Stucco Moisture Inspection Report
Property Address
123 Our Street
OurTown, USA 12345
Report Ordered By:
Mr. & Mrs. Client
TABLE OF CONTENTS
1. Introduction
1.1 Purpose of this inspection
1.2 Scope of this inspection
1.3 Limitations of Liability
1.4 Further Testing
1.5 Repair Follow-up and Annual Inspections
2. Your Moisture Inspection
-North, South, East and West Elevation Grid-Style Photos with potential
problem areas marked
-Summary
3. Typical Moisture Problems in Stucco Homes & Remedial Methods
3.1 Moisture Problems Related to Unsealed Stucco Penetrations
3.2 Moisture Problems Related to Doors & Windows
3.3 Moisture Problems Related to Improper Stucco Termination at Grade
3.4 Moisture Problems Related to Improper Kickout and Other Roof Flashings
3.5 Moisture Problems Related to Improper Deck, Balcony & Patio Terminations
3.6 Moisture Problems Related to Cracks and Breaches in the Stucco
3.7 Moisture Problems Related to Stucco Accents and Flat Stucco Surfaces
3.8 Moisture Problems Related to Chimneys
3.9 Moisture Problems Related to Gutters and Downspouts
3.10 Moisture Problems Related to Improper Transitions (Brick to Stucco, etc.)
4. Stucco Information, Care and Maintenance
4.1 Types of Stucco
-Exterior Insulation Finish Systems (EIFS)
-Traditional Hard Coat Stucco Systems
-Water Management or Drainable EIFS Systems
4.2 Is Stucco a Good Cladding System?
4.3 Care and Maintenance
5. Information About Our Company
12344 Mobile Highway � Good Street, FL 32000 � www.iamgoodinspector.com � [email protected]
888.888.8888 � 777.777.7777� FAX: 123.456.7890
1
I. INTRODUCTION
1.1 PURPOSE: Enclosed is your Stucco Moisture Inspection. The purpose of this moisture inspection
is to help assess the condition of the stucco system by looking for visible installation flaws, inadequate
water diversion and sealant failures and conduct random moisture readings using electronic moisture
scan devices. Please note that the provision of a scope of work for remedial repairs is not the purpose of
this inspection. Further investigation may be needed to determine the extent of water damage, if any,
and how best to modify your home to address any moisture problems that may be indicated by this
inspection.
1.2 SCOPE OF INSPECTION: This is a basic, stucco inspection limited to the following:
• A visual examination of the condition of the stucco, exterior sealants, flashing, windows,
doors, roof-to-stucco transitions, parapets, gutters, deck-to-building connections, stucco
terminations and any penetrations through the stucco.
• Conducting of random electronic moisture scanning of the building envelope.
• Preparing a report of our observations of potential problem areas and recording any high
readings found.
• Providing detailed information on typical moisture-related problems in stucco homes to
assist you in maintaining the value of your home.
1.3 LIMITATIONS OF LIABILITY: Because this is a limited inspection, we can make no
guarantee, express or implied, that our observations and random moisture readings offer conclusive
evidence that no installation or moisture problems exist, or that problems found are all-inclusive. This
inspection company, its employees and any divisions shall not be liable for non-visual defects, unseen
defects, unspecified defects or hidden damage and conditions existing on the subject property and
hereby disclaims any liability or responsibility thereof. All parties concerned agree to hold harmless and
indemnify this inspection company involving any liabilities that may result.
1.4 FURTHER TESTING / INVESTIGATION: Our policy is to rely on moisture meter readings as
an indicator of relative moisture values between different test spots, not as an absolute value of water
content in the substrate. It is difficult to determine if the structural wood of your home has been
damaged in areas of high readings without 'probing' and/or removing a core sample of the stucco to
allow for visual inspection. Should we feel that further investigation is needed this will be indicated in
the summary section of the report.
1.5 REPAIR FOLLOW-UP AND ANNUAL INSPECTIONS: A repair follow-up inspection should
be conducted within three months after completion of the repairs to assess the effectiveness of the
moisture modifications. This is extremely important. Annual inspections should also be scheduled to
ensure that your stucco system remains dry. This way any sealant failures, stucco cracks, etc. can be
caught and repaired promptly. Testing and maintaining your home on a regular basis is the best way to
prevent costly repairs associated with moisture damage. Also, should you decide to sell your home,
annual inspections and maintenance documentation will be a valuable selling tool, providing evidence to
show that your home has been inspected and maintained on a regular basis by a reputable and qualified
firm.
