Upload
others
View
0
Download
0
Embed Size (px)
Citation preview
raft
SURRY EXAM 50-280, 50-281 12004-301
FEBRUARY 24 - MARCH 2 & MARCH 4,2004 (WRITTEN)
Appendix D Scenario Outline Form ES-D-1
Examiners: Operators:
Initial Conditions: 75% Reactor Power Known leakage in 1A Steam Generator Thunderstorms are approaching from the West
Turnover: Shift orders are to maintain power at 100%.
- Event
NO. - 1
2
3
4
5
6
a
8
- (M)0rfll
Transmitter Bails low. Ramped to allow adequate operator response to gain control of SG level prior to trip OR steam /
(R)eactivity, (I)nstrument, (C)omponent, (Mlajjar
Appendix D Required Operator Actions
Scenario No.: I
Fom ES-D-2
Page 1 of 14
EventNo.: 1
Event Description: l ass of Component Coaling Water to NRHX requiring letdown to be secured.
Required Operator Actions
Scenario No.: 1
Appendix D
Op-Test No.: 2084-301
EventNo.: 2
Event Description: Place Excess Letdown in service.
Form ES-D-2
Page 2 of 14
Applicant% Actions or Behavior Obtains copy of OP-CH--006.
Reviews Precautions and Limitations.
Places 1-@H-HCV-1389 to the PDTT position. (Step 5.1.13)
Opens €-CW-HCV-1201 Excess Letdown HX Isolation. (Step 5.1.15)
Records charging flow. (Step 5.1.16)
Opens 1 Loop drain isolation valve l-RC-HGV-I557A, B, or 6 (Step 5.1.17)
Opens I-GH-HCV-I 137 to establish 15 gaLlons per minute flow. (Step 5.1.18)
Places 1-CH-HCV-1389 to VCT position. (Step 5.1.21)
Verifies or places 1-CN-PCV-1145 in MANUAL. (Step 5.1.27.a)
Verifies or closes 1-CH-LCV-1460A and B. (Step 5.1.27.b)
Verifies or closes 1-CH-FCV-1122. (Step 5.1.27.d)
Verifies or closes 1-CN-HCV-1200A, B, and @(Step 5.1.27.0
Fully opens I-GH-PGV-I €45. (Step 5.1.27.g)
Appendix D
@-Test No.: 2084-301
Required Operator Actions
scenario No.: I
EventNo.: 3
Event Description: Median Select Tave fails high.
Form ES-B-2
Page 3 of 14
Apgllsant's Actions or Behavior Acknow!edge.s annunciator 1 H-H7, S W DUMP VV T R P OPEN. ... . . . . . . ._ . . . __. . _. . . -. . . -. . . . . __ . . . . -. . . .-. . . . . . . -
Acknowledges annunciator cH-A4, Tave - Tref%VIATION.
Places rod control in MANUAL to stop rod motion.
Places Charging Flow Contml in MANUAL and lowers demand to stop Pressurizer level rise.
Reviews annunciators.
Reviews Tech Specs and identifies no applicable limiting actions.
Notifies I&C of failure.
Notifies OMOC of failures and unit conditions.
Discusses plant operation with Steam Dumps with trip open demand, B V s with RQ trip close criteria at 554 T7 and operation with rods and charging flow control in M A N A L .
Appendix B
Op-Test No.: 2004-301
EventNo.: 4
Event Description: l A Steam Generator Level Transmitter fails low. Ramped to allow adequate operator response to gain control of SG level prior to trip on s t e m / feed mismatch.
Required Operator Actions
scenario No.: 1
fedwater, and F W heater oscillations.
channel 3 in trip.
Appendix D Required Operator Actions Form E§-B-2
Qp-T'est NO.: 2804-301 Scenario No.: 1 Page 5 Qf 14
EventNs.: 5
Event Description: Pressurizer Pressure Controller (PC-444A / Channel 1) fails high. Rmped to allow adequate operator response to gain control of pressure.
Position WO
RO
SRO
Applicant's Actions or Behavior Diagnose high failure of either PZR Pressure Transmitter p T p - 4 4 or Master Controller.
- - 1C-?38, P Z R LO PRESS
- 1C-D8, P m LO LVL - - I C W , PRZR RELIEF TANK PRESS -
1C-A$, PRZR PRESS CONTR IllI BUTPUT
~ 1D-H4, PRZR SITY VV PWR FGLDZF VV QPEN
BC-D7, PRZt PWR RELIEF LINE HI TEMP
1G-F3 & W 0VTE;MP DELTA T TURB R W M & ROD STOP
MCB meter for pTp-444 reads maximum pressure PRZR Master Controller goes to maximum output P E R Spray valves go full open
Actual RCS pressure as indicated by MCB for FT-445 lowering rapidly
Indications: - - - - P o R v 1455c QPnS -
rakes actions IAW Am BC-A$ (Note: actions taken for any other ARP will delay actions necessary to avoid a Rx Trip OH SI).
- - -
Place Master Controller in MANUAL. and lower output. Verify closed or close 1-RC-PCV-1455C. Verify closed or close PWZR spray valves.
Directs RO to control pressure U W 1-AP-3 1 .OO. Should note that 6-WC-PCV-1455C is inoperable while control is in manual. SRO hould review TS 3.1.6. (TS 3.1.6.3 states that with ti PORV noperable but capable of being manually cycled, within 1 hour :ither restore to operable or close the block valve and maintain lower to the block valve.)
Appendix D Required Operator Actions Form ES-D-2
@-Test NO.: 2004-301 Scenario No.: 1 pa@? 6 of 14
Position a0
Applicant’s Actions QP Behavior Maintains RCS pressure JAW 1-AP-31.00
Check RCS pressure lowering
Place I-CH-PC-1444J in MANUN-. Decrease demand on PRZR Press Master Controller to raise
Close or verify closed P m R PORvs Close Block Valve to isolate a PORV that will not close. Turn QB] pressurizer heaters. Close or verify closed 1-CH-HCV-1311, Aux Spray Isolation. Check Aux Spray Line for leakage. (None should be detected.) Place spray valve controllers in MANUAL and adjust demand to zero.
acs pressure.
Zheck Turbine load stable. Provide notifications to OMOC, STA, and Shift Supervis~r.
Appendix D Required Operator Actions Fom E§-D-2
Qp-Test NO.: 2004-301 Scenario KO.: 1 h@? 9 of 14
EventNo.: 6
Event Description: IC Steam Generator tube le& with failure of Condenser Air Ejector Rad Monitor auto actions. slowly ramp leak until Condenser Air Ejector Monitor alarms.
Position BOP
BOP
BOP
BOP
SRO
SRU
Applicant's Actions or Behavior Diagnose IC Steam Generator Tube Leak as evidenced by Condenser Air Ejector alarm.
A l m s : - 16-BB, P m LO PRESS ~ 1@-D8, PWZR LU LEVEL
~ 1-RM-GS, C0NH)ENSER Aw EJECTOR 'UER'PIFAEURE
Indications: - Upscale om 1-SV-N-111 - Upscale on 1-RM-RR- 15QB Pen 4
Verifies alarm reading greater than background or radiation level has trended up by reading 1-SV-IPI-111 or 1-RM-RR-150B Pen 4.
Checks EWCS points using Group 80 Review: - RlRM204C, MS-RI-124 - W1M205C, MS-WI-125 - W1Rh1[206C9 MS-WZ-126
Monitor SG BIowdown Monitors: - I-SS-RI-112 - I-SS-w-183
Directs verification of automatic actions associated with Condenser Air Ejector a l m .
AP-16.00, Excessive WCS Leakage
Directs compensatory actions or physical positioning of TV-SV- 102 and TV-SV-103 per ARP I-WM-GE: Attachment 1.
Reposition TV-SV-102 and TV-SV-103 per ARP 1-RM-G8 4tFachrnent 1.
____~ -
Appendix D Required Operator Actions Form ES-D-2
Op-Test No.: 2004-301 Scenario No.: 1 Page 8 of 14
Position
RO
Applicant% Actions or Behavior
Checks RCS l e d a t e .
PRZW level lowering (slight) Annunciator IlDB5, CHG PP TO REGEN FIX HI-LQ m W A discemable negative change in VCT level trend has developed.
Note: At this point, these indications will be inconclusive due to small magnitude of leak.
Directs the following: Performance of Q-BSP-RC-002, Steam Generator Primary to Secondary Leakage Monitoring. Performance of 1-OPT-RC-10.0, Reactor Coolant Leakage - Computer Calculated. AP-16.00 Step 3: Verify closed or close normal and excess letdown isolations:
~ 1-CH-LCV-146OA 1 -CH-LCV- 146QB
- 1-RC-HCV-1 S57A - 1-RC-WCV-I 557B - 1 -WC-HCV- 1557c - 1-RH-HCV-1142
AP-16.00 Step 4: Verify PRZR level, PRZR pressure, and RCS subcooling stable or rising. (Ideally they will be stable or rising, but if they are not applicants may choose FQ manually trip reactor and proceed to E-Q at this point). AP-16.00 Step 3: Verify adequate makeup being supplied by blender and Leak Rate > 50 gpm. (VCT level will be going down and Leak Rate will be > 50 gpm. This is another criteria for Rx Trip). AH”-16.00 Step 7: Align Charging Pump Suction to the RWST: - Open 1-CHI-MOV-1 I15B - Open 1 -6H-MOV- 1 1 15D - Close I-CH-MOV-1115C
Close I-CW-MOV-H 11% Manual Reactor Trip. Proceed to E-0.
-_ _ _ ~
Appendix D Required Operator Actions Fom ES-D-2
Op-Test XO.: 2004-301 Scenario No.: 1 Page 9 of 14
Event No.: 7 & 8
Event Description: BC Steam Generator tube rupture coincident with Loss of Offsite Power. #1 EDG fails to auto start, requiring manual start from the Cont~~ol Room.
Pssitior AH
AB1
Applicant% Actions or Behavior Diagnose requirements to trip Reactor. (Also see the previous event, which will lead into this Event.)
A l m s : - 1H-A7, STM GEN IC €€I LVL
1C-B8, PRZR LO PIPESS - lC-D8, Pam LO LEVEL - 1D-E5, CHG PP TO REGEN HX HI-LO FLOW
Indications (Pre-trip): - - Tavgstable - Charging line flow rising -
PRZR pressure and level lowering
Lowefing feed flow to 1A SG
Rx trips on QTDT or ]Low PRZR Pressure
Rx trip and bypass breakers open Rod bottom lights ape lit Generator trip 30 seconds after Rx trip
HP & LB Heater Drain Pumps trip Safety Injection on &ow PKiX pressure
Indications (POSt-trip): - - Turbine trip by RX Trip - - -
- - - Phase 1 isolation
- AH1 rn pumps S t a t
Diagnose Loss of Offsite Power. This malfunction should he triggered by Reactor Trip.
A l m s : ~
- - -
1K-H4,4 KV Ei"vERG BUS TIE STUB BUS BKR T R P 1K-G6,4 KV RES BUS S U P BKR OPEN 1K-E7, CC PPS DBCH HDR LO PRESS 0-VSP-A3, DIESEL FzEgE PUMP AUTO START
ndications: - Breakers lSA1,15B1, 3SC31,15D1, 15E1, 15F1,15A2,
15B2, and 1.322 all open. EDG 3 auto starts and energizes the emergency bus. Emergency stub bus breakers open AI1 station service loads are de-energized
- - - - RCPstrip
Appendix B Required Operator Actions
Bp-Test NO.: 2004-301 Scenario No.: 1
Position
RO
BOP
BOP
SRB
SRO
Applicant’s Actions OF Behavior - CCPumpstrip
Verify Reactor Trip (E-0, Step 1 - Immediate Action Step) - Manually trip Reactor -
- Check neutron flux lowering
Check all rod bottom lights lit Check Reactor Trip and Bypass Breakers open
Verify Turbine Trip (E-& Step 2 - Immediate Action Step) - Manually trip Turbine - - -
Verify all Turbine Stop Valves closed Close MSR Steam Supply 1-MS-SOV-104 Verify Generator Output Breaker Open (30 see time delay)
Verify both Emergency AC Buses energized (E-Q, Step 3 - hmeciiate Action Step)
EBG #I &id not auto start. EDG must be manually started from the Control Room. SRO should direct 1-M-10.07, Loss of Unit I Power, to restore power to the AC Emergency Bus.
