Symap IEC61850 Implementation Specification
- Power Protection - Monitoring - Diesel Control - Power Management
SYMAP
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 2/29
FOR THIS DOCUMENT WE RESERVE ALL RIGHTS.
WITHOUT OUR CONSENT IN WRITING IT SHALL NOT BE REPRODUCED BY ANY MEANS NOR BE MADE ACCESSIBLE TO THIRD PARTIES. ANY VIOLATION WILL BE SUBJECT TO CRIMINAL PROSECUTION.
THE CONTENT OF THIS MANUAL IS FURNISHED FOR INFORMATIONAL USE ONLY.
THE CONTENT IS SUBJECT TO CHANGE WITHOUT NOTICE, AND SHOULD NOT BE CONSTRUED AS A COMMITMENT BY STUCKE ELEKTRONIK GMBH.
STUCKE ELEKTRONIK GMBH ASSUMES NO RESPONSIBILITY OR LIABILITY
FOR ANY ERRORS OR INACCURACIES THAT MAY APPEAR IN THIS DOCUMENTATION.
Version: 12.01.2012 File: SYMAP_IEC61850.doc IEC61850 V.1.4 Firmware:
- CU: 1.10 - MU: 1.10 - RU: 1.10 - IEC61850 1.4
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 3/29
Table of Contents 1 IEC61850 Model Implementation Conformance Statement (MICS) ....................... 4 1.1 Logical Nodes List ...................................................................................................... 4 1.2 Generic Logical Node Mappings ................................................................................. 5
2 Protocol Implementation Conformance Statement (PICS) .................................. 14 2.1 ASCI basic conformance statement .......................................................................... 14 2.2 ACSI models conformance statement....................................................................... 15 2.3 ACSI service conformance statement ....................................................................... 17
3 Protocol Implementation eXtra Information for Testing (PIXIT) .......................... 20 3.1 PIXIT for Association model ..................................................................................... 20 3.2 PIXIT for Server model ............................................................................................. 21 3.3 PIXIT for Data set model .......................................................................................... 22 3.4 PIXIT for Reporting model ........................................................................................ 22 3.5 PIXIT for Generic substation events model ............................................................... 23 3.6 PIXIT for Control model ............................................................................................ 25 3.7 PIXIT for Time and time synchronization model ........................................................ 27
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 4/29
1 IEC61850 Model Implementation Conformance Statement (MICS)
This model implementation conformance statement is applicable for Symap Y(ECG,EC,F,T,M;LD,D);BC(BC,BCG) firmware version CU1.10 and communication version 1.4.
This MICS document specifies the modelling extensions compared to IEC 61850 edition 1. For the exact details on the standardized model please compare the ICD substation configuration file: Symap.icd, version 1.4.
Chapter 1.1 contains the list of implemented logical nodes.
Chapter 1.2 specifies defined mappings of used generic logical nodes to the Symap data points.
1.1 Logical Nodes List
The following table contains the list of logical nodes implemented in the device:
L: System Logical Nodes
LPHD (Physical device information)
LLN0 (Logical node zero)
G: Logical Nodes for generic references
GGIO (Generic process I/O)
M: Logical Nodes for metering and measurement
MDIF (Differential measurements)
MMTR (Metering)
MMXN (Non phase related measurements)
MMXU (Measurement)
X: Logical Nodes for switchgear
XCBR (Circuit breaker)
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 5/29
1.2 Generic Logical Node Mappings
The following table contains the list of generic GGIO Data Object mappings to Symap data points. For any additional information, please refer to the Symap Service manual.
