ALL FIRE SPRINKLER PIPING SHALL BE CONCEALED ABOVE CEILING OR IN SPRINKLER CONTRACTOR SHALL COORDINATE SPRINKLER HEAD INSTALLATION WITH NEW LIGHTING AND DIFFUSER LOCATIONS. ALL SPRINKLER HEADS SHALL BE PLACED IN THE CENTER OF ALL CEILING TILES WHERE NEW CEILING TILES ARE LOCATED. ALL DIMENSIONS AND EXISTING CONDITIONS SHALL BE CHECKED AND VERIFIED BY CONTRACTOR AT THE SITE. REQUIREMENTS. PIPE SIZING SHALL BE BY HYDRAULIC CALCULATION. INSTALLATIONS SHALL CONFORM TO NFPA AND INSURANCE UNDERWRITER OF WORK AND SPECIFICATIONS. ALL SPRINKLER SYSTEM COMPONENT WALLS, WHERE POSSIBLE. 3. 5. 4. 2. SUPPRESSION INSTALLATION AS PER THE INTENT OF THE PROJECT SCOPE RESPONSIBLE TO PROVIDE ALL COMPONENTS FOR A COMPLETE FIRE REVIEW AND INFORMATIONAL PURPOSES ONLY. THE CONTRACTOR IS SPRINKLER SYSTEM COMPONENTS ARE INDICATED ON THE DRAWING FOR FIRE PROTECTION GENERAL NOTES 1. QUICK RESPONSE UPRIGHT SPRINKLER HEAD (SP) ON DRAWING AND NOTE NUMBER INDICATES NOTE LOCATED ELSEWHERE QUICK RESPONSE DRY PIPE SPRINKLER HEAD (SP) FUNNEL DRAIN GENERAL CONTRACTOR HEATING CONTRACTOR HC CAP OR PLUG CHECK VALVE GATE OR GLOBE VALVE BALANCING COCK OS & Y SUPERVISED VALVE FNL DR GC CLG BLW ABV CEILING BELOW ABOVE QUICK RESPONSE SEMI-RECESSED PENDENT FIRE PROTECTION SYMBOL AND ABBREVIATION SCHEDULE FIRE STANDPIPE LINE (F) F FIRE SPRINKLER LINE (FS) FS SPRINKLER HEAD (SP) QUICK RESPONSE SIDEWALL SPRINKLER HEAD (SP) QUICK RESPONSE UPRIGHT SPRINKLER HEAD BELOW OBSTRUCTION (SP) FIRE DEPARTMENT CONNECTION XX FIRE SPRINKLER WATER DEMAND SEE SCHEDULE .10 GPM/SQ FT SEE SCHEDULE CATEGORY 2 GUEST ROOMS AND PUBLIC AREAS SPRINKLER TEMPERATURE RATING: SEE SCHEDULE SPRINKLER SCHEDULE: EXCEPT AS INDICATED BELOW: ROOM/SPACE $// 635,1./(5 +($'6 6+$// %( 48,&.5(63216( ) 72 ) 6(0,5(&(66(' 7<3( QUICK RESPONSE, CORROSION RESISTANT SPRINKLER TYPE MECHANICAL/ELECTRICAL ROOMS ELEVATOR MACHINERY SWIMMING POOLS QUICK RESPONSE QUICK RESPONSE TEMPERATURE RATING ) ) 72 ) ) 1. FIRE SPRINKLER WATER DEMAND INDICATED ABOVE PENDING INSURANCE UNDERWRITER NOTE: AND AUTHORITY HAVING JURISDICTION APPROVAL. HOSE STREAM ALLOWANCE: SPRINKLER HEAD TYPE: SPRINKLER 'K' FACTOR: 