Verify both 4160 V Emergency Buses energized. (1-AP-10.07, Step 2 ) - H Bus will not be energized. RNO directs operators to Att. 1.
[f any EDG has failed to start, then: (I-A?-10.07, Att. E , Step 2) - Put ED6 #1 in EXERCISE
Place EDG #1 in AUTO If ED6 loads, then go to Step 6
- St&tDG#1 - -
f either Emergency Bus energizes and both of the fd8owm.g iarnpers are not open, then initiate Att. 10: (1-AP-10.07, Step 6)
- I-VS-MOD-103B - B-VS-MOD-103D
4tt. 10 centins instructions for battery room ventilation. Local .ctions to open slide dampers, Battery Room 1A door, and stabhh a fire watch.
Leturn to procedure step in effect. (1-M-10.07, Att. I , Step 8)
:heck if SI initiated. (E-0, Step 4 - bmediate Action Step)
- ~~~~
Appendix D Required Operator Actions Form ES-D-2
@-Test No.. 2004301 Scenario No.: 1 Page 11 of 14
rime Position
RQ/BOP
BOP
RO
BOP
WO
a0
BOP
BOP
d
Applicamt's Actions 01- Behavior Directs manual initiation of SI after Reactor Trip. Expect SRO brief.
Manually initiates SI and verifies 1A-F3 and 1A-W annunciators lit. (E-Q, Step 4 - Immediate Action Step)
Verify Peedwater isolation. (E-0, Step 5) -
- MFW Bumps tripped - Feed Reg Valves closed - - SG Blowdown TVs closed
Feed Pump Discharge MOVs closed (l-FW-MOV-1SOA 6% B)
SG F W bypass Wow demand at z e r ~
Verify CTMT Isolation Phase I. (E-0, Step 6) - Phase I TVs closed - 1-CH-MOV-1381 closed - l-SV-TV-102A closed - PAM isolation l-DA-TV-183A closed - PAM isolation 1-DA-TV-103B closed
Verify AFW pumps running. (E-Q, Step 7) - -
MD A@w Pumps (time delayed) "El AFW Pump (if necessary)
May discuss isolating AI;'w to IC SG with SRO at this time.
Verify SI Pumps running. (E-0, Step 8) - CHG Pumps running - LIISI Pumps running
:heck Charging Pump Auxiliaries. (50, Step 9) - CHG Pump CC Pump - CHG Pump SW Pump
Sheck Intake Canal level > 24 feet and being maintained. (E-0, ,tep 10)
:heck Main Steam Line Isolation required. @-(I, Step B I ) - Check if any of the following annunciators have been lit.
~ E-F-10, HI STEAM FLOW SI - (should he off)
B-C-5, Hi HI CLS TWAIN B - (should he off) - B-C-4, HI HI CLS TRAIN A - (should be off) -
lheck if CTMT Spray required (E-0, Step 12)
Appendix B Required Operator Actions Form ES-D-2
Bp-Test No.: 2004-301 Ssenario No.: 1 Page 12 of 14
Applicant's Actions or Behavior ( C T W Pressure should be near pre-event levels - RNO directs operators to Step 13)
Verify SI flow: (E-0, Step 13) - "SI to Cold Legs > 0 pm:
- I -SI-F?-1961 - 1 -SI-R-1962 - 1 -SI-R-1963 - I -SI-R-1943 or 19434
Check three CHG Bumps running
Stop one CHG Pump and place in AUTO Check RCS pressure > 185 psig (should be > 185 psi@
Stop one LHSI Pump and place in AUTO
Verify total AFW flow > 358 gpm (E-0, Step 14)
- - Reset SI - - - Verify SI reset -
Check AFW MOVs open (IC SG may require manual alignment) (E-0, Step 15)
Verify SI Valve Alignment IAW Att. 2 (BO, Step 14) - Verify open or open CWG Pump Suction from RWST
MOVs - 1-CH-MOV-1115B - I-CH-MOV-1115D
Verify closed or close CHG Pump Suction from VCT MOVs - 1-CH-MOV-1 I15C - l-CH-MOV-1115E
Verify closed or close CHG Line Isolation MOVs - I-CH-MOV- 12898 - I-CH-MOV-1289B
Verify closed or close Letdown orifice isolation valves - I-CH-HCV- 12008 - l-CH-HCV-120B - I -CH-HCV- 1 200C
Verify open or open HHSI to cold legs MOVs - I-SI-MOV-1867C - 1-SI-MOV-1867D
Verify open or open LHSI suction from WWST MOVs - I-SI-MOV-I 8628 - 1-SI-MOV-B 862B
Verify open or open LHSI to cold legs MOVs
-
-
-
-
-
-
Appendix D Required Operator Actions Form ES-B-2
Op-Test NO.: 2004-301 Scenario No.: 1 Page 13 of 14
Time Applicant's Actions or Behavior I-SI-MBV-I 8698 I -SI-MBV- 18443
Verify ventilation alignment and AC power alignment MaW Attachment 3 (E-0, Step 17) (E-0, An. 3 is attached) (Only one switch to be manipulated on the Ventilation Panel)
Check RCS Avg Temp stable OH trending toward 547 9. (E-0, Step 18) If e 547 'P, then stop dumping steam and reduce MW flow if SS Levels permit (SG Levels > 12% in at least one SG). If cooldown continues, then close MSTVs. If > 547 OF, then dump s t e m via Atmospherics (LOSP - condenser not available)
Check PFZR PQWVs and Spray Valves: (E-0, Step 19) - PRZR PORVs closed - PWZR Spray controls at zero demand (Spray valves
closed) At least one PORV Block Valve open. -
Check RCP Trip and Miniflow Recirc Criteria (E-0, Step 20) - HHSI flow to Cold Legs > 0 g~ppn - -
RCS Subcooling < 30 F WCS pressure < 1275 psig
If RCS Pressure < 1275 psig then close CHG Pump miniflow recirc valves (1-CM-MOV-1275A Cpr B & C)
Check SG Not Faulted: @-Q Step 21) Pressure in all SGs stable or rising Pressure in all SGs > 100 psig
- -
Check SG Tubes ruptured: [E-0, Step 22) - - - - -
Condenser air ejector radiation > normai SG Blowdown Radiation > normal SG MS Radiation > normal TD AFW Pinnap exhaust > normal l A SG level increasing in an uncontrolled manner
Directs transition to E-3, Steam Generator Tube Rupture. (E-0, Step 22)
Check RCP Trip and Miniflow Recirc Criteria (E-3, Step I ) - "SI flbw to Cold kegs > 0 gpm
Appendix D Required Operator Actions
Op-Test NO.: 2004-301 Scenario No.: 1
Form ES-B-2
Page 14 of 14
If RCS Pressure < 1245 psig then close CHG Pump miniflow recirc valves (1-CH-MOV-1275A 8r B B C)
- Level rise - - SG Blowdown monitor high
SC Main Steam Line Monitor high
Isolate IC SG (E-3, Step 3 - Critical Task) Adjust 16: SG POWV controller to 1035 p i g Verify 1C SG PORV closed Verify IC! SG Blowdown TVs closed Directs local closure of 1-MS-158 (161 supply to TD AFN Pump)
- - - -
- Close IC SG MSTV
Isolation of 1C SG prior to exsting E-3 is a critical task.
Check ruptured SG Level > 12% (E-3, Step 4) Flow to 116 SG must be maintained until level > 12%. When level > I%%, AFW flow to IC S B shall be stopped.
Zheck P%RZ PORVs and Block Valves (E-3, Step 5) Check power available to Block Valves Check PRZR PORVs closed Ensure at least one P E R PORV Block Valve open
-
-
:heck if SG not faulted. @-39 Step 6 ) Check pressure stable or rising in all SGs Check pressure > BO psig in all 3 0 s -
:heck IA B 1B (intact) SG levels (E-3, Step 7) - -
Any AR SG Level >12% Check emergency buses both energized (RNO should p 1 ~ 1
need to be. performed if bus was restored by manually starting #I EDG earlier in scenario. However, local isolation of AFW header on H Bus may be necessary if H Bus not energized. 1-Ew-141/ 156 / 171) Control AFW flow to maintain 22 to 50% in I A 63c 1B SGs
-
beset both trains of SI (E-3. Steo 8)
Appendix D Required Operator Actions Form ES-B-2
Op-Tesli NO.: 2084-301 Scenario No.: 1 Page 15 of 15
BOP
BOP
BQPIRO
SRQ
RO
BOP
Appiicant’s Actions OF Behavior
Verify Instrument Air Available (E-3, Step 10) - -
- Verify 1-IA-TV-108 open.
Check Annunciator W E 6 not lit. Check at Least one CThlT Instrument Air Compressor running.
Align Condenser Air Ejector to CT,W (E-3- Step 11) - Verify 1-SV-TV-182 open - Verify 1-SV-TV-103 closed - Open 1-SV-TV-102A
Verify all AC buses energized by offsite power. (This will not be the case. EDGs will be powering buses). @-3> Step 12)
3irect implementation of 1-AP-10.07. Loss of Unit 1 Power (if lot already implemented). (E-3, step 12)
:heck if LHSI Pumps should be stopped. (E-3, Step 13) - -
Check RCS pressure > 250 psig Stop LHSI Pumps and piace in AUTO.
:heck IC SG isolated from 1B and la SGs @-3, Step 14) - -
Check 1@ SO MSTV or NRV closed. Check 1C SG pressure > 358 psig.
nitiate RGS Cooldown (E-3. Step 15) - Determine required core exit temperature (SW TIME):
- Lowest Ruptured SG P Qpsig) GET (OF)
1001 - 1085 495 901 - 1008 485
~ 801 - 900 470 - 701 - 800 455
601 - 700 440 - 501 - 608 420
401 - 500 400 ~ 350 - 400 385
Place Steam Dump Mode Select Switch in Steam Pressure Mode. C O ~ ~ ~ O W R at maximum rate using SG PORVs. Check CETs Iess than required temperature
Maintain CETs less than required temperature
-
- - - Stop COOldow~ -
Appendix B Required Opemtor Actions Form ES-D-2
Op-Test No.: 2004-381 Scenario No.: B Page 16 of 16
'ime
ritiC&l
RO
RO
]Ea0
Applicant's actions or Behavior This step should be completed prior to depressurizing.
Check ruptured SC pressure stable or rising (E-3, Step 14)
Check RcS subcooling based on CETs > 50 F
Depressurize RCS to minimize break flow and refill PRZR (E-3 Step 18)
- Check n o m d spray available and WCPs A & C running (normal sprays will not be available and RCPs will be off) - RNO directs to Step 19
Depressurize RCS using PRZR PORV to minimize break flow and refiSl PRZR (53, Step 19 - Critical Task)
- ~
Check at least one PRZR PORV available Open one PRZR PORV until any of the foliowing conditions edst: - P U R Level > 49%
RCS Subcooling based on CETs < 30 "F PWZR Level > 22% & RCS P < 1c SG P ~
. . .- . . . . -. . . . . . - SCENARIO CQh.TPI,ETE ONCE RCS IS TSEPRESSIIRLZED. . . . -. . . -. . . . __
Appendix D Scenario Outline Fa rrn , ES-D- 1
e Facility: Surry
Examiners: Operators:
&gTAMbbi”Cb 2.. he3
Initial Conditions: d A 3 L B as+- cce&cd/p 7-3
50% Reactor Power Known leakage in 1A Steam Generator Thunderstorms are approaching from the West 1-EH-P-MP2 (EHC Pump) is Tagged Out of Service for Thermal O ~ e r l ~ a d Replacement
1 - 1.S h-3
TUtT?QVer: Shift orders are to maintain power at 50%.
Description
MW‘
f 4 S - t
p.,
actuate. Manuai actuation from the control room is
Required Operator Actions
Scenario No.: 2
Form ES-D-2
Page 1 of 16
Appendix H)
Op-Test NO.: 2004-301
EventNo.: 1
Event Description: Bearing Cooling Water Pump trips and standby pump fails to auto start.
I
f BOP
Applicant’s Actions or Behavior Acknowledges 1B-G2, BC HElR LO Pressure.
Acknowledges 1K-D2,4KV BKR AUTO TRUP.
Identifies loss of I-BC-P-1B and failure of I-BC-P-IA to automatically start on low system pressure.
Manually starts 1-BC-P-la.
Verifies running amps on 1-BC-P-IA and BC system low pressure alarm clears.
Performs focus brief on the failure and actions in progress.
