Control System for heating and cooling applications

MDG

Technical Specification

Page 2: T-H Control System - Home :: TPS Thermal Controls · 2x relay outputs, max 2 A - 230 Vac 5x triac outputs, max 3 A - 230 Vac 1x analog output 0-10 Vdc 1x analog output 3 Vdc (20 mA)

MDG System Technical Specification 1/13

General MDG is a simple to use controller for regulation of temperature and humidity in dwellings with one or more heating-cooling zones. The system not only makes it easier to achieve building regulation compliance, but also simplifies the installation process for the contractor. The system foresees one or more room controllers providing time and temperature control, which are wired on a BUS within the dwelling. For example, one of the room controllers can be installed in the living zone and the others in the sleeping zone, bathrooms etc. The system consists of:

• Control board MM4TTL

• Room controller UA10/UA11

• Room thermostat TSRM

• 12 Vdc supplier ALI3010

• Minimaster GSM100FP

• Temperature probes

• Remote monitoring system

Control board MM4TTL

This is a custom designed electronic controller for heating/cooling management. It includes all the measurement and control circuits to drive pumps, valves and other devices used in such applications. It has also three communication channels to connect it to slave devices as well as to a main communication bus used to collect data from the modules.

Technical characteristics 2x relay outputs, max 2 A - 230 Vac 5x triac outputs, max 3 A - 230 Vac 1x analog output 0-10 Vdc 1x analog output 3 Vdc (20 mA) 1x free voltage analog output 1x PWM output to manage a variable speed pump 2x free voltage contacts 4x PT1000 temperature inputs 3x NTC temperature inputs 1x RS485 insulated communication channel 1x RS485 non insulated communication channel 1x local bus communication channel 1x power supply 12-18 Vdc 1x 8-10 Vdc power supply for UA10/UA11 Operating temperature: 5 - 60°C

Page 3: T-H Control System - Home :: TPS Thermal Controls · 2x relay outputs, max 2 A - 230 Vac 5x triac outputs, max 3 A - 230 Vac 1x analog output 0-10 Vdc 1x analog output 3 Vdc (20 mA)

MDG System Technical Specification 1/13

Room controller UA10/UA11 The Room Controller (UA10 for heating, UA11 for heating and cooling) is a white ABS box with back lit graphic display. It must be installed in the apartment in such a way to read the average room temperature. It allows holiday settings, summer and winter operation programming, heating and hot water programming. It has to be connected to the MM4TTL by means a 4x0.35 mm2 screened cable. The cable must not be installed adjacent to other 230 Volt lines. The room controller’s power is supplied by the MM4TTL board and does not require batteries. Technical characteristics 3x temperature set-points (comfort, reduced and anti-freeze) 4x daily schedules (comfort, reduced, comfort, reduced 1x NTC room sensor 1x STH11 humidity sensor (UA11 only) 1x local bus communication channel 1x 8-10 Vdc power supply (from MM4TTL)

Room thermostat TSRM It is a simple and functional room thermostat allowing to increase-decrease by 6 °C (or 14-26 °C) the set of the UA10/UA11 thus allowing to control each room independently.

Technical characteristics 1x set-point regulation range (+/- 6 °C the set point of the UA10/11) 1x Relay output max 2 A - 230 Vac 1x NTC room sensor 1x RS485 non insulated communication channel 1x Power supply 230 Vac

Page 4: T-H Control System - Home :: TPS Thermal Controls · 2x relay outputs, max 2 A - 230 Vac 5x triac outputs, max 3 A - 230 Vac 1x analog output 0-10 Vdc 1x analog output 3 Vdc (20 mA)

MDG System Technical Specification 1/13

Power supplier ALI3010

It provides power supply at 12 Vdc to the MM4TTL and at 5 Vdc to the heat meter SND or any other device.

Minimaster GSM100FP The Minimaster is used for remote monitoring. It allows the direct connection from and to a remote supervisor personal computer to be provided with a GSM modem. Main features The firmware allows to perform the following functions: � Sending SMS to a remote monitoring system with

programmable intervals of all working parameters, namely:

− Project code

− Apartment code

− Room temperature

− Room humidity

− Setpoint

− Primary water flow

− Primary supply temperature

− Primary return temperature

− Apartment circuit supply temperature

− Apartment circuit return temperature

− Storage temperature

− Outdoor temperature

− Consumptions (heating cooling and cold water)

− Credit card parameters � Sending via SMS alarms (together with project and apartment codes) to a list of GSM

numbers (GSM supervisor, GSM maintenance); the list of GSM numbers can be set on the supervisor only;

� Receiving SMS commands to change status and setpoint of the room unit from any GSM (GSM supervisor, maintenance or GSM user) if known password and apartment code

� The SMS variable size from the MiniMaster is max 160 characters � The SMS alarm size is max 50 characters

Page 5: T-H Control System - Home :: TPS Thermal Controls · 2x relay outputs, max 2 A - 230 Vac 5x triac outputs, max 3 A - 230 Vac 1x analog output 0-10 Vdc 1x analog output 3 Vdc (20 mA)

MDG System Technical Specification 1/13

Temperature probes The control system can be completed with the following probes according to the required functions:

• Water probe PT1000: it is normally used to measure the temperature of the apartment circuit return;

• Water probes NTC: they allow the measurement of the apartment circuit supply and the dhw cylinder;

• Ambient probe SES: it allows to regulate the apartment circuit supply temperature according to the outside temperature (climatic regulation);

Remote monitoring system The Master Unit is the plant management system and consists of a power supply and modem communication interface. The module provides the monitoring of working parameters and consumptions of up to 32 or 128 or 384 apartments. The unit is also provided with four digital inputs for alarm acquisition.

