3 system structure 3 System Structure As the controller, XC series PLC can connect with many types of peripheral equipments, expansions etc. In this chapter, we mainly tells the peripheral devices, the connection principle of CPU with expansions, installation, calculate the I/O points, input/output ID etc. For the introduction of expansions, please refer to chapter 8; 3-1System Structure 3-2Peripheral Devices 3-3Combination Principle 3-4Expansion's ID assignment 3-5Install the Products

System Structure - primeta.com.uaprimeta.com.ua/download/manual_plc/3_System_Structure.pdf※1:Please use the program cable offered by Xinje Electronic, or make the cable by yourself;

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: System Structure - primeta.com.uaprimeta.com.ua/download/manual_plc/3_System_Structure.pdf※1:Please use the program cable offered by Xinje Electronic, or make the cable by yourself;

3 system structure

3 System Structure

As the controller, XC series PLC can connect with many types of peripheral equipments,

expansions etc. In this chapter, we mainly tells the peripheral devices, the connection principle of

CPU with expansions, installation, calculate the I/O points, input/output ID etc.

For the introduction of expansions, please refer to chapter 8;

3-1.System Structure

3-2.Peripheral Devices

3-3.Combination Principle

3-4.Expansion's ID assignment

3-5.Install the Products

Page 2: System Structure - primeta.com.uaprimeta.com.ua/download/manual_plc/3_System_Structure.pdf※1:Please use the program cable offered by Xinje Electronic, or make the cable by yourself;

3-1.System Structure

In the below Graph, we show the common system structure according to XC series PLC basic

configuration. Via this graph, we could know the basic connection among PLC and peripheral

equipments; also classic applications of PLC's each COM port, connection and expansion etc.

FGCOM

COM X0X1X2X3X4X5X6X7 X15

X16X14X13

X12X11

X10X17X20X21

PWR

Y

X

PORT1 PORT2

Y15Y14

Y13Y12COM3

Y5Y7

Y6Y11COM4Y10

Y4Y3COM2

Y2COM1

Y1COM0

Y0AB24V

0V

10 4532

RUN

ERR

XC3-32R-E

67

7623 5401

AO1AO0VO0 VO1

C1C0

VI3AI3

C0VI0 AI1AI0 VI1 C2 AI2

C3VI2C1

PWR

AI

AO

AO1AO0

VO0 VO1C1C0

VI3AI3

C0

VI0 AI1AI0 VI1 C2 AI2

C3VI2C1

PWR

AI

AOAO

AI

PWR

C1 VI2 C3AI2C2VI1AI0

AI1VI0C0

AI3VI3

C0 C1VO1VO0

AO0 AO1

※1:In the above graph, the communication devices connected to the COM port are only samples for your

reference. Each COM port can connect with many devices in real applications.

HMI

Expansion

Inverter

Network Module

Program Software

CPU Unit BD Card

Page 3: System Structure - primeta.com.uaprimeta.com.ua/download/manual_plc/3_System_Structure.pdf※1:Please use the program cable offered by Xinje Electronic, or make the cable by yourself;

3 system structure

3-2.Peripheral Equipments

XC series PLC basic units can work with many kinds of peripheral equipments.

3-2-1.Program Software

Via program software, users can write to or upload program from PLC. Real time monitor PLC,

configure PLC etc; After installing XCPPro on your PC, use the program cable, via COM1 or

COM2 on PLC (CPU Units) to link PLC with XCPPro;

l Program Interface

※1:Please use the program cable offered by Xinje Electronic, or make the cable by yourself; the making method

is showing in Chapter 2-4

Page 4: System Structure - primeta.com.uaprimeta.com.ua/download/manual_plc/3_System_Structure.pdf※1:Please use the program cable offered by Xinje Electronic, or make the cable by yourself;

3-2-2.Human Machine Interface (HMI)

The HMI link PLC to the operators. The HMI can send the commands from operators to PLC,

then PLC execute the commands.

XC series PLC support diverse brands of HMI; the connection is based on the

communication protocol. Generally communicate via Modbus protocol, the detailed parameters

setting depends on the HMI.

The Xinje HMI can work with PLC directly (the communication parameters are set in

accordance already). Presently Xinje HMI has TP, OP, MP three series.

l Size: 4.7"、5.7"、7"、10.4"

l Display: 256 true color TFT

l Operation: Touch Screen

l Interface: RS232、RS422、RS485

l Communication work with many PLC brands, inverters, instruments etc.

Communicate with Xinje Inverters

Driver panel printer directly

Dual COM ports, work with two different devices separately

Support free format protocol, the user can write the driver program freely

l Recipe

l Advanced Function

l RTC: Real Time Clock

l Password: nine-level setting

1 TP Series Touch Panel

Monitors

l Size 3.7"、5.7"

l Display Blue LCD、256 true color

l Buttons Nr. 7、20、42

l Interface RS232、RS485

l Communication work with many PLC brands.