Directs BOP to dispatch Service BLDG operator to 1-BC-P-TB’s breaker 1568.
Directs RO to dispatch Turbine BLDG operator to locally investigate conditions at BC pumps.
Place control switch for 1-BC-P-1B in PTL position
Direct Electrical Maintenance to investigate breaker 15C8.
Notifies Shift Manager and direct initiation of Work Order.
Required Operator Actions
Scenario No.: 2
Appendix D
Op-Test NO.: 2004-301
Event No.: 2
Event Description: Letdown Divert Valve fails open
Form ES-D-2
Page 2 of 16
Applicant’s Actions or Behavior Identifies normal make-up in progress to VCT.
~~
Identifies 1-CH-LCV-1115A diverted to PDT.
Identifies L -CH-LCV-l115A controller demand at 100% for unknown reason
May utilize A W lD-Gl, VCT HI-LO L W for guidance based on normal make-up flow ability to maintain VCT level.
Direct RO to place 1-CK-LCV-I B 15A controller in Manual rend reduce demand to align 1 -@N-LCV- 1 1 15A to VCT position or place controi switch for 1-CH-LCV-I 115A in N O M position.
Performs the directed action to align 1-CH-LCV-1 I1 514 back to VCT.
Performs a focus briefon the failure and actions in progress. - ..... - ..... . . . . . . . -. . . .-
Directs I & C: Maintenance te investigate the faiiure of 1-CI-I-1.W-11 I5A contrsller.
Notifies Shift Manager and STA of failure and actions in progress.
Required Operator Actions
Scenario No.: 2
Appendix D
Op-Test No.: 2004-301
Event No.: 3
Event Description: Selected 1' Stage Turbine Pressure Transmitter fails low
I
SRQ
Applicant's Actions or Behavior Acknowiedges annunciator 1 H-A4, Tavg > < T r d DEVIATION.
-. .-. . . .__ . ._ . . __ . -. . . . .- . . - ._ . . .- Acknow!edges annunciator I H-H?, S l M I N J 3 W T W OPEN
Identifies control rods are stepping due to Channel 3 Transmitter failure low.
Stage Turbine Pressure
Directs RO to place control rods in Manual.
Piaces control rods in Manual to stop the rod motion.
Identifies Main FRVs are reducing SG levels to the no load setpoint based on Channel 3 failure.
Reviews annunciator response procedures for remaining of alarms
Reviews Tech Specs Section 3 7 and identifies TS Table 3 7-1 items 20 b 6t 20c requiring Operator Action #13, one-hour clock to verify permissives status In addition, identifies TS Table 3 7-2 item le and TS Table 3 4-3 item 2a requiring Operator .4ctiOn #20, 72 hour dock to place channel in trip
Performs focus brief on failure and actions in progress Discuss plant impact with Stm Dump trip open signal and Main FRVs due to falure
Notifies I & C Maintenance to place channel in trip.
Directs RQ to perform I-QPT-KP-O0I, CHECK OF IT3%h4ISSIVE STATUS LIGHTS P-6, P-'3, P-8, AND P-10, to verify permissive status lights are correctly illuminated.
Pedorms 1-QPT-RP-O0I, CHECK OF PERMISSIVE. STATUS LIGHTS P- 6, P-7, P-8, AND P-10 and reports results of completed OPT to SRO.
Appendix D Required Operator Actions Form ES-D-2
Op-Test NO.: 2004301 Scenario KO,: 2 Page 4 of 16
Event No.: 3
Event Description: Selected 1' Stage Turbine Pressure Transmitter fails low
I I
Applicant's Actions or Behavior Directs BOP to swap instrumentation channels in accordance with perform
OF CN.4". I, II,IlI, AND IV PROCESS AND PROTECTION TESTING.
Performs 1 -0P-a-00 1 to swap instrumentation channels. Should note that this procedure ndi not be completed before proceeding to next event
I -0P-RP-001, ALIGNING CONTROL SYSTEM FOR PEwFORhgANCE
~
Notifies Shift Manager and ST.4 of failure and actions in progress.
Appendix D Required Operator Actions Form ES-B-2
Op-Test NQ.: 2004-301 Scenario No.: 2 Page 5 of 16
Event N o . : H b
Event Description: Selected 1B Steam Generator Steam Flow Transmitter fails high
Identifies “B” SG Steam Flow channel failed high (1-MS-LT-lXXX).
Direst BOP to place “B” Main FRV in Mamual and restore “B” SG level.
Takes manual control of “B” Main FRV and reduces feedwater flow to restore Ievel.
Reviews AM%.
Performs focus brief on failure and actions in progress.
Reviews Tech Specs Section 3.7 and identifies TS Table 3.7-1 items 17 requiring Operator Action #6; identifies TS Table 3.7-2 item le and TS Table 3.7-3 item 2a requiring Operator Action #20, 72 hour clock to place channel in trip.
Notifies I & C Maintenance to place channel in trip
May elect to swap controlling Steam Plow channel to IV for “’B” SG in accordance with 1H-%, STM GEN IB LVL ERROR
- Return Ievel to program - Select redundant channel - When level returned to normal, then place FRV in AUTO.
Notifies Shift Manager and STA of failure and actions in progress.
Required Operator Actions
Scenario No.: 2
Appendix 19
Bp-Te~t NO.: 2004-301
Event No.: 5
Event Description: Pressurizer Level Controller fails low
Form ES-D-2
Page 6 of 16
0 f d e ~ /A/$%aY&b
Applicant’s Actions or Behavior Acknowledges annuciator lC-BS, PWR LO LVL.
Identifies CHG flow reduction.
Identifies CMG flow controller output demand at 0%.
Directs RO to take manual control of CHG flow and return CHG flow to normal.
Takes CWG flow controller tu MWAk amd increases CEIG flow to normal.
Notifies IRrC Maintenanw to investigate the failure.
Perform foms brief on failure and actions in progress.
Notifies Shift Manager and STA of failure and actions in progress.
Appendix D
Op-Test No.: 2004-301
Event No.: 6
Required Operator Actions
Scenario NQ.: 2
FOITTI ES-D-2
Page 7 of 16
Event Description: Tavg Taylor Math Unit fails low
Appendix D
Op-Test No.: 2004-301
Event No.: 7
Event Description: Turbine Governor Valve fails closed. Ramp in slow enough for BOP to detect and respond.
Time
Required Operator Actions
Scenario No.: 2
FOP^ ES-B-2
Page 8 of 16
I
Appendix D Required Operator Actions F o ~ ES-D-2
Qp-Test No.: 2004-301 Scenario No.: 2 Page 9 of 16
Event No.: 8, 9, Br 10 Event Description: LBLOCA - Auto Reactor Trip, Turbine fails to trip, and both trains of Safety Injection fail to automatically actuate. Manual actuation from the control room is *&&N 0 u r p o r &L& dL .p Ot-4 Time
RO
SRO
BOP
RO/SRO
RQ/SRO (Event 9)
ROISRB
RO/SRQ ’Event 10)
AppBicsnt’s Actions or Behavior Acknowledges annunicators.
Identifies decreasing RCS Pressure
Identifies automatic Reactor Trip and initiates 1-E-0 Immediate Actions.
Directs performance of 143-0 Immediate Actions.
Acknowledges annunciators while RO performs I-E-0 Immediate Actions.
Verifies Reactor Trip (EO> Step 1 - Immediate Action Step) - Manually trip Reactor - - - Check Neutron flux lowering
Check ail Rods On Bottom Light lit Check Reactor Trip and Bypass Breakers open
Verify Turbine Trip (E-0, Step 2 - Immediate Action Step) -
- -
-
-
Identify that Turbine failed to automatically trip Manually trip the turbine by pressing both Trip Pushbuttons Identify all Turbine Stup Valves dose Close MSR Steam Supply 1-MS-SOV-I04 Verify Generator Output Breaker open (39 second time delay)
Verify both Emergency A@ Buses energized (E-0, Step 3 - Immediate Action Step)
Check if SI is actuated. (E-0, Step 4 - Immediate Action Step) Identify that ST failed to automatically actuate.
e- hlanualiy actuate both trains of SI d~~~~~~~ d e w h e 53 -
- Verify LHSI pumps running - Verify SI annunciators lit
- A-F-3 - A-F-4
Appendix 6) Required Operator Actions
Bp-Test No.: 2004301 Scenario No.: 2
Form ES-D-2
Page 10 of 16
AipBicant’s Actions or Behavior Verify FW Isolation. @-a, Step 5)
- - MFW pumps tripped - Peed Reg valves closed -
- Phase I TVs closed
Feed pump discharge MQVs closed (l-PW-MBV-lSOA & B)
SG FW bypass flow demand at zero Verify CTMT Isolation Phase T (E-0, Step 6)
- 1-CH-MQV-1381 closed - I-SV-TV-102A OS& - -
PAM Isolation vaives 1-BA-TV-103A closed PAM Isolation valves I-DA-TV-IO3A closed
Verify AFW pumps Running (EO, Step 7 ) - -
MD AFW Pumps running (time delayed) TD AFW Pump running (time delayed)
Verify SI Pumps Running (E-0, Step 8) - CHG Pumps running - LHSH Pumps running
Verify CHG Pump Auxiliaries (E-0, Step 9) CHG Pump CG Pump running CHG Pump SW Pump running
- -
Check Intake Canal. (E-07 Step 10) - Leve1.24FT - Levef being maintained by CW Pumps
“heck if Main Stearnlines should be isolated (,E-(& Step I I ) Check if any ofthe following annunciabars have been lit - E-F-10, HI S T E M FLOW SI - (should be of%) - B-@-4, HI HI CLS TRAIN A - (should be on) - B-C-5, HI M CLS T W N B - (should be on)
Check either ofthe following actuated - - Verify RWST crosstie valves open - 1-SI-TV-102A & B open - 2-SE-TV-262A & B open Check RCS pressure < 185 PSIG - (should be yes)
-
- Check MSTVs closed -
Hi Steam flow SI - (should be no) Header to line SI - (should be yes)
-
-
Appendix D Required Operator Actions
Qp-Test NO.: 2004-301 Scenario No.: 2
F o ~ ES-B-2
Page 11 of 16
Applicant’s Actions OF Behavior Check if CTMT Spray Required. (E-0, Step 12)
- - - TripallRCPs - Verify 63s pumps running - - -
CTMT pressure has exceeded 23 &a Manually initiate Hi Hi CLS
Check HSRS pumps running (Time Delayed) Check OSRS pumps running (Time Delayed) Initiate Attachment I, CLS Component Verification
Low PRZR pressure SI signal should be blocked when P M K pressure decreases < 2000 psig
- Blocks Low P U R pressure SI signal by using bIsck switches High steam flow SI signal should be blocked when T a w decreases < 543°F
- B l ~ c k s High steam flow SI signal by using the block switches CHG pumps should be mn in the following order of priority: CI B, A
Verify SI Flow. (E-0, Step 13) - HHSI to cold legs flow indicated
- 1 -SI-FI- 196 1 - 1-SI-FI-1962 - 1 -SH-FH- 1963 - 1 -SI-BP- 1943 or I943 A Check three CHG Pumps running
Stop one GHG Pump and place in AUTO Check WCS pressure
- - Reset SI -
- - Identie LHSI flow indicated.
