375 WEST 200 SOUTHSALT LAKE CITY, UT
84101
801.521.8600801.521.7913
PF
www.gsbsarchitects.com
OWNER PROJECT NO.:GSBS PROJECT NO.:ISSUED DATE:
REVISIONS:
GSBARCHITEC
PLSPR201700272
Contsruction Ducuments
06/02/2017
2015.122.00
ES001
SHEET INDEX,ABBREVIATIONS, ANDGENERAL NOTES
City of South Jordan
Highland Park
Daybreak Village 8South Jordan, UT
10996 S. Redwood RoadSouth Jordan, UT 84095
ELECTRICAL SHEET INDEXES001 SHEET INDEX, ABBREVIATIONS, AND GENERAL NOTES
ES101 SITE ELECTRICAL PLAN
ES102 SITE ELECTRICAL PLAN - PHASE 1
ES103 SITE ELECTRICAL PLAN - PHASE 2
ES201 PHASE 1 ENLARGED ELECTRICAL PLAN - CONCESSIONS AND RESTROOM
ES202 PHASE 1 ENLARGED ELECTRICAL PLAN - PAVILION AND STORAGE SHED
ES203 PHASE 2 ENLARGED ELECTRICAL PLAN - PAVILION AND RESTROOM
ES204 SITE SPORTS FIELD PHOTOMETRICS
ES205 MUSCO PHOTOMETRICS
ES501 SITE ELECTRICAL DETAILS
ES502 SITE ELECTRICAL DETAILS
ES601 ONE-LINE DIAGRAM
ES602 PANEL SCHEDULES
ES603 EQUIPMENT SCHEDULE
ES701 TYPICAL MOUNTING HEIGHT DETAILS
GENERAL ELECTRICAL NOTES
3. EXPOSED STRUCTURE AREAS (EXCLUDING MECHANICAL, ELECTRICAL, ANDCOMMUNICATION SPACES): INSTALL RACEWAYS BETWEEN DECK ANDSTRUCTURE WHEREVER POSSIBLE IN EXPOSED STRUCTURE CEILING AREAS.ROUTE RACEWAYS IN CONCEALED AREAS WHEREVER POSSIBLE. REFER ALLCONDITIONS WHERE RACEWAYS MUST BE INSTALLED WHICH CANNOT COMPLYWITH THESE REQUIREMENTS TO THE ARCHITECT.
4. SUBMITTALS: PROVIDE ORIGINAL ELECTRONIC PDF FORMAT, BOUND,BOOKMARKED (EACH SECTION AND PRODUCT), AND HIGHLIGHTED. JOB NAMEAND SUBCONTRACTOR SHALL BE ON THE FRONT COVER. PREPARE INDEX OFEQUIPMENT SUBMITTED IN EACH TAB.
5. REFLECTED CEILING PLANS: COORDINATE THE LOCATION OF LIGHT FIXTURESWITH THE ARCHITECTURAL REFLECTED CEILING PLANS. REFER ALLDISCREPANCIES TO THE ARCHITECT AND ENGINEER.
6. ALL WORK SHALL BE DONE ACCORDING TO THE CURRENT NATIONAL ELECTRICCODE (NEC), IBC, NFPA, AND IFC. COMPLIANCE AND FINAL APPROVAL IS SUBJECTTO THE ON SITE FIELD INSPECTION OF THE AHJ.
1. CLARIFICATION METHODS: AT THE TIME OF BIDDING, BIDDERS SHALL FAMILIARIZETHEMSELVES WITH THE DRAWINGS AND SPECIFICATIONS. ANY QUESTIONS,MISUNDERSTANDINGS, CONFLICTS, DELETIONS, DISCONTINUED PRODUCTS,CATALOG NUMBER DISCREPANCIES, DISCREPANCIES BETWEEN THE EQUIPMENTSUPPLIED AND THE INTENT OR FUNCTION OF THE EQUIPMENT, ETC, SHALL BESUBMITTED TO THE ARCHITECT/ENGINEER IN WRITING FOR CLARIFICATION PRIORTO ISSUANCE OF THE FINAL ADDENDUM AND BIDDING OF THE PROJECT. WHEREDISCREPANCIES OR MULTIPLE INTERPRETATIONS OCCUR, THE MOST STRINGENT(WHICH IS GENERALLY RECOGNIZED AS THE MOST COSTLY) THAT MEETS THEINTENT OF THE DOCUMENTS SHALL BE ENFORCED.
2. OWNER FURNISHED ITEMS: THE OWNER WILL FURNISH MATERIAL ANDEQUIPMENT AS INDICATED IN THE CONTRACT DOCUMENTS TO BE INCORPORATEDINTO THE WORK. THESE ITEMS ARE ASSIGNED TO THE INSTALLER AND COSTSFOR RECEIVING, HANDLING, STORAGE, IF REQUIRED, AND INSTALLATION AREINCLUDED IN THE CONTRACT SUM.
A. THE INSTALLER'S RESPONSIBILITIES ARE THE SAME AS IF THE INSTALLERFURNISHED THE MATERIALS OR EQUIPMENT.
B. THE OWNER WILL ARRANGE AND PAY FOR DELIVERY OF OWNERFURNISHED ITEMS FREIGHT ON BOARD JOB SITE AND THE INSTALLER WILLINSPECT DELIVERIES FOR DAMAGE. IF OWNER FURNISHED ITEMS AREDAMAGED, DEFECTIVE OR MISSING, DOCUMENT DAMAGED ITEMS WITHTHE TRANSPORT COMPANY AND THE OWNER WILL ARRANGEFOR REPLACEMENT. THE OWNER WILL ALSO ARRANGE FORMANUFACTURER'S FIELD SERVICES, AND THE DELIVERY OFMANUFACTURER'S WARRANTIES AND BONDS TO THE INSTALLER.
C. THE INSTALLER IS RESPONSIBLE FOR DESIGNATING THE DELIVERY DATESOF OWNER FURNISHED ITEMS AND FOR RECEIVING, UNLOADING ANDHANDLING OWNER FURNISHED ITEMS AT THE SITE.THE INSTALLER ISRESPONSIBLE FOR PROTECTING OWNER FURNISHED ITEMS FROMDAMAGE, INCLUDING DAMAGE FROM EXPOSURE TO THE ELEMENTS, ANDTO REPAIR OR REPLACE ITEMS DAMAGED AS A RESULT OF HISOPERATIONS.
DEFINITIONSNOTE: ALL DEFINITIONS MAY NOT BE USED.
INDICATED: THE TERM "INDICATED" REFERS TO GRAPHIC REPRESENTATIONS, NOTES, OR SCHEDULES ON THE DRAWINGS, OTHER PARAGRAPHS OR SCHEDULES IN THE SPECIFICATIONS, AND SIMILAR REQUIREMENTS IN THE CONTRACT DOCUMENTS. WHERE TERMS SUCH AS "SHOWN", "NOTED", "SCHEDULED", AND "SPECIFIED" ARE USED, IT IS TO HELP THE READER LOCATE THE REFERENCE, NO LIMITATION ON LOCATION IS INTENDED.
DIRECTED: TERMS SUCH AS "DIRECTED", "REQUESTED", AUTHORIZED", "SELECTED", "APPROVED", "REQUIRED", AND "PERMITTED" MEAN "DIRECTED BY THE ENGINEER", "REQUESTED BY THE ENGINEER", AND SIMILAR PHRASES.
APPROVED: THE TERM "APPROVED", WHERE USED IN CONJUNCTION WITH THE ENGINEER'S ACTION ON THE CONTRACTOR'S SUBMITTALS, APPLICATIONS, AND REQUESTS, IS LIMITED TO THE ENGINEER'S DUTIES AND RESPONSIBILITIES AS STATED IN GENERAL AND SUPPLEMENTARY CONDITIONS.
