If you can't read please download the document
Upload
tranhanh
View
218
Download
1
Embed Size (px)
Citation preview
Synthetic Data for Power Grid R&D
Tom Overbye and Adam Birchfield Texas A&M University
[email protected], [email protected] July 20, 2017
1
Background Access to data about the actual power grid is often
restricted because of requirements for data confidentiality (e.g., critical energy infrastructure)
For power system community to engage in research that adheres to the scientific principle of reproducibility of results, we need common access to models the mimic the grid complexity
Work presented here is mostly based an ongoing ARPA-E Grid Data Project involving researchers at TAMU, Illinois, Cornell, ASU and VCU
2
Overview The overall goal of the project is the creation and
dissemination of synthetic (fictional) models and scenarios associated with the high voltage grid The models will be of varying size and complexity, ranging
from 200 buses up to 100,000 buses; the models will also include contingencies and extra parameters for transient stability and GMD analysis
All delivered models with have geographic coordinates Scenarios will be hourly for a year, SCOPF solved Validation metrics are also a key consideration
3
Approach The approach is to make models that look real and
familiar by siting these synthetic models in North America, and serving a population density the mimics that of North America The transmission grid is, however, totally fictitious
This approach is predicated on gathering statistics associated with actual grids, and then using those statistics as appropriate Actual grids have idiosyncratic characteristics that need to be
considered; outlier characteristics can be quite important!
4
Model Complexity Examples A recent 76,000 bus Eastern Interconnect (EI) power
flow model has 27,622 transformers including 98 phase shifters Impedance correction tables are used for 351, including
about 2/3 of the phase shifters; tables can change the impedance by more than two times
The voltage magnitude is controlled at about 19,000 buses (by Gens, LTCs, switched shunts) 94% regulate their own terminals with about 1100 doing
remote regulation. Of this group 572 are regulated by two or more devices, 277 by three or more, 12 by eight or more, and three by 12 devices!
5
Geography is Key! Actual power grids are geographically consistent
This is an inherent characteristic that has profound modeling implications
Examples include line impedance, and constraints such as lakes and mountains
Traditionally power system planning models did not usually include location
This is now changing, partially because of GMD studies that require geography
6
Current Status Weve created 200, 500 and 2000 bus systems, with a
10,000 bus model almost finished The 200 bus model has OPF, transient stability GMD data,
contingencies plus 8760 hourly scenarios The 500 bus has OPF, transient stability and GMD data The 2000 bus has OPF data Additional scenarios and models are being developed
All models are (or will be) publicly available in a variety of common formats at different locations https://electricgrids.engr.tamu.edu/
7
Example: 2000 Bus Model Geographic footprint is part of
Texas (corresponding with ERCOT footprint)
Four voltage levels: 115 kV, 161 kV, 230 kV, and 500 kV
Eight areas, appealing onelines
This is a synthetic power system model that does NOT represent the actual grid. It was developed as part of the US ARPA-E Grid Data research project and contains no CEII. To reference the model development approach, use:
For more information, contact [email protected].
A.B. Birchfield, T. Xu, K.M. Gegner, K.S. Shetye, and T.J. Overbye, "Grid Structural Characteristics as Validation Criteria for Synthetic Networks," to appear, IEEE Transactions on Power Systems, 2017.