Communicate with Xinje Inverters

l RTC

2

3 MP Series Operation Panels with

Touch Function

OP Series Operation

Panels

Page 5: System Structure - primeta.com.uaprimeta.com.ua/download/manual_plc/3_System_Structure.pdf※1:Please use the program cable offered by Xinje Electronic, or make the cable by yourself;

3 system structure

3-2-3.Network Module

PLC can build Modbus network, the special models can build CANBUS network.

If the basic units configure with the special network module, they can connect to GPRS network,

Ether net etc.

l Transfer data wirelessly, open and transparent;

l Remote program and debug PLC, realize upload/download PLC;

l Integral data transfer terminal of TCP/IP protocol pallet, support TCP, UDP, DNS, PPP

etc.

l Standard industrial interface (RS-232 or RS-485)

l Support long time online mode, equipped re-dial and heart-beat functions;

l Support SMS to control PLC

l Support local configuration

l Support GPRS network and GSM network

l Suitable for distribution system and remote control applications.

l Size 3.7"、7"

l Display 256 true color、blue LCD

l Buttons Nr.: 26、42, the LCD is a touch screen

l Interface: RS232、RS485

l Communication work with many PLC brands.

Communicate with Xinje Inverters

l RTC: Real Time Clock

1 G-BOX

Page 6: System Structure - primeta.com.uaprimeta.com.ua/download/manual_plc/3_System_Structure.pdf※1:Please use the program cable offered by Xinje Electronic, or make the cable by yourself;

As industrial Ether Net module, T-BOX supports Modbus-RTU devices, the design is applied to

industrial Ether net control system.

l Remote integral maintenance and diagnose of PLC program on IP devices;

l Remote integral monitor of PLC program on IP devices;

l The traditional Modbus communication is one master, multi-slave form. The

communication speed is slow. Via the connection by T-Box, users can realize the data

exchange among master PLC and each subsidiary PLCs.

l Realize flexible distributing automation structure, simplify the system management

l Realize Ether net visit via RJ45 interface, the communication is based on standard

TCP/IP protocol

l Realize remote program, monitor, diagnose via industrial Ether net, save great time and

cost;

l Store and operate data information via Ether net, build base to simplify the data disposal

and file

l Enable the communication between Ether net and automation equipments, enable these

devices to be used in complicated systems;

l High performance-price ratio, link the ether net to all the automation devices and levels

in a simple form.

l Easy to maintenance, support simple diagnose function

2 T-BOX

Page 7: System Structure - primeta.com.uaprimeta.com.ua/download/manual_plc/3_System_Structure.pdf※1:Please use the program cable offered by Xinje Electronic, or make the cable by yourself;

3 system structure

3-3.Configuration Principle

About COM port

l XC series PLC (CPU units) are usually equipped with COM1 and COM2.

l Normally, both COM ports can be used to program, download, communication; but please

make sure not change the parameters on two COM ports at one time, or the COM ports can't

be used to program and download any more;

l COM2 is equipped with RS232 and RS485. But COM2 can't use these two modes at one time;

that's to say, COM2 can only be applied to one interface mode;

Correct(√) Incorrect(×)

About Expansion Devices

l Generally, one CPU unit can work with different types of expansions, can expand digital I/O,

analog I/O, temperature control etc.

l One CPU unit can work with 7 expansions and an extra BD card.