250 GPM K=5.6 SEE SCHEDULE 100 GPM K=5.6 BACK OF HOUSE AREAS DESIGN AREA OF WATER APPLICATION: TYPE OF SPRINKLER SYSTEM: OCCUPANCY CLASSIFICATION: MINIMUM DENSITY: .15 GPM/SQ FT 1500 SQ FT ORDINARY GROUP 1 WET WET LIGHT 1 CATEGORY 1 SEE SCHEDULE 250 GPM SEE SCHEDULE K=5.6 2 ORDINARY GROUP I .15 GPM/SQ FT 1500 SQ FT WET KITCHEN AND KITCHEN STORAGE CATEGORY 3 3 WITH SHALLOW (1/2" D) ESCUTCHEONS (IF VISIBLE) QUICK RESPONSE PENDENT TYPE IN GUEST LAUNDRY, ADMIN AREA, AND BACK-OF-HOUSE AREAS. WHITE FINISH QUICK RESPONSE SEMI-RECESSED IN GUEST SUITES AND PUBLIC SPACES. CAGE-TYPE COVERS IN SERVICE AND UTILITY AREAS. 3. 2. 1. SPRINKLER APPLICATION CRITERIA: 1500 SQ FT DATE OF TEST: 04/24/13 WATER TEST INFORMATION TEST HYDRANT ELEVATION: STATIC PRESSURE: RESIDUAL PRESSURE: SOURCE OF INFORMATION: FLOW RATE: TEST HYDRANT: BAUM & VINTAGEB1480, BAUM B747 --- 75 PSI 72 PSI 1280 GPM RYCO FIRE PROTECTION CONCEALED PENDENT SPRINKLER HEADS ARE NOT PERMITTED. 4. STAINLESS STEEL, WAX COATED REFER TO MARRIOTT MODULE 14 AND THE PROJECT SPECIFICATIONS FOR ADDITIONAL INFORMATION REGARDING FIRE SPRINKLER SYSTEM REQUIREMENTS. SPRINKLER CONTRACTOR SHALL COORDINATE BRANCH PIPING INSTALLATIONS TO AVOID PIPING INSTALLATIONS IN BEARING WALLS. 6. 7. QUICK RESPONSE EXTENDED COVERAGE SIDEWALL SPRINKLER HEAD (SP) SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLETE COMPLIANCE WITH MARRIOTT MODULE 14. 8. POOL EQUIPMENT THE RESULTS OF A WATER FLOW TEST FROM THE LOCAL WATER AUTHORITY. THE TEST MUST BE DATED LESS THAN ONE (1) YEAR FROM THE PRESENT DATE TO BE CONSIDERED AN ACCEPTABLE TEST. IF THE WATER AUTHORITY CANNOT PROVIDE THIS INFORMATION, THEN THE FIRE SPRINKLER CONTRACTOR SHALL CONDUCT A NEW WATER FLOW TEST. THE CONTRACTOR WILL BE RESPONSIBLE FOR ANY COSTS INCURRED TO DO THE NEW WATER FLOW TEST, AND WILL CONDUCT THE TEST WITH THE OWNER, ENGINEER AND INSURANCE COMPANY PRESENT AS WITNESSES. ANY NEW WATER FLOW TEST SHALL BE COORDINATED WITH THE LOCAL WATER AUTHORITY. 9. QUICK RESPONSE DRY SIDEWALL SPRINKLER HEAD (SP) ELEVATOR HOISTWAY QUICK RESPONSE ) F0.01 SYMBOLS, ABBREVIATIONS AND GENERAL NOTES FIRE PROTECTION

