    Instructions - Flush Mounting Installation System

    SunMaxx-M2 Flat Plate Collector

  • 8/6/2019 SunMaxx TitanPower-AL2 Flush Mounting Instructions

    2/16

    SunMaxx M2 Flush Mounting Installation System 2

    EXPLOSION DRAWING

  • 8/6/2019 SunMaxx TitanPower-AL2 Flush Mounting Instructions

    3/16

    SunMaxx M2 Flush Mounting Installation System 3

    PARTS LIST

    No. DesignationQuantity

    basic kit

    Quantity

    extension kit

    1 Collector2 Rail, 1,155 mm3 Rail, 1,172 mm

    020

    002

    4 Collector fixing kit4.1 4x M8 x 14 hexagonal bolt4.2 4x mounting profile (Z-hooks)4.3 4x 8.4 mm washer4.4 1x installation aid4.5 2x M8 x 10 hexagon socket head cap screw

    1 1

    5 Rafter anchor for pantiles (variation A) 4 2

    6 Rafter anchor kit

    6.1 4x 10 wood screw6.2 2x M10 hexagonal bolt6.3 6x 10.5 mm washer6.4 2x M10 hexagonal nut6.5 2x slot nut6.6 4x wooden equalisation board (2 x 5 mm, 2 x 10 mm thick)

    2 1

    7 Rail connection kit7.1 2x rail connector7.2 4x M8 x 50 hexagonal bolt7.3 8x 8.4 mm washer7.4 4x M8 hexagonal nut7.5 2x 20 mm self-adhesive spacer

    0 1

    8

    Rail end set8.1 4x rail connector8.2 4x end piece8.3 4x M8 x 50 hexagonal bolt8.4 8x 8.4 mm washer8.5 4x M8 hexagonal nut

    1 0

    9 Corrugated pipe, 800 mm9.1 1x 800 mm corrugated pipe with 12 mm compression fitting and

    insulation tube9.2 1 x 12 mm support sleeve9.3 2 x seal

    2 0

    10 Corrugated pipe, 250 mm10.1 1x 250 mm corrugated pipe with 12 mm compression fittings and

    insulation tube10.2 2 x 12 mm support sleeve

    0 1

    11 Rafter anchor for plain tiles (variation B) 4* 2*

    12 Corrugated slab fastening (variation C)12.1 1x hanger bolt12.2 3x M10 hexagonal nut12.3 1x seal12.4 1x rail holder

    4* 2*

    * optional

  • 8/6/2019 SunMaxx TitanPower-AL2 Flush Mounting Instructions

    4/16

    SunMaxx M2 Flush Mounting Installation System 4

    GENERAL

    The on-roof installation kit is for installing the K4-EM2S type collectors vertically or horizontally on

    a roof. It can be used on roofs with slopes of 20 and above.The rafter anchors are available in variations for the following roof coverings: pan tiles and similar

    roof tiles, and plain tiles. Fastening elements are also available for corrugated slabs (e.g.

    corrugated sheeting, corrugated fibre cement). Alternatively, standing seam clamps for standing

    seam roofs or fastenings for other types of roofs can be combined with the system. These must

    be procured by the contractor from the local roofing supplier.

    Extra materials such as ventilation tiles for the roof opening for the collector array connections

    (available from specialist suppliers) and tin/lead sheets for sealing the rafter anchors on a plain

    tile covering may be required.

    In some cases it is necessary to plan a means of transporting the collectors onto the roof. Werecommend considering roof access near to the collectors so that checking and maintenance

    work can be carried out more easily.

    When connected hydraulically, up to 3 K4-EM2S collectors can be connected in series. If more

    than 3 collectors are connected, this must be done using a combination of series and parallel

    connection.

    We recommend declaring the solar energy system to your insurer as added value to the building,

    and taking out insurance against lightning and possibly glass breakage.

    SAFETY INSTRUCTIONS

    The installation and safety instructions must be observed and adhered to. The accident

    prevention regulations of the trade associations must be adhered to, particularly when working

    on the roof. Where there is a danger of falling, precautions must absolutely be taken.

    The entire solar energy system must be installed and operated in accordance with the recognised

    technical regulations.

    Due to snow and wind loads, extreme forces can be at work on the collector fixings. Attention

    should therefore be paid to carrying out the installation carefully. The roof construction (rafters)

    must be capable of withstanding the additional load. Furthermore, care must be taken that the

    snow and wind loads are discharged into the roof construction at certain points. It may be

    necessary to consult a structural engineer.

    In case of snow loads of zone 3 and above, and installation locations more than 600 m above sea

    level, we ask that you enquire with us about the static test.

    When installing the collectors towards the edges of the roof, a minimum gap of 1.5 m from the

    eave and of 1.2 m from the ridge must be observed. If this minimum gap cannot be observed, a

    structural engineer must be consulted.