LN DO Symap Identification
GGIO1 SPCSO1 Shunt1
SPCSO2 Shunt 2
SPCSO3 Lockout
SPCSO4 SyncON
SPCSO5 Basic Binary Output Fct 1
SPCSO6 Basic Binary Output Fct 2
SPCSO7 Basic Binary Output Fct 3
SPCSO8 Basic Binary Output Fct 4
SPCSO9 Basic Binary Output Fct 5
SPCSO10 Basic Binary Output Fct 6
SPCSO11 Basic Binary Output Fct 7
SPCSO12 Basic Binary Output Fct 8
SPCSO13 Optional Binary Output Fct 81
SPCSO14 Optional Binary Output Fct 82
SPCSO15 Optional Binary Output Fct 83
SPCSO16 Optional Binary Output Fct 84
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 6/29
LN DO Symap Identification
GGIO2 Ind10 Basic Binary Input Fct 10
Ind11 Basic Binary Input Fct 11
Ind12 Basic Binary Input Fct 12
Ind13 Basic Binary Input Fct 13
Ind14 Basic Binary Input Fct 14
Ind15 Basic Binary Input Fct 15
Ind16 Basic Binary Input Fct 16
Ind17 Basic Binary Input Fct 17
Ind18 Basic Binary Input Fct 18
Ind19 Basic Binary Input Fct 19
Ind20 Basic Binary Input Fct 20
Ind21 Basic Binary Input Fct 21
Ind22 Basic Binary Input Fct 22
Ind23 Basic Binary Input Fct 23
Ind54 Optional Binary Input Fct 54
Ind55 Optional Binary Input Fct 55
Ind56 Optional Binary Input Fct 56
Ind57 Optional Binary Input Fct 57
Ind58 Optional Binary Input Fct 58
Ind59 Optional Binary Input Fct 59
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 7/29
LN DO Symap Identification
GGIO3
Alm1 Programmable alarm status 1
Alm2 Programmable alarm status 2
Alm3 Programmable alarm status 3
Alm4 Programmable alarm status 4
Alm5 Programmable alarm status 5
Alm6 Programmable alarm status 6
Alm7 Programmable alarm status 7
Alm8 Programmable alarm status 8
Alm9 Programmable alarm status 9
Alm10 Programmable alarm status 10
Alm11 Programmable alarm status 11
Alm12 Programmable alarm status 12
Alm13 Programmable alarm status 13
Alm14 Programmable alarm status 14
Alm15 Programmable alarm status 15
Alm16 Programmable alarm status 16
Alm17 Programmable alarm status 17
Alm18 Programmable alarm status 18
Alm19 Programmable alarm status 19
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 8/29
LN DO Symap Identification
Alm20 Programmable alarm status 20
Alm21 Programmable alarm status 21
Alm22 Programmable alarm status 22
Alm23 Programmable alarm status 23
Alm24 Programmable alarm status 24
Alm25 Programmable alarm status 25
Alm26 Programmable alarm status 26
Alm27 Programmable alarm status 27
Alm28 Programmable alarm status 28
Alm29 Programmable alarm status 29
Alm30 Programmable alarm status 30
Alm31 Programmable alarm status 31
Alm32 Programmable alarm status 32
Alm33 Programmable alarm status 33
Alm34 Programmable alarm status 34
Alm35 Programmable alarm status 35
Alm36 Programmable alarm status 36
Alm37 Programmable alarm status 37
Alm38 Programmable alarm status 38
Alm39 Programmable alarm status 39
Alm40 Programmable alarm status 40
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 9/29
LN DO Symap Identification
Alm41 Programmable alarm status 41
Alm42 Programmable alarm status 42
Alm43 Programmable alarm status 43
Alm44 Programmable alarm status 44
GGIO3 Alm45 Programmable alarm status 45
Alm46 Programmable alarm status 46
Alm47 Programmable alarm status 47
Alm48 Programmable alarm status 48
Alm49 Programmable alarm status 49
Alm50 Programmable alarm status 50
Alm51 Programmable alarm status 51
Alm52 Programmable alarm status 52
Alm53 Programmable alarm status 53
Alm54 Programmable alarm status 54
Alm55 Programmable alarm status 55
Alm56 Programmable alarm status 56
Alm57 Programmable alarm status 57
Alm58 Programmable alarm status 58
