPICAL CABLE LABELING
7
SCALE: NOT TO SCALE
GROUNDING BUSBAR DETAILS AND NOTES
8
SCALE: NOT TO SCALE
TEL/DATA OUTLET
1
SCALE: NOT TO SCALE
VOICE OUTLET
2