FURNISH: THE TERM "FURNISH" IS USED TO MEAN "SUPPLY AND DELIVER TO THE PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY, INSTALLATION, AND SIMILAR OPERATIONS."
INSTALL: THE TERM "INSTALL" IS USED TO DESCRIBE OPERATIONS AT PROJECT SITE INCLUDING THE ACTUAL "UNLOADING, UNPACKING, ASSEMBLY, ERECTION, PLACING, ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING, CURING, PROTECTING, CLEANING, AND SIMILAR OPERATIONS."
PROVIDE: THE TERM "PROVIDE" MEANS "TO FURNISH AND INSTALL, COMPLETE AND READY FOR THE INTENDED USE."
INSTALLER: AN "INSTALLER" IS THE CONTRACTOR OR AN ENTITY ENGAGED BY THE CONTRACTOR, EITHER AS AN EMPLOYEE, SUBCONTRACTOR, OR SUB-SUBCONTRACTOR, FOR PERFORMANCE OF A PARTICULAR CONSTRUCTION ACTIVITY, INCLUDING INSTALLATION, ERECTION, APPLICATION, AND SIMILAR OPERATIONS. INSTALLERS ARE REQUIRED TO BE EXPERIENCED IN THE OPERATIONS THEY ARE ENGAGED TO PERFORM.
TECHNOLOGY SYSTEMS: THE TERM "TECHNOLOGY SYSTEMS" IS USED TO DESCRIBE ALL LOW VOLTAGE SYSTEMS GENERALLY REFERRED TO AS "SPECIAL SYSTEMS". THESE SYSTEMS INCLUDE BUT ARE NOT NECESSARILY LIMITED TO ALL SYSTEMS WHICH UTILIZE VOLTAGES OF LESS THAN 71 VOLTS SUCH AS SOUND SYSTEMS, VIDEO SYSTEMS, TV SYSTEMS, SECURITY SYSTEMS, VOICE AND DATA CABLING SYSTEMS, ETC...
ABBREVIATIONSNOTE: ALL ABBREVIATIONS MAY NOT BE USED.
IR INFRARED
J-BOX JUNCTION BOX
kV KILOVOLT
kVA KILOVOLT AMPERE
kVAR KILOVOLT AMPERE REACTIVE
kW KILOWATT
kWh KILOWATT HOUR
LED LIGHT EMITTING DIODE
LFMC LIQUID TIGHT FLEXIBLE METALCONDUIT
LFNC LIQUID TIGHT FLEXIBLENONMETALLIC CONDUIT
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTG LIGHTING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISIONSYSTEM
MAX MAXIMUM
MC METAL CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTION
MDP MAIN DISTRIBUTION PANEL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENTPROTECTION
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIOANL ELECTRICALMANUFACTURERSASSOCIATION
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTIONASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OCP OVER CURRENT PROTECTION
OF/CI OWNER FURNISHED/CONTRACTOR INSTALLED
OF/OI OWNER FURNISHED/ OWNERINSTALLED
OFP OBTAIN FROM PLANS
OH DR OVERHEAD (COILING) DOOR
OL OVERLOAD
PB PUSHBUTTON
PF POWER FACTOR
PH PHASE
PNL PANEL
PT POTENTIAL TRANSFORMER
PTZ PAN/TILT/ZOOM
QTY QUANTITY
R REMOVE
RCP REFLECTED CEILING PLAN
RMC RIGID METAL CONDUIT
RNC RIGID NONMETAL CONDUIT
RPM REVOLUTIONS PER MINUTE
RR REMOVE AND RELOCATE
S/S START/STOP
SCA SHORT CIRCUIT AMPS
SCBA STANDARD COLOR ASSELECTED BY ARCHITECT
SF SQUARE FOOT (FEET)
SFBA STANDARD FINISH ASSELECTED BY ARCHITECT
SPD SURGE PROTECTIVE DEVICE
SPDT SINGLE POLE, DOUBLE THROW
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
ST SINGLE THROW
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TL TWIST LOCK
TP TELEPHONE POLE
TP TWISTED PAIR
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGESUPPRESSER
TYP TYPICAL
UF UNDERFLOOR
UGND UNDERGROUND
UPS UNINTERRUPTIBLE POWERSUPPLY
V VOLTS
VA VOLT AMPERE
VFC/VFD
VARIABLE FREQUENCY MOTORCONTROLLER
W/ WITH
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
1P SINGLE POLE
1PH SINGLE-PHASE
1WAY ONE-WAY
2/C TWO-CONDUCTOR
2WAY TWO-WAY
3/C THREE-CONDUCTOR
3WAY THREE-WAY
4OUT QUADRUPLE RECEPTACLEOUTLET
4PDT FOUR-POLE DOUBLE THROW
4PST FOUR-POLE SINGLE THROW
4W FOUR-WIRE
4WAY FOUR-WAY
A ABOVE COUNTER
AC ARMORED CABLE
ADA AMERICANS WITH DISABILITIESACT
ADJ ADJACENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTINGCAPACITY
ALUM ALUMINUM
AMP AMPERE
ANN ANNUNCIATOR
AP ACCESS POINT (WIRELESSDATA)
AR AS REQUIRED
ASC AMPS SHORT CIRCUIT
ATS AUTOMATIC TRANSFERSWITCH
AV AUDIO VISUAL
AWG AMERICAN WIRE GAGE
BBXFMR
BUCK-BOOST TRANSFORMER
C CEILING MOUNTED
CATV COMMUNITY ANTENNATELEVISION
CB CIRCUIT BREAKER
CCBA CUSTOM COLOR AS SELECTEDBY ARCHITECT
CCTV CLOSED CIRCUIT TELEVISION
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CFBA CUSTOM FINISH AS SELECTEDBY ARCHITECT
CKT CIRCUIT
CM CONSTRUCTION MANAGER
CND CONDUIT
CO CONVENIENCE OUTLET
COR CONTRACTING OFFICER'SREPRESENTATIVE
CP CONTROL PANEL
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
dBA UNIT OF SOUND LEVEL
DPDT DOUBLE POLE, DOUBLETHROW
DS DISCONNECT SWITCH
EA EACH
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENT ELECTRIC NONMETALLICTUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
EX EXISTING
F FURNITURE MOUNTED
FA FIRE ALARM
FCP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPS
FMC FLEXIBLE METAL CONDUIT
FOB FREIGHT ON BOARD
FVNR FULL VOLTAGENON-REVERSING
FVR FULL VOLTAGE REVERSING
G GROUND
GEN GENERATOR
GFCI GROUND FAULT INTERRUPTER
GFP GROUND FAULT PROTECTION
HD HEAVY DUTY
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSE POWER
HPF HIGH POWER FACTOR
HPS HIGH PRESSURE SODIUM
HV HIGH VOLTAGE
HZ HERTZ
I/O INPUT/ OUTPUT
IG ISOLATED GROUND
IMC INTERMEDIATE METALCONDUIT
IN/IS INSULATED/ ISOLATED
SYMBOL DESCRIPTION
SYMBOLS LEGENDSYMBOL DESCRIPTION
SYMBOLS LEGEND
SWITCH, WEATHERPROOF.WP
RECEPTACLE, DUPLEX, TAMPER RESISTANT: NEMA 5-20R.T
SWITCH, OCCUPANCY SENSOR.OS
SWITCH, TIMER OPERATED.T
FLUSH FLOOR BOX. "#" SHOWN ON DRAWINGS. REFER TOWIRING DEVICE SCHEDULE IN THE ELECTRICAL SPECIFICATIONSFOR CONFIGURATION AND DEVICES.
FB#
SWITCH, DIMMER.D
SWITCH, SINGLE POLE ("x" INDICATES FIXTURES CONTROLLED).X
RECEPTACLE, QUADRAPLEX: NEMA 5-20R.