Alm59 Programmable alarm status 59
Alm60 Programmable alarm status 60
Alm61 Programmable alarm status 61
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 10/29
LN DO Symap Identification
Alm62 Programmable alarm status 62
Alm63 Programmable alarm status 63
Alm64 Programmable alarm status 64
Alm65 Programmable alarm status 65
Alm66 Programmable alarm status 66
Alm67 Programmable alarm status 67
Alm68 Programmable alarm status 68
Alm69 Programmable alarm status 69
Alm70 Programmable alarm status 70
Alm71 Programmable alarm status 71
Alm72 Programmable alarm status 72
Alm73 Programmable alarm status 73
Alm74 Programmable alarm status 74
Alm75 Programmable alarm status 75
Alm76 Programmable alarm status 76
Alm77 Programmable alarm status 77
Alm78 Programmable alarm status 78
Alm79 Programmable alarm status 79
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 11/29
LN DO Symap Identification
GGIO4 SPCS0330 Programmable command event 330
SPCS0331 Programmable command event 331
SPCS0332 Programmable command event 332
SPCS0333 Programmable command event 333
SPCS0334 Programmable command event 334
SPCS0335 Programmable command event 335
SPCS0336 Programmable command event 336
SPCS0337 Programmable command event 337
SPCS0338 Programmable command event 338
SPCS0339 Programmable command event 339
GGIO5 AnIn1 Basic analogue input 1
AnIn2 Basic analogue input 2
AnIn3 Basic analogue input 3
AnIn4 Basic analogue input 4
GGIO6 Ind1 GOOSE subscriber information 1
Ind2 GOOSE subscriber information 2
Ind3 GOOSE subscriber information 3
Ind4 GOOSE subscriber information 4
Ind5 GOOSE subscriber information 5
Ind6 GOOSE subscriber information 6
Ind7 GOOSE subscriber information 7
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 12/29
LN DO Symap Identification
Ind8 GOOSE subscriber information 8
Ind9 GOOSE subscriber information 9
Ind10 GOOSE subscriber information 10
Ind11 GOOSE subscriber information 11
Ind12 GOOSE subscriber information 12
Ind13 GOOSE subscriber information 13
Ind14 GOOSE subscriber information 14
Ind15 GOOSE subscriber information 15
Ind16 GOOSE subscriber information 16
Ind17 GOOSE subscriber information 17
Ind18 GOOSE subscriber information 18
Ind19 GOOSE subscriber information 19
Ind20 GOOSE subscriber information 20
Ind21 GOOSE subscriber information 21
Ind22 GOOSE subscriber information 22
Ind23 GOOSE subscriber information 23
Ind24 GOOSE subscriber information 24
Ind25 GOOSE subscriber information 25
Ind26 GOOSE subscriber information 26
Ind27 GOOSE subscriber information 27
Ind28 GOOSE subscriber information 28
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 13/29
LN DO Symap Identification
Ind29 GOOSE subscriber information 29
Ind30 GOOSE subscriber information 30
Ind31 GOOSE subscriber information 31
Ind32 GOOSE subscriber information 32
Ind33 GOOSE subscriber information 33
Ind34 GOOSE subscriber information 34
Ind35 GOOSE subscriber information 35
Ind36 GOOSE subscriber information 36
Ind37 GOOSE subscriber information 37
Ind38 GOOSE subscriber information 38
Ind39 GOOSE subscriber information 39
Ind40 GOOSE subscriber information 40
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 14/29
2 Protocol Implementation Conformance Statement (PICS)
The following ACSI conformance statements are used to provide an overview and details about Symap, with firmware version 1.4 ASCI basic conformance statement,
ACSI models conformance statement,
ACSI service conformance statement
The statements specify the communication features mapped to IEC 61850-8-1.