SYMBOLS, ABBREVIATIONS - Erie Construction Councilerieconstructioncouncil.com/plan_room_documents/FP Bid Set of 9.pdf · symbols, abbreviations and general notes fire protection

  • Upload
    others

  • View
    38

  • Download
    0

Embed Size (px)

Citation preview

ALL FIRE SPRINKLER PIPING SHALL BE CONCEALED ABOVE CEILING OR IN

SPRINKLER CONTRACTOR SHALL COORDINATE SPRINKLER HEAD INSTALLATION

WITH NEW LIGHTING AND DIFFUSER LOCATIONS.

ALL SPRINKLER HEADS SHALL BE PLACED IN THE CENTER OF ALL CEILING

TILES WHERE NEW CEILING TILES ARE LOCATED.

ALL DIMENSIONS AND EXISTING CONDITIONS SHALL BE CHECKED AND VERIFIED

BY CONTRACTOR AT THE SITE.

REQUIREMENTS. PIPE SIZING SHALL BE BY HYDRAULIC CALCULATION.

INSTALLATIONS SHALL CONFORM TO NFPA AND INSURANCE UNDERWRITER

OF WORK AND SPECIFICATIONS. ALL SPRINKLER SYSTEM COMPONENT

WALLS, WHERE POSSIBLE.

3.

5.

4.

2.

SUPPRESSION INSTALLATION AS PER THE INTENT OF THE PROJECT SCOPE

RESPONSIBLE TO PROVIDE ALL COMPONENTS FOR A COMPLETE FIRE

REVIEW AND INFORMATIONAL PURPOSES ONLY. THE CONTRACTOR IS

SPRINKLER SYSTEM COMPONENTS ARE INDICATED ON THE DRAWING FOR

FIRE PROTECTION GENERAL NOTES

1.

QUICK RESPONSE UPRIGHT SPRINKLER HEAD (SP)

ON DRAWING AND NOTE NUMBER

INDICATES NOTE LOCATED ELSEWHERE

QUICK RESPONSE DRY PIPE SPRINKLER HEAD (SP)

FUNNEL DRAIN

GENERAL CONTRACTOR

HEATING CONTRACTORHC

CAP OR PLUG

CHECK VALVE

GATE OR GLOBE VALVE

BALANCING COCK

OS & Y SUPERVISED VALVE

FNL DR

GC

CLG

BLW

ABV

CEILING

BELOW

ABOVE

QUICK RESPONSE SEMI-RECESSED PENDENT

FIRE PROTECTION SYMBOL AND ABBREVIATION SCHEDULE

FIRE STANDPIPE LINE (F)F

FIRE SPRINKLER LINE (FS)FS

SPRINKLER HEAD (SP)

QUICK RESPONSE SIDEWALL SPRINKLER HEAD (SP)

QUICK RESPONSE UPRIGHT SPRINKLER HEAD BELOW OBSTRUCTION (SP)

FIRE DEPARTMENT CONNECTION

XX

FIRE SPRINKLER WATER DEMAND

SEE SCHEDULE

.10 GPM/SQ FT

SEE SCHEDULE

CATEGORY 2

GUEST ROOMS AND PUBLIC AREAS

SPRINKLER TEMPERATURE RATING:

SEE SCHEDULE

SPRINKLER SCHEDULE:

EXCEPT AS INDICATED BELOW:

ROOM/SPACE

ALL SPRINKLER HEADS SHALL BE QUICK-RESPONSE, 155° F TO 165° F, SEMI-RECESSED TYPE

QUICK RESPONSE, CORROSION RESISTANT

SPRINKLER TYPE

MECHANICAL/ELECTRICAL ROOMS

ELEVATOR MACHINERY

SWIMMING POOLS

QUICK RESPONSE

QUICK RESPONSE

TEMPERATURE RATING

212° F

155° F TO 165° F

212° F

1. FIRE SPRINKLER WATER DEMAND INDICATED ABOVE PENDING INSURANCE UNDERWRITER

NOTE:

AND AUTHORITY HAVING JURISDICTION APPROVAL.

HOSE STREAM ALLOWANCE:

SPRINKLER HEAD TYPE:

SPRINKLER 'K' FACTOR:

250 GPM

K=5.6

SEE SCHEDULE

100 GPM

K=5.6

BACK OF HOUSE AREAS

DESIGN AREA OF WATER APPLICATION:

TYPE OF SPRINKLER SYSTEM:

OCCUPANCY CLASSIFICATION:

MINIMUM DENSITY:

.15 GPM/SQ FT

1500 SQ FT

ORDINARY GROUP 1

WET

WET

LIGHT

1

CATEGORY 1

SEE SCHEDULE

250 GPM

SEE SCHEDULE

K=5.6

2

ORDINARY GROUP I

.15 GPM/SQ FT

1500 SQ FT

WET

KITCHEN AND KITCHEN STORAGE

CATEGORY 33

WITH SHALLOW (1/2" D) ESCUTCHEONS (IF VISIBLE)

QUICK RESPONSE PENDENT TYPE IN GUEST LAUNDRY, ADMIN AREA, AND BACK-OF-HOUSE AREAS.