185 psig (should be < 185 psig)
Verify Total AFW flow
Check AFW MOVs open. (E-0, Step 15)
350 gpm [450 gpm]. (E-0, Step 14)
Veri@ SI Valve Alignment IAW Att. 2 (E-Q, Seep 16) - Verify open GHG Pumps Suction from RWST MBVs
- l-CM-MQV-1115B 1 -CH-MBV- 1 I 1 5D
Verify closed CHG Pump Suction from VCT MOVs 1 -CH-MOV- I I 156 1 -CH-MOV- 1 1 15E
-
-
-
Verify closed CHG Line Isolation MQVs - 1 -@H-MOV- l289A - 1 -@H-MOV- 1289B
Appendix B Required Operator Actions Form E§-D-2
Scenario No.: 2 Page 12 of 16
Position RO/SWC
Unit 2 OPR
RO/SRQ
ROiSRQ
Appk?ant's Actions or ]Behavior Verify SI Valve alignment IAW Att. 2. (50, Step 14) CQNTINLED - Verify open HHSI to cold legs h/lBVs
- l-SI-MBV-1867C - I-Si-MQV-I867D Verify open LHST suction from RWST MOVs - - I-SI-MOV-1862A - I-SB-MQV-1862B
- Verify open LHSI to cold legs MaVs - 1-SZ-MOV-1864A - I-SI-MMBV-1864B
Verify ventilation alignment and AC power alignment IAW Attachment 3 (E-0, Step 17) @-Q Att. 3 is attached) (Qnly one switch to be manipulated on the Ventilation Panel)
Check RCS Avg Temp stable or trending towards 547'F. (E-0, Step 18) - Identify 547'F - Identifgr not dumping steam and control total feed flow. Maintain >
450 gpm [450 gpm] until NW IeveE > 12% [18%1] in at least one SG. - Identify MSTVs closed
Check PRZR PORVs and Spray Valves: (E-0, Step 19) - PRZR PORVs closed - -
P U R Spray controls at zero demand (Spray valves closed) At Ieast One PORV Block Valve open
:heck RCP Trip and Miniflow Recirc Criteria. (E-0, Step 20) HHSI flow to Cold legs indicated RCS Subcooling e 3 0 T [85"F] Stop ail RCPs Identify RCS pressure 1275psig [I475 psiel Close CHG Pump miniflow recirc valves (l-CH-MOV-l275A, W, Br C)
:heck SG Not Faulted. @-Q> Step 2 1) Pressures in all SGs stable for plant conditions Pressures in all SGs 100 pig
:heck SG Tube ruptured. (E-0, Step 22) Condenser air ejector radiation - normal SG Blowdown radiation - normal SG hlS radiation - normal TB M W Pump exhaust - normal
Appendix D Required Operator Actions
Op-Test No.: 2004-301 Scenario No.: 2
Position RO/SRO
SKO
STA
SRO
BOF!SRO
Form ES-D-2
Page 13 of 16
Applicant's Actions or Behavior Check RCS Intact Inside CTMT. @-0? Step 23) - CTMT radiation normal - CTMT pressure > normal - CTMT RS sump level > normal
Directs transition to E-l, Loss ofReactor or Secondary Coolant
Identify Red Path on CSF Status F-4 Integrity requiring transition to FR- P. 1
Directs transition to FR-P. 1, Response to Imminent Pressurized Thermal Shock
Check RCS Pressure > 185 psig [250 psig] (FR-P.l, Step 1) - - -
Directs transition to E-1, Loss of Reactor or Secondary Coolant
Check RCP Trip and Miniflow Recirc Criteria. @-I; Step 1) - - - Identify all RCPs stopped - Identify RCS pressure 1275psig 61475 psig] -
Identify RCS Pressure < 185 psig [a50 p ig ] Identifsr LHSI pump flow > 1000 gpm E T U R N $0 procedure and step in effect.
HE-ISI f l ~ ~ to Cold legs indicated RCS Subcooling < 30'F [85"F]
Identify CHG Pump miniflow recirc valves (l-CH-MQV-l295A, B, B C) closed
Check SG Not Faulted. (El, Step 2) - - Pressures in ali S a 100 psig
Pressures in all SGs stable far plant conditions
Zheck Intact SG Levels. (E-1, Step 3) - - -
NR level > 12% [I8%] Check emergency buses both energized Control feed flow to maintain NR level between 22% and 58%
:heck SG Tube mptured. (E-1, Step 4) -
.
.
Condenser air ejector radiation - normal SG Blowdown radiation - normal §G MS radiation - normal Ti3 AFW Pump exhaust - normal SG NR level not increasimg in an uncontrolled manner
Appendix D Required Operator Actions
Op-Tst No.: 2004-301 Scenario No.: 2
Form ES-D-2
Page 14 of 16
Time Position ROiSRO
RO/SRQ
RQ/SRO
WO/SRO
RO/SRO
AppIicant's Actions or Behavior If any P W R PORV opens because of high F U R pressure, the PORV must be verified closed or isolated afkr pressure decreases to less than 2435 pig. (E-1, Caution prior to Step 5)
Cheek PRZR PORVs and Block Valves. (E- 1, Step 5) - Power to PRZR PORV block valves available - PKZR PORVs closed - P U R PORV block valve at least one open
Check If SI Flow should be reduced @-I? Step 6) - RCS Subcooling based on CETCs 30°F [85"H] - (30 TO Step7
Check If Hi Hi CLS Initiated. (E-1, Step 4 ) - Identify RS Pumps running - Idcnti@ Hi Hi CLS annunciators lit
Verify Service Water Available. @-I> Step 8) - - G O T 0 1 2
Check If CTMT Depressurization Equipment can be stopped. @-I9 Step
- -
- - - Close CS Discharge valves
Check Intake Canal level being maintained by CW Pumps
1 a> CTMT pressure < 12 psia Reset both trains of CLS Stop OSRS Pump(s) and put in AUTQ Stop CS Pump(s) and put in AUTO
- 1 -CS-MBV- 10 1 A - l-@S-MOV-IOlB - 1 -CS-MOV- 101 e - I-CS-MOV-lO1D
- 1-cs-haoV-102A - I -CS-MBV- I02B
Close CHEM ADD TK OUTLT valves
. Operate ISRS Pumps with SW aligned to maintain CTMT pressure
CCS Pressure should be monitored. TfRCS Pressure decreases in an ncontrolled manner to < 250 psig [400 pig], on LHSI pump must ianually restarted to supply water to RCS. @-I> Caution prior to Step 13)
Appendix D Required Operator Actions Form ES-D-2
Qp-Test NO.: 2004-301 Scenario No.: 2 Page 15 of 16
Time ___
__
Position RBISRO
ROISRO
ROISRO
ROISRB
Applicant’s Astions or Behavior Check IfLHSI Pumps should be stopped. (E-1, Step 13) - Check RCS pressure 250 psig [400 psig] - GO TO Step 15
Check IfEBGs can be stopped. (E-1, Step 15) - - -
Veri@ AC ernergency buses energized by ofissite power. Reset both trains of SI, ifnecessary (should not be) Stop any unloaded EDGs IAW Attachment 1, Stopping Unloaded
WO direct the Sewice BLBG operator to secure EDGs ZAW Att. 1 EDGS
-
Verify Instrument Air Available (23-1, Step 16) - - - -
Initiate Evaluation of Plant Status. (E- 1: Step 17) - Verify cold leg recirculatisn capability
- Power to LHSI Pumps available - Power to the following SI valves avairable
Check annunciator BB-6 not lit (should not be) Check at least one CTMT fA compressor running (should be one) Verify both trains of CLS reset (should be reset) Manually open 1 -1A-TV- 100
- 1-SI-MQV-1863A & €3 - 1-SI-MOV-18858 $t B - l-SI-MOV-1885B & C - l-SI-MBV-I860A & B - I-SZ-MQV-I862A & B - I-SI-MOV-1115B & D
- Check auxiliary building radiation - normal - Kaman vent-vent monitors - normal - Auxiliary Building Control area monitor -normal
- RCS ~ Consult with TSC on need ta obtain any ofthe folIowing samples
- Boron - Activity
- CTMTSump - Chlorides - Boron - Pl-H - Activity
- m - Activity
- CTMT Atmosphere
Required Operator Actions Form ES-D-2
Page 16 of 16
Appendix D
Scenario Ne.: 2 Qp-Test NO.: 2004-301
- SGS - Activity - Sodium - Chlorides
- Conductivity - Boron
- PH
- Initiate evaluation of plant equipment - Electrical Distribution - Safeguards - WatedGaseous supply and storage - Radiation Monitoring - %cleat Instrumentation - CVCS - Ventillation - Past-Accident Monitoring - Instrument Air System
Appendix D Scenario Outline Form ES-D-’I
f Facility: Surry
initial Conditions: Reactor Power is 75%
Known ieakage in 1A Steam Generator Thunderstorms are approaching from the West
a m f P
Turnover: Shift orders are to raise power immediately following turnover.
Description
I I I I I
(Njorrnal, (W)eactivity, (I)nstrurnent, (C)ornponent,
Appendix D Required Operator Actions
Qp-Tesb No.: 2004-301
Event No.: 1
S~enario No.: 3
~
Time
Form ES-D-2
Page I of21
Event De$CPiptiQn: Raise power. (Rods initially should be positioned to prompt dilution, as opposed
Conduct brief for raising power in accordance with 1-QP-TM-005. Unit Position
TEAM
TEAM
TEAM
SROIBOP
SROXO
RO
_ _ Ramping Operations
Review I-OP-TM-OQS: Section 5.3, Preparations for Turbine Ramp Up. - Identifies that last shift completed Section 5.3
Review 1-OP-TM-005, Section 5.4, Power Increase Between 50% and 100% Reactor Power. - Identifies that last shift completed Section 5.4 up to step 5.4.12 - Continue the power escalation to 90 to 91 percent power.
Commence the power increase at the ramp rat - Recall the Shift Manager directed setting the Load Rate
-
iced by Shift Manager
Thumbwheel. - w ISS- md/Av Using the Load Rate % per %fin thumbwheel, rotate until setting of “8”
Initiate power increase by depressing the GO pushbutton is displayed.
-
Initiate dilution and use control rods as required to maintain A B in band. - Observe the expected response on
- FR- 1 - 1 13, BA-PRO WTR Fhw - ‘d86-114A, PWI WTR SUP BATCH Integrator -
Identi@ that b 0 is high in the band, SO dilution would be preferred prior to outward rod motion.
[nitiate dilution
Appendix D
Bg-Test No.: 2004-301
Required Operator Actions
Scenario No.: 3
Event No.: 2
Event Description: FT-CH-1114, Primary Water Flow XMTR fails low
AppBicant’s Actions Behavior Identifies normal dilution to VCT stops and investigates why no PG flow indicated.
Acknowledges annunciator 1D-A4,
Directs BOP to stop the ramp to stabilize plant conditions based on the fai lure.
Stop the turbine ramp by depressing the HOLD pushbutton.
Reviews annunciator alarm response 1D-A4.
Reset the blendes controls back to AUTO.
Performs a focus brief the failure and actions in progress
Directs I & C Maintenance to investigate the failure.
Notifies Shifi Manager and STA of failure and actions in progress.
Appendix D Required Operator Actions
Scenario KO.: 3
F O H ~ ES-D-2
Page 3 of21
Event No.: 3
Event Description: I-CN-P-l A, Condensate Pump Performance Degradation ramped in to require timely operator response. Failure of standby pump auto stant. Manual start required
J
Required Operator Actions
Scenario No.: 3
Form ES-D-2
Page 4 of21
Appendix D
Op-Test No.: 2004-301
Event No.: 4
Event Description: Selected 1.4 Steam Generator MFW Flow Transmitter fails low
- Return level to program - Select redundant channel
hifi Manager and STA of failure and actions in progress
Appendix D
Bp-Test No.: 2604301
Required Operator Actions
Scenario No.: 3
Event No.: 5
Event Description: 1A SG PORV Controller fails high
Form E§-D-2
Page 5 of 21
Appendix D Required Operator Actions
OB-Test No.: 2004-301 Scenario No.: 3
Event No.: 6
Event Description: IsaIable letdown line leak in containment
Form ES-D-2
Page 6 OF 21
Applicant's Actions QP Behavior Acknowledges annunciator 1B-A3, CTMT SURP HI LEVEL
~
Identifies increasing CYhtT Sump level with CTMT Sump pump running in auto.