2.1 ASCI basic conformance statement
The basic conformance statement is defined in Table A.1. Table A.1 Basic conformance statement
Client/ Subscriber
Server/ Publisher
Value/ Comments
Client-Server roles
B11 Server side (of TWO-PARTY-APPLICATION-ASSOCIATION)
Y
B12 Client side of (TWO-PARTY-APPLICATION-ASSOCIATION)
SCSMs supported
B21 SCSM: IEC 6185-8-1 used Y B22 SCSM: IEC 6185-9-1 used N B23 SCSM: IEC 6185-9-2 used N B24 SCSM: other
Generic substation event model (GSE)
B31 Publisher side N B32 Subscriber side N
Transmission of sampled value model (SVC)
B41 Publisher side N B42 Subcriber side N Y = supported N or empty = not supported
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 15/29
2.2 ACSI models conformance statement
The ACSI models conformance statement is defined in Table A.2. Table A.2 ACSI models conformance statement
Client/ Subscriber
Server/ Publisher
Value/ Comments
If Server or Client side (B11/12) supported
M1 Logical device Y
M2 Logical node Y M3 Data Y M4 Data set Y M5 Substitution N M6 Setting group control N Reporting M7 Buffered report control N M7-1 sequence-number N M7-2 report-time-stamp N M7-3 reason-for-inclusion N M7-4 data-set-name N M7-5 data-reference N M7-6 buffer-overflow N M7-7 entryID N M7-8 BufTim N M7-9 IntgPd N M7-10 GI N M7-11 conf-revision N M8 Unbuffered report control Y M8-1 sequence-number Y M8-2 report-time-stamp Y M8-3 reason-for-inclusion Y M8-4 data-set-name Y M8-5 data-reference Y M8-6 BufTim Y M8-7 IntgPd Y M8-8 GI Y M8-9 conf-revision Y Logging N M9 Log control N M9-1 IntgPd N M10 Log N M11 Control Y
If GSE (B31/32) is supported
M12 GOOSE Y Y M13 GSSE
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 16/29
Client/ Subscriber
Server/ Publisher
Value/ Comments
If SVC (41/42) is supported
M14 Multicast SVC N M15 Unicast SVC N
If Server or Client side (B11/12) supported
M16 Time Y M17 File Transfer N
Y = service is supported
N or empty = service is not supported
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 17/29
2.3 ACSI service conformance statement
The ACSI service conformance statement is defined in Table A.3 (depending on the statements in Table A.1).
Table A.3 ACSI service Conformance statement
Services AA: TP/MC
Client (C) Server (S) Comments
Server S1 ServerDirectory TP Y
Application association S2 Associate Y S3 Abort Y S4 Release Y
Logical device S5 LogicalDeviceDirectory TP Y
Logical node S6 LogicalNodeDirectory TP Y S7 GetAllDataValues TP Y
Data S8 GetDataValues TP Y S9 SetDataValues TP Y
S10 GetDataDirectory TP Y S11 GetDataDefinition TP Y
Data set S12 GetDataSetValues TP Y S13 SetDataSetValues TP N S14 CreateDataSet TP Y S15 DeleteDataSet TP Y S16 GetDataSetDirectory TP Y
Substitution S17 SetDataValues TP N
Setting group control S18 SelectActiveSG TP N S19 SelectEditSG TP N S20 SetSGValues TP N S21 ConfirmEditSGValues TP N S22 GetSGValues TP N S23 GetSGCBValues TP N
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 18/29
Services AA: TP/MC
Client (C) Server (S) Comments
Reporting Buffered report control block (BRCB)
S24 Report TP N S24-1 data-change (dchg) N S24-2 qchg-change (qchg) N S24-3 data-update (dupd) N
S25 GetBRCBValues TP N S26 SetBRCBValues TP N
Unbuffered report control block (URCB)
S27 Report TP Y S27-1 data-change (dchg) Y S27-2 qchg-change (qchg) Y S27-3 data-update (dupd) Y
S28 GetURCBValues TP Y S29 SetURCBValues TP Y
Logging Log control block
S30 GetLCBValues TP N S31 SetLCBValues TP N
Log
S32 QueryLogByTime TP N S33 QueryLogByEntry TP N S34 GetLogStatusValues TP N
Generic substation event model (GSE) GOOSE-CONTROL-BLOCK
S35 SendGOOSEMessage MC Y S36 GetReference TP N S37 GetGOOSEElementNumber TP N S38 GetGoCBValues TP Y S39 SetGoCBValues TP N
GSSE-CONTROL-BLOCK
S40 SendGSSEMessage MC N S41 GetReference TP N S42 GetGSSEElementNumber TP N S43 GetGsCBValues TP N S44 SetGsCBValues TP N N
Transmission of sampled value model (SVC) Multicast SVC
S45 SendMSVMessage MC N S46 GetMSVCBValues TP N S47 SetMSVCBValues TP N
Unicast SVC
S48 SendUSVMessage TP N S49 GetUSVCBValues TP N
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 19/29
Services AA: TP/MC
Client (C) Server (S) Comments
S50 SetUSVCBValues TP N
Control S51 Select N S52 SelectWithValue TP N S53 Cancel TP N S54 Operate TP Y S55 Command-
Termination TP N
S56 TimeActivated-Operate TP N
File transfer S57 GetFile TP N S58 SetFile TP N S59 DeleteFile TP N S60 GetFileAttributeValues TP N
Time
T1 Time resolution of internal clock 7 nearest negative power of 2 in seconds
T2 Time accuracy of internal clock 10 T0
T1
T2
T3
T4
T5
T3 Supported TimeStamp resolution - 10 nearest negative power of 2 in seconds
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 20/29
3 Protocol Implementation eXtra Information for Testing (PIXIT)
This section specifies the protocol implementation extra information for testing (PIXIT) of Symap IEC 61850 implementation. Together with the PICS and the MICS the PIXIT forms the basis for a conformance test according to IEC 61850-10. Each chapter specifies the PIXIT for each applicable ACSI service model as structured in IEC 61850-10.