21%A
Amps
5%A
Amps
37%A
Amps
36%A
Amps
55%A
Amps
4%A
Amps
34%A
Amps
23%A
Amps
34%A
Amps
8%A
Amps
12%A
Amps
16%A
Amps 39%
A
Amps
13%A
Amps
27%A
Amps
15%A
Amps
37%A
Amps 37%
A
Amps
A
35%A
Amps
24%A
11%A
Amps
32%A
Amps
45%A
Amps
41%A
Amps
20%A
Amps
26%A
Amps
13%A
Amps
34%A
Amps
2%A
Amps
6%A
Amps
40%A
Amps
28%A
Amps
34%A
Amps
29%A
Amps
30%A
Amps
15%A
Amps
13%A
Amps
36%A
Amps
33%A
Amps
5%A
Amps
19%A
Amps
18%A
Amps
37%A
Amps DALLAS 1North Central
500.00 kV10
DALLAS 3North Central
500.00 kV2
WILMERNorth Central
161.00 kV1
LANCASTER 1North Central
161.00 kV1
HUTCHINSNorth Central
161.00 kV1
LANCASTER 2North Central
161.00 kV1
DALLAS 14North Central
161.00 kV1
DALLAS 17North Central
161.00 kV1
FERRISNorth Central
161.00 kV1
DESOTONorth Central
161.00 kV1
MESQUITE 2North Central
161.00 kV1
TERRELL 2North Central
161.00 kV1
FORNEYNorth Central
161.00 kV1
MESQUITE 1North Central
161.00 kV1
ROCKWALL 1North Central
161.00 kV1
QUINLANNorth Central
161.00 kV1
SUNNYVALENorth Central
161.00 kV1
GARLAND 1North Central
500.00 kV2
TERRELL 1North Central
161.00 kV2
DALLAS 38North Central
161.00 kV1
DUNCANVILLE 2
North Central
161.00 kV1
CEDAR HILLNorth Central
161.00 kV1
DALLAS 34North Central
161.00 kV1
DUNCANVILLE 1
North Central
161.00 kV1
WILLS POINTEast
115.00 kV1
DALLAS 43North Central
161.00 kV1
KEMPNorth Central
161.00 kV1
CANTONEast
115.00 kV1
North Central
KAUFMANNorth Central
161.00 kV1
SEAGOVILLENorth Central
161.00 kV1
MABANK 1North Central
161.00 kV1
ADDISONNorth Central
161.00 kV1
DALLAS 31North Central
161.00 kV1
DALLAS 42North Central
161.00 kV1
DALLAS 24North Central
161.00 kV1
DALLAS 30North Central
161.00 kV1
DALLAS 39North Central
161.00 kV1
DALLAS 21North Central
161.00 kV1
DALLAS 23North Central
161.00 kV1
IRVING 4North Central
161.00 kV1
DALLAS 26North Central
161.00 kV1
DALLAS 18North Central
161.00 kV1
DALLAS 36North Central
161.00 kV1
IRVING 2North Central
161.00 kV1
North Central
FORT WORTH 14North Central
161.00 kV1
ARLINGTON 7North Central
161.00 kV1
BURLESONNorth Central
50000 kV2
FORT WORTH 8
North Central
161.00 kV1FORT WORTH 24
North Central
161.00 kV1
FORT WORTH 20North Central
161.00 kV1
FORT WORTH 5
North Central
161.00 kV1
FORT WORTH 13North Central
161.00 kV1
ARLINGTON 11
North Central
161.00 kV1
ARLINGTON 2North Central
161.00 kV1
DALLAS 44North Central
161.00 kV1
GRAND PRAIRIE 3North Central
500.00 kV2
MANSFIELDNorth Central
500.00 kV2
ARLINGTON 8North Central
161.00 kV1
MESQUITE 3North Central
161.00 kV1
DALLAS 11North Central
161.00 kV1
DALLAS 13North Central
161.00 kV1
DALLAS 16North Central
161.00 kV1
DALLAS 4North Central
161.00 kV1
DALLAS 15North Central
161.00 kV1
DALLAS 27North Central
161.00 kV1
DALLAS 9North Central
161.00 kV1
DALLAS 20North Central
161.00 kV1
DALLAS 5North Central
161.00 kV1
ROYSE CITYNorth Central
161.00 kV1
ROWLETT 1North Central
161.00 kV1
CADDO MILLSNorth Central
161.00 kV1
GARLAND 2North Central
161.00 kV1
ROWLETT 2North Central
161.00 kV1
BALCH SPRINGSNorth Central
161.00 kV1
ROCKWALL 2North Central
161.00 kV1
JOSEPHINENorth Central
161.00 kV1
DALLAS 32North Central
161.00 kV1
DALLAS 7North Central
161.00 kV1
DALLAS 12North Central
161.00 kV1
GARLAND 5North Central
161.00 kV1
DALLAS 10North Central