Acknowtedges annunciator 1D-A4, PRI WTR TO BLEND DEVIATION FLOW
Implements AP-16.Q0, EXCESSIVE RCS LEAKAGE. ~~~
Identifies LTDW flow at zero
If SI Accumulators are isolated I-@- 16 0 1 , SHUTDOWN LOCA should be used €or guidance RCS average temperature has a direct impact on pressurizer level (APB6 00, Notes prior to Step 1)
Increase CWG flow using I-CH-FCV-1122 in manual to maintain P U R level at program setpoint, as necessary (AP-16 00, Step 1) - Identifies PWR level at setpoint
Check RGS leak rate (AI?-16 00, Step 2) - PRZR !eve$ decreasing (should not be) - Annunciator D-3-5 lit (should not be) - Go TO Step 12
Check a@% leak rate < 10 gpm (AP-16 80, Step 12) -
- - Evaluate EPP applicability
Check Unit Conditions stable (-4P-16 00, Step 13) - P U R level (should be) - PRZR pressure (should be) - Taw (should be)
Check Letdown Ieak indicated (AP-16 00. Step 14) -
Initiate unit shutdown IAW W P Control CHG flow and seal injection to maintain P U R level
Identifies annunciator lB-M, CTMT Sump Hi Lvl lit
Appendix D Required Operator Actions Form ES-D-2
Bp-Test No.: 2004-301 Scenario No.: 3 Page 7 of 21
- 1 -CM-LCV- 1 4 6 0 ~ - I-RC-HCV-l557A, 14, & c - 1 -M-HCV- 1 142
Perform focus briefon failure and actions in progress. Chec.k RCS leak rate with letdown secured reduced. (AP-16.00, Step 16) - Identifies letdown leak st0ppe.d following securing letdown isolations
Place intact Letdown System in service IAW Shift Supervisor direction.
ce Excess letdown IAW 1-OP-CH-886 eviews precautions and limitations erify all of the following Loop Drain header isolation valves are
I-RC-HCV-1557A7 B, SZ C (should be) H-HPCV- 120 1, Excess LDTN HX ISOL valve is
dosed Iqhould be) - Verify 1- H-HK-1137, Excess LDTN Flow setpoint is zero
- Verify 1-Cd\FCV-i389, Excess LDTN Divert is in the VCT
- Verify open 1 -C@-MO\r- 13 8 1 ~ RPCP Seal Return (should be) - Verify running at'lqast one cc ~ u m p (should be) - Verify FI-CC-109; b T N HX Outlet Flow is indicating =: 140
- Notes the reset switch lbcated on the RFW flats must be held in
- Verify TI-CC-108, LDTNNX Outlet temp is indicating ambient.
- Veri5 1-CH-FZ-I 138, Excess CQT" FIX Outlet pressure is indicating Z= 50 pisg (should be) '~,\
- Verify 1-CH-TI-I 139, Excess L D h HX Outlet temp is indicating ambient. (should be) "\
- Notes the first 50 gallons of Excess L D W flow should be directed to the PDTT so that the Excess kDTN flow is not
(should be !h
(should be) \.,
gpm (should be) '\,\
the open position until I-~C-HCV-IOS opens h11y.
(should be) '\
'\
returned to the RCS. \ - Places 1-CH-HCV-I389 Excess LDTN Divertualve to the PDTT
position to flush the Excess LBTN pwi
Appendix D Required Operator Actions Form BS-D-2
Scenario No.: 3 Page I of 21 Qp-Test No.: 2004-301
AppBicmt’s Actions or Behavior Place Excess letdown MW I-OP-CH-OD6 (Continued)
- Verify I-CH-Pi-1138, Excess LDTN MX Outlet pressure indicates = 10 psig (should be) Open 1-CH-HCV-1201, Excess LDTN HX HSQI Veri@ 1-CH-FI-1 122A, GHG Line flow is stable and record the
’\flow (should be zero) iews caution about potential leak points downstream of the
caution about only one loop drain valve may be open 00T, to prevent the possibility of bypassing SI flow to
ct loops in a DSA, due tQ h o p cross-connect through
Drain header isolation valve 1 -RC-HCV-I 557A
rate can be calculated by using 1 -D@- level changes is = 1 S gallons
- Notes Attachment - Slowly open 1-CH
- Verify TI-GC-108, L tlet temp indicates I50’F - Veri@ I-CH-TI-I 139, Excess
- When the PDTT level has increa
ed to lower P U R level if required , Excess LBTN Flow using 1-CHI-
HC-1137 until zz 15 s established to the PDTT
E X Outlet temp indicates c: 195OF
10% as indicated on
\
GO TO 31 (AP-16.00, Step 18)
Check RCS leak rate. (Ap-16.00, Step 3 1) -
- Stabilize unit conditions Perform RCS leak sate
Unidentified leakage less than 1 gpm (should be)
Evaluate source of leakage unit operation may contain if none of the following exists. (M-16.00, Step 3 2 ) - A non-isolable fault in an RCS component body, pipe well, vessel wall,
or pipe weld
END OF AI’-16.00
Form ES-D-2 Appendix D Required Operator Actions
Qp-Te~t NO.: 2004-301 Scenario No.: 3 Page 9 of 21
be brought to HSD within 6 hours.
Appendix D Required Operator Actions Form BS-D-2
Bp-Test No.: 2004-301 Event No.: 7
Everf' ~escription: Loss of Semi-vital Bus. Bus will not be recoverable
Scenario No.: 3 Page 10 of 21
~
Applicant's Actions or Behavior Acknowledges numerous annunciators
Identifies loss of Semi-Vital Bus by observing zero voltage on indicator.
Reviews annunciators.
9 - Identifies condenser vacuum decreasing - Directs placing condenser hoggers in service
- Identified GS System in service
Condenser - 1-VP-4 - 1-VP-4
-- __I-.
Appendix D Required Operator Actions Form ES-D-2
io1 S@C!DaB.iQ NQ.: 3 Page 11 of21 Applicant’s Actions or Behavior
- 1-VP-19 - 1-VP-20
- 1-as-19 - 1-AS-20
- I-VP-I - 1-w-2
- Open Nogger steam supply valves
- Open Hogger suction valves
- Make entry in Narrative Logs that Hoggers are in service - Notify IIP Count Room that Hoggers are in service
Power tu the Steam Header Pressure MitnuallAuto station has been lost, ‘ h the associated controller in Auto-Hold with fixed output demand. The
minutes. The PORVS will continue to control in setpoint set on the MCR ManuaUAuto station
:ontrolier to shift to Relay rack at last setpoint which faiied low.
nually close 1-MS-86.
Or
9. WHEN fault corrected then
ause.
Appendix D Required Qperator Actions Form E§-D-2
Bp-Test NO.: 2004-301 Scenario Yo.: 3 Page 12 Of21
Applicant’s Adorns or Behavior Perform focus brief on failure and actions in progress.
Breaker 15 for Unit I and Breaker I S on Unit 2 Semi-vital Bus should be opened before performing the following step. (AP-I 0.05, Note prior to Step 9)
Directs the Electrical Department to swap the Gai-tronics power supply to unit 2 semi-vital bus (Junction Box in Unit 1 ESGR). (AP=10.05, Step 9)
~ alternate steam release will be required to keep the Main Stean es from lifting. (AP10.05, Caution prior to Step 10)
- I-CV-P-lA& - 1 -BA-P-4A & B, - 1 -DG-P- 1 A & B, Pri ain zXFER Pumps
Locally Transfer NRC Supply as necessary.
- Direct Service [AP-10.05, Step 12)
necessary (should be no)
Secure the following as necessary - BR-P-SA & B, Stripper Circ Pumps (S~SU~C! b
- Check LW and BR Panels for failed indications and c - BR-P-4A & B, PRT DRW TK PP
Appendix D Required Operator Actions Form E§-D-2
Scenario No.: 3 Page 13 of 21 Op-Test NO.: 2004-301
AppBicant’s Actions or Behavior Monitor the following components which have failed indications. (Ae- 10.05, Step 14) - RCPS - Instrument and Service Air - r n W P u m p s
autoiatically shifted to unit 2. (m-1 - SROBO Direct Service BLDG op check power supply
alignment
Appendix D Required Operator Actions Form E§-D-2
Op-Test No.: 2004-301 Scenario No.: 3 Page 14 of21
Event No.: 8, 9, 10, & 11
Event Description: Main Steam Line Break in Containment in 1A Steam Generator. Auto and Manual Reactor Trips fail. Failure of one Hi CLS Train fails to activate. Failure of B -CC-TV- 1 OSA (CCW return from RCP 1 A) to close an Phase ID Isolation
Time Position RO
RQ
TEAM
KQ
SRO
Applicant’s Actions or Behavior Acknowledges annunicators.
Identifies decreasing RCS Pressure and Temperature with control rods stepping out .
Identifies abnormal indications on “ K 9 SG and inside CTMT
Identifies failure automatic Reactor Trip and initiates 1 - E 4 Immediate Actions.
Directs performance of 1-E-0 Immediate Actions.
Acknowledges annunciators while RO performs Immediate Actions.
Verifies Reactor Trip @-0, Step 1 -Immediate Action Step) - - - Informs the TEAM
Attempts to manually trip Reactor Identifies failure of both Reactor Trip Pushbuttons
Directs performance of I -FK-S. 1 Immediate Actions.
Verify Reactor Trip. (FR-S.-l, Step 1) - Manually insert control rods - Afler Turbine tripped return the control rods to automatic
Verify Turbine Trip (PR-S.l, Step 2) - - Manually trip the turbine
Verify AE;W Pumps Running. (FR-S. 1, Step 3) - Identifies MD AFW Pumps running (should be) - Identifies TD AFW Pump running (should be)
Initiate Emergency Boration ofRCS. (FR-S. 1 , Step 4) - Verify CHG flow > 75 gpm (should not be) - Identifies SI in service, so CHG Pump suction align to RWST - Verify P U R pressure 2335 psig (should be)
Verify ail turbine stop valves closed (should not be)
Appendix D Required Operator Actions FOITII ES-El-2
OpTest No.: 2004-301 Scenario No.: 3 Page 15 Of 21
Position T E N
TEAM
T E N
SROiRO
SROWOP
Applicant’s Actions or Behavior If an SI signal exists or occurs, Attachment I should be performed while continuing with this procedure. (FR-S.1, Caution prior to Step 5)
Identifies SI occurred due to Hi CLS
Hdentifies AMSAC initiated a Reactor Trip by opening MG set breakers.
Directs performance of Attachment 1, Verifying Steps 1 through 13 of I-E- 0. - - - - - - - - - - -
-
Verify Reactor Trip - dispatch an operator to perform local trip Verify Turbine Trip - isolate reheaters by closing 1-MS-SQV-104 Verify both AC Emergency Buses energized (should be) Identifies SI initiated - manually initiate SI Verify FW Isolation (should be) Verify CTMT Isolation Phase 1 (should be) Veri@ M W Pumps mnning (should be) Verify SI Pumps running (should be) Check CHG Pump Auxiliaries running (should be) Check Intake Canal > 24 FT and level being maintained by CW Pumps Check ifMain Steamlines should be isolated (should be) Cheek if CS Required > 23 psia
- Manually initiate Hi Hi CLS - Trip aH1RCPs - Initiate Attachment 2, CLS Component Verification
- Manually close 1-RM-TV-lOOC (HI CLS Train failure) - Manually close 1-Kh.I-TV-IOOA (Hi CLS Train fdure) - Manually close 1-CC-TV-IOSA (Component failure)
a
- -
Blocks Low PRZR pressure and High Steam Flow SI signals Verify SI flow (should be)
- Reset both trains of SI - Stops “A” CHG Pump and put in AUTO - Identifies RCS pressure - Stops one LHSl Pump and put in AUTO
I85 psig
:heck if the following trips have occurred (FR-S. 1, Step 5) Reactor Trip (depends on ASMSAC)
- Direct Service BLDG operator to open Unit 1 Reactor Trip Breakers
Turbine Trip (should be)
Uternate water sources for AFW Pumps will be necessary if ECST leveh fecreases 20%. (FR-S. 1, Caution prior to Step 6 )
Identifies ECST level 9 20%
Appendix D Required Operator Actions Form ES-I3-2
Position SWQ/BgPP
Applicant’s Actions or Behavior Check SG Levels. (FIX-S. 1, Step 6) - - -
Verify all dilution paths isolated. (FR-S. 1 , Step 7) - - - -
Check NR level in at least one SG Verify total feed flow > 708 gpm Control feed flow to maintain NR level between 22% and 50%
12% (should not be)
Put PG PUMP control switches to OFF Close PG to Blender Flow Control Valve, l-CH-FCV-1114A Veri@ PRT PG outside TV, I-RC-TV-1519A dosed (should be) Initiate Attachment 3, PG Isolation
- Directs Auxiliary BLDG operator to complete Att. 3
Check for Reactivity Insertion from uncontrolied RCS Cooldown @It-
- RCS temperatures decreasing in an uncontrolled manner (should be) - “A” SG pressure decreasing in an uncontrolled manner (should be) - Identifies “A” SG faulted inside CTMT
Check MSTVs closed. (FR-S 1, Step 9) -
s 1, Step 8)
Identifies MSTVs closed on Hi Hi CLS
- Check pressures in all SGs - Identifies “A” SG pressure decreasing in an uncontrolled manner
At least one SG must be maintained available for RCS cooldown Hf all SGs are faulted, at least 60 gpm El00 gpm] feed flow should be maintained to each SG. Ifthe TD AFW Pump must be maintained from at least one SG (EX-S. I, Cautions prior to Step B I)
Isolate FauIted SG(s). (FR-S. 1, Step 11) - Isolate W W line
- Close “A” SG PW isolation MOV, l-FW-MOV-154A - Locaily close feed REG bypass valve manual isolation valve, 1-
- Isolate ‘‘A” SG AFW MOVs - Locally close steam supply valve to TB AI;W Pump, 1-MS-87 - Close or verify closed SG PORV (should be) - Close or verify closed SG b1owdown TVs (should be)
FW-26
:heck CETCs 1200°F (FR=S.l, Step 12) (sho~ld be)
Appendix D Required Operator Actions
Op-Test No.: 2004-301 Scenario No.: 4
Time s_
Form ES-B-2
Page 13 of 21
Applicant’s Actions or Behavior If adverse CTMT conditions have been exceeded, the Gamma-Metrics Excore Neutron Monitor system (Source and Wide Ranges) should be used t~ monitor neutron flux for the duration ofthe event. (FR-S. 1, Note prior to Step 13)
Verify Reactor Subcritical. (FR-S.1, Step 13) -
- Check the following
Check power range channels < 5% [Gamma-Metries Wide Range Power] 5% (should be)
- Intermediate range channels negative startup rate [Gamma-
- or - Shutdown margin IAW 1-OF-RX-002, SHUTDOWN MARGIN
Metrics Wide Range Power decreasing]
(CALCULATED AT ZERO PQWR) > 1.7’3%
Boration s h ~ u k i be continued to obtain adequate shutdown margin during subsequent actions. (FR-S. 1, Caution prior Step141
Return to procedure and step in effect.
