29
Symap IEC61850 Implementation Specification - Power Protection - Monitoring - Diesel Control - Power Management SYMAP ®

SYMAP_IEC61850

  • Upload
    zinab90

  • View
    212

  • Download
    0

Embed Size (px)

DESCRIPTION

dear

Citation preview

  • Symap IEC61850 Implementation Specification

    - Power Protection - Monitoring - Diesel Control - Power Management

    SYMAP

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 2/29

    FOR THIS DOCUMENT WE RESERVE ALL RIGHTS.

    WITHOUT OUR CONSENT IN WRITING IT SHALL NOT BE REPRODUCED BY ANY MEANS NOR BE MADE ACCESSIBLE TO THIRD PARTIES. ANY VIOLATION WILL BE SUBJECT TO CRIMINAL PROSECUTION.

    THE CONTENT OF THIS MANUAL IS FURNISHED FOR INFORMATIONAL USE ONLY.

    THE CONTENT IS SUBJECT TO CHANGE WITHOUT NOTICE, AND SHOULD NOT BE CONSTRUED AS A COMMITMENT BY STUCKE ELEKTRONIK GMBH.

    STUCKE ELEKTRONIK GMBH ASSUMES NO RESPONSIBILITY OR LIABILITY

    FOR ANY ERRORS OR INACCURACIES THAT MAY APPEAR IN THIS DOCUMENTATION.

    Version: 12.01.2012 File: SYMAP_IEC61850.doc IEC61850 V.1.4 Firmware:

    - CU: 1.10 - MU: 1.10 - RU: 1.10 - IEC61850 1.4

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 3/29

    Table of Contents 1 IEC61850 Model Implementation Conformance Statement (MICS) ....................... 4 1.1 Logical Nodes List ...................................................................................................... 4 1.2 Generic Logical Node Mappings ................................................................................. 5

    2 Protocol Implementation Conformance Statement (PICS) .................................. 14 2.1 ASCI basic conformance statement .......................................................................... 14 2.2 ACSI models conformance statement....................................................................... 15 2.3 ACSI service conformance statement ....................................................................... 17

    3 Protocol Implementation eXtra Information for Testing (PIXIT) .......................... 20 3.1 PIXIT for Association model ..................................................................................... 20 3.2 PIXIT for Server model ............................................................................................. 21 3.3 PIXIT for Data set model .......................................................................................... 22 3.4 PIXIT for Reporting model ........................................................................................ 22 3.5 PIXIT for Generic substation events model ............................................................... 23 3.6 PIXIT for Control model ............................................................................................ 25 3.7 PIXIT for Time and time synchronization model ........................................................ 27

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 4/29

    1 IEC61850 Model Implementation Conformance Statement (MICS)

    This model implementation conformance statement is applicable for Symap Y(ECG,EC,F,T,M;LD,D);BC(BC,BCG) firmware version CU1.10 and communication version 1.4.

    This MICS document specifies the modelling extensions compared to IEC 61850 edition 1. For the exact details on the standardized model please compare the ICD substation configuration file: Symap.icd, version 1.4.

    Chapter 1.1 contains the list of implemented logical nodes.

    Chapter 1.2 specifies defined mappings of used generic logical nodes to the Symap data points.

    1.1 Logical Nodes List

    The following table contains the list of logical nodes implemented in the device:

    L: System Logical Nodes

    LPHD (Physical device information)

    LLN0 (Logical node zero)

    G: Logical Nodes for generic references

    GGIO (Generic process I/O)

    M: Logical Nodes for metering and measurement

    MDIF (Differential measurements)

    MMTR (Metering)

    MMXN (Non phase related measurements)

    MMXU (Measurement)

    X: Logical Nodes for switchgear

    XCBR (Circuit breaker)

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 5/29

    1.2 Generic Logical Node Mappings

    The following table contains the list of generic GGIO Data Object mappings to Symap data points. For any additional information, please refer to the Symap Service manual.