12344 Mobile Highway � Good Street, FL 32000 � www.iamgoodinspector.com � [email protected]
888.888.8888 � 777.777.7777� FAX: 123.456.7890
2
12344 Mobile Highway � Good Street, FL 32000 � www.iamgoodinspector.com � [email protected]
888.888.8888 � 777.777.7777� FAX: 123.456.7890
Project Information
OWNER INFORMATIONOWNER INFORMATION BUYER INFORMATIONBUYER INFORMATION
Owners Mr. & Mrs. Client Buyers Mr. & Mrs. Buyer
Property Address 123 Our Street Buyers Address 456 Old Street
City, State, ZIP OurTown, USA 12345 City, State, ZIP My Town, USA 54321
Phone 888-888-8888 Phone
Owner's Email Buyer's Email
Owners Realtor IB Realtor Buyers Realtor Mrs. Realtor
Realty Company Great Realty Inc. Realty Company Super Realty Inc
Phone 111-111-1111 Phone 222-222-2222
FAX FAX
Realtor's Email Realtor's Email
PROPERTY INFORMATIONPROPERTY INFORMATION INSPECTION INFORMATIONINSPECTION INFORMATION
Type of Exterior Hardcoat Stucco Date of Inspection December 14, 2005
Substrate (if known) Plywood Inspector IB Inspector
Age of Property 2000 Present at Inspection Owner
Square Footage 2200 Temperature/Humidity 65 Degrees 50%
Stories 1 Weather Conditions Partly cloudy
Type of Windows Vinyl Windows Last Rain Within last few weeks
Inspection Test EquipmentInspection Test EquipmentInspection Test EquipmentInspection Test EquipmentInspection Test EquipmentInspection Test Equipment
Test Equipment DescriptionTest Equipment Description Test RangeTest RangeTest Range Setting
Low Medium High
A Tramex Interior Moisture 10-14 15-19 > 19 2
B Tramex Exterior Wet Wall Detector 10 - 20 21-50 51-100 4.5
C Delmorst Moisture Probe Meter 10-14 15-19 > 19 1
D Structural Resistance Tester (SRT) >44 = Pass <44 = Fail Higher is betterHigher is better
NOTE: The test equipment is used to help locate problem areas. It must be understood that the test equipment is not an exact science but rather good tools used as indicators of possible problems. At times, because of hidden construction within the wall cavity, the meters get false readings or no readings at all. Some meters will pick up on metals, wiring, unique wall finishes, etc. Positive readings do not always mean there is a problem, nor do negative readings necessarily mean there is not a problem. We do not use the equipment to obtain exact moisture content, but rather to obtain relative readings between suspected problem areas and non problem areas.This information is then used to help determine potential problem areas which may warrant more investigation.
NOTE: The test equipment is used to help locate problem areas. It must be understood that the test equipment is not an exact science but rather good tools used as indicators of possible problems. At times, because of hidden construction within the wall cavity, the meters get false readings or no readings at all. Some meters will pick up on metals, wiring, unique wall finishes, etc. Positive readings do not always mean there is a problem, nor do negative readings necessarily mean there is not a problem. We do not use the equipment to obtain exact moisture content, but rather to obtain relative readings between suspected problem areas and non problem areas.This information is then used to help determine potential problem areas which may warrant more investigation.
NOTE: The test equipment is used to help locate problem areas. It must be understood that the test equipment is not an exact science but rather good tools used as indicators of possible problems. At times, because of hidden construction within the wall cavity, the meters get false readings or no readings at all. Some meters will pick up on metals, wiring, unique wall finishes, etc. Positive readings do not always mean there is a problem, nor do negative readings necessarily mean there is not a problem. We do not use the equipment to obtain exact moisture content, but rather to obtain relative readings between suspected problem areas and non problem areas.This information is then used to help determine potential problem areas which may warrant more investigation.