RECEPTACLE, SPECIAL PURPOSE. PROVIDE RECEPTACLE TOMATCH EQUIPMENT PLUG.
RECEPTACLE, DUPLEX, WEATHERPROOF: NEMA 5-20R.WP
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUITINTERRUPTER: NEMA 5-20R.
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUITINTERRUPTER, WEATHERPROOF: NEMA 5-20R.WP
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER, WET LABEL, "WEATHERPROOF IN USE": NEMA 5-20R.W
S RECEPTACLE, DUPLEX, SWITCHED: NEMA 5-20R.
RECEPTACLE, DUPLEX, ISOLATED GROUND: NEMA 5-20R.IG
DF
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER, DRINKING FOUNTAIN: CONCEAL WATER COOLER RECEPTACLE BEHIND WATER COOLER. SEE MECHANICAL/PLUMBING SHOP DRAWINGS FOR INSTALLATION REQUIREMENTS.
RECEPTACLE, DUPLEX, CEILING: NEMA 5-20R.C
RECEPTACLE, DUPLEX, ABOVE COUNTER: NEMA 5-20R.A
RECEPTACLE, DUPLEX: NEMA 5-20R.
WIRING DEVICES
SITE ELECTRICAL AND COMMUNICATIONS UTILITIES
3ØUPELECTRIC LINE: THIN LINE. 1Ø = SINGLE PHASE,2Ø = 2-PHASE, 3Ø = 3-PHASE, O = OVERHEAD,U = UNDERGROUND, P = PRIMARY, S = SECONDARY
LIGHTNING ARRESTOR.
UTILITY POLE.
UTILITY, DISTRIBUTION SWITCH OR SWITCHING STATION.
UTILITY, PRIMARY ELECTRICAL HAND HOLE.E
UTILITY SERVICES, MANHOLE.M
UTILITY, COMMUNICATIONS MANHOLE.C
UTILITY, ELECTRICAL MANHOLE.E
UTILITY, TELEPHONE MANHOLE.T
PRECAST CONCRETE, COMMUNICATION VAULT.C
PRECAST CONCRETE, ELECTRICAL VAULT.E
PRECAST CONCRETE, TELEPHONE VAULT.T
PRECAST CONCRETE, MANHOLE, TRANSFORMER VAULT.TM
PRECAST CONCRETE, TRANSFORMER PAD.TP
TRANSFORMER.T
HAND HOLE.H
SUBSTATION.S
LIGHTING CONTROL STATION.
DIMMING ENTRY STATION OR CONTROL STATION, FLUSHMOUNTED.
75 TRANSFORMER: NUMBER INDICATES kVA.
PUSHBUTTON.
PUSHBUTTONS, MOTOR CONTROL.
PANELBOARD CABINET, SURFACE MOUNTED, 1 SECTION.
PANELBOARD CABINET, SURFACE MOUNTED, 2 SECTION.
DP#__DISTRIBUTION PANEL OR SWITCHBOARD.
SERVICE ENTRANCE SURGE PROTECTION (ONE-LINE DIAGRAM).
PANELBOARD (ONE-LINE DIAGRAM)."1H"
PANELBOARD WITH MAIN CIRCUIT BREAKER. SIZE AND PHASE ASSHOWN (ONE-LINE DIAGRAM).
225/3
"1H"
PANELBOARD WITH MAIN AND SUB FEED CIRCUIT BREAKER(ONE-LINE DIAGRAM).
60/3
225/3
"1H"
PANELBOARD WITH MAIN LUGS ONLY AND SURGE PROTECTIONWITH CIRCUIT BREAKER (ONE-LINE DIAGRAM).
25/3
225/3
"1H"
TRANSFORMER (ONE-LINE DIAGRAM).
EXHAUST FAN OUTLET.F
CIRCUIT BREAKER, MOLDED CASE (ONE-LINE DIAGRAM).
CIRCUIT BREAKER, MOLDED CASE WITH SHUNT TRIP(ONE-LINE DIAGRAM).
CIRCUIT BREAKER, MOTOR CIRCUIT PROTECTION(ONE-LINE DIAGRAM).
MCP
ELECTRICAL POWER AND DISTRIBUTION
EXIT SIGN: DOUBLE FACE; WALL MOUNTED
EXIT SIGN: SINGLE FACE; CEILING MOUNTED
EXIT SIGN: DOUBLE FACE; CEILING MOUNTED
EXIT SIGN: SINGLE FACE; WALL MOUNTED
LIGHTING (REFER TO FIXTURE SCHEDULE FOR SYMBOLS)
FIXTURE IDENTIFICATION: (W-3) INDICATES FIXTURE TYPE ASSCHEDULED.
(W-3)
FIXTURE IDENTIFICATION, EMERGENCY WITH BATTERY PACK,AS INDICATED: (EX-X) INDICATES FIXTURE TYPE AS SCHEDULED.
(EX-X)
EM EMERGENCY.
NL NIGHT LIGHT: DO NOT SWITCH.
EGRESS DIRECTION ARROW (EXIT SIGNS).
LOW VOLTAGE LIGHTING TRANSFORMER.LV
VACANCY SENSOR, DUAL TECHNOLOGY, WALL.
VACANCY SENSOR, DUAL TECHNOLOGY,OMNI-DIRECTIONAL, CEILING.
LIGHTING CONTROL
OCCUPANCY SENSOR, DUAL TECHNOLOGY,OMNI-DIRECTIONAL, CEILING.
OCCUPANCY SENSOR, DUAL TECHNOLOGY, WALL.
OCCUPANCY SENSOR, DUAL TECHNOLOGY, DIRECTIONAL.
OCCUPANCY SENSOR, ULTRASONIC, OMNI-DIRECTIONAL,CEILING.U
PHOTOCELL.P
TWO-WAY EMERGENCY COMMUNICATION DEVICE PER IBC, WALL MOUNTED IN RECESSED BOX.
STRUCTURED CABLING
TELEPHONE, WALL MOUNTED ("X" INDICATES QUANTITY OFCABLES).
X
DATA CONNECTION: WIRELESS ACCESS POINT (WAP). REQUIRES (2) DATA DROPS PER DEVICE
TELEPHONE, WALL MOUNTED: WALL PHONE.W
OUTLET, DATA COMMUNICATION ("X" INDICATES QUANTITY OFCABLES).
X
OUTLET, BUILDING STANDARD COMBINATION TELEPHONE/ DATACOMMUNICATION.
TELEPHONE TERMINAL BOARD, FIRE TREATED PLYWOODPAINTED.
LAN RACK, FLOOR STANDING.
DATA CABLE, CATEGORY 5 (ONE-LINE DIAGRAM).D
VOICE CABLE, CATEGORY 3 (ONE-LINE DIAGRAM).V10
HIDDEN FEATURES LINE: HIDDEN, THIN LINE
NEW LINE: MEDIUM LINE.
CU-1 EQUIPMENT INDICATOR.
REVISION INDICATOR.1
KEYNOTE INDICATOR.1
ROOM IDENTIFIER WITH ROOM NAME AND NUMBER.ROOM NAME
100
DETAIL INDICATOR: A5 INDICATES DETAIL NUMBER, E-501INDICATES DRAWING SHEET WHERE DETAIL IS SHOWN.
A5
E-501
REFERENCE AND LINE SYMBOLS
MECHANICAL EQUIPMENT CONNECTION. REFER TO EQUIPMENT SCHEDULE FOR REQUIREMENTS.
JUNCTION BOX, CEILING.CJ
EARTH GROUND (ONE-LINE DIAGRAM).
