stulz data c climatiseur entre cooling

Embed Size (px)

Citation preview

  • 8/10/2019 stulz data c climatiseur entre cooling

    1/26

    STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 1

  • 8/10/2019 stulz data c climatiseur entre cooling

    2/26

    STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 2

    1. INTRODUCTION

    2. AIR FLOW LEAKAGE3. PERFORATED TILES: NUMBER AND OPENING FACTOR

    4. PERFORATED TILES: WITH ADJUSTABLE DAMPER

    5. PERFORATED TILES: PLACEMENT

    6. CLOSE UNUSED UNITS IN THE RACKS WITH BLANKING PANELS TO

    AVOID AIRFLOW SHORT CIRCUIT INSIDE THE RACK

    7. AIRFLOW PHILOSOPHIES

    8. RAISED FLOOR HEIGHT

    9. RETURN AIR CONDITIONS

    10. CHILLED WATER SYSTEM WATER CONDITIONS

    11. STANDBY UNIT OPERATION

    12. USE CRAC UNITS WITH STATE-OF-THE-ART COMPRESSOR AND FAN

    TECHNOLOGY

  • 8/10/2019 stulz data c climatiseur entre cooling

    3/26

    STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 3

    1. Introduction

    This presentation summarises todays Best Practise for data-centre cooling

    systems.

    It will give you a rough overview about all concerned parts of the data-centre.

    This lis t is not exhaustive, but it will impart the most important matters how to

    design, build and run an as energy efficient as poss ible data-centre.

  • 8/10/2019 stulz data c climatiseur entre cooling

    4/26

    STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 4

    2. Airflow Leakage

    Airf low leakages (short air circuit) leads to dramatic inefficienciesdue to air ci rculation back to the CRAC unit w ithout taking heat from

    the computer equipment.

    Close all unwanted openings in the raised floor

    Close all unwanted openings below the racks

    Close all cable cut outs use cable sealings

    Al l gaps (near walls and CRAC units) have to be sealed

  • 8/10/2019 stulz data c climatiseur entre cooling

    5/26

    STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 5

    2. Airflow Leakage

    The target is to create an overpressure under the raised floor torealize an even air supply to all areas of the data-centre.

    This overpressure can only be achieved w ith an as low as possible

    amount of unwanted airflow leakage.

    A maximum loss of 2 6% of the total

    airflow of the data-centre is acceptable.

  • 8/10/2019 stulz data c climatiseur entre cooling

    6/26

    STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 6

    3. Perforated Tiles: Number and Opening Factor

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15Tile number

    Example (Data-centre):

    Design airflow: 50.000 m/h, ESP 20Pa

    Chosen ti le: airf low : 500m/h, 20Pa 100 tiles are required

    Actual aif low : 30.000 m/h,

    Tile number to be reduced to 60

    Only a raised floor with sufficient

    height and perforated tiles

    with limited openings allow an

    even air distribution !!!

    The number of perforated tiles must be in line with:

    A) the designb) the actual / real airflow

  • 8/10/2019 stulz data c climatiseur entre cooling

    7/26STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 7

    4. Perforated Tiles: With Adjustable Damper

    Perforated ti les with integral adjustable

    dampers can be used to avoid having to

    replace perforated tiles with sol id tiles.

    In this case the number of perforatedtiles can remain unchanged but all ti les

    need to be adjusted according to the

    actual requirements in the room.

    It is also possib le to work with different adjustments to vary the amount of

    air in different areas of the data-centre.

    In any case the static pressure under the raised floor has to be kept at the

    design level.

  • 8/10/2019 stulz data c climatiseur entre cooling

    8/26STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 8

    5. Perforated Tiles: Placement

    Perforated tiles should only be

    placed at posi tions, where cold

    air is really required to cool

    equipment.

    Do not place perforated tiles directly near the CRAC unit; a distance of minimum

    2m has to be kept. Perforated tiles near CRAC units can induce warm room air into

    the raised floor (negative airf low).

  • 8/10/2019 stulz data c climatiseur entre cooling

    9/26STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 9

    6. Close Unused Units in the Racks with Blanking Panels

    Recirculation of cooling air

    inside the rack leads to

    overheating of servers.

    Blanking panels installed

    in unused areas or slots of

    a rack eliminate a possib le

    internal recirculation of the

    hot air.

