1MRK 580 022-BEN
Stub protection
Page 1
Issued: January 2001Status: NewData subject to change without notice
Features • Phase segregated current measurement • Activation from line disconnector position
Application The stub protection operates for faults in the parts of 1 1/2 and ring bus station configura-tions, which cannot be protected by the dis-tance protection function if the line isolators
are opened. The use of the function can be extended to various other purposes, when a three phase overcurrent protection can oper-ate only under special external conditions.
Design The function operates as a three phase instan-taneous overcurrent protection. The function is released when the line disconnector is open; a normally closed auxiliary contact of
the line disconnector has to be connected to the STUB-RELEASE functional input by configuration.
The operating level of the overcurrent protec-tion is settable over a wide range.
Function block
Input and output signals
Table 1: Input signals for the STUB (STUB-) function block
Table 2: Output signals for the STUB (STUB-) function block
Technical data Table 3: STUB - Stub protection
xx00000199.vsd
STUB-STUB
BLOCKRELEASE
TRIP
Signal Description
BLOCK Block of stub protection
RELEASE Release of stub protection
Signal Description
TRIP Trip by stub protection
Function Setting range Accuracy
Operate current I> (20-300) % of Ir +/- 2.5 % of Ir at I ≤Ir +/- 2.5 % of I at I > Ir
Stub protection STUB1MRK 580 022-BEN
Page 2
ManufacturerABB Automation Products AB
Substation Automation Division