Transitions to I-E-0, Step 1
Perform transient brief on failures and actions in progress.
Verifies Reactor Trip (E-0, Step 1 - Immediate Action Step) - - - - Check Neutron flux lowering
Identifies Reactor was tripped by AMSAC Check all Rods On Bottom Light lit Check Reactor Trip and Bypass Breakers open Iocally
Verify Turbine Trip (€93, Step 2 - Immediate Action Step) - - - -
Manually tripped the turbine by pressing both Trip Pushbuttons Identify all Turbine Stop Valves close Close MSR Steam Supply I-MS-SOV-IO4 Verifi Generator Output Breaker open (30 second time delay)
Verify both Emergency AC Buses energized (E-0, Step 3 - Immediate kction Step)
Appendix D Required Operator Actions Fom ES-D-2 Qp-Test No.: 2004-301 Scenario No.: 3 Page I8 of21
30P/SRO
WO/SRO
- veri@ ~ H S I pumps running - Veri@ SI annunciators lit
- A-F-3 - A-F-4
Verify FW Isolation. @-Ox Step 5) - Feed pump discharge MQVs closed (1-FW-MOV-150A & B) - MFW pumps tripped - Feed Reg valves closed - SG FW bypass flow demand at zero
Veri& CTMT Isolation Phase I. (E-0, Step 0) - Phase I TVs closed - 1-CH-MBV-1381 closed - 1-SV-TV-1028 C ~ S S ~ - -
PAM Isolation valves l-DA-TV-lO3A closed PAM Isolation valves 1-DA-TV-103A closed
- CHG Pumps running - LHSI Pumps running
- Level being maintained by CW Pumps
Appendix D Required Qperator Actions
Bp-Test NO.: 2004-361 Scenario No.: 3
Form ES-D-2
Page 19 of 21
Applicant's Actions or Behavior Check $Main Steamlines should be isolated. (€33, Step 11)
- Check if any ofthe following annunciators have been lit. - - -
E-F- 10, HT S T E M FLOW SI - (should be OB^) B-@-4, HI HI CLS TRAIN A - (should be on) B-C-5, HI HI CLS T W B - (should be on)
- Check MSTVs closed - Check either ofthe following actuated
- - Verify KWST crosstie valves open
- 2-SI-TV-202A & B open
Hi S t e m flow SI - (should be no) Header to line SI - (should be yes)
- - I-SI-TV-102A $r B open
Check RCS pressure < 185 PSIG - (should be no)
- - - Trip all RCPs - Veri@ CS pumps running - - -
=heck if CTMT Spray Required (E-0, Step 12) CTMT pressure has exceeded 23 psia Manually initiate Hi Hi CLS
Check ISRS pumps running (Time Belayed) Check QSRS pumps running (Time BeIayed) Initiate Attachment 1, CLS Component Verification
,ow PRZR pressure SI signal should be blocked when P U R pressure lecreases < 2800 psig
BEocks LSW PR%R pressure SI signal by using block switches ligh steam flow SI signal should be blocked when Tave decreases < i43'F
Blocks High steam Bow SI signal by using the block switches :HG pumps should be run in the following order of priority. C, B, A
Jerify SI Flow. (E-0, Step 13) - HHSI to cold legs flow indicated
- 1 -SI-PI- 196 1 - 1 -SI-PI- 1962 - 1-SI-FI-1963 - 1-SI-FI-1943 or 19438
- Check thee CHG Pumps running - Reset SI - Stop one 6HS Pump and place in AUTO - Check RCS pressure 185 psig (should not be)
rerify Total AFW flow > 350 gpm [450 gpm]. @-Q Step 14)
Appendix E) Required Operator Actions Form ES-D-2
Op-Test No.: 2004-301 Scemario Ne.: 3 Page 20 of 21 ~
Time Position BQP/SRC
Applicant's Actions or B e h a ~ i ~ r Check AFW MOVs open. (E-0, Step 15)
Verify SI Valve Alignment IAW Att. 2. (E-0, Step 16) - Verify open CHG Pumps Suction from RWST MOVs
- -
1 -CH-MOV- 1 1 15B 1 -CH-MBV- 1 1 1 5D
- Verify closed CHG Pump Suction from VCT MOVs - I-CH-MOV- 1 1 15C - 1 -CH-MOV-l115E Verify closed CHG Line Isolation h?lBVs - l-CH-MOV-1289A - 1 -CH-MQV- 1289B
-
- Verify open NHSI to cold legs MOVs - l-§I-MOV- 1867C - l-SI-LWQV-I86919 Verify open LHSI suction from RWST MOVs - 1-SI-MOV-18628 - 1-SI-MOV-1862B
-
- Verify open LHSI to cold legs MQVs - I-SI-MQV-1864A - I-SI-MBV- 18643
Verify ventilation alignment and AC power alignment IAW Attachment 3 )3-0, Step 17) (€54, Att. 3 is attached) :Only one switch to be manipulated on the Ventilation Panel)
?heck RCS Avg Temp stable or trending towards 547°F. (E-0, Step IS} - Identify 547°F . Identi6 not dumping steam and control total feed flow. Maintain >
350 gpm [450 gpm] until WR level > 12% [IS%] in at least one SC. . Identify MSTVs closed
:heck PRZR PQRVs and Spray Valves: (E-0, Step 19) P U R PQRVs closed PRZR Spray controls at zero demand (Spray valves closed) Ai least one PORV Block Valve open
:heck RCP Trip and Miniflow Recirc Criteria. (E-0, Step 20) HHSI flow to Cdd legs indicated RCS Subcooling > 30CF [ W F ]
Appendix D Required Operator Actions PQrIII ES-D-2
Scenario No.: 3 Page 21 of21
- Pressures in all SGs > 108
Appendix D Scenario Outline Form ES-D-1
Examiners: Operators:
Initial Conditions: 700% Reactor Power Preparing to conduct partial rod movement testing.
Turnover: Off normal conditions for Unit 1: 1-KC-HCV-1557A (Excess Letdown) is isolated due to Ieakby, 1-EH-P-MP2 (EH6 Pump) is tagged out for thermal overload replacement. Unit 2 is at 100% power with 2-FW-P-2 (TDAFW Pump) tagged out for governor replacement.
I I
9 M 1 (ALL) Main Steam bine Break at header (50, E-2)
t I I 12 M (ALL) RCS bleed and feed
i
(M)ormal, (R)eactivity, (I)nstrument, (C)omponent, (M)ajor
Appendix D Required Operator Actions Form ES-D-2
Op-Test NO.: 2004-301 Scenario No.: Spare Page 1 of22
Event No.: I
Event Description: Conduct Rod Movement Testing (1-OPT-RX-005)
PARTIAL MOVEMENT
SRORO
(OPT-RX-005, Section 6 1)
Bank Overlap Verification and Documentation (OPT-KX-005, Section 5 2 ) - Record the step counter DEMAND POSTN for control banks A, R, and
c - Direct an uperator to record and report the bank overlap thumbwheel
settings - Direct an operator to record and report the bank overlap counter (BOC)
number and RO records the step counter BEMAhD POSTN for control bank D Determine the diEerence between BOG and control bank B Identifies the difference is 384
- -
Control Bank D COPT-RX-005, Section 6 3) - Turn the ROD CQNT -MODE §EL switch to CBD
Table 1 , Control Bank I3 Insert Control Bank D 12 steps Complete the Inserted line in Attachment I, Table 1 Withdraw Control Bank B 12 steps
compare with the Reference
- Record the baseline rod position on the Withdrawn line in Attachment 1,
- - - - Calculate in Attachment 1, Table I the Control Bank D Insertion and
I I I
Appendix D Required Operator Actions
Qp-Test No.: 2004-301 Scenario No.: Spare
Porn1 ES-D-2
Page 2 of22
Position SRO/KQ
SRO/RO
Apphmt ' s A c t h s or Behavior Control Bank C (OPT-RX-005, Section 6.4) - Turn the ROD CON" MODE SBL switch to CBC
Table 2, Control Bank C Insert Control Bank C 12 steps Complete the Inserted line in Attachment I , Table 2 Verify 1G-B5, COMPU PRINTOUT ROD CONTR SYS is lit Verify 16437, ROD BANK C LO L M T is lit.
the same after the next Step, they must be made the same by stepping out only to prevent a Rod Croup Sequence Enor This will leave rods at 230 steps and prevent rod group misalignment.
Demand Counters
Attachment 2 for guidance
compare with the Reference.
- Record the baseline rod position on the Withdrawn line in Attachment 1,
- - - -
- Notes that in the event the Group 1 and Group 2 Step Counters are not
- Withdraw Control Bank C to 235 steps as indicated by the Group Step
- Pulse the Group Group Step Demand Counters down to 230 steps using
- Caiculate in Attachment 1 , Table 2 the Control Bank 6 Insertion and
- Veri@ alarms 1G-B5 and 1G-B7 are not lit
Control Bank €3 (OPT-RX-005, Section 6.5) - Turn the ROB CONT MODE SEL switch to CBB.
Table 3, Control Bank B Insert Control Bank B 12 steps Complete the Inserted line in Attachment 1, Table 3 Verify 16-B5, COMPU PRINTOUT ROD CONTR SYS is lit Verify 16436, ROD BANK B LO L M T is lit.
the same after the next Step, they must be made the same by stepping out only to prevent a Rod Croup Sequence Error This will leave rods at 230 steps and prevent rod group misalignment.
Demand Counters
Attachment 2 for guidance.
compare with the Reference
- Record the baseline rod position on the Withdrawn line in Attachment 1,
-
- - -
- Notes that in the event the Group 1 and Group 2 Step Counters ape not
- Withdraw Control Bank B to 235 steps as indicated by the Group Step
- Pulse the Group Group Step Demand Counters down to 230 steps using
- Calculate in Attachment 1, Table 3 the Control Bank B Insertion and
- veri^ alarms BGB5 and 1 G-B6 are not lit.
Appendix D Required Operator Actions Form ES-D-2
Qp-Test NO.: 2004-301 Scenario No.: Spare Pa@! 3 Qf 22
Time Position SIPOBO
1 - Turn the ROD COXT MODE SEL switch to CBA.
Table 4, Control Bank A. Insert Control Bank A 12 steps. Complete the Inserted line in &4ttachment 1 , Table 4 Verify lG-B5, COMPU PRHNTOUT ROD CONTR SYS is lit. Verify 16-B5, ROD BANK A LO LLMT is lit.
the same after the next Step, they must be made the same by stepping out only to prevent a Rod Croup Sequence Error. This will leave rods at 230 steps and prevent rod group misalignment.
Demand Counters.
Attachment 2 for guidance.
compare with the Reference.
- Record the baseline rod position on the Withdrawn line in Attachment 1,
- - -
- - Notes that in the event the Group I and Group 2 Step Counters are mot
- Withdraw Control Bank A to 235 steps as indicated by the Group Step
- Pulse the Group Group Step Demand Counters down to 230 steps using
- Calc.ulate in Attachment 1, Table 4 the Control Rank A Insertion and
- Verify alarms 1'3435 and 1GB5 are not lit.