3.1 PIXIT for Association model
Description Value / Clarification Maximum number of clients that can set-up an association simultaneously
4
TCP_KEEPALIVE value 10 Lost connection detection time 15 seconds Is authentication supported N What association parameters are necessary for successful association
Transport selector N Session selector N Presentation selector N AP Title N AE Qualifier N
If association parameters are necessary for association, describe the correct values e.g.
Transport selector 0001 Session selector 0001 Presentation selector 00000001 AP Title na AE Qualifier na
What is the maximum and minimum MMS PDU size
Max MMS PDU size 10000 Min MMS PDU size 10000
What is the maximum startup time after a power supply interrupt
5 seconds
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 21/29
3.2 PIXIT for Server model
Description Value / Clarification Which analogue value (MX) quality bits are supported (can be set by server)
Validity: N Good, N Invalid, N Reserved, N Questionable N Overflow N OutofRange N BadReference N Oscillatory N Failure N OldData N Inconsistent N Inaccurate Source: N Process N Substituted N Test N OperatorBlocked
Which status value (ST) quality bits are supported (can be set by server)
Validity: N Good, Y Invalid, N Reserved, N Questionable N BadReference N Oscillatory N Failure N OldData N Inconsistent N Inaccurate Source: N Process N Substituted N Test N OperatorBlocked
What is the maximum number of data values in one GetDataValues request
15
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 22/29
3.3 PIXIT for Data set model
Description Value / Clarification What is the maximum number of data elements in one data set (compare ICD setting)
49
How many persistent data sets can be created by one or more clients
20
How many non-persistent data sets can be created by one or more clients
20
3.4 PIXIT for Reporting model
Description Value / Clarification The supported trigger conditions are (compare PICS)
integrity Y data change Y quality change N data update N general interrogation Y
The supported optional fields are sequence-number Y report-time-stamp Y reason-for-inclusion Y data-set-name Y data-reference Y buffer-overflow N entryID N conf-rev Y segmentation Y
Can the server send segmented reports N Mechanism on second internal data change notification of the same analogue data value within buffer period
Send report immediately
Multi client URCB approach Each URCB is visible to all clients May the reported data set contain: - structured data objects? - data attributes? - timestamp data attributes?
Y
Y
Y, will/will not be included in a dchg report
What is the scan cycle for binary events? Is this fixed, configurable
10 ms Fixed
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 23/29
3.5 PIXIT for Generic substation events model
Description Value / Clarification What elements of a subscribed GOOSE header are checked to decide the message is valid and the allData values are accepted? If yes, describe the conditions. Note: the VLAN tag may be removed by a ethernet switch and should not be checked
N source MAC address Y destination MAC address Y Ethertype = 0x88B8 N gocbRef, NULL gocbRef is
considered an error N timeAllowedtoLive N datSet N goID N t Y stNum N sqNum Y test Y confRev Y ndsCom N numDatSetEntries;
numDataSetEntries=0 is considered an error
Can the test flag in the published GOOSE be turned on / off
N
What is the behavior when a GOOSE message with test flag set is received?