WHITE FINISH

QUICK RESPONSE SEMI-RECESSED IN GUEST SUITES AND PUBLIC SPACES.

CAGE-TYPE COVERS IN SERVICE AND UTILITY AREAS.3.

2.

1.

SPRINKLER APPLICATION CRITERIA:

1500 SQ FT

DATE OF TEST:

04/24/13

WATER TEST INFORMATION

TEST HYDRANT ELEVATION:

STATIC PRESSURE:

RESIDUAL PRESSURE:

SOURCE OF INFORMATION:

FLOW RATE:

TEST HYDRANT: BAUM & VINTAGEB1480, BAUM B747

---

75 PSI

72 PSI

1280 GPM

RYCO FIRE PROTECTION

CONCEALED PENDENT SPRINKLER HEADS ARE NOT PERMITTED.4.

STAINLESS STEEL, WAX COATED

REFER TO MARRIOTT MODULE 14 AND THE PROJECT SPECIFICATIONS FOR

ADDITIONAL INFORMATION REGARDING FIRE SPRINKLER SYSTEM REQUIREMENTS.

SPRINKLER CONTRACTOR SHALL COORDINATE BRANCH PIPING INSTALLATIONS

TO AVOID PIPING INSTALLATIONS IN BEARING WALLS.

6.

7.

QUICK RESPONSE EXTENDED COVERAGE SIDEWALL SPRINKLER HEAD (SP)

SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLETE COMPLIANCE

WITH MARRIOTT MODULE 14.

8.POOL EQUIPMENT

THE RESULTS OF A WATER FLOW TEST FROM THE LOCAL WATER AUTHORITY.

THE TEST MUST BE DATED LESS THAN ONE (1) YEAR FROM THE PRESENT DATE

TO BE CONSIDERED AN ACCEPTABLE TEST. IF THE WATER AUTHORITY CANNOT

PROVIDE THIS INFORMATION, THEN THE FIRE SPRINKLER CONTRACTOR SHALL

CONDUCT A NEW WATER FLOW TEST. THE CONTRACTOR WILL BE RESPONSIBLE

FOR ANY COSTS INCURRED TO DO THE NEW WATER FLOW TEST, AND WILL

CONDUCT THE TEST WITH THE OWNER, ENGINEER AND INSURANCE COMPANY

PRESENT AS WITNESSES. ANY NEW WATER FLOW TEST SHALL BE COORDINATED

WITH THE LOCAL WATER AUTHORITY.

9.

QUICK RESPONSE DRY SIDEWALL SPRINKLER HEAD (SP)

ELEVATOR HOISTWAY QUICK RESPONSE 250° F

F0.01

SYMBOLS, ABBREVIATIONSAND GENERAL NOTESFIRE PROTECTION

eroman
JCST_Signature
eroman
JCST_Stamp

SUPERVISED VALVE

FLOW SWITCH

INSPECTOR'S TEST VALVE - SEE DETAIL ON DRAWING

FP5.1

2 1/2" FIRE DEPARTMENT VALVE W/ 2 1/2" X 1 1/2" REDUCER IN RECESSED

CABINET

4" FIRE STANDPIPE

4" SPRINKLER RISER

2" SPRINKLER TEST DRAIN

TERMINATE 2" SPRINKLER TEST DRAIN OVER CONCRETE SPLASH BLOCK

WITH INSECT SCREEN.

INSTALL FIRE SPRINKLER IN LAUNDRY CHUTE AS REQUIRED TO MEET NFPA

13 REQUIREMENTS.

ALL FIRE SPRINKLER PIPING LOCATED IN THE POOL AREA SHALL BE

GALVANIZED PIPING, WITH STAINLESS STEEL WAX COATED SPRINKLER

HEADS.

HIGH TEMPERATURE UPRIGHT QUICK RESPONSE UPRIGHT SPRINKLER

HEAD.