JUNCTION BOX, SECURITY SYSTEM. PROVIDE CONDUIT AND ROUGH-IN PER SECURITY DRAWINGS.SEJ
JUNCTION BOX.J
ADA ACCESS PUSH PLATEHC
CONDUCTOR & CONDUIT ("CC") SCHEDULE INDICATOR. REFERTO ONE-LINE DIAGRAM.
1
LOW VOLTAGE WIRING: DIVIDE, MEDIUM LINE.
WIRING AND/OR RACEWAY: THIN LINE. WHERE "X" = :
CATV = CABLE TELEVISION NC = NURSE CALLCCTV = CLOSED CIRCUIT P = POWER
TELEVISION RC = RIGID CONDUITFA = FIRE ALARM S = SOUNDFO = FIBER OPTICS T = TELEPHONE
I = INTERCOM TV = TELEVISION
OTHERS AS NOTED IN OTHER SCHEDULES. RACEWAYS AND WIRING SHALL BE SIZED AS SHOWN AND/OR SPECIFIED.
X
BRANCH CIRCUIT HOME RUN TO PANELBOARD: NUMBER OFARROWS INDICATES NUMBER OF CIRCUITS. LETTER ANDNUMBER NOTATIONS IDENTIFY PANEL AND CIRCUIT NUMBERS.USE #12 CONDUCTORS, EXCEPT #10 CONDUCTORS SHALL BEINSTALLED IF DISTANCES EXCEED THOSE SPECIFIED IN THEELECTRICAL SPECIFICATIONS.
A-1,3,5
WIRING.
WIRING METHODS
CCTV
CCTV CABLE, POWER.P
CCTV CABLE, VIDEO SIGNAL.V
CCTV CCTV HEADEND EQUIPMENT.
CCTV MONITOR.M
CCTV CAMERA/ENCLOSURE WITH LENS, TYPICAL. SEE SCHEDULE.
CCTV CAMERA WITH PAN, TILT AND ZOOM.PTZ
PANNING CAMERA TRANSVERSE ANGLE.360°
MASTER STATION, INTERCOM.MSI
ANNUNCIATOR PANEL.AP
ULTRASONIC MOTION DETECTOR.U
PANIC DURESS SWITCH.P
PASSIVE INFRARED SENSOR.IR
DUAL TECHNOLOGY PASSIVE INFRARED SENSOR ANDULTRASONIC MOTION DETECTOR.
IRU
INTERCOM STATION.IC
CONTROLLED ACCESS POINT.CA
SENSOR, VOLUMETRIC.
SENSOR, GLASS BREAK.
SENSOR, BURIED VEHICULAR.
BUZZER, COMBINATION BELL.
BUZZER.
BELL.
REMOTE DOOR RELEASE BUTTON.RL
EXIT REQUEST.ER
DOOR SWITCH, BALANCED MAGNETIC CONTROL.
KEYPAD/CARD READER COMBINATION.KCR
CARD READER.CR
CARD ACCESS DOOR TYPE #1 OR AS NOTED. SEESCHEDULE.
#1
INTRUSION DETECTION HEADEND EQUIPMENT.SEC
SECURITY CONTROL PANEL.CTR
ACCESS CONTROL HEADEND EQUIPMENT.ACC
SECURITY CABLE. SEE EQUIPMENT SCHEDULE FOR CABLETYPE.
X
SECURITY
TERMINATOR, 75 OHM (TV DISTRIBUTION).
TV ANTENNA (ONE-LINE DIAGRAM).
SATELLITE ANTENNA.
TV OUTLET.
TV DISTRIBUTION
TV DISTRIBUTION CABLE, INDIVIDUAL DROPS.T
TV DISTRIBUTION CABLE, TRUNK.TR
COMBINER.CMB
DIRECTIONAL COUPLER.DC
DISTRIBUTION AMPLIFIER (ONE-LINE DIAGRAM).DA
SPLITTER (ONE-LINE DIAGRAM).SPL
SYMBOL DESCRIPTION
SYMBOLS LEGEND
1 10-17-17 ADDENDUM #1
C
SB
CORD REEL. SEE DETAIL
SPIDER BOX. SEE DETAIL C3 SHEET ES502.
1
1
1
J
SB SB SB
SB
SB
J
"1HA"
"1LA"
(S3)
(S4)
(S2)
(S1)
SCOREBOARD
DAKTRONICS
MS-2002
1
2
1
1
1
(ZL-1D)
(ZL-1D)
(ZL-1D)
(ZL-1D)(ZL-1D)(ZL-1D)
(ZL-2)
(ZL-2)
(ZL-2)
(ZL-2)
(ZL-2)
(ZL-2)
(FP-1)(FP-1)
(FP-1)
FLAG
POLE
ES201
A1ES202
A1
(FL-1)
(FL-1)
(FL-1)
(FL-1)
1HA-5
33
1LA-17,19
1LA-18,20 1LA-21,23
H
H
H
H
H
H
4
4
4
4
4
4
556
6
5
"T1"
"MDSB"
"RMP XFMR"
7
8
8 8
7
1
1LA-22,241
1LA-25,27 1
1LA-26 1
1
1HA-61HA-8,10
1HA-12,14
9
9
10
10
1HA-13,15
1HA-17,19
LIGHTING
CONTACTOR1LA-291
375 WEST 200 SOUTHSALT LAKE CITY, UT
84101
801.521.8600801.521.7913
PF
www.gsbsarchitects.com
OWNER PROJECT NO.:GSBS PROJECT NO.:ISSUED DATE:
REVISIONS:
GSBARCHITEC
PLSPR201700272
Contsruction Ducuments
06/02/2017
2015.122.00
ES102
SITE ELECTRICAL PLAN -PHASE 1
City of South Jordan
Highland Park
Daybreak Village 8South Jordan, UT
10996 S. Redwood RoadSouth Jordan, UT 84095
SCALE: 1" = 30'-0"A1SITE ELECTRICAL PLAN - PHASE 1
1 NEW MUSCO LIGHT POLE, FIXTURES, AND BASE PROVIDED AND INSTALLED AS PART
OF THIS PROJECT. CIRCUIT BY ELECTRICAL CONTRACTOR.
2 NEW SCOREBOARD MANUFACTURED BY DAKTRONICS MS-2002. RUN 2 #10 CU THWN
+ #10 CU GND IN 3/4" CONDUIT FOR ELECTRICAL CIRCUIT.
3 ENTRY MONUMENT.
4 9" X 13" HAND HOLE FOR FUTURE SPORTS LIGHTING CIRCUIT.
5 1" CONDUIT WITH #200 NYLON PULL STRING TO PANEL 1HA OR IHB FOR FUTURE
SPORTS LIGHTING CIRCUIT.
6 1 1/2" CONDUIT WITH #200 NYLON PULL STRING TO PANEL 1HA OR IHB FOR FUTURE
SPORTS LIGHTING CIRCUIT.
7 REFER TO SPIDERBOX DETAIL ON SHEET ES502, DETAIL C3.
8 SPIDER BOX RECEPTACLE, MOUNTED IN LIGHT POLE BASE. REFER TO DETAILS C3,
ES502 AND A4, ES502.