    LN DO Symap Identification

    GGIO1 SPCSO1 Shunt1

    SPCSO2 Shunt 2

    SPCSO3 Lockout

    SPCSO4 SyncON

    SPCSO5 Basic Binary Output Fct 1

    SPCSO6 Basic Binary Output Fct 2

    SPCSO7 Basic Binary Output Fct 3

    SPCSO8 Basic Binary Output Fct 4

    SPCSO9 Basic Binary Output Fct 5

    SPCSO10 Basic Binary Output Fct 6

    SPCSO11 Basic Binary Output Fct 7

    SPCSO12 Basic Binary Output Fct 8

    SPCSO13 Optional Binary Output Fct 81

    SPCSO14 Optional Binary Output Fct 82

    SPCSO15 Optional Binary Output Fct 83

    SPCSO16 Optional Binary Output Fct 84

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 6/29

    LN DO Symap Identification

    GGIO2 Ind10 Basic Binary Input Fct 10

    Ind11 Basic Binary Input Fct 11

    Ind12 Basic Binary Input Fct 12

    Ind13 Basic Binary Input Fct 13

    Ind14 Basic Binary Input Fct 14

    Ind15 Basic Binary Input Fct 15

    Ind16 Basic Binary Input Fct 16

    Ind17 Basic Binary Input Fct 17

    Ind18 Basic Binary Input Fct 18

    Ind19 Basic Binary Input Fct 19

    Ind20 Basic Binary Input Fct 20

    Ind21 Basic Binary Input Fct 21

    Ind22 Basic Binary Input Fct 22

    Ind23 Basic Binary Input Fct 23

    Ind54 Optional Binary Input Fct 54

    Ind55 Optional Binary Input Fct 55

    Ind56 Optional Binary Input Fct 56

    Ind57 Optional Binary Input Fct 57

    Ind58 Optional Binary Input Fct 58

    Ind59 Optional Binary Input Fct 59

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 7/29

    LN DO Symap Identification

    GGIO3

    Alm1 Programmable alarm status 1

    Alm2 Programmable alarm status 2

    Alm3 Programmable alarm status 3

    Alm4 Programmable alarm status 4

    Alm5 Programmable alarm status 5

    Alm6 Programmable alarm status 6

    Alm7 Programmable alarm status 7

    Alm8 Programmable alarm status 8

    Alm9 Programmable alarm status 9

    Alm10 Programmable alarm status 10

    Alm11 Programmable alarm status 11

    Alm12 Programmable alarm status 12

    Alm13 Programmable alarm status 13

    Alm14 Programmable alarm status 14

    Alm15 Programmable alarm status 15

    Alm16 Programmable alarm status 16

    Alm17 Programmable alarm status 17

    Alm18 Programmable alarm status 18

    Alm19 Programmable alarm status 19

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 8/29

    LN DO Symap Identification

    Alm20 Programmable alarm status 20

    Alm21 Programmable alarm status 21

    Alm22 Programmable alarm status 22

    Alm23 Programmable alarm status 23

    Alm24 Programmable alarm status 24

    Alm25 Programmable alarm status 25

    Alm26 Programmable alarm status 26

    Alm27 Programmable alarm status 27

    Alm28 Programmable alarm status 28

    Alm29 Programmable alarm status 29

    Alm30 Programmable alarm status 30

    Alm31 Programmable alarm status 31

    Alm32 Programmable alarm status 32

    Alm33 Programmable alarm status 33

    Alm34 Programmable alarm status 34

    Alm35 Programmable alarm status 35

    Alm36 Programmable alarm status 36

    Alm37 Programmable alarm status 37

    Alm38 Programmable alarm status 38

    Alm39 Programmable alarm status 39

    Alm40 Programmable alarm status 40

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 9/29

    LN DO Symap Identification

    Alm41 Programmable alarm status 41

    Alm42 Programmable alarm status 42

    Alm43 Programmable alarm status 43

    Alm44 Programmable alarm status 44

    GGIO3 Alm45 Programmable alarm status 45

    Alm46 Programmable alarm status 46

    Alm47 Programmable alarm status 47

    Alm48 Programmable alarm status 48

    Alm49 Programmable alarm status 49

    Alm50 Programmable alarm status 50

    Alm51 Programmable alarm status 51

    Alm52 Programmable alarm status 52

    Alm53 Programmable alarm status 53

    Alm54 Programmable alarm status 54

    Alm55 Programmable alarm status 55

    Alm56 Programmable alarm status 56

    Alm57 Programmable alarm status 57