COORDINATE SPRINKLER HEAD LOCATIONS WITH INTERIOR DESIGN

DRAWINGS.

4" FIRE STANDPIPE

KEYNOTES:

2

3

4

5

6

7

8

9

10

11

12

1

13

MA

TC

HL

IN

E

MA

TC

HL

IN

E

STORAGE

017a

MECHANICAL/ELECTRICAL

020

SITE STORAGE

019

COR.

016

KITCHEN

017

BUFFET

009

MENS

014

WOMENS

015

BILLIARDS

013

DINING AREA

012

COMMUNAL AREA

011

DEN

010

SOCIAL SEATING AREA

008

1

1

1

2

F

SP SP

9'-0" CLG. HT.

9'-3" CLG. HT.

9'-0" CLG. HT.

11'-8" CLG. HT.

12'-4" CLG. HT.

10'-0" CLG. HT.

10'-0" CLG. HT.

OPEN TO

STRUCTURE

OPEN TO

STRUCTURE

OPEN TO

STRUCTURE

7'-6" CLG. HT.

7'-6" CLG. HT.

9'-0" CLG. HT.

9'-0" CLG. HT.

11'-0" CLG. HT.

9'-6" CLG. HT.

9'-0" CLG. HT.

9'-6" CLG. HT.

11'-0" CLG. HT.

10'-0" CLG. HT.

10

8'-6" CLG. HT.

8'-6" CLG. HT.

9'-6" CLG. HT.

SPRAY-APPLIED

ACOUSTICAL

INSULATION

SPRAY-APPLIED

ACOUSTICAL

INSULATION

SPRAY-APPLIED

ACOUSTICAL

INSULATION

4

5

6

2

1

3

TERMINATE 2" SPRINKLER TEST

DRAIN WITH INSECT SCREEN

COORDINATE SPRINKLER HEAD LOCATIONS

WITH INTERIOR DESIGN DRAWINGS.

NOTE:

13

CHECK VALVE

F1.01A

PARTIAL GROUND FLOORFIRE PROTECTION

01 FIRE PROTECTIONSCALE: 1/8" = 1'-0"

PARTIAL GROUND FLOOR PLAN

eroman
JCST_Signature
eroman
JCST_Stamp

SUPERVISED VALVE

FLOW SWITCH

INSPECTOR'S TEST VALVE - SEE DETAIL ON DRAWING

FP5.1

2 1/2" FIRE DEPARTMENT VALVE W/ 2 1/2" X 1 1/2" REDUCER IN RECESSED

CABINET

4" FIRE STANDPIPE

4" SPRINKLER RISER

2" SPRINKLER TEST DRAIN

TERMINATE 2" SPRINKLER TEST DRAIN OVER CONCRETE SPLASH BLOCK

WITH INSECT SCREEN.

INSTALL FIRE SPRINKLER IN LAUNDRY CHUTE AS REQUIRED TO MEET NFPA

13 REQUIREMENTS.

ALL FIRE SPRINKLER PIPING LOCATED IN THE POOL AREA SHALL BE

GALVANIZED PIPING, WITH STAINLESS STEEL WAX COATED SPRINKLER

HEADS.

HIGH TEMPERATURE UPRIGHT QUICK RESPONSE UPRIGHT SPRINKLER

HEAD.

COORDINATE SPRINKLER HEAD LOCATIONS WITH INTERIOR DESIGN

DRAWINGS.

4" FIRE STANDPIPE

KEYNOTES:

2

3

4

5

6

7

8

9

10

11

12

1

13

MA

TC

HL

IN

E

MA

TC

HL

IN

E

CORRIDOR

035

REFUSE/

RECYCLE

052

CORRIDOR

051

PRE-FUNCTION

026

STORAGE

034

CORR.