NOTE: The test equipment is used to help locate problem areas. It must be understood that the test equipment is not an exact science but rather good tools used as indicators of possible problems. At times, because of hidden construction within the wall cavity, the meters get false readings or no readings at all. Some meters will pick up on metals, wiring, unique wall finishes, etc. Positive readings do not always mean there is a problem, nor do negative readings necessarily mean there is not a problem. We do not use the equipment to obtain exact moisture content, but rather to obtain relative readings between suspected problem areas and non problem areas.This information is then used to help determine potential problem areas which may warrant more investigation.
NOTE: The test equipment is used to help locate problem areas. It must be understood that the test equipment is not an exact science but rather good tools used as indicators of possible problems. At times, because of hidden construction within the wall cavity, the meters get false readings or no readings at all. Some meters will pick up on metals, wiring, unique wall finishes, etc. Positive readings do not always mean there is a problem, nor do negative readings necessarily mean there is not a problem. We do not use the equipment to obtain exact moisture content, but rather to obtain relative readings between suspected problem areas and non problem areas.This information is then used to help determine potential problem areas which may warrant more investigation.
NOTE: The test equipment is used to help locate problem areas. It must be understood that the test equipment is not an exact science but rather good tools used as indicators of possible problems. At times, because of hidden construction within the wall cavity, the meters get false readings or no readings at all. Some meters will pick up on metals, wiring, unique wall finishes, etc. Positive readings do not always mean there is a problem, nor do negative readings necessarily mean there is not a problem. We do not use the equipment to obtain exact moisture content, but rather to obtain relative readings between suspected problem areas and non problem areas.This information is then used to help determine potential problem areas which may warrant more investigation.
3
12344 Mobile Highway � Good Street, FL 32000 � www.iamgoodinspector.com � [email protected]
888.888.8888 � 777.777.7777� FAX: 123.456.7890 4
General Observations
Item Description Yes No Improper Comments
Sealants at window perimeters X XInadequate, failed, or missing sealants-suggest that all
are resealed
Mitre joints (bottom corners) of X Vinyl Welded miters
Alarm sensor penetrations at windows xNot observed: Seal any alarm sensor penetration through
the window sills
Fixed window units and mullion joints X X Suggest to wet-glaze fixed units and mullion joints
Head flashing at top of windows X Common for this area.
Sealants around door perimeter X XSome Inadequate, failed, or missing sealants--suggest
resealing
Sealants at door threshold details X X Suggest sealing thresholds to casing where not present
Penetrations thru door threshold / tracks X N/A 1st floor doors
Head flashing at top of doors X Common for this area.
Penetrations through stucco sealed X
General appearance X Excellent general appearance
Cracking evident X X Few cracks noted--more may be present--see elev. Pages
Expansion joints / Control joints X
Exposed mesh X XFew areas noted where mesh is visible through finish on
bands
Impact damage X
Rusting aggregates X
Flat horizontal surfaces X
Delamination / Fasteners X No obvious visible evidence
Terminations and Vinyl accessories X Some vinyl accessories used
Transition joints (stucco to brick, etc.) X
Termination below grade (ground level) XSystem terminates below grade--hardcoat sys. (see
summary)
Termination below or at slab levels XSystem terminates below slab--hardcoat sys. (see
summary)
Deck flashing X N/A
Flashing at columns X Design requires no special flashing
Kick-out flashing
Roof soffit terminations into stucco X XAny soffit penetrations into stucco needs to be properly
sealed
Eave drip edge flashing X
Sprinkler System XRe-aim as needed to prevent wetting of the sills and rust
stains on the EIFS.
Gutters X Some gutters clean out
12344 Mobile Highway � Good Street, FL 32000 � www.iamgoodinspector.com � [email protected]
888.888.8888 � 777.777.7777� FAX: 123.456.7890 4-B
General Observations Cont.....
Scan and Probe Results
5
All Interior Random Scans were NORMAL
Scan and Probe Results
6
12344 Mobile Highway � Good Street, FL 32000 � www.iamgoodinspector.com � [email protected]
888.888.8888 � 777.777.7777� FAX: 123.456.7890 7
Item Item DescriptionApplies to
Entire BldgObservations / Comment
A Cracks No Exposed cracks on bands need to be caulked.
A Windows YesExisting sealant appears to be too thin or inadequate to prevent moisture intrusion, or may be the wrong type for this application.
B Doors Yes Seal perimeters of all doors including garage doors
C Roof Terminations Yes Seal all roof terminations with stucco.