Shutdown Bank B (OPT-RX-005, Section 6.4) - Turn the ROD CONT MODE SEL switch to SBB.
Table 5, Shutdown Bank B. Insert Shutdown Bank B 12 steps. Complete the Inserted line in Attachment, 1, Table 5 Verify 16435, C O W U FNNTOUT ROD CONTR SYS is lit.
the same after the next Step, they must be made the same by stepping out only to prevent a Rod Croup Sequence Error. This will leave rods at 230 steps and prevent rod group misalignment.
- Withdraw Shutdown Bank B to 235 steps as indicated by the Group Step Demand Counters.
- Pulse the Group Goup Step Demand Counters down to 230 steps using Attachment 2 for guidance.
- Calculate in Attachment 1, Table 5 the Shutdown Bank B Insertion and compare with the Reference.
- Verify alarm 1G85 is net lit.
- Record the baseline rod position on the Withdrawn line in Attachment 1,
- - - - Notes that in the event the Group 1 and Group 2 Step Counters are not
1 I I
Appendix D Required Operator As.tions Form ES-D-2
Op-Test NO.: 2004-301 Scenario No.: Spare Page 4 of22
SRORO
SRORO
Applicant’s Actions or Behavior Shutdown Bank A (OPT-RX-005, Section 6 8) - Turn the ROB CONT MODE §EL switch to SBA
Table 6, Shutdown Bank A Insert Shutdown Bank A 12 sreps Complete the Inserted line in Attachment 1, Table 6 Veri@ BG-B5, COMPU PRINTOUT ROD CONTR SYS is lit
the same after the next Step, they must be made the same by stepping out only to pievent a Rod Croup Sequence Error This will leave rods at 230 steps and prevent rod group misalignment
- Withdraw Shutdown Bank A to 235 steps as indicated by the Group Step Demand Counters
- Pulse the Group Goup Step Demand Counters down io 230 steps using Attachment 2 for guidance
- Calculate in Attachment 1, Table 6 the Shutdown Bank A Insertion and compare with the Reference
- Record the baseline rod position on the Withdrawn line in Attachment 1,
-
- - - Notes that in the event the Group 1 and Group 2 Step Counters are not
Verify alarm B G-B5 is not lit
Rods in Automatic, and Bank Overlap Verification and Documentation (OPT-RX-005, Section 6 9) - M e r verifying that Tavg is within 5 l°F of Tref, then put ROD CONT
MODE SEL switch in AUTO - Record the step counter DEMAbD POSTK for control banks A, B. and
c - Direct an operator to record and report the bank overlap thumbwheel
settings - Direct an operator to record and report the bank overlap counter (BOC)
number and R 8 records the step counter DEMAND PBSTN for control bank D Determine the diEerence between BO@ and control bank B Identifies the difference is 384
- -
Follow-On. (OPT-RX-085, Section 7.0) - Evaluate the test results by reviewing the Acceptance Criteria.
- Identifies the rods are inserted 12 steps, the GPI and GP2 step
- Identifies when the rods are inserted 12 steps, the WPI Insertion is
- Identifies the difference between Bank Overlap Counter and
- Identifies the thumbwheel settings are corrected based on criteria.
counter Insertion is 12.
12 6.
Control Bank D is 384.
I I I
Appendix D
Op-Test NO.: 2004-301
Event No.: 2
Event Description: P E R pressure transmitter fails high (1-RC-PT-1445).
Time Position RQ
RO
R 8
SRO
SRO
FOMI ES-D-2
Page 5 of 22
Closes P U R PORV that open due to instrumemtation failure.
Verifies PRZR pressure recovering following the opening of P U R PORV
Performs a focus brief on the failure and actions in progress.
Reviews annunciator response procedures.
Evaluates Tech Specs sections 3.1 .A.6, 3 . I .G, and 3.12.F. Declare P E R PORV, 1-RC-PCV-1456 inoperable and close PRZW PORV block valve, 1- RC-MQV-1535 within o g - h z r If PRZR pressure decreased < 2205 psig then identify a two-hour to restore PBPZR pressure
Directs I B C Maintenance to investigate the failure of 1-RC-PT-1445, BRZR Pressure control channel.
Kotifias Shift Manager and STA of failure and actions in progress.
Appendix D Required Qperator Actions
Op-Test NO.: 2'304-301
Event No.: 3
Event Description: P U R PORV Leakage (I-RC-PCV-1455C)
Scenario Noo: Spare
Time Position RO
Applicant's Actions or Behavior Acknowledges annunciator lC-F?, PRZR RELIEF TK HI PRESS.
Identifies P U R pressure decreasing and reviews annunciator response procedures.
Acknowledges annunciator 1C-D4, P U R PWR W L E F LINE HI TEMP.
Direct implementation of AP-3 1 00, INCREASING OR DECmASIYG RCS PWESSURE.
Check Turbine Load stable. (AP-3 1 00, Step 1)
Check RTS pressure decreasing. (AP-3 1.06, Step 2) - Identifies RCS pressure is slowly decreasing.
Decreasing RCS pressure will cause the QTAT setpoint to decrease. (AP- 3 I .OO, Caution prior to Step 3 ) - Monitor OTAT setpoint.
PZR PQRV I-RC-PCV-1455C shoiald be declared inoperable when the Master Controller is placed in Manual. (AP-3 1.00, Note prior to Step 3 )
Stop Pressure Decrease. (AP-3 1.00, Step 3) - Place l-CH-PC-1444J, P U R P E S S MASTER CKTRL in
MAW&. - Decrease demand on PKZR PRESS MASTER CNTRL to raise RCS
pressure. - Declare PaZR PORV inoperable
Check RCS pressure still decreasing. (AP-3 1.00, Step 4) -
Veri@ no pressure loss through the PRZR PORVs. (AP-3 1 .00, Step 5) - - Close Block M 8 V to isolate any PQRV, which will not close or is
- Identifies when the remaining Biock MQV closes RCS pressure will
Identifies RCS pressure is still decreasing.
Close or verify dose P W R PORVs
leaking.
start increasing.
Appendix I9 Required Operator Actions
Qp-Test No.: 2004-301
Event No.: 3
Event Description:
Scenario No.: Spare
Foran BS-B-2
Page 7 of 22
Applicant’s Actions or B~laavior Turn on ail PRZR heaters. ( M - 3 1 .OO, Step 6) (should be)
Verie closed or close 1-CH-HCV-13 11, AUX Spray I s ~ l i & ~ . (AP-3 I .OO, Step 7) (should be)
Check ALJX Spray line leakage suspected. (Ap-3 1 .OO, Step 8) (should not
- GOTO §tep 10 be)
Place Spray valve controllers in Manual and adjust demand to zero. (AI?- 31.00, Step 10) - - Verifies demand at zero
Places both spray valves controllers in Manual.
Check either of the following conditions. (AP-3 I .OO, Step 1 1) - Identifies both spray valves closed.
Identifies spray valves not leaking to abnormal PRT conditions. - Go TO Step 13
Check RCS Pressure stabilizing or increasing. (“-31 .OO, Step 13) - Identifies R.CS pressure increasing following closing last P U R BORV
block valve. - TO Step 17
Peturn PRZR PRESS MASTER CNTRL and P U R Spray Valve :ontrollers back to AUTO.
3vaiuates Tech Specs sections 3.2.A.6, 3.1.6, and P.12.F. Declare PR%R JOKV, 1-RC-PCV-1456 inoperable and close PRZR PORV block valve, 1 - IC-MOV-1535 within one-hour. If P U R pressure decreased hen identify a two-hour to restore ]PUR pressure. Determine RCS leak ate after stabilizing plant conditions.
2205 psig
iotifiies Shift Manager and STA of failure and actions in progress.
Appendix D Required Operator Actions
Bp-Test No.: 2004-301 Scenario No.: Spare
Event No.: 4
Event Description: Unit Load Reduction (AP-23.00)
Position BOP
Form ES-D-2
Page 8 of 22
AppBicrant9s Actions OF Behavior Acknowledges annunciator 1 E@, GEN LEADS CLG TKBL + W r w h p- wck&?M. &t5 Pa%.
Direct the Turbine BLDG operator to local annunciator panel to inwstigate cause of alarm.
Reviews annunciator response procedure while awaiting field report
Perform ARP 1G-E5, GEN LEELBS CLG TREK
lsophase Bus Duct Cooling (BDC) Fan - Turbine BLDG operator reports Low &r Flow due to a loss of “A”
- Reviews cautions - If one or more fan is inoperable, a unit ramp down to the self
cooled rating of 14,250 amps should be initiated immediately - Power should be reduced at the rate of 1% power per minute to
78% power Power reduction sh~uld continue fiom 78% to 14,250 m p s at normal rate of 155 MWehKR
- Reviews note in accordance with OPAP-0006, Shift Operating Practices, at the discretion sfthe Shift Supervisor, the thermal overload devices may be reset only once.
- Attempt to restart Pran - Dispatch operator to check circuit breaker MCC 1A2-2-1B. GEN
- Report from field is the breaker is tripped - Initiate a ramp down to reduce generator amps to 14,250 amps in
- G8 TO Step 8 to initiate work request to repair B D C fan
LEADS CLR PH A Pan
accordance with 8-AP-23 00, W D LOAD REDUCTION
Votify Electrical Maintenance to investigate failure of the IBBC Fan
Yotifies Shift Manager and STA of failure and actions in progress.
Directs M-23.60, Rapid Load Reduction based on loss of WDC Fan.
3onservative decision-making must be maintained during rapid load aiuctions. If uncertain or degrading conditions arise which could idversely affect the safety ofthe plant, or if any criteria in Attachment 1 is :xceeded, the load reduction should be terminated by tripping the Reactor )r the turbine, or both, depending on power level. (AP-23.00, Caution xior to Step 1)
Appendix D Required Operator Actions Form ES-D-2
Bp-Test No.: 2004-301 Scenario No.: Spare Page 9 of22
actions should continue at Step 25. - RCS Tave must be maintained 5 57’9’F and RCS pressure 2 2205 psig.
Tech Spec 3.12.P.1 should be reviewed if either parameter is exceeded - I&C should be contacted to provide assistance with adjusting IRPIs.
Initiate Plant Load Reduction at I % M N T E or less. (Ap-23.00, Step 1) - - Insert control rods in AUTO or I M ” W A % as necessary to maintain
Verify turbine valve position not on limiter. (should not be)
Tave and Trefmatched. - Veri5 or place Turbine in WLP INPd. - Adjust LOAH> RATE %/“ thumbwheel to 1%MIN ramp rate. - Initiate Turbine load reduction using OPERATOR AUTO. - Perform emergency boration for 30 to 60 seconds IAW the following:
- Verify or r i s e CHG flow to 9 95 gpm - Transfer the in-sewice BATP to FAST
- Momitor EMER BORATE: FLOW - After required emergency boration, perform the following:
- Open 1CH-MOV-1350
- Close 1-CH-MOV-1350 - Transfer the in-senlice BATP to AUTO - Restore CHG Bow control to normal
- Establish a continuous 10 gprn normal boration to maintain control rod position above the LO-LO- insertion limits.
- Check all PRZR heaters energized. - Contra! ramp rate to maintain RCS pressure 2205 psig. - Monitor steam dumps for proper operation. - Reduce Turbine valve position limiter as load decreases.
Appendix D Required Operator Actions Form ES-D-2
Op-Test NO.: 2004-301 Scenario No.: Spare Page 10 of22
- VPFLP-2802, Notifications and Report applicability
Appendix D
Qp-TESt No.: 2004-301
Event Yo.: 5
Event Description: HA Steam Generator Level Transmitter fails low (1-FW-LT-1476)
Required Operator Actions
Scenario No.: Spare
Form ES-D-2
Page 11 of 22
_I
I
Applicant’s Actions or Behavior Acknowledges annunciators associated with the SG levels and high
Identifies “A” SG channel 3 faiied low (1-FW-LT-1476).
Direct BOP to place “A” Main FRV in Manual and restore “A’’ SG level.
Takes manual control d “ A ” Main FRV and reduces feedwater flow to restore level.
Reviews W s .
Performs focus brief on failure and actions in progress.
Reviews Tech Specs Section 3.7 and identifies TS Table 3.7-1 items 12 B 17 requiring Operator Action #6; identifies TS Table 3.7-2 item 3a and TS Table 3.7-3 item 3a requiring Operator Action #20, 72 hour clock to place channel in trig.