028

GM OFFICE

027

COMPUTER

023

EMPLOYEE

LOUNGE

047

POOL TOILET

050

POOL EQUIPMENT

039

INDOOR POOL

049

CORRIDOR

048

CORRIDOR

038

FITNESS

040

ELEVATOR

LOBBY

025

OFFICE

044

LINEN

STORAGE

043

LAUNDRY

045

MEETING ROOM

STORAGE

042

CORRIDOR

030

SALES OFFICE

029

WORK AREA

022

MARKET

004

STORAGE

024

STAIR 2

054

F

1

1

F

Xref E:\HOSPITALITY\HOTELS\Concord Hospitality\Hyatt House Shadyside\Drawings\Plans\Ground Floor Plan.dwg

SP SP

11'-8" CLG. HT.

12'-4" CLG. HT.

8'-6" CLG. HT.

9'-0" CLG. HT.

11'-0" CLG. HT.

11'-0" CLG. HT.

9'-0" CLG. HT.

9'-0" CLG. HT.

10'-0" CLG. HT.

9'-8" CLG. HT.

9'-8" CLG. HT.

8'-0" CLG. HT.

7'-6" CLG. HT.

7'-6" CLG. HT.

9'-0" CLG. HT.

OPEN TO

STRUCTURE

9'-0" CLG. HT.

8'-0" CLG. HT.

9'-0" CLG. HT.

9'-0" CLG. HT.

8'-0" CLG. HT.

9'-0" CLG. HT.

OPEN TO

STRUCTURE

12'-4" CLG. HT.

CS CS

8'-0" CLG. HT.

OPEN TO

STRUCTURE

OPEN TO

STRUCTURE

OPEN TO

STRUCTURE

7'-0

" C

LG

. H

T.

9

7'-0

" C

LG

. H

T.

4

5

7

8

9

10

10

10

10

11

13

10

F1.01B

PARTIAL GROUND FLOORFIRE PROTECTION

01 FIRE PROTECTIONSCALE: 1/8" = 1'-0"

PARTIAL GROUND FLOOR PLAN

eroman
JCST_Signature
eroman
JCST_Stamp

MA

TC

HL

IN

E

MA

TC

HL

IN

E

STAIR 1

253

CORRIDOR

241

CORRIDOR

240

STORAGE

237

ELECTRICAL

ROOM

236

217

KD

TYPE 2

216

QQ

TYPE 2

214

KS

215

KS

213

KDL

212

KD

TYPE 1

210

KS

211KS

209

QQA

208

KS

207

K

TYPE 2

206

K

TYPE 1

205

QQ

TYPE 1

201

QQ

TYPE 1

202

FSFS

F

S

1

2

4

5

6

7

10

QUICK RESPONSE SEMI-RECESSED

PENDENT SPRINKLER HEAD

AT TOP OF STAIR. FIETH LEVEL ONLY

QUICK RESPONSE SEMI-RECESSED

PENDENT SPRINKLER HEAD

(TYPICAL)

QUICK RESPONSE SEMI-RECESSED

PENDENT SPRINKLER HEAD

(TYPICAL)

F1.02A

PARTIAL TYPICAL 2ND-5THLEVEL - FIRE PROTECTION

01 FIRE PROTECTION

SCALE: 1/8" = 1'-0"