161.00 kV1
DALLAS 22North Central
161.00 kV1
DALLAS 8North Central
161.00 kV1
RICHARDSON 2North Central
500.00 kV2
GARLAND 3North Central
161.00 kV1
SACHSENorth Central
161.00 kV1
DALLAS 6North Central
161.00 kV1
DALLAS 2North Central
500.00 kV5
DALLAS 25North Central
161.00 kV1
DALLAS 37North Central
161.00 kV1
DALLAS 33North Central
161.00 kV1
DALLAS 29North Central
161.00 kV1
DALLAS 40North Central
161.00 kV1
GARLAND 4North Central
161.00 kV1
DALLAS 28North Central
161.00 kV1
DALLAS 41North Central
161.00 kV1
FORT WORTH 23North Central
161.00 kV1
GRAHAMNorth Central
500.00 kV4
PALO PINTO 1
North Central
500.00 kV7
STRAWNNorth Central
161.00 kV1
6 00 1
BOWIENorth
161.00 kV1
JACKSBORO 2
North Central
161.00 kV1
ALVORDNorth Central
161.00 kV1
WINDTHORSTNorth
161.00 kV1
BRIDGEPORTNorth Central
500.00 kV9
KRUMNorth Central
161.00 kV1
DECATURNorth Central
161.00 kV1
DENTON 6North Central
161.00 kV1
RHOMENorth Central
161.00 kV1
CHICONorth Central
161.00 kV1
NEWARKNorth Central
161.00 kV1
PARADISENorth Central
161.00 kV1
MINGUSNorth Central
161.00 kV1
EASTLANDNorth Central
161.00 kV1
DE LEONNorth Central
161.00 kV1
OLNEY 1North Central
500.00 kV3
BRYSON 1North Central
500.00 kV3
BRYSON 2North Central
161.00 kV1
ARCHER 2North
161.00 kV2
NORTH RICHLAND HILLS 1
North Central
161.00 kV1
KELLER 1North Central
161.00 kV1
FORT WORTH 17
North Central
161.00 kV1
FORT WORTH 18North Central
161.00 kV1
KELLER 2North Central
500.00 kV2
FORT WORTH 22
North Central
161.00 kV1
ALEDO 1North Central
500.00 kV3
FORT WORTH 16North Central
161.00 kV1
HASLETNorth Central
161.00 kV1
FORT WORTH 4North Central
161.00 kV1
COPPELLNorth Central
161.00 kV1
GRAPEVINENorth Central
161.00 kV1
BEDFORD 1North Central
161.00 kV1
IRVING 1North Central
161.00 kV3
EULESS 1North Central
161.00 kV1
FORT WORTH 9North Central
161.00 kV1
NORTH RICHLAND HILLS 2
North Central
161.00 kV1
COLLEYVILLENorth Central
161.00 kV1
SOUTHLAKENorth Central
161.00 kV1
WEATHERFORD 1North Central
161.00 kV1
POOLVILLENorth Central
500.00 kV5
WEATHERFORD 3North Central
161.00 kV1
BOYDNorth Central
161.00 kV1
AZLENorth Central
161.00 kV1
MINERAL WELLSNorth Central
161.00 kV1
JACKSBORO 1North Central
500.00 kV3
GRAFORDNorth Central
161.00 kV1
PERRINNorth Central
161.00 kV1
FORT WORTH 25North Central
161.00 kV1
ALEDO 2North Central
161.00 kV1
WEATHERFORD 2
North Central
161.00 kV1
FORT WORTH 26
North Central
161.00 kV1
FORT WORTH 29North Central
161.00 kV1
SANTONorth Central
161.00 kV1
FORT WORTH 27North Central
161.00 kV1SPRINGTOWN
North Central
161.00 kV1
MILLSAPNorth Central
161.00 kV1
PALO PINTO 2North Central
161.00 kV1
LIPANNorth Central
161.00 kV1
GORDONNorth Central
161.00 kV1
TOLARNorth Central
161.00 kV1
STEPHENVILLE
North Central
ARLINGTON 5North Central
161.00 kV1
ARLINGTON 4North Central
161.00 kV1
ARLINGTON 10
North Central
161.00 kV1
ARLINGTON 3North Central
161.00 kV1
GRAND PRAIRIE 1North Central
161.00 kV1
GRANBURY 3North Central
161.00 kV1
FORT WORTH 28North Central
161.00 kV1
GRANBURY 1North Central
500.00 kV5
GRANBURY 2North Central
500.00 kV6
ARLINGTON 9North Central
161.00 kV1
HALTOM CITYNorth Central
161.00 kV1
FORT WORTH 21North Central
161.00 kV1
FORT WORTH 19North Central
161.00 kV1