9 RUN 2 #10 CU THWN AND #10 CU GND IN 3/4" CONDUIT.
10 RUN 2 #6 CU THWN AND #10 CU GND IN 1" CONDUIT.
SHEET KEYNOTES
1 10-17-17 ADDENDUM #1
1
1
JJ
C C
CC
CONCESSIONS
103
WOMENS
RESTROOM
102
MECHANICAL
100
MENS
RESTROOM
101
WP
A
A
A
A
ICE
REFRIG
FREEZER
WP
WP
WPWP
1HA-1
1LA-3
1LA-1
1LA-2
1LA-4
1LA-5
1LA-6
1LA-7
1LA-8
1LA-9
1LA-10
(SA-1)
(SA-1)
(SA-1)(SA-1)
(SA-1)
(SA-1)
(FD-2)
(FD-2)
(FD-2)
(FD-2)
(FD-2)(FD-2)
(FD-2)
(FD-2)
(FD-2)
(SA-1)
(SA-1)
(OC-32) (OC-32)
(OC-32) (OC-32) (OC-32)
1HA-4
1LA-12
1LA-13
HAND DRYERHAND DRYER
A AA
1LA-14
1LA-15
(WH-1)1HA-7,9,11
TYP
1
TYP
1
TYP
1
EE
E
1
1 1
22
2
2
1
11
1
375 WEST 200 SOUTHSALT LAKE CITY, UT
84101
801.521.8600801.521.7913
PF
www.gsbsarchitects.com
OWNER PROJECT NO.:GSBS PROJECT NO.:ISSUED DATE:
REVISIONS:
GSBARCHITEC
PLSPR201700272
Contsruction Ducuments
06/02/2017
2015.122.00
ES201
PHASE 1 ENLARGEDELECTRICAL PLAN -CONCESSIONS ANDRESTROOM
City of South Jordan
Highland Park
Daybreak Village 8South Jordan, UT
10996 S. Redwood RoadSouth Jordan, UT 84095
SCALE: 1/2" = 1'-0"A1PHASE 1 ENLARGED ELECTRICAL PLAN - CONCESSIONS AND RESTROOM
1 EXTERIOR LIGHTING CONTROLLED BY PHOTOCELL
2 CORD REEL RECEPTACLE, REFER TO CORD REEL DETAIL D4 SHEET ES502.
SHEET KEYNOTES
1 10-17-17 ADDENDUM #1
1
J
J
J
STORAGE
SHED
104
LARGE
PAVILION
105
WP
WP
WP
T
1HA-2
1HA-3
1LA-11
(ESA-1) (SA-1) (SA-1)
(SA-1)(SA-1)(SA-1)
(SA-1) (SA-1) (SA-1)
(ESA-1)(SA-1)(SA-1)
(FD-2)
(FD-2)
(FD-2)
(FD-2)
(FD-2) (FD-2) (FD-2)
(FD-2)(FD-2)
(FD-2)(FD-2)
(FD-2)(FD-2)
(FD-2)(FD-2)
(OC-32)
1LA-16
1
2
1
1
3
1
IRRIGATION
CONTROLLER
1LA-281
1
1
375 WEST 200 SOUTHSALT LAKE CITY, UT
84101
801.521.8600801.521.7913
PF
www.gsbsarchitects.com
OWNER PROJECT NO.:GSBS PROJECT NO.:ISSUED DATE:
REVISIONS:
GSBARCHITEC
PLSPR201700272
Contsruction Ducuments
06/02/2017
2015.122.00
ES202
PHASE 1 ENLARGEDELECTRICAL PLAN -PAVILION AND STORAGESHED
City of South Jordan
Highland Park
Daybreak Village 8South Jordan, UT
10996 S. Redwood RoadSouth Jordan, UT 84095
SCALE: 1/2" = 1'-0"A1PHASE 1 ENLARGED ELECTRICAL PLAN - PAVILION AND STORAGE SHED
1 60 MINUTE TWIST TIMER FOR CONTROL OF LIGHT FIXTURE FD-2.
2 3/4" CONDUIT AND #200 NYLON PULL STRING WITH J-BOX FOR DOOR CONTROL./
SWITCH / CONDUCTORS PROVIDED AND INSTALLED BY OTHERS.
3 EXTERIOR LIGHTING CONTROLLED BY PHOTOCELL
SHEET KEYNOTES
1 10-17-17 ADDENDUM #1
1
J
J
LargePavilion
106MECHANICAL
108
MensRestroom
107
WomensRestroom
109
WP
WP
WP
1HB-1
1LB-1
1LB-2
WP
1LB-3
1LB-4HAND
DRYER
HAND DRYER
(SA-1)
(OC-32)
(SA-1)
(FD-2) (FD-2) (FD-2)
(FD-2)
(FD-2)
(FD-2)
(FD-2)(FD-2)(FD-2)
(FD-2)
(FD-2)
(FD-2) (FD-2)
(FD-2)(FD-2)
(FD-2)(FD-2)
(FD-2)
(FD-2) (FD-2)(FD-2)
(OC-32)
(OC-32)
(OC-32)
(OC-32)
1HB-2
(WH-2)1HB-4,6,8
TYP
1 1
TYP
1
1
E
E1
1
TYP
1
1
T2
1
375 WEST 200 SOUTHSALT LAKE CITY, UT
84101
801.521.8600801.521.7913
PF
www.gsbsarchitects.com
OWNER PROJECT NO.:GSBS PROJECT NO.:ISSUED DATE:
REVISIONS:
GSBARCHITEC
PLSPR201700272
Contsruction Ducuments
06/02/2017
2015.122.00
ES203
PHASE 2 ENLARGEDELECTRICAL PLAN -PAVILION AND RESTROOM
City of South Jordan
Highland Park
Daybreak Village 8South Jordan, UT
10996 S. Redwood RoadSouth Jordan, UT 84095
SCALE: 1/2" = 1'-0"A1PHASE 2 ENLARGED ELECTRICAL PLAN - PAVILION AND RESTROOM
1 EXTERIOR LIGHTING CONTROLLED BY PHOTOCELL
2 60 MINUTE TWIST TIMER FOR CONTROL OF LIGHT FIXTURE FD-2.
SHEET KEYNOTES
1 10-17-17 ADDENDUM #1
1
LIGHTING FIXTURE SCHEDULENOTE TO BIDDERS: COMPLY WITH THE SPECIFICATIONS.
REFER TO SPECIFICATIONS FOR IMPORTANT TECHNICAL REQUIREMENTS FOR LIGHTING FIXTURES, BALLASTS, AND LAMPS. THE CATALOG NUMBERS LISTED
BELOW HAVE BEEN CAREFULLY PREPARED TO ASSIST BIDDERS IN SELECTING PRODUCTS TO ACHIEVE THE DESIGN CONCEPT, HOWEVER, PRIOR TO BIDDING,
EACH MANUFACTURER SHALL COMPARE THE CATALOG NUMBERS SHOWN WITH THE DESCRIPTION AND REQUIREMENTS ON THE DRAWINGS, AND SHALL
NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES. SPECIFICALLY INCLUDED IN THIS EVALUATION SHALL BE THE VERIFYING OF PROPER MOUNTING
KITS OR ACCESSORIES TO FACILITATE INSTALLATION AS SHOWN AT EACH LOCATION ON THE DRAWINGS. NO ALLOWANCE OR REDRESS WILL BE ALLOWED
FOR DISCREPANCIES THAT WERE NOT REPORTED TO THE ARCHITECT/ENGINEER IN TIME FOR CORRECTION OR CLARIFICATION BEFORE THE BID. THE
REPORTING OF ANY AMBIGUITY IS THE RESPONSIBILITY OF THE BIDDER. PROVIDE UNIT PRICES AND FIXTURE BRAND SELECTED FOR ADD/DELETE CHANGES
FOR EACH FIXTURE TYPES SHOWN WITHIN 48 BUSINESS HOURS OF THE BID DATE. FAILURE TO COMPLY WITH THIS REQUIREMENT MAY DISQUALIFY THE
PRODUCTS AND EMPOWER THE ENGINEER TO DETERMINE FAIR VALUE FOR FIXTURE AND INSTALLATION CHANGES, WITHOUT FURTHER INPUT FROM THE
CONTRACTOR OR INSTALLER. SUBMITTAL PACKAGE SHALL INCLUDE LAMP MANUFACTURER AND CATALOG NUMBER ON EACH FIXTURE SHEET. ON ALL
PENDANT MOUNTED FIXTURES, PROVIDE A SECOND SET OF PENDANTS, OF A DIFFERENT LENGTH, AS DIRECTED BY THE ARCHITECT/ENGINEER, PROVIDED
AND INSTALLED AT NO ADDITIONAL CHARGE. ALL FIXTURES SHALL BE APPROVED BY UL OR ANOTHER ACCEPTABLE TESTING LAB FOR THE PURPOSE
INTENDED AND WITH THE LAMP AND BALLAST PROPOSED. CONTRACTOR ALLOWANCE PRICES ARE ACCURATE WHEN THIS JOB WAS SPECIFIED,
CONTRACTOR AND ELECTRICAL DISTRIBUTOR SHALL VERIFY THIS ALLOWANCE AND REPORT ANY PROBLEMS TO THE ENGINEER BEFORE THE BID.