N X0 X2 X4 X6X7X5X3X1FGL

COM

A0V B COM0 Y1 Y2 Y4

Y5Y3COM1Y024V

PWR

RUN

ERR

XC-8PT

Y

X

45 67

3210

7654

32100 1 23

4 5 67

0 1 23

7654

X

Y

XC3-4AD2DA

ERR

RUN

PWR

24V Y0 COM1 Y3 Y5Y4Y2Y1COM0B0V

A

COML FG X1 X3 X5 X7

X6X4X2X0NN X0 X2 X4 X6X7X5X3X1FGL

COM

A0V B COM0 Y1 Y2 Y4

Y5Y3COM1Y024V

PWR

RUN

ERR

XC-E16YR

Y

X

4 5 67

3210

7654

3210 0 1 23

4 5 67

0 1 23

7654

X

Y

XC-E16X

ERR

RUN

PWR

24V Y0 COM1 Y3 Y5Y4Y2Y1COM0B0V

A

COML FG X1 X3 X5 X7

X6X4X2X0N N X0 X2 X4 X6X7X5X3X1FGL

COM

A0V B COM0 Y1 Y2 Y4

Y5Y3COM1Y024V

PWR

RUN

ERR

XC-8AD

Y

X

45 6 7

3210

7654

321001 2 3

45 6 7

01 2 3

7654

X

Y

XC-E8X8YR

ERR

RUN

PWR

24V Y0 COM1 Y3 Y5Y4Y2Y1COM0B0V

A

COML FG X1 X3 X5 X7

X6X4X2X0N N X0 X2 X4 X6X7X5X3X1FGL

COM

A0V B COM0 Y1 Y2 Y4

Y5Y3COM1Y024V

PWR

RUN

ERR

XC-6PT-P

Y

X

4 56 7

3210

7654

3210

Y

X

X0X1COM

COM X2X3X4X5X6X7X10X11X12X13X14X15X16X17X20X21X22X23X24X25X26X27X30

X37X40X36

X35X34

X33X32

X31 X41X42X43

Y27Y26

Y25Y24

Y15Y17

COM6Y21

Y20COM7Y23Y22

Y16Y13Y14COM5

Y11Y12

Y7Y10

Y6COM4

Y4Y5

COM3Y3

Y2Y1COM2

Y0COM1COM0

CAN+CAN-

AB0V

24V

PORT2PORT1XC5-60R-E

ERR

RUNPWR

01 32 6754

45 762310

l After connect the CPU unit with the expansion, if the "PWR" LED on expansion ON, then

the expansion can work properly; after installing the BD card to CPU unit, users need to

configure it before using;

How to calculate the I/O

l After connect with the expansions, the total I/O points=I/O on basic unit+I/O on expansions.

l Digital I/O is octal

l Analog I/O is Decimal

l After expansion, the total I/O can reach 284 points

RS232 Target

device COM2

RS232 Target

device 1

COM2

RS485

Target

device 2

RS485 Target

device COM2

Page 8: System Structure - primeta.com.uaprimeta.com.ua/download/manual_plc/3_System_Structure.pdf※1:Please use the program cable offered by Xinje Electronic, or make the cable by yourself;

How To Calculate the I/O Points

Basic Unit XC3-32R-E (18I/14O) connect with 5 expansions: XC-E8X8Y、

XC-E16X、XC-E32Y、XC-E2AD、XC-E4DA. Then the total I/O points should be:

Input Points: 18 + 8 + 16 = 42

Output points: 14 + 8 +32 = 54

Total points: Input+ Output = 42+54=96

Page 9: System Structure - primeta.com.uaprimeta.com.ua/download/manual_plc/3_System_Structure.pdf※1:Please use the program cable offered by Xinje Electronic, or make the cable by yourself;

3 system structure

3-4.ID Assignment of Expansions

Expansion

Position Type ID (As Register)

Maximum

points/channels

Digital Input X X100~X137 32 points

Digital Output Y Y100~Y137 32 points

Analog Input ID ID100~ID131 16 channels

Analog Output QD QD100~QD131 16 channels

Position

1#

Module's Value D D8250~D8259 -

Digital Input X X200~X237 32 points

Digital Output Y Y200~Y237 32 points

Analog Input ID ID200~ID231 16 channels

Analog Output QD QD200~QD231 16 channels

Position

2#

Module's Value D D8260~D8269 -

Digital Input X X300~X337 32 points

Digital Output Y Y300~Y337 32 points

Analog Input ID ID300~ID331 16 channels

Analog Output QD QD300~QD331 16 channels

Position

3#

Module's Value D D8270~D8279 -

Digital Input X X400~X437 32 points

Digital Output Y Y400~Y437 32 points

Analog Input ID ID400~ID431 16 channels

Analog Output QD QD400~QD431 16 channels

Position

4#

Module's Value D D8280~D8289 -

Digital Input X X500~X537 32 points

Digital Output Y Y500~Y537 32 points

Analog Input ID ID500~ID531 16 channels

Analog Output QD QD500~QD531 16 channels

Position

5#

Module's Value D D8290~D8299 -

Digital Input X X600~X637 32 points

Digital Output Y Y600~Y637 32 points

Analog Input ID ID600~ID631 16 channels

Analog Output QD QD600~QD631 16 channels

Position

6#

Module's Value D D8300~D8309 -

Digital Input X X700~X737 32 points

Digital Output Y Y700~Y737 32 points

Analog Input ID ID700~ID731 16 channels

Analog Output QD QD700~QD731 16 channels

Position

7#

Module's Value D D8310~D8319 -

Digital Input X X1000~X1037 32 points

Digital Output Y Y1000~Y1037 32 points

Analog Input ID ID1000~ID1031 16 channels

BD Card

Analog Output QD QD1000~QD1031 16 channels

Page 10: System Structure - primeta.com.uaprimeta.com.ua/download/manual_plc/3_System_Structure.pdf※1:Please use the program cable offered by Xinje Electronic, or make the cable by yourself;

Module's Value D D8320~D8329 -

Page 11: System Structure - primeta.com.uaprimeta.com.ua/download/manual_plc/3_System_Structure.pdf※1:Please use the program cable offered by Xinje Electronic, or make the cable by yourself;

3 system structure

3-5.Install The Products

PWR

1 Installation Position

Use DIN or screws to install the CPU units and expansions.

2 Installation Method

l Directly install by screws

M3 Screw

DIN installation

Use DIN46277

Page 12: System Structure - primeta.com.uaprimeta.com.ua/download/manual_plc/3_System_Structure.pdf※1:Please use the program cable offered by Xinje Electronic, or make the cable by yourself;

Please install the products according to chapter 2-1-1

3 Installation Environment