  • 8/6/2019 SunMaxx TitanPower-AL2 Flush Mounting Instructions

    5/16

    SunMaxx M2 Flush Mounting Installation System 5

    TECHNICAL INSTRUCTIONS

    Anti-freeze protection

    The solar energy system may only be filled with antifreeze mixture. As it is not possible to empty

    the collectors completely, it is imperative that the system be filled with the antifreeze mixture,

    even for function tests. We recommend using premixed antifreeze mixtures; alternatively, the

    water and antifreeze must be mixed outside the solar energy system.

    Caution! As the collector can reach temperatures of over 200C, an antifreeze which is suitable for

    use in such conditions must be chosen (e.g. with a propylene glycol base).

    Bleeding

    The solar circuit must generally be bled below the roof. If automatic bleed valves are used, it is

    imperative that additional ball valves be installed for manual closure of the system. These ball

    valves must be closed after filling the plant again. Otherwise, the antifreeze mixture might leak

    during high temperatures and steam build-up in the collector.

    Recycling

    We guarantee that we will take back and recycle our products once they have come to the end of

    their life cycle. We have already ensured that our products are suitable for recycling during the

    development stage. This is therefore guaranteed.

    Electrical connections

    A dedicated electrical circuit/circuit breaker should be provided for the solar system.

    Earthing and l ightning protectionIf the building already has lightning protection, the solar system's metal pipes must be connected

    to the lightning protection by means of a green/yellow conductor of at least 6 mm Cu (H07 V-U

    or R). Otherwise it is possible to earth the system to an earth rod.

    Pictograms

    Here you will find important

    instructions which must be

    observed under all

    circumstances.

    Here you will find notices regarding

    dangers concerning health, damage

    to equipment and financial losses.

    Required tools

    Cordless screw driver with

    6 mm wood drill bit, 13 mm

    socket wrench and 14 mm

    masonry drill bit

    Spanners

    13/ 17/ 19/ 20/ 22

    Measuring tape

    Angle grinder with stone

    cutoff wheel

    6 mm Allen key

  • 8/6/2019 SunMaxx TitanPower-AL2 Flush Mounting Instructions

    6/16

    SunMaxx M2 Flush Mounting Installation System 6

    RAFTER ANCHOR AND HANGER BOLT INSTALLATION

    Vertical

    1. The collector array can be installed vertically or

    horizontally.

    For vertical installation, the rails (2/3) are installed

    horizontally. The distance A of the profile rail can be

    taken from the adjoining table. The distances B and C

    from the rails to the outer edge of the collector must be

    between 150 and 350 mm.

    Up to 3 collectors can be connected in series (1 basic kit

    and 2 extension kits).

    A in m

    M2 1,2 1,5

    Horizontal

    2. For horizontal installation, the rails (2/3) are installed

    vertically. The distance A of the profile rail can be

    taken from the adjoining table. The distances B and C

    from the rails to the outer edge of the collector must be

    between 150 and 500 mm.

    Up to 3 collectors can be connected in series (1 basic kit

    and 2 extension kits).

    A in m

    M2 0,9 1,5

    A. Pan tiles and similar roof tiles

    1. Remove one (or more) roof tiles above the planned

    installation position of each rafter anchor (5). The

    horizontal spacing is derived from the rafter spacing

    and the vertical spacing is derived from the roof tiles.

    The number of rafter anchors is derived from the size of

    the collector array (basic kit: 4 rafter anchors, extension

    kit: 2 rafter anchors)

    2. Determine the position of the rafter anchor (5) so that it

    is located in the trough of the roof tile. Mark two fixing

    points on the rafter for each rafter anchor and pre-drill

    them with a 6 mm wood drill bit.

  • 8/6/2019 SunMaxx TitanPower-AL2 Flush Mounting Instructions

    7/16

    SunMaxx M2 Flush Mounting Installation System 7

    RAFTER ANCHOR AND HANGER BOLT INSTALLATION

    3. If necessary, cut a recess in the lower tile with an angle

    grinder at the point where the rafter anchor (5) comes

    through.

    Pay particular attention to the leak-tightness of the roof

    at the position where the rafter anchor comes through.

    The roof hook must not exert any pressure on the roof

    tile.

    4. Fix each rafter anchor (5) to the roof rafters with 2

    wood screws (6.1) and washers (6.3).

    The screws (6.1) must enter into the wood to a depth of

    at least 40 mm.

    The rafter anchors (5) must not rest on the roof tiles! A

    spacing of 5 mm must be kept between the rafter and

    the roof tile. If necessary, underlay the rafter anchors with

    equalisation boards (6.6).

    5. Cut a recess in the upper tile with an angle grinder at the

    point where the rafter anchor (5) comes through.

    6. Replace the upper roof tile.

    Pay particular attention to the leak-tightness of the roof

    at the position where the rafter anchor comes through.