PARTIAL TYPICAL SECOND TO FIFTH LEVEL FLOOR PLAN

eroman
JCST_Signature
eroman
JCST_Stamp

MA

TC

HL

IN

E

MA

TC

HL

IN

E

STAIR 2

254

CORRIDOR

243

CORRIDOR

HOUSE

KEEPING

235

ELEVATOR

LOBBY

234

KS

CORNER

229

KDA

228KD

TYPE 1

226

KD

TYPE 1

224

KS

225

KS

223

KS

221

KS

219

KS

217

QQ

TYPE 2

220

KD

TYPE 2

218

KD

TYPE 2

216

ELEV

2

ELEV

1

FSFS

F

S

SUPERVISED VALVE

FLOW SWITCH

INSPECTOR'S TEST VALVE - SEE DETAIL ON DRAWING FP5.1

2 1/2" FIRE DEPARTMENT VALVE W/ 2 1/2" X 1 1/2" REDUCER

2 1/2" FIRE DEPARTMENT VALVE W/ 2 1/2" X 1 1/2" REDUCER IN RECESSED

CABINET

4" FIRE STANDPIPE

4" FIRE SPRINKLER RISER

2" SPRINKLER TEST DRAIN

INSTALL FIRE SPRINKLER IN LAUNDRY CHUTE AS REQUIRED TO MEET NFPA

13 REQUIREMENTS.

4" FIRE STANDPIPE

KEYNOTES:1

2

3

4

5

6

7

8

9

FS

1

2

3

4

5

6

8

9

10

10

QUICK RESPONSE UPRIGHT

SPRINKLER HEAD AND

ASSOCIATED PIPING AT TOP

OF ELEVATOR SHAFT.

FIFTH LEVEL ONLY

QUICK RESPONSE SEMI-RECESSED

PENDENT SPRINKLER HEAD

AT TOP OF STAIR. FIETH LEVEL ONLY

QUICK RESPONSE SEMI-RECESSED

PENDENT SPRINKLER HEAD

(TYPICAL)

QUICK RESPONSE SEMI-RECESSED

PENDENT SPRINKLER HEAD

(TYPICAL)

F1.02B01 FIRE PROTECTION

SCALE: 1/8" = 1'-0"

PARTIAL TYPICAL SECOND TO FIFTH LEVEL FLOOR PLAN

PARTIAL TYPICAL 2ND-5THLEVEL - FIRE PROTECTION

eroman
JCST_Signature
eroman
JCST_Stamp

MA

TC

HL

IN

E

MA

TC

HL

IN

E

F1.03A

PARTIAL TYPICAL 2ND-5THLEVELS ABOVE CEILING

01 FIRE PROTECTIONSCALE: 1/8" = 1'-0"

PARTIAL TYPICAL FLOOR PLAN - 2ND THRU 5TH LEVELS ABOVE CEILING

FIRE PROTECTION

eroman
JCST_Signature
eroman
JCST_Stamp

MA

TC

HL

IN

E

MA

TC

HL

IN

E

F1.03B01 FIRE PROTECTION

SCALE: 1/8" = 1'-0"

PARTIAL TYPICAL FLOOR PLAN - 2ND THRU 5TH LEVELS ABOVE CEILING

PARTIAL TYPICAL 2ND-5THLEVELS ABOVE CEILINGFIRE PROTECTION

eroman
JCST_Signature
eroman
JCST_Stamp

F5.01

RISER DIAGRAMSFIRE PROTECTION

eroman
JCST_Signature
eroman
JCST_Stamp

TERMINATE SLEEVE FLUSH

WITH FINISH WALL SURFACE

FINISHED WALL SURFACE

FIRE RATED PARTITION

RATED WALLS AND MAKE

FIREPROOF AND SMOKE TIGHT.

PIPE TO BE CENTERED IN

SLEEVE. DO NOT SUPPORT

PIPE FROM SLEEVE.

SEAL SLEEVE THRU FIRE

PIPE INSULATION SHALL

TERMINATE AT WALL.

FINISHED WALL SURFACE

PROVIDE FIREPROOFING MATERIAL

BETWEEN PIPE SLEEVE AND PIPE.

INTERIOR WALLS

C

L

PIPE

SCHEDULE 40 STEEL PIPE SLEEVE

OF SIZE TO PASS PIPE.

L

CC

L

FIRE STANDPIPE- SEE FIRE

2 1/2" NIPPLE

NEW FIRE STANDPIPE

PIPE CLAMP TIGHT TO FLOOR SLAB

SPANNER LUGS

PROTECTION FLOOR PLANS FOR

STANDPIPE LOCATIONS AND SIZES

PACK SPACE BETWEEN SLEEVE AND PIPE

WITH FIREPROOF AND WATERPROOF MATERIAL

TO MAKE AIR-TIGHT AND WATER-TIGHT. (NOT

PIPE SLEEVE (MINIMUM 8")

REQUIRED IN STAIRWELLS)