  • 8/10/2019 stulz data c climatiseur entre cooling

    10/26STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 10

    7. Airflow philosophies

    A) The old/traditional way:

    Uncontrolled placement ofperforated supply air tiles

    anywhere in the room

    Cold air is supplied in anuncontrolled way to the low

    density equipment

    Uncontrolled recirculation Supply and return air mixing

    takes place

    NOT RECOMMMENDEDANYMORE Very inefficient

  • 8/10/2019 stulz data c climatiseur entre cooling

    11/26STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 11

    7. Airflow philosophies

    B) Hot Aisle, Cold Aisle Concept:

    Hot/Cold AisleConcept

    Cold supply air distribution only in the cold aisles Warm return air only in the hot aisles Open tiles only in the cold aisle Risk of mixing cold and hot air is high This risk can be reduced by using suspended

    ceilings

  • 8/10/2019 stulz data c climatiseur entre cooling

    12/26STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 12

    7. Airflow philosophies

    C) Hot Aisle Containment:

    Hot Aisle

    Containment

    Hot Aisle between the racks will be covered on the top and the end ofrack rows Cold supply will be delivered into the room Open tiles only in the room Full separation between supply and return air The room itself will be at low temperature level

  • 8/10/2019 stulz data c climatiseur entre cooling

    13/26STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 13

    7. Airflow philosophies

    D) Cold Aisle Containment:

    Cold Aisle

    Containment

    Cold supply air distribution only in the cold aisles

    The cold aisle is separated from the hot aisle Warm return air only in the hot aisles Open tiles only in the cold aisle No risk of mixing cold and hot air The room itself will be at high temperatures

  • 8/10/2019 stulz data c climatiseur entre cooling

    14/26STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 14

    7. Airflow philosophies

    Debate: Hot aisle or cold aisle containment ???

    Keeps the hot air in a confined area.

    The room outside is cold.

    Servers are stable and can be operated

    for an extended period in case of loss

    of airflow.

    Hot Spots in the cold aisle disappear.

    Overall stabil ity can be increased.

    Disadavantage:

    CRACs have to be calculated carefully

    to deal with the high return air

    temperatures.

    Keeps the cold air in a confined area, no need

    to cool the entire space.

    Floor space around the cold aisle is warm.

    Disadvantages:

    Air balancing can be di ffi cult if CRACs are

    sequencing and the raised floor pressure ischanging.

    In case of power outage the cold ais le is

    exposed to high threat due to loss of airflow .

    Control of supply air temperature with DX-units

    only possible to a certain extend.

  • 8/10/2019 stulz data c climatiseur entre cooling

    15/26STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 15

    7. Airflow philosophies

    E) Room Supply, Direct Rack-Out Return Concept:

    Room supply,

    Ducted return air

    Cold supply air enters the rack through the room Open tiles only in the cold aisle Warm return air leaves the rack through a duct and suspended ceiling Full seperation of hot and cold air The room itself will be at low temperature level

  • 8/10/2019 stulz data c climatiseur entre cooling

    16/26

    STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 16

    7. Airflow philosophies

    F) Close Coupling of CRAC units and Racks on Supply and Return Side:

    Ducted Supply and

    Return Air Concept

    Cold supply air into ducts fitted to the supply air side of the racks Warm return air through ducts fitted to the exhaust side of the racks Open tiles only in the area of supply air ducts No risk of mixing cold and hot air

  • 8/10/2019 stulz data c climatiseur entre cooling

    17/26

    STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 17

    7. Airflow philosophies

    Summary:

    Target of all these various possibilities is the complete separation of warmreturn air and cold supply air

    This separation leads to an increased temperature difference betweenreturn and supply air temperature of the CRAC unit

    A high temperature difference increases the efficiency of the CRAC unitand therefore the efficiency of the data-centre in general

    What kind of separation can be used in a data-centre is depending on thesituation and used equipment

    The highest level of efficiency is reached if each m of circulating air takesthe design amount of heat from the IT-euipment

  • 8/10/2019 stulz data c climatiseur entre cooling

    18/26

    STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 18

    8. Raised floor height

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

    Tile number

    Rule of thumb:

    The higher, the better !

    The raised floor height has got a

    major influence on the efficiency

    of the whole data-centre !

    The required free height is

    depending on room size, heatdensity and number and position

    of instaled CRAC units.

    A certain obstacle free area is

    required for a proper supply of

    cold air to any area of the room !

  • 8/10/2019 stulz data c climatiseur entre cooling

    19/26

    STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 19

    The leading and most important temperatureis the air entering the IT equipment (server).

    According to the new ASHRAE environmental

    envelope supply air temperatures up to 27C

    are possible. That would lead to return air

    temperatures of approx. 37C.

    Please note: A low return air set-point does not

    cure problems with heat load. It is the other

    way around: The lower the return air set-point

    the lower the usable cooling capacity of the

    unit. Furthermore the operating costs are

    increasing.

    High return air temperatures and lower return

    air humidity do not change the content of

    water in the room. The risk of ESD is as low.

    8K

    35C

    27C

    9. Return Air Condit ions

  • 8/10/2019 stulz data c climatiseur entre cooling

    20/26

    STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 20

    Advantages of high return air temperatures:

    (1) CW-units: High return air temperatures are leading towards higher

    water temperatures (with same sensible cooling capacity). The

    starting temperature of the free-cooling is much higher.

