OUTLINE COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
1
1. INTRODUCTION
2. METHODOLOGY
3. RESULTS
4. CONCLUSION
INTRODUCTION COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 2
Northridge (1994) & Kobe (1995) Earthquake
Failure in the conventional beam-column connection showed that steel
moment frames wasn’t as ductile as believed
After years of research, it produced new types of connection, one of them is RBS (Reduced
Beam Section) connection
BACKGROUND
INTRODUCTION COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 3
RBS ?
What
• Reduced the section of the beam flange near of the connection area.
Why
• The concept is to weakening the beam, which effectively make the connection area stronger than the beam.
Purpose • Plastic hinges are expected to be formed in the RBS area.
INTRODUCTION COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 4
FEMA 350 [1] / 351 [12] EC 8. Part 3 [13] a = 0.50 – 0.75 bf a = 0.60 bf b = 0.65 -0.85 db b = 0.75 db
c ≤ 0.25 bf g ≤ 0.25 bf s = a + b/2 s = a + b/2
r = (4c2 + b2) / 8c r = (4g2 + b2) / 8g
INTRODUCTION COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 5
LOAD
PLASTIC HINGE
Conventional Portal
INTRODUCTION COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 6
LOAD
PLASTIC HINGE
Portal with RBS
RBS
INTRODUCTION COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 7
• Plastic Hinge will be formed in the RBS area. • RBS could increasing the inelastic drift by 9% corresponding to a flange reduction of 50% (FEMA350, 2011) • With radius-cut RBS, which is using angular cut, cracks would tend to develop when the beams are subjected to large forces (Engelhardt, 1995)
INTRODUCTION COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 8
Rigid Connections are kind of connections which have enough rigidity to keep the angle between the elements joint. Then, rigid connections could transfer significant moment to the columns and are assumed that there is no deformations.
RIGID CONNECTIONS
TYPES OF RIGID
CONNECTIONS IN THIS
RESEARCH
WELDED RIGID CONNECTION
REFERENCE :
SIMPLE CONNECTION
(D.T. Pachoumis, 2009)
EXTENDED END PLATE
CONNECTION
T-CONNECTION
INTRODUCTION COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 9
This research aim to compare the behaviour (deformation, displacement, stress, and strain) of 4-types rigid connections, which all using RBS (Reduced Beam Section) at column face.
PURPOSE
TYPES OF RIGID
CONNECTIONS IN THIS
RESEARCH
WELDED RIGID CONNECTION
REFERENCE :
SIMPLE CONNECTION
(D.T. Pachoumis, 2009)
EXTENDED END PLATE
CONNECTION
T-CONNECTION
METHODOLOGY COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 10
METHODOLOGY COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 11
Dimension Depth Width Thickness r (mm) A (cm2) W (kg/m)
h (mm) b (mm) tw
(mm) tf (mm)
Balok 1 (HE200A)
190 200 6.5 10 18 53.8 42.3
Balok 2 (HE220A)
210 220 7 11 18 64.3 50.5
Balok 3 (HE240A)
230 240 7.5 12 21 76.8 60.3
Kolom (HE300B)
300 300 11 19 27 149.1 117
Dimension Depth Width Thickness r (mm) Zx (mm3) Z RBS (mm3)
db (mm) bf RBS
(mm) tw
(mm) tf (mm)
Balok I (HE200A)
190 100 6.5 10 18 406962.5 226962.5
Balok 2 (HE220A)
210 110 7 11 18 543432 302642
Balok 3 (HE240A)
230 120 7.5 12 21 707407.5 393487.5
Dimension of beam and column
Design of RBS (50% cut)
• Plastic Section Modulus of RBS : • Plastic moment in RBS area :
• Shear at the inflection point : • Plastic moment of beam : •Total moment at the column face :
METHODOLOGY COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 12
⋅−⋅⋅⋅+⋅
−⋅⋅= ffffbwRBS thbttdtZ
21
21
21
21(2
2
Pelatbadan460x268x12
Pelatmenerus262x130x12
Stiffenerdbx1
2bfx12
1000 200
1200
1797Balok
Kolom
Applied Load
Applied Loadba
898.5
898.5
METHODOLOGY COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 13