(4

'-0

") M

AX

IM

UM

INSTALL PRESSURE GAUGE

AT TOP OF EACH FIRE

STANDPIPE

FIRE DEPARTMENT

VERIFY THREAD ON VALVE WITH LOCAL

2 1/2" FIRE DEPARTMENT HOSE VALVE

W/2 1/2" x 1 1/2" REDUCER

PIPE SUPPORTS

FLOW SWITCH

TO BUILDING

6"

DRAIN VALVE PLUGGED AND

CHAINED CLOSED

EXTEND AND TERMINATE

OVER FUNNEL DRAIN

6" FIRE PROTECTION

WATER SUPPLY

REFER TO SITE UTILITY PLAN

WALL SLEEVE & SEAL

OR MECHANICAL

SLEEVE SEAL

EXTERIOR WALL

4"

A A

20 GAUGE STEEL

SPRINKLER SHIELD

SHEET METAL SCREWS 2" ON

CENTERS. SMOOTH SCREW

HEADS WITH FILE OR EMERY

PAPER. ATTACHMENT MAY BE

BY SPOT WELDING

FRONT ELEVATION

SECTION A-A

SIDE ELEVATION

18

"

3"

1"

C

H

U

T

E

W

A

L

L

6" RADIUS

5"x 6" INCREASER

WATER FLOW SWITCH

6" FIRE STANDPIPE-

SEE FLOOR PLANS

SUPERVISORY SWITCH

CONTROL VALVE WITH

INDICATING TYPE FLOOR

CHECK VALVE

PRESSURE GAUGE

TO FIRE SPRINKLERS

01 (SHOWN FROM RISER) NOT TO SCALE

02 LINE/CHUTE SPRINKLER DETAILNOT TO SCALE

05 FIRE DEPARTMENT VALVE DETAILNOT TO SCALE

04 PIPE SLEEVE THRU FIRE-RATED WALL DETAILNOT TO SCALE

03 FIRE PROTECTION WATER SERVICE DETAILNOT TO SCALE

SPRINKLER FLOOR CONTROL VALVE ASSEMBLY DETAIL

06DETAILED CORRIDOR SECTION FOR ELECTRICAL & MECHANICAL ITEMSNOT TO SCALE

6" DOUBLE DETECTOR

CHECK VALVE ASSEMBLY

6"

SITE GLASS

INSPECTORS TEST VALVE

EXTEND SPRINKLER TEST

DRAIN TO EXTERIOR. SEE

FLOOR PLAN FOR LOCATION

FROM END OF REMOTE BRANCH

LINE FOR EACH ZONE

4"Ø MAIN

SPRINKLER PIPE

8"W x 4"H EXH DUCT 8"W x 4"H SA DUCT

8" HIGH MAX SUPPLY AIR DUCT

WIDTH VARIES, REFER TO FLOOR PLANS

8" HIGH MAX EXHAUST AIR DUCT

WIDTH VARIES, REFER TO FLOOR PLANS

DOWN

LIGHT

BATHROOM

CORRIDOR

GUESTROOM TV COAX AND/OR TELE/DATA HOMERUNS

BUNDLED TOGETHER ABOVE THE CEILING WITH PLENUM

RATED TIE-WRAPS 5'-0" O.C. AND SUPPORTED FROM

THE STRUCTURE ABOVE THE BRIDAL RINGS 10'-0" OC (TYP)

1"C STUBS FOR TELEPHONE AND

CABLE TV WIRING IN EACH

GUESTROOM (TYPICAL).

1" SPRINKLER PIPING INTO EACH

GUEST ROOM

1" SPRINKLER PIPING INTO EACH

GUEST ROOM

NOTE:

HVAC, PLUMBING, AND ELECTRICAL CONTRACTORS

SHALL COORDINATE LOCATIONS OF ALL DUCTS,

PIPING, CONDUIT, ETC., IN THE CORRIDOR SPACE.

CORRIDOR WALL

CORRIDOR WALL

6x6 ERC

6x6 SDC

1" CONDUITS

WALL MOUNTED 5" STORZ FIRE

DEPARTMENT CONNECTION

F6.01

DETAILSFIRE PROTECTION

eroman
JCST_Signature
eroman
JCST_Stamp