ALLOWANCE PRICE MAY OR MAY NOT INCLUDE LAMP(S) OR FREIGHT AS NOTED, AND DO NOT INCLUDE ANY TAXES. UNIVERSAL VOLTAGE (120/277)
BALLASTS REQUIRED UNLESS NOTED OTHERWISE. DIMENSION SEQUENCE = (LENGTH X WIDTH X DEPTH) IN INCHES.
SYMBOL MARK
E
E
DL-1
DL-1
E1
E-1
E-2
SA
SA-1
FD
FD-2
FP
FP-1
FP
FP-1
FL-1
OC-1
ZL
ZL-1D
ZL-2
FIXTURE CHARACTERISTICS
BODY / AIR / MOUNTING / DOOR
LENS/LOUVER/REFLECTOR/OTHER
E PREFIX INDICATES THAT FIXTURE IS PROVIDED WITH AN EMERGENCY BATTERY PACK TO PROVIDE POWER TO ANY 2, 3,
4 OR 8 FOOT FLOURESCENT LAMP COMPATIBLE WITH ALL STANDARD AND ELECTRONIC BALLASTS; COMPLETELY SELF-CONTAINED
TO PROVIDE 90 MINUTES OF EMERGENCY POWER TO FIXTURE BALLAST; MINIMUM LIGHT OUTPUT FOR TYPICAL 4' LAMP SHALL
BE 1100 LUMENS OR HIGHER;UNIVERSAL TRANSFORMER FOR 120 OR 277 VOLTS; LOW VOLTAGE PROTECTION, COMBINATION
TEST SWITCH AND AC "ON" INDICATOR; 10 YEAR PRO-RATA WARRANTY; INSTALL TEST SWITCH IN A MANNER THAT REQUIRES
NO DISASSEMBLY FOR TESTING.
EMERGENCY BATTERY PACK.
LED DOWNLIGHT; THERMALLY PROTECTED HOUSING: TO ACCOMMODATE MULTIPLE TRIMS AND REFLECTOR ASSEMBLIES
FOR LAMPS AS LISTED BELOW; LOW IRIDESCENT REFLECTOR FINISH (EVEN IF NOT SHOWN IN CATALOG
#); SELF FLANGING TRIM UNLESS NOTED.
6" RECESSED DOWNLIGHT
4000K HIGH ABUSE
EXIT SIGN: THERMOPLASTIC HOUSING; CEILING MOUNT, SEE DRAWINGS; ARROWS PER PLANS; LED LAMPS;EMERGENCY BATTERY PACK
WITH 10 YEAR PRO-RATA WARRANTY; SELF-TESTING; DIFUSE LEN PANEL; GREEN LETTERS ON WHITE BACKGROUND.
MUST MEET NFPA ILLUMINATION STANDARDS. UNITS SHOWN ARE CEILING MOUNT MODELS.
SINGLE FACE:
DUAL FACE:
GENERAL PURPOSE INDUSTRIAL: WHITE ENAMEL; AIRCRAFT CABLING MOUNTING
4', LED.
WALL OR CEILING HIGH ABUSE LINEAR
HIGH ABUSE LINEAR FIXTURE
12" WIDE
INGROUND FLOOD LIGHT, DIE-CAST BRASS, ROCK GUARD, TRIM RING, LED; INSTALL IN CONCRETE PER MANUFACTURER'S
RECOMMENDATIONS; CONTROL BY PHOTOCELL.
6", SPOT FLOOD, LED 5100K
INGROUND FLOOD LIGHT, DIE-CAST BRASS, ROCK GUARD, TRIM RING, LED; INSTALL IN CONCRETE PER MANUFACTURER'S
RECOMMENDATIONS; CONTROL BY PHOTOCELL.
6", SPOT FLOOD, LED 5100K
6", FLOOD, LED 4000K
EXTERIOR TRAPEZOID
LIGHT POLES: TOTALLY ENCLOSED RAINTIGHT, DUST-TIGHT AND CORROSION RESISTANT; POLE AS SHOWN IN DETAIL WITH
HANDHOLE, COVER, BOLT COVER, AND BASE; PAINTED (COLOR TO BE SELECTED BY ARCHITECT / ENGINEER WHICH MAY
DIFFER FROM CATALOG NUMBER SHOWN). MTB= 120,208,240,277 VOLT MULTI-TAP BALLAST. ALL BALLASTS HPF. ARM MOUNT.
HORIZONTAL LAMP, SEGMENTED OPTICS.
FULL CUTOFF
LUMINAIRE DOUBLE HEAD,
TYPE III DISTRIBUTION, LED.
30' POLE
FULL CUTOFF
LUMINAIRE SINGLE HEAD,
TYPE III DISTRIBUTION, LED.