    (2) CW-units: To get the same cooling capacity with high return airtemperatures and high water temperatures the airflow of the unit can

    be reduced. Lower airflow leads to lower fan power consumption and

    a lower noise level.

    (3) DX-units: Higher return air temperatures are leading towards higher

    evaporating pressure. With constant condensing pressure the delta

    between evaporating and condensation pressure is reduced. The

    compressor power consumption is decreasing. Furthermore the fan

    speed also can be reduced.

    But please be aware that too high evaporating pressure can damage

    the compressor.

    9. Return Air Condit ions

  • 8/10/2019 stulz data c climatiseur entre cooling

    21/26

    STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 21

    10. Chilled Water System Water Conditions

    Heat loads in data-centres are nearly allsensible cooling load with only a small latent

    cooling load due to fresh air ventilation.

    In accordance to the increased return air

    temperatures the chil led water temperatures

    can be increased as well.

    Chiller efficiency will be increased due to increased evaporating temperature.

    The higher the chil led water temperature the earlier the starting temperature

    of the chiller free-cooling.

    The balance between cool ing capacity of the CRAC unit and chiller efficiency

    has to be evaluated.

  • 8/10/2019 stulz data c climatiseur entre cooling

    22/26

    STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 22

    11. Standby Unit Operation

    Fan laws dictate that air volume is directly proportional to fan speed and that fan

    power is a cube of the fan speed.

    0%

    10%

    20%30%

    40%

    50%

    60%

    70%

    80%

    90%

    100%

    Airf low Absorbed Power

    0%

    10%

    20%

    30%

    40%

    50%

    60%

    70%

    80%

    90%

    100%

    Airf low Absorbed Power

    1/2

    Airflow 1/8

    Absorbed

    Power

  • 8/10/2019 stulz data c climatiseur entre cooling

    23/26

    STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 23

    4x ASD1900CW at 26C/40%

    Water 10/15C

    Standby

    4x 114,6 kW = 458,6 kW net sensible

    Airflow: 3x 39.000 m/h

    Fan power = 3x 12,6 kW = 37,8 kW

    Lpa,2m = 3x 71,6 dB(A) = 76,4 db(A)

    3x 146,8 kW = 440,4 kW net sensible

    Airflow: 4x 29.000 m/h

    Fan power = 4x 5,3 kW = 21,2 kW

    Lpa,2m = 4x 62,7 dB(A) = 68,7 db(A)

    => Energy savings:

    16,6 kW x 8760h x 0,13 = 18.904 /year @ 0,13 /kWh

    11. Standby Unit Operation

    Therefore, by running the stand-by CRACunit at reduced air volume the overall

    fan power is greatly reduced.

    Example:

  • 8/10/2019 stulz data c climatiseur entre cooling

    24/26

    STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 24

    4x 110,3 kW = 441,2 kW net sensible

    Reduction of fan power consumption

    Reduction of noise level

    Increase of net sensible cooling capacity And: even more energy can be saved if net sensible coolingcapacity is kept constant:

    Advantages of Standby-Management:

    Airflow: 4x 27.800 m/h

    Fan power = 4x 4,7 kW = 18,8 kW

    Lpa,2m = 4x 61,5 dB(A) = 67,5 db(A)

    => Energy savings:

    19,0 kW x 8760h x 0,13 = 21.637 /year @ 0,13 /kWh

    11. Standby Unit Operation

  • 8/10/2019 stulz data c climatiseur entre cooling

    25/26

    STULZ THE NATURAL CHOICE

    01/2010

    Best Practice - Data Centre Cooling 25

    12. Use CRAC Units with state-of-the-art Technology

    EC fan technology:

    Advantages:1. Lower power consumption due to better overall degree of efficiency

    2. No in-rush current, speed is ramped up, never draws more than full load amps

    3. Low vibrat ion reduced sound level

    4. Long maintanance free operation due to direct drive technology

    5. Scalable air flow easy adaptation on requirements on site

    http://../Pfleiderer/Lokale%20Einstellungen/Temporary%20Internet%20Files/OLK45/Copy%20of%20new09_2006_EC%20Fan%20Energy%20CCD2300CWE%20Final%20September05.xls
  • 8/10/2019 stulz data c climatiseur entre cooling

    26/26

    STULZ THE NATURAL CHOICE

    01/2010

    B t P ti D t C t C li

    Example:

    Munich airport data centre, source:

    600 m data centre, 75 server cabinets arranged in 3 rows

    5 CRAC units (4+1), each 32 kW cooling capaci ty

    Changes (Best practise only ):

    installation of hot aisle/cold aisle containment

    re-routing cables inside the racks

    reconfiguring of floor tile layout, sealing of raised floor

    installation of 1U blanking panels at the front of the racks installation of ventilated front doors

    increasing of room temperature to 28C (supply air = 22C)

    => Due to these changes the power consumption of the CRAC units are reduced by 35%.

    => Cabinet temperatures are reduced by 4C extended lifetime of servers and more reliabil ity.