D Utility No This utility breach location need to be caulked.
E Foam Insulation NoFoam insulation appears to extend below grade at the entry and needs to be modified to prevent insect infestations.
12344 Mobile Highway � Good Street, FL 32000 � www.iamgoodinspector.com � [email protected]
888.888.8888 � 777.777.7777� FAX: 123.456.7890
Detail Photos for page 7
8
7A 7A
7B 7C
7C
12344 Mobile Highway � Good Street, FL 32000 � www.iamgoodinspector.com � [email protected]
888.888.8888 � 777.777.7777� FAX: 123.456.7890 9
Item Item DescriptionApplies to
Entire BldgObservations / Comment
A Roof Terminations Yes Seal all roof terminations with stucco.
12344 Mobile Highway � Good Street, FL 32000 � www.iamgoodinspector.com � [email protected]
888.888.8888 � 777.777.7777� FAX: 123.456.7890
Detail Photos for page 9
10
9A
12344 Mobile Highway � Good Street, FL 32000 � www.iamgoodinspector.com � [email protected]
888.888.8888 � 777.777.7777� FAX: 123.456.7890 11
Item Item DescriptionApplies to
Entire BldgObservations / Comment
A GuttersGutter obstruction observed. Gutters need to be cleared of all leaves and debris.
Covered Area
12344 Mobile Highway � Good Street, FL 32000 � www.iamgoodinspector.com � [email protected]
888.888.8888 � 777.777.7777� FAX: 123.456.7890
Detail Photos for page 11
12
10A
12344 Mobile Highway � Good Street, FL 32000 � www.iamgoodinspector.com � [email protected]
888.888.8888 � 777.777.7777� FAX: 123.456.7890 13
Item Item DescriptionApplies to
Entire BldgObservations / Comment
A Finishes Yes Exposed mesh on several bands - suggest coat with elastomeric
B Cracks Yes Exposed cracks need to be caulked. Several bands noted with cracks.
C Doors YesThin / Inadequate sealants at door perimeters - suggest all are professionally resealed
12344 Mobile Highway � Good Street, FL 32000 � www.iamgoodinspector.com � [email protected]
888.888.8888 � 777.777.7777� FAX: 123.456.7890 14
Item Item DescriptionApplies to
Entire BldgObservations / Comment
A Finishes Yes Exposed mesh on several bands - suggest coat with elastomeric
B Cracks Yes Exposed cracks need to be caulked. Several bands noted with cracks.
C Doors YesThin sealants at some door perimeters. Suggest resal all as preventative measure
Detail Photos for page 13
14
13B
13C
Stucco Inspection Summary
This residence is a one story tile roofed residence clad with conventional concrete stucco (hardcoat)
or what appears to be wood sheathing. Random interior moisture scans showed normal readings
through-out the residence in scanned areas. A moisture probe was made below a few areas as shown on
the scan & probe pages which showed normal moisture readings and the substrate 'solid' to an ice pick
probe.
Overall the stucco inspection was good with the primary need being sealant maintenance. We suggest
that all of the windows / doors and all penetrations through the Stucco be professionally resealed using a
quality sealant such as 'Dow Corning' or Sonneborne 150 and that adequate sealant be used to give long
lasting protection. The casing to casing joints and mullion joints of double window units and all
elements of the fixed units should to be wet glazed as a preventative measure (see Cpt 3.1 & Cpt 3.2).
We also suggest that all alarm penetrations through the window sills (if any) be sealed.
Any minor cracks through the bands should also be sealed. There was some exposed mesh profile noted
on some bands. We suggest coating the bands with elastomeric after sealing any cracks.
There were areas of decorative foam trim which has been cut out of the grade (as it should) with the
exception of 1 area on the front elevation which still needs to be cut above the grade level. The exposed
foam on the cut bottom edge should be properly finished to protect the foam from the elements &
insects. Foam in the grade is primarily a termite concern.
See other report pages for additional suggestions / items.
There are no 'exact' industry level standards for Stucco repairs as yet. The above suggestions are based
on our experience with the systems and emerging repair practices. We make no warranty whatsoever for
the suggested repair methods. We recognize that there may be more than one way to effectively correct
the reported problems. Repair contractors should specify their proposed methods and any applicable
warranty.
Mr. I.B. InspectorJanuary 11, 2006