    Alm58 Programmable alarm status 58

    Alm59 Programmable alarm status 59

    Alm60 Programmable alarm status 60

    Alm61 Programmable alarm status 61

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 10/29

    LN DO Symap Identification

    Alm62 Programmable alarm status 62

    Alm63 Programmable alarm status 63

    Alm64 Programmable alarm status 64

    Alm65 Programmable alarm status 65

    Alm66 Programmable alarm status 66

    Alm67 Programmable alarm status 67

    Alm68 Programmable alarm status 68

    Alm69 Programmable alarm status 69

    Alm70 Programmable alarm status 70

    Alm71 Programmable alarm status 71

    Alm72 Programmable alarm status 72

    Alm73 Programmable alarm status 73

    Alm74 Programmable alarm status 74

    Alm75 Programmable alarm status 75

    Alm76 Programmable alarm status 76

    Alm77 Programmable alarm status 77

    Alm78 Programmable alarm status 78

    Alm79 Programmable alarm status 79

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 11/29

    LN DO Symap Identification

    GGIO4 SPCS0330 Programmable command event 330

    SPCS0331 Programmable command event 331

    SPCS0332 Programmable command event 332

    SPCS0333 Programmable command event 333

    SPCS0334 Programmable command event 334

    SPCS0335 Programmable command event 335

    SPCS0336 Programmable command event 336

    SPCS0337 Programmable command event 337

    SPCS0338 Programmable command event 338

    SPCS0339 Programmable command event 339

    GGIO5 AnIn1 Basic analogue input 1

    AnIn2 Basic analogue input 2

    AnIn3 Basic analogue input 3

    AnIn4 Basic analogue input 4

    GGIO6 Ind1 GOOSE subscriber information 1

    Ind2 GOOSE subscriber information 2

    Ind3 GOOSE subscriber information 3

    Ind4 GOOSE subscriber information 4

    Ind5 GOOSE subscriber information 5

    Ind6 GOOSE subscriber information 6

    Ind7 GOOSE subscriber information 7

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 12/29

    LN DO Symap Identification

    Ind8 GOOSE subscriber information 8

    Ind9 GOOSE subscriber information 9

    Ind10 GOOSE subscriber information 10

    Ind11 GOOSE subscriber information 11

    Ind12 GOOSE subscriber information 12

    Ind13 GOOSE subscriber information 13

    Ind14 GOOSE subscriber information 14

    Ind15 GOOSE subscriber information 15

    Ind16 GOOSE subscriber information 16

    Ind17 GOOSE subscriber information 17

    Ind18 GOOSE subscriber information 18

    Ind19 GOOSE subscriber information 19

    Ind20 GOOSE subscriber information 20

    Ind21 GOOSE subscriber information 21

    Ind22 GOOSE subscriber information 22

    Ind23 GOOSE subscriber information 23

    Ind24 GOOSE subscriber information 24

    Ind25 GOOSE subscriber information 25

    Ind26 GOOSE subscriber information 26

    Ind27 GOOSE subscriber information 27

    Ind28 GOOSE subscriber information 28

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 13/29

    LN DO Symap Identification

    Ind29 GOOSE subscriber information 29

    Ind30 GOOSE subscriber information 30

    Ind31 GOOSE subscriber information 31

    Ind32 GOOSE subscriber information 32

    Ind33 GOOSE subscriber information 33

    Ind34 GOOSE subscriber information 34

    Ind35 GOOSE subscriber information 35

    Ind36 GOOSE subscriber information 36

    Ind37 GOOSE subscriber information 37

    Ind38 GOOSE subscriber information 38

    Ind39 GOOSE subscriber information 39

    Ind40 GOOSE subscriber information 40

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 14/29

    2 Protocol Implementation Conformance Statement (PICS)

    The following ACSI conformance statements are used to provide an overview and details about Symap, with firmware version 1.4 ASCI basic conformance statement,

    ACSI models conformance statement,

    ACSI service conformance statement

    The statements specify the communication features mapped to IEC 61850-8-1.

