DescriptionThe DSC-1146E is a fully programmable, Native BACnet™ Building Controller that communicates onTwisted-Pair Ethernet 10-BaseT using BACnet IP and BACnet over Ethernet, or on an RS-485 LANusing the BACnet MS/TP protocol. The DSC-1146E is designed for a wide-range of applications thathave medium local I/O requirements. It also supports BACstats and other Delta LINKnet devices.
ApplicationThe DSC-1146E is suitable for controlling various packaged units and equipment with medium I/O requirements such as small Air Handling Units, Boilersand Chillers.
The fully programmable DSC-1146E can be tailored tospecific applications by creating and modifying BACnetobjects and GCL+ programs.
Features—Native BACnet firmware
—Serial port for modem connection
—BACnet IP and BACnet over Ethernet communications
—Super capacitor for real-time clock and SRAM backup (requires no maintenance)
—Supports 12 BACstat network sensors on LINKnet for room sensing and control or 2 Delta FieldModules on LINKnet for I/O expansion
—Actuator power terminal (24VAC) for each analogoutput
—Fully programmable in GCL+
—Application database can be flash loaded over thenetwork
—Controller firmware can be flash loaded over the network
—Supports Modbus capability by flash loading in thefield via hardware key
—Derived Network Addressing (DNA) for simple integration into a standard network architecture
—Service port
Specifications
BACnet Device ProfileBACnet Building Controller(B-BC)
Inputs11 Universal inputs - 10 bit (supporting 0-5v, 0-10v, 10kΩ, 4-20mA)
Outputs 6 Binary triac outputs
4 Analog outputs (0-10v)
Jumper selection for internal or external poweron binary outputs
LED status indication of each output
Technology32-bit processor
2 MB (16 megabit) Flash memory
319 KB SRAM memory for database
LED indication of CPU and SCAN status
Real-time clock
Super capacitor for 72-hr backup of real-timeclock and SRAM
Device TypeConfigured as either a System or Subnetdevice
Device AddressingSet via DIP switch and jumpers or softwaresetup
HVAC
Document Edition 1.0 August 2009
System ControllersDSC-1146E
System ControllersDSC-1146E: Board Layout Diagram
AccessoriesDZNR-768—Delta Network Repeater for BACnetMS/TP
TRM-768—Delta Network Terminator for BACnet MS/TP
CON-768BT—Wireless Service Port access
OrderingOrder the DSC-1146E with the desired options accord-ing to the following product numbers:
DSC-1146E—11 inputs, 4 AO’s, 6 BO’s
Specifications (Continued)
Communications PortsTwisted-Pair Ethernet (10-BaseT) @ 10 MB (optional), BACnet IP,BACnet over Ethernet
SubLAN (NET2)Delta LINKnet @ 76800 bps (maximum 12devices on LINKnet, with no more than 2 DFM devices) ,
Main LAN (NETI)BACnet MS/TP @ 9600, 19200, 38400 or76800 bps (default) (maximum of 99 devicesper BACnet MS/TP segment)
Serial RS-232 BACnet PTP 9600, 19200 or38400 bps
ConnectorsRemovable screw-type terminal connectors
Wiring ClassClass 2
Power 24 VAC only
14VA, 86VA with BOs fully-loaded
Ambient32° to 131°F (0° to 55°C)
10 - 90% RH (non-condensing)
Dimensions103⁄8 x 4 x 17⁄8 in. (26.4 x 10.2 x 4.8 cm) with housing
1.062 lb. (482 g) with housing
ComplianceCE
FCC
ListingsC-UL Listed
UL 916 Listed
BTL Listed
HVAC