    The roof tile must not be pushed up by the rafter anchor

    (5).

  • 8/6/2019 SunMaxx TitanPower-AL2 Flush Mounting Instructions

    8/16

    SunMaxx M2 Flush Mounting Installation System 8

    RAFTER ANCHOR AND HANGER BOLT INSTALLATION

    B. Plain tiles

    1. Remove several roof tiles above the planned installation

    position of each rafter anchor (11). The spacing to the side

    is derived from the rafter spacing and the number of rafter

    anchors. The spacing between the rails must be observed

    as described on Page 6.

    2. Determine the position of the rafter anchor (11) so that it

    is located on a roof rafter directly above a roof batten.

    Mark two fixing points on the roof rafter for each rafter

    anchor and pre-drill them with a 6 mm wood drill bit.

    3. Fix the rafter anchors (11) to the roof rafters using

    wood screws (6.1) and the washers which go with these

    (6.3).

    The wood screws (6.1) must enter into the wood to a

    depth of at least 40 mm.

    4. Using an angle grinder, at the point where the rafter

    anchor (11) comes through, cut a recess in the upper tile

    which overlaps the crown of the rafter anchor.

  • 8/6/2019 SunMaxx TitanPower-AL2 Flush Mounting Instructions

    9/16

    SunMaxx M2 Flush Mounting Installation System 9

    RAFTER ANCHOR AND HANGER BOLT INSTALLATION

    5. Replace the roof tiles.

    Pay particular attention to the leak-tightness of the roof

    at the position where the rafter anchor comes through.

    6. Cover each rafter anchor (11) with a metal sheet.

    7. As you do so, hang the plate with the standing seam

    edge on the upper edge of the roof tiles and fix it here.

    Replace the roof tiles.

    Once all the roof tiles have been replaced, check the

    leak-tightness of the roof!

    C. Corrugated slabs

    1. In accordance with the planning, pre-drill the

    corrugated slabs at the crest with a 14 mm drill bit.

    Remove existing hanger bolts as an alternative. The

    spacing to the side is derived from the rafter spacing and

    the number of rafter anchors. The spacing between the

    rails must be observed as described on Page 6.

    Do not drill the rafters!

  • 8/6/2019 SunMaxx TitanPower-AL2 Flush Mounting Instructions

    10/16

  • 8/6/2019 SunMaxx TitanPower-AL2 Flush Mounting Instructions

    11/16

  • 8/6/2019 SunMaxx TitanPower-AL2 Flush Mounting Instructions

    12/16

    SunMaxx M2 Flush Mounting Installation System 12

    INSTALLING THE RAILS ON THE ROOF

    Vertical

    4. Lock the lower rail (2/3) with the studs into the

    mounting profiles (4.2); mount the rail facing upwards. To

    do so, position the M10 hexagonal bolt (6.2) with slot nut

    (6.5) in the rail according to the positions of the rafter

    anchors and fix it to the rafter anchor (5/11) by hand with a

    washer (6.3) and an M10 hexagonal bolt (6.4).

    Vertical

    5. Attach the upper rail (2/3) as described in steps 1 to 3

    and position it sideways.

    To do so, position the rails with respect to each other so

    that the diagonals D and E are of equal length. Mark the

    correct position before installing them. Next, fasten both

    rails in place by tightening the M10 hexagonal bolts (6.4).

    The rail end pieces (8) must be on the side where the first

    collector is to be installed.

    Horizontal

    4.1 Mount the first rail (2/3). Lock the stud into the

    mounting profiles (4.2), align towards the planned position

    of the collector connections. To do so, position the M10

    hexagonal bolt (6.2) with slot nut (6.5) in the rail according

    to the positions of the rafter anchors and fix it to the rafter

    anchor (5/11) by hand with a washer (6.3) and an M10

    hexagonal bolt (6.4).

    Horizontal

    5.1 Attach the second rail (2/3) as described in steps 1 to

    3 and position it vertically.

    To do so, position the rails with respect to each other so

    that the diagonals D and E are of equal length. Mark the

    correct position before installing them. Next, fasten both

    rails in place by tightening the M10 hexagonal bolts (6.4).

    The rail end pieces (8) must be at the bottom end of the

    rails.

  • 8/6/2019 SunMaxx TitanPower-AL2 Flush Mounting Instructions

    13/16

    SunMaxx M2 Flush Mounting Installation System 13

    PREPARING THE COLLECTORS

    1. Position the square nuts in the slot on the back of the

    collector with a screwdriver and secure them with the

    installation aid (4.4).

    Using the installation aid, the square nut can easily be

    positioned for further installation of the fixing profile (4.2)

    when the collector (1) has been erected.

    2. Preassemble the mounting profile (4.2) with an M8

    hexagonal bolt (4.1) and washer (4.3) on the square nuts

    on the rear side of the collector.