    2.1 ASCI basic conformance statement

    The basic conformance statement is defined in Table A.1. Table A.1 Basic conformance statement

    Client/ Subscriber

    Server/ Publisher

    Value/ Comments

    Client-Server roles

    B11 Server side (of TWO-PARTY-APPLICATION-ASSOCIATION)

    Y

    B12 Client side of (TWO-PARTY-APPLICATION-ASSOCIATION)

    SCSMs supported

    B21 SCSM: IEC 6185-8-1 used Y B22 SCSM: IEC 6185-9-1 used N B23 SCSM: IEC 6185-9-2 used N B24 SCSM: other

    Generic substation event model (GSE)

    B31 Publisher side N B32 Subscriber side N

    Transmission of sampled value model (SVC)

    B41 Publisher side N B42 Subcriber side N Y = supported N or empty = not supported

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 15/29

    2.2 ACSI models conformance statement

    The ACSI models conformance statement is defined in Table A.2. Table A.2 ACSI models conformance statement

    Client/ Subscriber

    Server/ Publisher

    Value/ Comments

    If Server or Client side (B11/12) supported

    M1 Logical device Y

    M2 Logical node Y M3 Data Y M4 Data set Y M5 Substitution N M6 Setting group control N Reporting M7 Buffered report control N M7-1 sequence-number N M7-2 report-time-stamp N M7-3 reason-for-inclusion N M7-4 data-set-name N M7-5 data-reference N M7-6 buffer-overflow N M7-7 entryID N M7-8 BufTim N M7-9 IntgPd N M7-10 GI N M7-11 conf-revision N M8 Unbuffered report control Y M8-1 sequence-number Y M8-2 report-time-stamp Y M8-3 reason-for-inclusion Y M8-4 data-set-name Y M8-5 data-reference Y M8-6 BufTim Y M8-7 IntgPd Y M8-8 GI Y M8-9 conf-revision Y Logging N M9 Log control N M9-1 IntgPd N M10 Log N M11 Control Y

    If GSE (B31/32) is supported

    M12 GOOSE Y Y M13 GSSE

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 16/29

    Client/ Subscriber

    Server/ Publisher

    Value/ Comments

    If SVC (41/42) is supported

    M14 Multicast SVC N M15 Unicast SVC N

    If Server or Client side (B11/12) supported

    M16 Time Y M17 File Transfer N

    Y = service is supported

    N or empty = service is not supported

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 17/29

    2.3 ACSI service conformance statement

    The ACSI service conformance statement is defined in Table A.3 (depending on the statements in Table A.1).

    Table A.3 ACSI service Conformance statement

    Services AA: TP/MC

    Client (C) Server (S) Comments

    Server S1 ServerDirectory TP Y

    Application association S2 Associate Y S3 Abort Y S4 Release Y

    Logical device S5 LogicalDeviceDirectory TP Y

    Logical node S6 LogicalNodeDirectory TP Y S7 GetAllDataValues TP Y

    Data S8 GetDataValues TP Y S9 SetDataValues TP Y

    S10 GetDataDirectory TP Y S11 GetDataDefinition TP Y

    Data set S12 GetDataSetValues TP Y S13 SetDataSetValues TP N S14 CreateDataSet TP Y S15 DeleteDataSet TP Y S16 GetDataSetDirectory TP Y

    Substitution S17 SetDataValues TP N

    Setting group control S18 SelectActiveSG TP N S19 SelectEditSG TP N S20 SetSGValues TP N S21 ConfirmEditSGValues TP N S22 GetSGValues TP N S23 GetSGCBValues TP N

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 18/29

    Services AA: TP/MC

    Client (C) Server (S) Comments

    Reporting Buffered report control block (BRCB)

    S24 Report TP N S24-1 data-change (dchg) N S24-2 qchg-change (qchg) N S24-3 data-update (dupd) N

    S25 GetBRCBValues TP N S26 SetBRCBValues TP N

    Unbuffered report control block (URCB)

    S27 Report TP Y S27-1 data-change (dchg) Y S27-2 qchg-change (qchg) Y S27-3 data-update (dupd) Y

    S28 GetURCBValues TP Y S29 SetURCBValues TP Y

    Logging Log control block

    S30 GetLCBValues TP N S31 SetLCBValues TP N

    Log

    S32 QueryLogByTime TP N S33 QueryLogByEntry TP N S34 GetLogStatusValues TP N

    Generic substation event model (GSE) GOOSE-CONTROL-BLOCK

    S35 SendGOOSEMessage MC Y S36 GetReference TP N S37 GetGOOSEElementNumber TP N S38 GetGoCBValues TP Y S39 SetGoCBValues TP N

    GSSE-CONTROL-BLOCK

    S40 SendGSSEMessage MC N S41 GetReference TP N S42 GetGSSEElementNumber TP N S43 GetGsCBValues TP N S44 SetGsCBValues TP N N