Page 6: T-H Control System - Home :: TPS Thermal Controls · 2x relay outputs, max 2 A - 230 Vac 5x triac outputs, max 3 A - 230 Vac 1x analog output 0-10 Vdc 1x analog output 3 Vdc (20 mA)

MDG System Technical Specification 1/13

Example 1: heating only single zone It is the basic solution without UA10, with TSRM only. The final user can adjust the set-point in the range between 14 and 26 °C (or any other +/- 6 °C range a preset value).

Code Qty Function MM4TTL 1 Pump and mixing valve management TSRM 1 Setting +/- 6 °C ALI3010 1 MM4TTL power supply at 12 Vdc

Options SMA 1 Apartment circuit supply (climatic regulation with mixing valve) SMA 1 Dhw cylinder sensor for dhw warm up PT1000 1 Ambient sensor for climatic regulation SES 1 Sonda esterna per regolazione climatica GSM100FP 1 GSM Minimaster for remote monitoring

Page 7: T-H Control System - Home :: TPS Thermal Controls · 2x relay outputs, max 2 A - 230 Vac 5x triac outputs, max 3 A - 230 Vac 1x analog output 0-10 Vdc 1x analog output 3 Vdc (20 mA)

MDG System Technical Specification 1/13

Example 2: heating or cooling single zone It is the basic solution with UA10 (or UA11 for cooling). The user can set the room set-points (comfort, reduced and anti-freeze), 4 daily schedules (comfort, reduced, comfort, reduced).

Code Qty Function MM4TTL 1 Pump and mixing valve management UA10/UA11 1 Setting of comfort parameters ALI3010 1 MM4TTL power supply at 12 Vdc

Options SMA 1 Apartment circuit supply (climatic regulation with mixing valve) SMA 1 Dhw cylinder sensor for dhw warm up PT1000 1 Ambient sensor for climatic regulation SES 1 Sonda esterna per regolazione climatica GSM100FP 1 GSM Minimaster for remote monitoring

Page 8: T-H Control System - Home :: TPS Thermal Controls · 2x relay outputs, max 2 A - 230 Vac 5x triac outputs, max 3 A - 230 Vac 1x analog output 0-10 Vdc 1x analog output 3 Vdc (20 mA)

MDG System Technical Specification 1/13

Example 3: heating only 2 zones This solution allows the independent temperature control of two zones, each managed by its own TSRM permitting to adjust the set-point in the range between 14 and 26 °C (or any other +/- 6 °C range a preset value).

Code Qty Function MM4TTL 1 Pump and mixing valve management TSRM Setting +/- 6 °C ALI3010 1 MM4TTL power supply at 12 Vdc Options SMA 1 Apartment circuit supply (climatic regulation with mixing valve)

SMA 1 Dhw cylinder sensor for dhw warm up PT1000 1 Ambient sensor for climatic regulation SES 1 Sonda esterna per regolazione climatica GSM100FP 1 GSM Minimaster for remote monitoring

Page 9: T-H Control System - Home :: TPS Thermal Controls · 2x relay outputs, max 2 A - 230 Vac 5x triac outputs, max 3 A - 230 Vac 1x analog output 0-10 Vdc 1x analog output 3 Vdc (20 mA)

MDG System Technical Specification 1/13

Example 4: heating and cooling 2 zones The zone 1, “master”, is managed by a UA10 (heating only) or a UA11 (cooling). The zone 2, “slave”, has its own TSRM. The UA10/UA11 permits the user to set the room set-points (comfort, reduced and anti-freeze) and 4 daily schedules (comfort, reduced, comfort, reduced). The TSRM permits to adjust the set-point in the range between+/- 6 °C the set point of the UA10/11. The UA11 allows also to bring on and off, according the RH set-point, a dehumidifier by means of a free voltage contact of the MM4TTL. Furthermore it is possible to command a three-way valve for summer/winter changeover.