    3. Determine the definitive lower spacing C of the

    mounting profiles (4.2) on the collector. To do so, keep a

    distance from the lower edge of the collector of 150-

    350 mm for vertical installation and 150-500 mm for

    horizontal installation.

    Attach the upper mounting profiles (4.2) in accordance

    with the spacing A of the rails (2/3) to the lower

    mounting rails (4.2). The distance B to the top edge of

    the collector must also be within the range given above.

    The mounting profiles must be facing downwards.

    Preassemble the securing screw (4.5) 100 mm beneath

    the lower mounting profiles.

    4. Punch the two drainage holes at each bottom corner of

    the collector, according to how it is positioned on the

    roof, with the aid of a slotted screwdriver. To do so,

    punch at the bottom edge.

    To ensure that water can drain properly from the

    collector, it is absolutely essential that all drainage holes

    are punched at the bottom of the collector (depending

    how it is oriented on the roof).

  • 8/6/2019 SunMaxx TitanPower-AL2 Flush Mounting Instructions

    14/16

    SunMaxx M2 Flush Mounting Installation System 14

    INSTALLING THE COLLECTORS ON THE ROOF

    5. Hoist the collectors (1) onto the roof. For hoisting onto

    the roof, fix two sufficiently sturdy ropes to the collector

    as shown in the diagram. When doing so, make sure that

    the ropes are not fed over the plastic edges of the

    collector. We recommend using a crane for doing the

    lifting If necessary, carefully hoist the collector up onto

    the roof via a ladder. Work as a pair: one installer secures

    the collector, the second guides it

    Observe the labour safety regulations! Do not walk under

    suspended loads. Secure the collectors (1) to prevent

    them falling!

    Vertical

    6. Carefully lift the collector (1) onto the rails (2), remove

    the hoisting guys and position the collector. To do so,

    position the collector against the rail end pieces (8) and

    slowly let it slide downwards until the mounting profiles

    (4.2) lock into the rails (2). Next, position the securing

    screws (4.5) against the rail from underneath and tighten

    it.

    Horizontal

    6.1 Carefully lift the collector (1) onto the rails (2), remove

    the hoisting guys and position the collector. To do so, let

    the collector slowly slide downwards against the rail end

    pieces (8) and move it sideways until the mounting

    profiles (4.2) lock into the rails (2). Next, position the

    securing screws (4.5) against the rail from the side and

    tighten it.

    7. Installing more collectors

    For both horizontal and vertical installation, first stick the

    spacer (7.5) onto the rails with the stopper against the

    first collector. Install another collector as described in

    subsection 5 and 6 or 6.1. This collector must be

    positioned next to the spacers.

    After installing the last collector, attach two rail end

    pieces (8) to the open ends of the rails (2/3).

  • 8/6/2019 SunMaxx TitanPower-AL2 Flush Mounting Instructions

    15/16

    SunMaxx M2 Flush Mounting Installation System 15

    HYDRAULIC CONNECTION

    1. Replace one roof tile with a ventilation tile above each

    connecting pipes (9.1) feed-through.

    2. Feed the connecting pipes (9.1) through the ventilation

    tile into the interior of the building. Next, if necessary,

    seal the sarking membrane with suitable adhesive tape.

    The piping (9.1) should be laid so that it rises upwards in

    order to allow ventilation at the highest point of the solar

    energy system.

    3. Install the connecting pipes (9.1) to each of the

    external collector connections. To do so, insert the

    support sleeve (9.2) into the connecting pipe. Push the

    screw connection until it meets the collector

    connections. Tighten the nut by hand first, then tighten

    by one turn with the spanner. Push the previously pulled

    back insulation tube over the connection until it meets

    the collector frame.

    When tightening, make sure you keep the screw fitting

    tight with a second spanner in order to prevent damageto the collector!

    4. Connect the collectors together in series. To do so,

    attach the connection pipe (10.1) to the appropriate

    collector connection. Insert the support sleeves (10.2) into

    the connecting pipes. Push the screw connection until it

    meets the collector connections. Tighten the nut by hand

    first, then tighten by one turn with the spanner. Push the

    previously pulled back insulation tube over the connection

    until it meets the collector frame.

  • 8/6/2019 SunMaxx TitanPower-AL2 Flush Mounting Instructions

    16/16

    SunMaxx M2 Flush Mounting Installation System 16

    INSTALLING THE SENSOR

    1. Carefully remove the plugs from the collector frame.

    2. Slide the plugs over the temperature sensor (included

    with the solar controller).

    3. Coat the temperature sensor with heat-conducting

    paste (included with the solar controller).

    4. Insert the temperature sensor fully into the immersion

    sleeve. Seal the collector frame with plugs. To do so, make

    sure that the plugs are positioned correctly.