The message will be ignored
What is the behavior when the GOOSE publish configuration is incorrect
DUT keeps GoEna=F
When is a subscribed GOOSE marked as lost? (TAL = time allowed to live value from the last received GOOSE message)
message does not arrive by 2x TAL
What is the behavior when one or more subscribed GOOSE messages isnt received or syntactically incorrect (missing GOOSE)
Quality flags of corresponding DOs are set to invalid
What is the behavior when a subscribed GOOSE message is out-of-order
Out-of-order message will be ignored
What is the behavior when a subscribed GOOSE message is duplicated
The duplicate message is ignored
Does the device subscribe to GOOSE messages with/without the VLAN tag?
Y, with the VLAN tag Y, without the VLAN tag
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 24/29
Description Value / Clarification May the GOOSE data set contain: - structured data objects? - data attributes? - timestamp data attributes?
Subscribed Published N N Y Y N N
What is the slow retransmission time? Is it fixed or configurable?
5000 mseconds with TAL = 10000 Fixed
What is the fast retransmission scheme? Is it fixed or configurable?
1) 2 mseconds with TAL = 4 2) 4 mseconds with TAL = 24 3) 16 mseconds with TAL = 9968 4) 5000 mseconds with TAL = 10000 Retransmission scheme is fixed
Can the Goose publish be turned on / off by using SetGoCBValues(GoEna)
Y
TAL = Time Allowed to Live
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 25/29
3.6 PIXIT for Control model
Description Value / Clarification What control modes are supported (compare PICS)
Y status-only Y direct-with-normal-security N sbo-with-normal-security N direct-with-enhanced-security N sbo-with-enhanced-security
Is the control model fixed, configurable and/or online changeable?
FIXED
Is Time activated operate (operTm) supported
NO
Is operate-many supported NO What is the behavior of the DUT when the test attribute is set in the selectwithvalue and/or operate request
n/a
What are the conditions for the time (T) attribute in the SelectWithValue and/or Operate request
DUT ignores the time value and execute the command as usual
Is pulse configuration supported NO What is the behavior of the DUT when the check conditions are set Is this behavior fixed, configurable, online changeable?
N synchrocheck N interlock-check Fixed
What additional cause diagnosis are supported
No additional cause is sent
How to force a test-not-ok response with Operate request?
DOns: n/a SBOns: n/a DOes: n/a SBOes: n/a
Which origin categories are supported? 2 What happens if the orCat is not supported?
DOns: execute as usual SBOns: n/a DOes: n/a SBOes: n/a
Does the IED accept an selectwithvalue/operate with the same ctlVal as the current status value?
DOns: Y SBOns: n/a DOes: n/a SBOes: n/a
Does the IED accept a select/operate on the same control object from 2 different
DOns: Y SBOns: n/a
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 26/29
Description Value / Clarification clients at the same time? DOes: n/a
SBOes: n/a Can a control operation be blocked by Mod=Off or Blocked
N
Does the IED support local / remote operation?
N
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 27/29
3.7 PIXIT for Time and time synchronization model
Description Value / Clarification What quality bits are supported? N LeapSecondsKnown
N ClockFailure Y ClockNotSynchronized
Describe the behavior of the IED when the time synchronization signal/messages are lost
TimeStamp Quality set to ClockNotSynchronized
When is the time quality bit "Clock failure" set?
N/A
When is the time quality bit "Clock not synchronised set?
If no SNTP response is received within 2 seconds after request
Is the timestamp of a binary event adjusted to the configured scan cycle?
N
Does the device support time zone and daylight saving?
Y
Which attibutes of the SNTP response packet are validated?
Y Leap indicator not equal to 3 Y Mode is equal to SERVER Y OriginateTimestamp is equal to
value sent by the SNTP client as Transmit Timestamp
Y RX/TX timestamp fields are checked for reasonableness
Y SNTP version 3 and/or 4 N other (describe)
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 28/29
IEC61850 Communication Interface
SYMAP SYMAP_IEC61850_rev3 - 29/29 Stucke Elektronik GmbH Merkurring 26 22143 Hamburg Germany
http://www.stuckegmbh.de