Code Qty Function MM4TTL 1 Pump and mixing valve management UA10/UA11 1 Setting of comfort parameters TSRM 1 Setting +/- 6 °C ALI3010 1 MM4TTL power supply at 12 Vdc Options SMA 1 Apartment circuit supply (climatic regulation with mixing valve) SMA 1 Dhw cylinder sensor for dhw warm up PT1000 1 Ambient sensor for climatic regulation SES 1 Sonda esterna per regolazione climatica GSM100FP 1 GSM Minimaster for remote monitoring

Page 10: T-H Control System - Home :: TPS Thermal Controls · 2x relay outputs, max 2 A - 230 Vac 5x triac outputs, max 3 A - 230 Vac 1x analog output 0-10 Vdc 1x analog output 3 Vdc (20 mA)

MDG System Technical Specification 1/13

Example 5: heating and cooling 2 zones Both the zones are controlled by a UA10 (heating only) or a UA11 (cooling). The UA10/UA11’s permit the user to set the room set-points (comfort, reduced and anti-freeze) amd 4 daily schedules (comfort, reduced, comfort, reduced). The UA11 allows also to bring on and off, according the RH set-point, a dehumidifier by means of a free voltage contact of the MM4TTL. Furthermore it is possible to command a three-way valve for summer/winter changeover.

Code Qty Function MM4TTL 1 Pump and mixing valve management UA10/UA11 2 Setting of comfort parameters

ALI3010 1 MM4TTL power supply at 12 Vdc Options SMA 1 Apartment circuit supply (climatic regulation with mixing valve) SMA 1 Dhw cylinder sensor for dhw warm up PT1000 1 Ambient sensor for climatic regulation SES 1 Sonda esterna per regolazione climatica

GSM100FP 1 GSM Minimaster for remote monitoring

Page 11: T-H Control System - Home :: TPS Thermal Controls · 2x relay outputs, max 2 A - 230 Vac 5x triac outputs, max 3 A - 230 Vac 1x analog output 0-10 Vdc 1x analog output 3 Vdc (20 mA)

MDG System Technical Specification 1/13

Example 6: heating and cooling of more zones The zone 1, “master”, is managed by a UA10 (heating only) or a UA11 (cooling). The other zones (max 12), “slave”, have their own TSRM. The UA10/UA11 permits the user to set the room set-points (comfort, reduced and anti-freeze) and 4 daily schedules (comfort, reduced, comfort, reduced). The TSRM permits to adjust the set-point in the range between+/- 6 °C the set point of the UA10/11. The UA11 allows also to bring on and off, according the RH set-point, a dehumidifier by means of a free voltage contact of the MM4TTL. Furthermore it is possible to command a three-way valve for summer/winter changeover.

Code Qty Function MM4TTL 1 Pump and mixing valve management UA10/UA11 1 Setting of comfort parameters TSRM (*) Setting +/- 6 °C ALI3010 1 MM4TTL power supply at 12 Vdc

Options SMA 1 Apartment circuit supply (climatic regulation with mixing valve) SMA 1 Dhw cylinder sensor for dhw warm up PT1000 1 Ambient sensor for climatic regulation SES 1 Sonda esterna per regolazione climatica GSM100FP 1 GSM Minimaster for remote monitoring

(*) total zone number minus 1 as managed by the UA10/UA11, max 12

Page 12: T-H Control System - Home :: TPS Thermal Controls · 2x relay outputs, max 2 A - 230 Vac 5x triac outputs, max 3 A - 230 Vac 1x analog output 0-10 Vdc 1x analog output 3 Vdc (20 mA)

MDG System Technical Specification 1/13

Example 7: heating and cooling of more zones There are two “master” zones each managed by a UA10 (heating only) or a UA11 (cooling). The other zones (max 11), “slave”, have their own TSRM. The UA10/UA11 permits the user to set the room set-points (comfort, reduced and anti-freeze) and 4 daily schedules (comfort, reduced, comfort, reduced). The TSRM permits to adjust the set-point in the range between+/- 6 °C the set point of the UA10/11. The UA11 allows also to bring on and off, according the RH set-point, 2dehumidifiers by means of a free voltage contact of the MM4TTL. Furthermore it is possible to command a three-way valve for summer/winter changeover.

Code Qty Function MM4TTL 1 Pump and mixing valve management UA10/UA11 2 Setting of comfort parameters

TSRM (*) Setting +/- 6 °C ALI3010 1 MM4TTL power supply at 12 Vdc Options SMA 1 Apartment circuit supply (climatic regulation with mixing valve) SMA 1 Dhw cylinder sensor for dhw warm up PT1000 1 Ambient sensor for climatic regulation SES 1 Sonda esterna per regolazione climatica

GSM100FP 1 GSM Minimaster for remote monitoring (*) total zone number minus 2 as managed by the UA10/UA11, max 11

Page 13: T-H Control System - Home :: TPS Thermal Controls · 2x relay outputs, max 2 A - 230 Vac 5x triac outputs, max 3 A - 230 Vac 1x analog output 0-10 Vdc 1x analog output 3 Vdc (20 mA)

NOTES

Page 14: T-H Control System - Home :: TPS Thermal Controls · 2x relay outputs, max 2 A - 230 Vac 5x triac outputs, max 3 A - 230 Vac 1x analog output 0-10 Vdc 1x analog output 3 Vdc (20 mA)