FORT WORTH 7North Central
161.00 kV1
FORT WORTH 12North Central
161.00 kV1
EULESS 2North Central
161.00 kV1
HURSTNorth Central
161.00 kV1
FORT WORTH 1
North Central
161.00 kV1
IRVING 5North Central
161.00 kV1
FORT WORTH 15
North Central
161.00 kV1
GRAND PRAIRIE 2
North Central
161.00 kV1
ARLINGTON 6North Central
161.00 kV1
FORT WORTH 3
North Central
161.00 kV1
IRVING 3North Central
161.00 kV1ARLINGTON 1
North Central
500.00 kV7
FORT WORTH 6North Central
161.00 kV1
FORT WORTH 11
North Central
161.00 kV1
FORT WORTH 2
North Central
161.00 kV1
BEDFORD 2North Central
161.00 kV1
CELINANorth Central
161.00 kV1
LITTLE ELMNorth Central
161.00 kV1
FRISCO 1North Central
161.00 kV1
PROSPERNorth Central
161.00 kV1
AUBREYNorth Central
161.00 kV1
JUSTINNorth Central
161.00 kV1
ARGYLENorth Central
161.00 kV1
FORT WORTH 10North Central
161.00 kV1
ROANOKENorth Central
161.00 kV1
PONDERNorth Central
161.00 kV1
DENTON 4North Central
161.00 kV1
DENTON 2North Central
161.00 kV1
DENTON 5North Central
161.00 kV1
DENTON 1North Central
500.00 kV4
FLOWER MOUND 1
North Central
161.00 kV1
LEWSIVILLENorth Central
161.00 kV3
LEWISVILLE 2North Central
161.00 kV1
LAKE DALLASNorth Central
161.00 kV1
DENTON 3North Central
161.00 kV1
FLOWER MOUND 2
North Central
161.00 kV1
LEWISVILLE 1North Central
161.00 kV3
LEONARDNorth
161.00 kV1
ANNANorth Central
161.00 kV1
TRENTONNorth
161.00 kV1
PLANO 1North Central
161.00 kV1
PLANO 2North Central
161.00 kV1
WHITEWRIGHT161.00 kV1
WOLFE CITYNorth Central
161.00 kV1
GREENVILLE 1North Central
500.00 kV4
NEVADANorth Central
161.00 kV1
GREENVILLE 2North Central
161.00 kV1LAVONNorth Central
161.00 kV1
PRINCETONNorth Central
161.00 kV1
WYLIENorth Central
161.00 kV1
FARMERSVILLENorth Central
161.00 kV1
RICHARDSON 1North Central
161.00 kV1
PLANO 6North Central
161.00 kV1
THE COLONYNorth Central
161.00 kV1
CARROLLTON 1
North Central
161.00 kV1
PLANO 4North Central
161.00 kV1
FRISCO 2North Central
500.00 kV2
MCKINNEY 2North Central
161.00 kV1
MELISSANorth Central
161.00 kV1
MCKINNEY 3North Central
500.00 kV2
CARROLLTON 3North Central
161.00 kV1
MCKINNEY 1North Central
500.00 kV9
PLANO 3North Central
161.00 kV1
PLANO 5North Central
161.00 kV1
ALLEN 1North Central
500.00 kV2
ALLEN 2North Central
161.00 kV1
PLANO 7North Central
161.00 kV1
CARROLLTON 2
North Central
161.00 kV1
DALLAS 19North Central
161.00 kV1
DALLAS 35North Central
161.00 kV1
A
Amps 40%A
Amps Zoomed View of North Texas
8
Synthetic Model Design Process The assumed peak load is based on population, scaled by geographic values
Generation is partially derived from public data (e.g., EIA-860)
Substation oriented approach
9
Matching Transmission Systems We use a number approaches to better mimic the
transmission system structure including Delaunay Triangulation, minimum spanning trees, and minimum cycle distribution
Below image shows Delaunay triangulation of 42,000 North America substations; statistics only consider single voltage levels; this is computationally fast (order n ln(n))
The minimum spanning tree (MST) is a subset of the Delaunay triangulation
10
Validation is Key! To-date weve developed about 20 metrics that cover
the proportions, size, and structure of actual power grids models, with more coming!