    Transmission of sampled value model (SVC) Multicast SVC

    S45 SendMSVMessage MC N S46 GetMSVCBValues TP N S47 SetMSVCBValues TP N

    Unicast SVC

    S48 SendUSVMessage TP N S49 GetUSVCBValues TP N

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 19/29

    Services AA: TP/MC

    Client (C) Server (S) Comments

    S50 SetUSVCBValues TP N

    Control S51 Select N S52 SelectWithValue TP N S53 Cancel TP N S54 Operate TP Y S55 Command-

    Termination TP N

    S56 TimeActivated-Operate TP N

    File transfer S57 GetFile TP N S58 SetFile TP N S59 DeleteFile TP N S60 GetFileAttributeValues TP N

    Time

    T1 Time resolution of internal clock 7 nearest negative power of 2 in seconds

    T2 Time accuracy of internal clock 10 T0

    T1

    T2

    T3

    T4

    T5

    T3 Supported TimeStamp resolution - 10 nearest negative power of 2 in seconds

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 20/29

    3 Protocol Implementation eXtra Information for Testing (PIXIT)

    This section specifies the protocol implementation extra information for testing (PIXIT) of Symap IEC 61850 implementation. Together with the PICS and the MICS the PIXIT forms the basis for a conformance test according to IEC 61850-10. Each chapter specifies the PIXIT for each applicable ACSI service model as structured in IEC 61850-10.

    3.1 PIXIT for Association model

    Description Value / Clarification Maximum number of clients that can set-up an association simultaneously

    4

    TCP_KEEPALIVE value 10 Lost connection detection time 15 seconds Is authentication supported N What association parameters are necessary for successful association

    Transport selector N Session selector N Presentation selector N AP Title N AE Qualifier N

    If association parameters are necessary for association, describe the correct values e.g.

    Transport selector 0001 Session selector 0001 Presentation selector 00000001 AP Title na AE Qualifier na

    What is the maximum and minimum MMS PDU size

    Max MMS PDU size 10000 Min MMS PDU size 10000

    What is the maximum startup time after a power supply interrupt

    5 seconds

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 21/29

    3.2 PIXIT for Server model

    Description Value / Clarification Which analogue value (MX) quality bits are supported (can be set by server)

    Validity: N Good, N Invalid, N Reserved, N Questionable N Overflow N OutofRange N BadReference N Oscillatory N Failure N OldData N Inconsistent N Inaccurate Source: N Process N Substituted N Test N OperatorBlocked

    Which status value (ST) quality bits are supported (can be set by server)

    Validity: N Good, Y Invalid, N Reserved, N Questionable N BadReference N Oscillatory N Failure N OldData N Inconsistent N Inaccurate Source: N Process N Substituted N Test N OperatorBlocked

    What is the maximum number of data values in one GetDataValues request

    15

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 22/29

    3.3 PIXIT for Data set model

    Description Value / Clarification What is the maximum number of data elements in one data set (compare ICD setting)

    49

    How many persistent data sets can be created by one or more clients

    20

    How many non-persistent data sets can be created by one or more clients

    20

    3.4 PIXIT for Reporting model

    Description Value / Clarification The supported trigger conditions are (compare PICS)

    integrity Y data change Y quality change N data update N general interrogation Y

    The supported optional fields are sequence-number Y report-time-stamp Y reason-for-inclusion Y data-set-name Y data-reference Y buffer-overflow N entryID N conf-rev Y segmentation Y

    Can the server send segmented reports N Mechanism on second internal data change notification of the same analogue data value within buffer period

    Send report immediately

    Multi client URCB approach Each URCB is visible to all clients May the reported data set contain: - structured data objects? - data attributes? - timestamp data attributes?

    Y

    Y

    Y, will/will not be included in a dchg report

    What is the scan cycle for binary events? Is this fixed, configurable

    10 ms Fixed

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 23/29

    3.5 PIXIT for Generic substation events model

    Description Value / Clarification What elements of a subscribed GOOSE header are checked to decide the message is valid and the allData values are accepted? If yes, describe the conditions. Note: the VLAN tag may be removed by a ethernet switch and should not be checked

    N source MAC address Y destination MAC address Y Ethertype = 0x88B8 N gocbRef, NULL gocbRef is

    considered an error N timeAllowedtoLive N datSet N goID N t Y stNum N sqNum Y test Y confRev Y ndsCom N numDatSetEntries;

    numDataSetEntries=0 is considered an error

    Can the test flag in the published GOOSE be turned on / off

    N

    What is the behavior when a GOOSE message with test flag set is received?