15' POLE
LAMP
LED
LED
LED
LED
LED
LED
LED
LED
LED
LED
LED
WATTS
120/277V
26W
1W
2W
42W
45W
11W
11W
36W
47W
232W
116W
VOLTS
3W
120/277V
120/277V
120/277V
277/120V
277/120V
277/120V
277/120V
277/120V
277/120V
277/120V
277/120V
MANUFACTURER
IOTA
BODINE
LITHONIA
PRESCOLITE
HUBBELL
CHLORIDE
LIGHTOLIER
SIDELITE
EMERGE
KENALL
MCPHILBEN
DUAL-LITE
LSI
EELP
LITHONIA
SURE-LITES
DAY-BRITE
CHLORIDE
LIGHTOLIER
CHLORIDE
EVENLITE
DUAL-LITE
EELP
LITHONIA
LSI
SURE-LITES
DAY-BRITE
CHLORIDE
LIGHTOLIER
MCPHILBEN
CHLORIDE
EVENLITE
LITHONIA
LSI
COOPER
PHILIPS
H. E. WILLIAMS
KENALL
KIM
FC LIGHTING
HYDREL
LUMIERE
LUMASCAPE
FC LIGHTING
KIM
FC LIGHTING
HYDREL
LUMIERE
LUMASCAPE
FC LIGHTING
INSIGHT
STONCO
FC LIGHTING
LIGMAN
LITHONIA
EATON
LSI
SPAULDING
NORIBACHI
LITHONIA
CREE
MCGRAW
BEACON
VISIONAIRE
LITHONIA
CREE
MCGRAW
BEACON
VISIONAIRE
CATALOG NUMBER
I-80
B50
PS-1400
EFPS-5
E96
CFP841
FBP50
S60F
FPDL-U
HRDL6ICL-26L30K-DV-DCC-FW-CSS-G
CXXL-1-GW
LXSGWE
EX-G-U-WB-WH
XE 1 GW EM
LQM S W 1 G 120/277 ELN
LPX70DGW
CXL-1-GW-EM
SLN1GW
LTN1GW
VEGWEM
TLX EM GU W
LXUGWE
XE 2 GW EM
LQM S W 3 G 120/277 ELN
EX-G-U-WB-WH
LPX70DGW
CXL-3-GW-EM
SLN2GW
LTN2GW
CXXL-3-GW
VU6LSD
TLX EM GU W
ZL1D L48 5000LM FST MVOLT 40K 80CRI WH
SDL-4-LED-HO-NW-UE
4SNLED-LD4-53SL-LN-UNV-L8XX-CD1-U
LF4FR52H40UDZT
LLM-4-L52/840-S-RD-DIM-UNV
MLHA12-48-F-MW-PP-45L40K-DCC-1-DV
LTV768WB/9L5KUV/RG60/TR60
FCD609R-UNV-LED3K-SP
PDX7 B 12LED WHT53K MVOLT NSP FLC 34S RG
3002N-RD-18LED40000-MFL-CLR-UNV-SCBA 3000-RG
LS363LED-15W4-A-M-85-XX-23-Q-09
FCD609R-UNV-LED3K-SP
LTV768WB/9L5KUV/RG60/TR60
FCD609R-UNV-LED3K-SP
PDX7 B 12LED WHT53K MVOLT NSP FLC 34S RG
3002N-RD-18LED40000-MFL-CLR-UNV-SCBA 3000-RG
LS363LED-15W4-A-M-85-XX-23-Q-09
FCD609R-UNV-LED3K-SP
MQ2/30/40K/45/TR
LPF2-E-4K-FL-K-F1-8-SCBA
FCW5806-UNV-LED4K-SCBA-NFL
UCE-50591-30W-M-W40-277V-SCBA
WST LED 2 10A700/50K SR3 MVOLT PE XXXXX
IST-E01-LED-E1-BL3-SCBA-7050
XGBWM3-WT-LED-28-450-CW-UE-CBA-PCXXX
TRP-30L5K-053-3-U-SCBA-PC
HEX-042-A-NW-MT WPJ
DSX2-LED-100C-700-50K-T3M-MVOLT-HS
ARE-EDG-3M-DA-10-UL-SCBA-525MA
GLEON-AE-06-LED-E1-T3-SCBA
VP-L-96NB-280-5K-T3-UNV-HSS*-RA-SCBA
VLX-1-T3-96LC-7-4K-UNV-AM-SCBA
DSX2-LED-100C-350-50K-T3M-MVOLT-HS
ARE-EDG-3M-DA-5-UL-SCBA-525MA
GLEON-AE-03-LED-E1-T3-SCBA
VP-L-96NB-140-5K-T3-UNV-HSS*-RA-SCBA
VLX-1-T3-47LC-7-4K-UNV-AM-SCBA
NOTES
3'-0"
3"
CLR
6'-0"
2"
CLR
30'-0"
+/- .75" GROUT BED UNDERLIGHT POLE BASE
ANCHOR BOLTS AND FULL BASE COVER PER LIGHT POLE MANUFACTURER. SEE LIGHT POLE MANUFACTURER TEMPLATE TO SET ANCHOR BOLTS
INTERIOR PAINTED WITH RUST INHIBITIVE PRIMER
PROVIDE IN-LINE FUSE WITHINSULATED FUSE HOLDER HERE
HAND HOLE COVER
ROUND STEEL POLEPAINTED TO MATCH FIXTURE
SEE FIXTURE SCHEDULE FORFIXTURE HEAD REQUIREMENTS
.75" CHAMFER ALL EXPOSED EDGES
2 SETS #4 TIES IN TOP 5" OF BASE
4 SETS #4 TIES AT 12" OC
#6 .75" CONDUIT
CONDUIT (TYPICAL)
8 #6 BARS VERTICAL WITH 3SETS #4 TIES AT 18" OCEXCEPT AS NOTED ABOVE
24"Ø CONCRETE BASE
8' X .75" COPPERWELD GROUND ROD
1
1
C
S1
S2
S3
-
1 CON
2 CON
3 CON
SK
10 POLE LIGHTING
CONTACTOR ELECTRICALLY
OPERATED/HELD, 120V COIL,
NEMA 3R ENCLOSURE,
MANUFACTURED BY SQUARE
D OR EQUAL. LABEL
"EXTERIOR LIGHTING
CONTACTOR"
1LA-29
S4
4 CON
SPARE
SPARE
3'-0"
3'-0"
CARLON WEATHERPROOF COVER E1212C24 WITH NEMA L14-50 RECEPTACLE
24"Ø CONCRETE BASE
1'-0"
1'-0"
3000 PSI CONCRETE FOOTING
UNDISTURBED EARTH
1/2" DIA. CONDUIT
3/4" CHAMFER TYPICAL
TENNON/ SLIPFITTER
FLOOD LIGHT
0'-6"
EQ EQ
BOTTOM OF CEILING
RIGIDLY SUPPORTED TOPREVENT MOVEMENT.COORDINATE WITHARCHITECTURAL /STRUCTURAL DRAWINGS.
CORD REEL
TYPE SO CORDWITH 25' OF CORD
TWIST LOCK PLUGAND CONNECTOR
TYPE SO CORD(SIZE AS SHOWN) 3WIRE 1 CIRCUITCORD.
36" AFF
CONDUIT (SIZE ASSHOWN) RIGIDLYSUPPORTED TO PREVENTMOVEMENT
OUTLET BOX WITHTWIST-LOCKRECEPTACLE
36"
AF
F
OUTLET BOX WITH 2 DUPLEX.EACH SERVED WITH TWO 20AMP CIRCUITS. DANIELWOODHEAD 3000 SERIES WITHINSULATED/ISOLATED GROUND.
1 DUPLEX1 DUPLEX
375 WEST 200 SOUTHSALT LAKE CITY, UT
84101
801.521.8600801.521.7913
PF
www.gsbsarchitects.com
OWNER PROJECT NO.:GSBS PROJECT NO.:ISSUED DATE:
REVISIONS:
GSBARCHITEC
PLSPR201700272
Contsruction Ducuments
06/02/2017
2015.122.00
ES502
SITE ELECTRICAL DETAILS
City of South Jordan
Highland Park
Daybreak Village 8South Jordan, UT
10996 S. Redwood RoadSouth Jordan, UT 84095
SCALE: NTS
PARKING LOT LIGHT POLEBASE DETAIL
A4SCALE: NTS
SPORTS FIELD LIGHTINGCONTROL
A3
SCALE: NTS
SPIDER BOX RECEPTACLEDETAIL
C3 SCALE: NTS
GROUND MOUNTED FLOODDETAIL
C4
SCALE: NTS
CORD REEL DETAILD4
1 10-17-17 ADDENDUM #1
1
1
1
**IG
(E.G.)
SBJIG/HHGSIZEQTY
CONDUCTOR(NOTE 1)NOTES
*
SYM AMP
COPPER CONDUCTOR AND
SUBSCRIPT (NOTE 5)
SCHEDULE NUMBER
5
CONDUIT SIZE
CONDUIT SCHEDULE
NO SCALE
GENERAL SHEET NOTES1. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT LOCATED OUTDOORS.
REFER TO PLANS FOR EQUIPMENT LOCATIONS.
2. REFER TO PLANS FOR CONSTRAINTS ON PHYSICAL DIMENSIONS AND
CLEARANCE REQUIREMENTS OF EQUIPMENT. PROVIDE EQUIPMENT
DIMENSIONS THAT FALL WITHIN THE CONSTRAINTS OF EACH SPECIFIC
LOCATION.
3. ALL EQUIPMENT SHALL BE CONSTRUCTED AND BRACED FOR THE SEISMIC
CONDITIONS OF THE PROJECT. REFER TO ELECTRICAL SPECIFICATIONS FOR
REQUIREMENTS.
4. PROVIDE PERFORMANCE TESTING FOR GROUND-FAULT PROTECTION
SYSTEMS ON SITE WITH A WRITTEN RECORD OF THIS TEST SUBMITTED TO THE
AUTHORITY HAVING JURISDICTION PER 2011 NEC 230.95(C).