For example: Buses/substation, Voltage levels, Load at each bus Generator commitment, dispatch Transformer reactance, MVA limit, X/R ratio Percent of lines on minimum spanning tree and various
neighbors of the Delaunay triangulation
Statistics collected from 3 actual interconnects and 12 subset cases from FERC 715 data
11
Validation of the 2000 Bus Model
*Note: this model represents a higher load-bus density than actual by design
12
Validation of the 2000 Bus Model Number of buses in substation Amount of load per bus
Orange/blue/black actual data, red synthetic
13
Validation of the 2000 Bus Model 14
Development of Model Scenarios Goal of project is to develop models and hourly
variation scenarios, SCOPF validated for a year This is being done initially for the 200 bus model
Assumed Hourly Maximum Wind Generation
Assumed Hourly Load
15
200 Bus SCOPF Validation We are currently combining the 200 bus model, the
load schedules, the wind generation variation and the contingencies to do SCOPF validation on model Using PowerWorld Simulator Time Step Simulation
The PowerWorld Simulator tool allows us to easily sequentially solve ac SCOPFs for each of the hourly time points
16
Transient Stability Models Ultimately all models will also include transient
stability models; this is done for the 200 and 500 bus models, with the 2000 bus almost done
Were developing models with increasing complexity in model diversity, while using models that run in PowerWorld, PSSE and PSLF
Validation metrics are also being developed
17
Next Up: Ten Thousand Bus Case Model has 10K buses,
4700 substations, 16 areas, seven nominal transmission voltages (765, 500, 345, 230, 161, 138 and 115kV); total peak load is 150GW
Green arrows show initial MW flows
Model should be publicly available soon!
18
Applications To be widely used synthetic models need to be high
quality and available in common formats Researchers will be able to exchange models and
demonstrate techniques on realistic models Larger models can be used to enhance teaching
TAMU use of 2000 bus model in undergrad courses Vendors adopting synthetic models for training
Utilities and ISOs may want models adopted to their particular footprints and needs Can be provided to a wider range of potential vendors
19
Conclusion Having access to realistic synthetic models can be an
important driver of innovation The field of synthetic electric grid models is rapidly
developing Creating realistic, large-scale synthetic model is difficult but
not impossible Larger scale models are now starting to be released
There is still much research still to be done especially in the areas of algorithms to create large models and validation metrics!
20
Thank You! 21
Questions?
Models are available at https://electricgrids.engr.tamu.edu
Synthetic Data for Power Grid R&DBackgroundOverviewApproachModel Complexity ExamplesGeography is Key!Current StatusExample: 2000 Bus ModelSynthetic Model Design ProcessMatching Transmission SystemsValidation is Key!Validation of the 2000 Bus ModelValidation of the 2000 Bus ModelValidation of the 2000 Bus ModelDevelopment of Model Scenarios200 Bus SCOPF ValidationTransient Stability ModelsNext Up: Ten Thousand Bus CaseApplicationsConclusionThank You!