Dimension Mp beam (kgcm)
Mp act (kgcm) Mf (kgcm)
Vpd (kg)
Balok I (HE200A) 1501895 837605.1 1054918 10549.18
Balok 2 (HE220A) 2005536 1116900 1444890 14448.9
Balok 3 (HE240A) 2610687 1452166 1931071 19310.71
Capacity Analysis of RBS
METHODOLOGY COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 14
• Vd = n. øf. Vn = n. Øf. r1. fub. Ab Shear strength of bolts
• Td = øf. Tu = øf. 0,75. fub. Ab Tensile strength of bolts
• Rd = øf. Rn = 2,4. øf. db. tp. fu Compressive strength of bolts
• Vd = ø. Vn = 1,13. ø. μ. m. Tb Shear strength of friction bolts
Design Analysis of Bolt Connections
METHODOLOGY COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 15
• Groove Weld
(Axial forces)
• Groove Weld
(Shear forces)
• Fillet weld
Design Analysis of Weld Connections
METHODOLOGY COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 16
Design of T-Connection
Balok HE200A
Kolom HE300B 300200
a
a
Potongan a - a
RBS
Profil T 130 x 131 x 11 x 15
4 - Ø 25
4 - Ø 25
Profil L 70 x 70 x 7
1 - Ø 22
4 - Ø 22
2 - Ø 22
4 - Ø 22
332
Balok HE220A
Kolom HE300B 300220
a
a
Potongan a - a
RBS
354
Profil T 143 x 132 x 12 x 19
4 - Ø 29
4 - Ø 29
Profil L 75 x 75 x 7
1 - Ø 25
4 - Ø 22
2 - Ø 25
4 - Ø 22
Balok HE240A
Kolom HE300B
300240
a
a Potongan a - a
Profil T 156 x 150 x 13 x 20
4 - Ø 32
4 - Ø 32
Profil L 90 x 90 x 9
1 - Ø 29
4 - Ø 25
4 - Ø 25
2 - Ø 29 393
Tensile Strength of T-Profile
Beam 1 (HE200A)
Beam 3 (HE240A)
Beam 2 (HE220A)
METHODOLOGY COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 17
Design of Extended End Plate
Balok HE200A
Kolom HE300B 300200
a
a
Potongan a - a
RBS
8 - Ø 19
t plat = 12 mm29
67
113
29
67
304
Balok HE220A
Kolom HE300B 300220
a
a
Potongan a - a
RBS
8 - Ø 22
t plat = 13 mm
33
77
122
33
77
342
Balok HE240A
Kolom HE300B
a
a
RBS
300240
Potongan a - a
8 - Ø 22
33
78
140 362
33
78
t plat = 14 mm
Tensile Strength of End Plate
Beam 1 (HE200A)
Beam 3 (HE240A)
Beam 2 (HE220A)
∑⋅
= 2max
ddM
T uu
METHODOLOGY COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 18
Design of Welded Rigid Connection
Balok HE200A
Kolom HE300B 300200
a
a
Potongan a - a
RBS
190
Profil L 80 x 80 x 14
1 - Ø 22
Balok HE220A
Kolom HE300B 300220
a
a
Potongan a - a
RBS
2101 - Ø 25
Profil L 90 x 90 x 16
Balok HE240A
Kolom HE300B 300240
a
a
Potongan a - a
RBS
230
Profil L 90 x 90 x 16
1 - Ø 29
Coupling force at beam flange
Beam 1 (HE200A)
Beam 3 (HE240A)
Beam 2 (HE220A)
METHODOLOGY COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGY IV. CONCLUSION
III. RESULTS 19
Specimen Test
Pelatbadan460x268x12
Pelatmenerus262x130x12
Stiffenerdbx1
2bfx12
1000 200
1200
1797Balok
Kolom
Applied Load
Applied Loadba
898.5
898.5
0 1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18 19 20 21 22 23
0 1 2 3 4 5 6 7 8 9 10 11 12
Load
(ton
)
Step
Loading Protocol
RESULTS COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGI IV. CONCLUSION
III. RESULTS 20
Finite element analysis using ABAQUS v.6.7
Behavior of the connection (deformation, displacement, stress-strain)
Compare the behavior of all types connections
RESULTS COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGI IV. CONCLUSION
III. RESULTS 21
5 cm from column face
Center of RBS
75 cm from column face
RESULTS COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGI IV. CONCLUSION
III. RESULTS 22
Behavior of The Connections in Profile
Beam 1 (HE200A)
RESULTS COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGI IV. CONCLUSION
III. RESULTS 23
Behavior of The Connections in Profile
Beam 2 (HE220A)
RESULTS COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGI IV. CONCLUSION
III. RESULTS 24
Behavior of The Connections in Profile
Beam 3 (HE240A)
RESULTS COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGI IV. CONCLUSION
III. RESULTS 25
Profil Balok
Jenis Sambungan Kode