    The message will be ignored

    What is the behavior when the GOOSE publish configuration is incorrect

    DUT keeps GoEna=F

    When is a subscribed GOOSE marked as lost? (TAL = time allowed to live value from the last received GOOSE message)

    message does not arrive by 2x TAL

    What is the behavior when one or more subscribed GOOSE messages isnt received or syntactically incorrect (missing GOOSE)

    Quality flags of corresponding DOs are set to invalid

    What is the behavior when a subscribed GOOSE message is out-of-order

    Out-of-order message will be ignored

    What is the behavior when a subscribed GOOSE message is duplicated

    The duplicate message is ignored

    Does the device subscribe to GOOSE messages with/without the VLAN tag?

    Y, with the VLAN tag Y, without the VLAN tag

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 24/29

    Description Value / Clarification May the GOOSE data set contain: - structured data objects? - data attributes? - timestamp data attributes?

    Subscribed Published N N Y Y N N

    What is the slow retransmission time? Is it fixed or configurable?

    5000 mseconds with TAL = 10000 Fixed

    What is the fast retransmission scheme? Is it fixed or configurable?

    1) 2 mseconds with TAL = 4 2) 4 mseconds with TAL = 24 3) 16 mseconds with TAL = 9968 4) 5000 mseconds with TAL = 10000 Retransmission scheme is fixed

    Can the Goose publish be turned on / off by using SetGoCBValues(GoEna)

    Y

    TAL = Time Allowed to Live

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 25/29

    3.6 PIXIT for Control model

    Description Value / Clarification What control modes are supported (compare PICS)

    Y status-only Y direct-with-normal-security N sbo-with-normal-security N direct-with-enhanced-security N sbo-with-enhanced-security

    Is the control model fixed, configurable and/or online changeable?

    FIXED

    Is Time activated operate (operTm) supported

    NO

    Is operate-many supported NO What is the behavior of the DUT when the test attribute is set in the selectwithvalue and/or operate request

    n/a

    What are the conditions for the time (T) attribute in the SelectWithValue and/or Operate request

    DUT ignores the time value and execute the command as usual

    Is pulse configuration supported NO What is the behavior of the DUT when the check conditions are set Is this behavior fixed, configurable, online changeable?

    N synchrocheck N interlock-check Fixed

    What additional cause diagnosis are supported

    No additional cause is sent

    How to force a test-not-ok response with Operate request?

    DOns: n/a SBOns: n/a DOes: n/a SBOes: n/a

    Which origin categories are supported? 2 What happens if the orCat is not supported?

    DOns: execute as usual SBOns: n/a DOes: n/a SBOes: n/a

    Does the IED accept an selectwithvalue/operate with the same ctlVal as the current status value?

    DOns: Y SBOns: n/a DOes: n/a SBOes: n/a

    Does the IED accept a select/operate on the same control object from 2 different

    DOns: Y SBOns: n/a

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 26/29

    Description Value / Clarification clients at the same time? DOes: n/a

    SBOes: n/a Can a control operation be blocked by Mod=Off or Blocked

    N

    Does the IED support local / remote operation?

    N

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 27/29

    3.7 PIXIT for Time and time synchronization model

    Description Value / Clarification What quality bits are supported? N LeapSecondsKnown

    N ClockFailure Y ClockNotSynchronized

    Describe the behavior of the IED when the time synchronization signal/messages are lost

    TimeStamp Quality set to ClockNotSynchronized

    When is the time quality bit "Clock failure" set?

    N/A

    When is the time quality bit "Clock not synchronised set?

    If no SNTP response is received within 2 seconds after request

    Is the timestamp of a binary event adjusted to the configured scan cycle?

    N

    Does the device support time zone and daylight saving?

    Y

    Which attibutes of the SNTP response packet are validated?

    Y Leap indicator not equal to 3 Y Mode is equal to SERVER Y OriginateTimestamp is equal to

    value sent by the SNTP client as Transmit Timestamp

    Y RX/TX timestamp fields are checked for reasonableness

    Y SNTP version 3 and/or 4 N other (describe)

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 28/29

  • IEC61850 Communication Interface

    SYMAP SYMAP_IEC61850_rev3 - 29/29 Stucke Elektronik GmbH Merkurring 26 22143 Hamburg Germany

    http://www.stuckegmbh.de