Notifies I B C Maintenance to place channel in trip.
Notifies Shift Manager and STA of failure and actions in progress.
Event No.: 6
Required Operator Actions
Seenaris No.: Spare
Event Description: 1B SG POW E -MS-R7 C
Form ES-D-2
Page 12 of22
Appendix Id Required Operator Actions Form ES-D-2
Op-TeSt No.: 2604-301 Scenario No.: Spare Page 13 of 22
Event No,: 7, 8, 9> 10, & 11
Event Description: Main Steam Line Break at header. “B” Charging Pump Trips and “A” and “C” fail to auto start. Motor Driven and Steam Driven AFW punips trip. MSTVs fail to close (I-MS-TV-101A €3, & C). “B” & “G“ Main Steam MXVs fail close.
Time _s
Position
RQWQP
RB
Applicant’s Actions or Behavior Acknowledges annunciators.
Identifies decreasing SG and RCS Pressure, along with RCS temperatures.
Identifies automatic Reactor Trip and initiates 1-E-0 Immediate Actions.
Directs perfbrmance of 1-E-0 Immediate Actions.
Acknowledges annunciators while RQ performs 18-0 Immediate Actions.
Verifies Reactor Trip (E-0, Step 1 - Immediate Action Step) - Manually trip Reactor - - - Cheek Neutron flux lowering
Verify Turbine Trip (E-0, Step 2 -Immediate Action Step) - Manually trip the turbine by pressing both Trip Pushbuttons - Identify ai1 Turbine Stop Valves close - Close MSR Steam Supply I-MS-SOV-104 - Verifi Generator Output Breaker open (30 second time delay)
Ver@ both Emergency AC Buses energized @-Q3 Step 3 -Immediate Action Step)
Check if SI is actuated. (E-Q? Step 4 - Immediate Action Step) - - Verifi LHSI pumps running - Verifi SI annunciators lit
Check all Rods On Bottom Light lit Check Reactor T ~ p and Bypass Breakers open
Manually actuate both trains of SI
- A-P-3 - A-F-4
May take actions BO isolate the steam break by: - Attempting to close MSTVs using control switches and App Ha
Emergency closure switch (Vertical Board 2) Closes “A’’ MS hXV and attempts to close “B” & “G” MS NwVs -
Appendix D Required Operator Actions
Qp-Test Me.: 2084-301 Scenario No.: Spare
Form ES-D-2
Page 14 of 22
Position SRODOP
SROBOP (Event 9)
SRCB
RO/SRO (Event 8 )
Applicant’s Actions or Behavior Veri@ FW Isolation. (E-0, Step 5) . , -
- Feed Reg valves closed -
Feed pump discharge MOVs &sed (l-FW-MOV-150A & B) - mw pumps tripped
SG FW bypass flow demand at zero
Verify CTMT Isolation Phase I. @-(I, Step 4) - Phase I TVs closed
- 1 -SV-TV- I02A closed PwR/B Isolation valves I-DA-TV-103A closed -
- I-CH-MOV-1381 closed
PAM Isolation valves 1-DA-TV-1038 closed
Veri@ AFW pumps Running. ( 5 0 , Step 4 ) - Identifies mw Pumps nQt running - Lockout annunciators lit for both mw Pumps - - Identifies no exhaust steam flow indicated for AFW Pump
Identifies TD AFW Pump not running
Direct Unit 2 Operator to crosstie M W and supply Unit I IAW Bp- 50.00.
Verify SI Pumps Running. @-O> Step 8) - Identifies “B” CHG Pump tripped - Identifies “A” and “C” CHG Pumps not running - Identifies no lockout annunciators lit - Manually start “A” and ‘‘Cy CHG Pumps - LHSI Pumps mnning
Veri@ CHG Pump Auxiliaries. @-O> Step 9) - -
GPEG Pump C@ Pump running CHG Pump SW Pump mnning
Check Intake Canal. (E-0, Step 10) Level>24FT
- Level being maintained by CW Pumps
Appendix D Required Operator Actions Form ES-B-2
Scenario No.: Spare Page 15 OF 22 Bp-Test NO.: 2004-301
I‘inne Applicant’s A C ~ ~ Q I I S or Behavior Check if Main Stearnlines should be isolated. (E-0, Step 1 I) - Cheek if any ofthe following annunciators have been lit.
- E-F-10, MB STEAM FLOW SI (should be on) - B-C-4, HI HI CLS TEMN A (should be o w - B-(2-5, Hl HI CLS TRAIN B (should be OR)
- Attempting to close MSTVs using control switches and App R Emergency closure switch (Vertical Board 2)
- Closes “A” MS NRV and attempts to close “B” C “C” MS NRVs - If annunciator E-H-10 (Header to line SI) (should be yes) - Verify RWST crosstie vaalves open
- 1 -SI-TV- 1028 - l-SI-TV-102B - 2-SI-TV-202A - 2-SI-TV-2Q2E
- Check RCS pressure 185 psig (should not be)
Check if CTMT Spray Required. (E-0, Step 12) - - - GOTOStep 13
CTMT pressure has exceeded 23 psia (should not be) If‘CTMT pressure has exceeded 17.7 psia (should not be)
Review notes. (E-0, Notes prior to Step ‘13) - Low P U R pressure SI signal should be blocked when PRZK pressure
decreases < 2000 pig - Blocks Low PRZR pressure SI signal by using block switches
- High steam flow SI signal should be blocked when Tam decreases < 543°F
CHG pumps should be pun in the following order of priority: C, B, A - Blocks High steam flow SI signal by using the block switches
-
Verify SH Plow. (E-0, Step 13) -
- 1 -SI-FI- 196 1 - I-SI-PI-1962 - 1-SI-”1963 - 1-SI-FI-1943 or 1943A
“SI to cold legs flow indicated
- - Reset SH -
Check three CHG Pumps running
Stop one CHG Pump and place in AUTO Check RCS pressure 185 psig (should be > 185 pig)
Appendix B Required Operator Actions
Bp-Test No.: 2004-301
Event No.: 12
Event De$CriptiQEI: RCS Bleed and Feed
Scenario No.: Spare
i I
I i-- I
Position SROWOP
SIP0
TEAM
TEAM
FOETI ES-D-2
Page 16 of 22
Appticant's Actions or Behavior Verify Total AFW flow - -
350 gpm [450 gpm]. @-0, Step 14) Identifies no AFW Pumps running AFW flow < 350 gprn
GO TO FR-H. 1
Transitions to FR-€3.1 Reviews Cautiomrs. (FK-H.1, Cautions prior to Step 1 ) - If total feed flow
Peed Bow should not be reestablished to any faulted SG if a non-
359 gpm 8450 gpm] due to operator action, this procedure shouId not be performed.
faulted SG is available. -
Check if Secondary heat sink is required: (TIR-H.1, Step 1) - -
RCS pressure > any non-faulted SG pressure (should be) RCS hot Beg temperature > 350°F (should not be)
Refer to 1-OF-W-001, RHR OPEKATIQNS. If adequate cooling with RFR is established, then RETURN TQ procedure and step in effect.
- Try to put ILPHfp system in service while continuing this procedure.
Review caution. (FR-H. 1, Caution prior to Step 2) - If wide range level in any 2 SGs 7% [22%] or PRZR pressure >_ 2435
psig due to loss of secondary heat sink, RCPs should be tripped and Steps 10 through 27 should b < @ Z 6
Identifies that 2 SGs < 7% [22%] on wide range level indication and actions required by the Caution or eke Comtinuous Action Page
~~
Stops all RCPs.
Reviews caution. (FR-H. 1, Caution prior to Step 10) - Steps 10 through 17 nust be performed quickly in order to establish
RCS heat removal by RCS bleed and feed.
Veri@ stopped or stop all RCPs pR-H.1, Step lo) - Identifies ai1 RCPs stopped.
Appendix B Required Operator Actions
Bp-Test No.: 2004-381 Scenario No.: Spare
F o ~ ES-D-2
Page 17 sf 22
- Manually initiate SI - Identifies SI was already in service.
Verify RCS Feed Path: (FR-H. 1, Step 12) - Check CHG Pumps at least one running (should be two) - Verifl SI valve emergency alignment
- CHG Pump suction from RWST MOVs opened (should be) - 1 -CH-MQV- 1 1% & D
- CNG Pump suction from VCT MOVs closed (should be) - l-CH--V8%1-115B & E
- HHSI to cold leg opened (should be) - I-SI-,MOV-I867C B D
- Verify HHSI flow to cold legs (should be)
mews no If an SI signal is actuated afler completion of Step 13, the SI signal should
for reset permissive.
- -
CTMT pressure < 14 psia (should be) Reset both trains of CLS, if necessary (should not be)
t Air available: (FR-H 1, Step 15) annunciator BB-6 not lit (should not be)
Check at least one CTMT EA compressor ninning (should be) Verify 1 -1A-W- 100 open (should be)
- -
- - Open both PRZR PORVs
Opeti both both PRZR PORV block valves
Verify adequate RCS Bleed Path: (FR-H. 1, Step 17) - P E R FQRVs both open (should be) - FRZR PORV block valves both open (should be)
I
Appendix D Required Operator Actions
Op-Test No.: 2004-301 Scenario No.: Spare
Time Applicant’s Actions or Behavior Initiate Attachment 4 while continuing with this procedure. (FIX-E3 1 , Step
- Veri@ Reactor Trip (should be) - Veri@ Turbine Trip (should be) - Verify both A@ Emergency Buses energized (should be) - Identifies SI actuated - Verify FW Isolation (should be) - Verify CTMT Isolation Phase I (should be) - Verify AFW Pumps running (should not be) - Verify SI Pumps running (should be two) - Check CHG Pump Auxiliaries running (should be) - Check Intake Canal > 24 PT and level being maintained by CW Fumps - Check $Main Steamlines should be isolated (should be only “A” SG) - Check if CS Required > 23 psia (should Rot be) - Blocks Low P M R pressure and High’Steam Plow SI signals - Verify SI flow (should be) - Reset both trains of Sh (should be) - Identifies RCS pressure > 185 psig Stops one LHSI Pump and put in AUTO
Maintain RCS Heat Removal: (PR-H.1, Step 19) - Maintain SI flow -
Reviews caution. (FR-H. 1, Caution prior to Step 20) If containment pressure increases to > 23 pia , containment spray should be verified
Check if 6s should be stopped. (FIR-H. 1, Step 20) -
Continue attempts to establish secondary heat sink in at least one SG using high pressure makeup. (FR-H. 1, Step 21) - - -
18)
Maintain RCS vent paths open
Identifies Spray Pumps not running
AFW flow (IAW Step 2) MFW flow (IAW Step 3) Condensate flow (IAW Step 7)
Appendix D Required Operator Actions Fom ES-D-2
op.-Test No.: 2004301 Scenario No.: Spare Page 19 of 22
Applicant’s Actions or Behavior Try to establish AFW flow to at least one SG: (FR-H. 1, Step 2 ) - -
Check SG blowdown TVs closed (should be) Verify M W MBVs open (should be)
SGS. - Identities that “B” and “6” SG faulted and isolate AFW MOVs to both
- Check ECST available (should be) - Check AFW available
- Identifies can not start AFW Pumps and carries out RNO - Identifies minimum feed flow net established, then do the
foilowing - StopRCBs - Have Unit 2 operator close Unit 2 AFW MOVs - Have Unit 2 operator open MOV-FW- I60A & €3 - Have Unit 2 operator start both
- Control MVIT flow to maintain total flow to SG
- Identifies AFW flow establish to ‘‘K SG via Unit 2 AFW
AFW Pumps (TD
350 AIaW Pump 00s initial conditions)
gpm [450 EPml.
crosstie. Check for adequate Secondary Heat Sink: (FR-H. 1, Step 22) - - . RETURN to Step 21
NR level in at least one SG 12% [ 18%] Identifies NR level in “A’’ SG increasing
Appendix D Kequired Operator Actions Form ES-D-2
Op-Test No.: 2004301 Scenario No.: Spare Page 20 of 22
Appendix D Required Operator Actions FOIXI BS-D-2
Qp-Test NO.: 2004-301 Scenario Ns.: Spare Page 21 of 22
Appendix B Required Operator Actions
Bp-Test No.: 2004-301 Scenario No.: Spare
Form ES-D-2
Page 22 of 22