SHEET KEYNOTES1. -
1 20 .75 2 12 12 12 8 2
2 20 .75 3 12 12 12 8 2,3
3 20 .75 4 12 12 12 8 2,3
4 30 .75 2 10 10 10 8 2
5 30 .75 3 10 10 10 8 2
6 30 .75 4 10 10 10 8 2
7 40 1 2 8 10 8 6 2
8 40 1 3 8 10 8 6 2
9 40 1 4 8 10 8 6 2
10 55 1 2 6 10 8 4 2
11 55 1 3 6 10 8 4 2
12 55 1.25 4 6 10 8 4 2
13 70 1 2 4 8 4 2 2
14 70 1.25 3 4 8 4 2 2
15 70 1.25 4 4 8 4 2 2
16 85 1.25 2 3 8 3 2 2
17 85 1.25 3 3 8 3 2 2
18 85 1.25 4 3 8 3 2 2
19 95 1.25 3 2 8 2 2 2
20 95 1.50 4 2 8 2 2 2
21 130 1.50 3 1 6 2 2 2
22 130 1.50 4 1 6 2 2 2
23 150 2 3 1/0 6 2 1/0 2
24 150 2 4 1/0 6 2 1/0 2
25 175 2 3 2/0 6 2 2/0 2
26 175 2 4 2/0 6 2 2/0 2
27 200 2 3 3/0 6 2 2/0 2
28 200 2.50 4 3/0 6 2 2/0 2
29 230 2.50 3 4/0 4 2 2/0 2
30 230 2.50 4 4/0 4 2 2/0 2
31 255 2.50 3 250 4 1 2/0 2
32 255 2.50 4 250 4 1 2/0 2
33 310 3 3 350 3 1/0 3/0 2
34 310 3 4 350 3 1/0 3/0 2
35 380 3.50 3 500 3 3/0 3/0 2
36 380 4 4 500 3 3/0 3/0 2
37 400 2 EA 2 3 3/0 3 3/0 3/0 2
38 400 2 EA 2.50 4 3/0 3 3/0 3/0 2
39 510 2 EA 2.50 3 250 1 4/0 3/0 2
40 510 2 EA 3 4 250 1 4/0 3/0 2
41 620 2 EA 3 3 350 1/0 4/0 3/0 2,4
42 620 2 EA 3 4 350 1/0 4/0 3/0 2,4
43 760 2 EA 3.50 3 500 1/0 4/0 3/0 2,4
44 760 2 EA 4 4 500 1/0 4/0 3/0 2,4
45 855 3 EA 3 3 300 2/0 4/0 3/0 2,4
46 855 3 EA 3 4 300 2/0 4/0 3/0 2,4
47 1000 3 EA 3.50 3 400 2/0 4/0 3/0 4
48 1000 3 EA 3.50 4 400 2/0 4/0 3/0 4
49 1140 3 EA 4 3 500 3/0 4/0 3/0 4
50 1140 3 EA 4 4 500 3/0 4/0 3/0 4
51 1240 4 EA 3 3 350 3/0 4/0 3/0 4
52 1240 4 EA 3 4 350 3/0 4/0 3/0 4
53 1675 5 EA 4 4 400 4/0 4/0 4/0 4
54 2010 6 EA 4 4 400 250 250 250 4
55 2660 7 EA 4 4 500 350 350 350 4
56 3040 8 EA 4 4 500 500 500 500 4
57 4180 11 EA 4 4 500 500 500 500 4
58 5 EA 4 6
59 5 6
60 10 EA 4 6
CONDUCTOR AND CONDUIT SCHEDULE NOTES
1. CONDUCTORS SHOWN ARE SHOWN FOR EACH CONDUIT WITH
MODIFICATIONS AS NOTED IN NOTE 5. ALL CONDUCTORS SHOWN ARE
THWN UNLESS OTHERWISE NOTED.
2. PROVIDE EQUIPMENT GROUND CONDUCTORS PER TABLE 250-122
WHEN CIRCUIT BREAKERS ARE SIZED GREATER THAN AMPERE RATING
SHOWN IN TABLE.
3. PROVIDE #10 NEUTRALS FOR MULTIWIRE BRANCH CIRCUITS SERVING
COMPUTERS.
4. GROUND CONDUCTOR SHALL BE OMITTED BETWEEN THE UTILITY
TRANSFORMER AND THE FIRST OVERCURRENT PROTECTIVE DEVICE.
5. SYMBOL SUBSCRIPTS:
"2N": INCLUDE TWO NEUTRAL CONDUCTORS, SIZED AS SCHEDULED
FOR PHASED AND NEUTRAL CONDUCTORS.
"FG": FULL SIZE GROUND, SIZE EQUIPMENT GROUNDING
CONDUCTOR TO BE THE SAME SIZE AS THE PHASE CONDUCTORS.
"HH": NEUTRAL CURRENTS EXIST DUE TO HIGH HARMONIC
"NONLINEAR" LOADS. CURRENT CARRYING CONDUCTORS DERATED
ACCORDINGLY. PROVIDE THE IG/HH SIZE FOR THE EQUIPMENT
GROUNDING CONDUCTOR.
"IG": INCLUDE IG (INSULATED/ISOLATED GROUND CONDUCTOR)
SCHEDULED ALONG WITH GROUND OF EQUIPMENT GROUND
CONDUCTOR.
"SBJ": SUBSTITUTE "SBJ" CONDUCTOR FOR "G" CONDUCTOR
SHOWN, WHICH IS SIZED FOR THE SYSTEM BONDING JUMPER OF
THE SEPARATELY DERIVED SYSTEM.
6. RACEWAY ONLY. CONDUCTORS PROVIDED BY UTILITY.
A3ONE-LINE DIAGRAM
FAULT CURRENT TABLEBUSMDSB
1HA
1HB
1LA
PROVIDE FULLY RATED CIRCUIT BREAKERS IN PANELBOARDS FOR THE
FAULT CURRENT SHOWN. SERIES RATINGS WITH NEXT LEVEL UPSTREAM
OVERCURRENT PROTECTIVE DEVICES ARE PERMITTED SUBJECT TO
FACTORY UL DOCUMENTATION OF SERIES RATING SUBMITTED TO ENGINEER.
IF DEVICE OR EQUIPMENT FAULT CURRENT RATING IS NOT SHOWN,
ASSUME 100,000 AIC.
FAULT CURRENT65,000 SCA
22,000 SCA
22,000 SCA
10,000 SCA
1LB 10,000 SCA
MAIN DISTRIBUTION SWITCHBOARD "MDSB"600A, 480/277V 3Ø, 4W, 65,000 AIC
600/3
250/3 250/3 90/3
GROUNDPER NEC
42
NEW
RMP
TRANSFORMER
32
250/3
"1HB"
PHASE 2
32
250/3
"1HA"
PHASE 1
T-175kVA
480-208Y/120V
3∅, 4W
DELTA/ WYE, K-1 RATEDDRY TYPE TRANSFORMER3.4% Z
19
30
225/3
"1LA"
PHASE 1
30
225/3
"1LB"
PHASE 1
42
M
600/3600/3 CT
ENCLOSURE
1
1
1
1
1
1
375 WEST 200 SOUTHSALT LAKE CITY, UT
84101
801.521.8600801.521.7913
PF
www.gsbsarchitects.com
OWNER PROJECT NO.:GSBS PROJECT NO.:ISSUED DATE:
REVISIONS:
GSBARCHITEC
PLSPR201700272
Contsruction Ducuments
06/02/2017
2015.122.00
ES601
ONE-LINE DIAGRAM
City of South Jordan
Highland Park
Daybreak Village 8South Jordan, UT
10996 S. Redwood RoadSouth Jordan, UT 84095
1 10-17-17 ADDENDUM #1
1