Kondisi di 5 cm di depan kolom (sambungan) saat RBS leleh
σ (N/mm2) Pengurangan tegangan (%)
U12 (mm) Pengurangan
displacement (%)
Balok 1 (HE200A)
T-Connection TC-200 63.414 31.52 0.186 14.68 Extended End Plate Connection EP-200 92.185 0.45 0.218 0.00 Welded Rigid Connection WR-200 89.937 2.88 0.199 8.72 D.T. Pachoumis (2009) DT-200 92.606 0.00 0.218 0.00
Profil Balok
Jenis Sambungan Kode
Kondisi di 5 cm di depan kolom (sambungan) saat RBS leleh
σ (N/mm2) Pengurangan tegangan (%)
U12 (mm) Pengurangan
displacement (%)
Balok 2 (HE220A)
T-Connection TC-220 60.301 40.67 0.242 9.70 Extended End Plate Connection EP-220 101.574 0.07 0.266 0.75
Welded Rigid Connection WR-220 82.621 18.71 0.257 4.10
D.T. Pachoumis (2009) DT-220 101.643 0.00 0.268 0.00
Results of the connections in Beam 1 (HE200A)
Results of the connections in Beam 2 (HE220A)
RESULTS COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGI IV. CONCLUSION
III. RESULTS 26
Results of the connections in Beam 3 (HE240A)
Profil Balok
Jenis Sambungan Kode
Kondisi di 5 cm di depan kolom (sambungan) saat RBS leleh
σ (N/mm2) Pengurangan tegangan (%)
U12 (mm) Pengurangan
displacement (%)
Balok 3 (HE240A)
T-Connection TC-240 96.297 18.16 0.286 9.49 Extended End Plate Connection EP-240 116.541 0.96 0.313 0.95 Welded Rigid Connection WR-240 111.057 5.62 0.301 4.75 D.T. Pachoumis (2009) DT-240 117.669 0.00 0.316 0.00
CONCLUSION COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGI IV. CONCLUSION
III. RESULTS 27
From the results of this study, it conclude that : 1. Extended End Plate Connection and Simple Connection (D.T. Pachoumis, 2009) have a similar behavior, it can be seen from the results of stress-strain behavior and the displacement occurred in 5 cm from column face (connection area). 2. Welded Rigid Connection is more rigid than the two connections before, it could reduce the stress by 2-18 % and also the displacement occurred by 4-8 % in 5 cm from column face (connection area). 3. T-Connection is the most rigid connection than the others connection, it could reduce the stress by 18-40 % and also the displacement occurred by 9-14 % in 5 cm from column face (connection area). 4. From those results, the behavior of rigid connections are still same for all kind of beam profile. So, smaller or bigger profile, the behavior of connections are same.
BIBLIOGRAPHY COMPARATIVE STUDY OF THE BEHAVIOR OF REDUCED BEAM SECTION RIGID CONNECTIONS
I. INTRODUCTION II. METHODOLOGI IV. CONCLUSION
III. RESULTS 28
Chen, S. J., Yeh, C. H., and Chu, J. M.,“Ductile steel beam-to-column connections for seismic resistance.” J. Struct. Engrg., ASCE, 122(11), 1292-1299, 1996. Davis, G., "Steel Moment-frame Buildings: The Saga Continues", Part II, Structural Engineer, June 2001. Departemen Pekerjaan Umum, 2002, Tata Cara Perhitungan Struktur Baja Untuk Bangunan Gedung (SNI 03-1729-2002), Yayasan LPMB, Bandung Departemen Pekerjaan Umum, 2002, Tata Cara Perencanaan Ketahanan Gempa Untuk Bangunan Gedung (SNI 03-1726-2002), Yayasan LPMB, Bandung D. T. Pachoumis, E. G. Galoussis, C. N. Kalfas, A. D. Christitsas, "Reduced Beam Section Moment Connections Subjected to Cyclic Loading: Experimental Analysis and FEM Simulation", 2009. Engelhardt MD, Sabol TA. Seismic-resistant steel moment connections: developments since the 1994 Northridge earthquake. J Prog Struct Eng Mater ;1(1):68_77, 1997. EC 8, Part 3: Design of structures for earthquake resistance. Assessment and retrofitting of buildings. EN 1998-3: June 2005E. FEMA 350. Recommended seismic design criteria for new steel moment-frame buildings. Washington (DC), 2000. Iwankiw, N., “Ultimate strength consideration for seismic design of the reduced beam section (internal plastic hinge).” Engrg. J. 34(1), 3-16, 1997.