STO uPVC VENTED ADJUSTABLE FOOT TRAY SCALE 1:5 6mm OVERHANG RECOMMENDED TO AVOID VARIANCES IN FOUNDATION TIMBER FRAMING TO NZS 3604 DPC INTERIOR LINING 225mm MIN. TO UNPAVED GROUND LEVEL 50mm clad. 150mm MIN. TO PAVED GL WALL UNDERLAY STOTHERM RENDER SYSTEM CAVITY SPACERS TO SUIT FIXINGS AS PER NZS 3604 STOTHERM PANEL FIXING 6 STO RENDER SYSTEM ON FOUNDATION CONCRETE SLAB/REINFORCING AS PER NZS 3604 OR ENGINEER SPECIFIC DESIGN - NOT SHOWN FOR CLARITY DPM INSULATION AS PER NZBC H1/AS1 100mm MIN. Sto Plaster 50mm Flexyl STOTHERM 20mm VH CAVITY BATTENS STOTHERM PANEL The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site. STOTHERM SYSTEM STOTHERM INSULATED FACADE SYSTEM FOUNDATION SLAB-ON-GROUND ST 200 2017

STOTHERM INSULATED FACADE SYSTEM FOUNDATION SLAB … · 1.concrete slab/reinforcing as per nzs 3604, specific design or engineer (sed) reinforcing not shown for clarity 2.where insulation

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: STOTHERM INSULATED FACADE SYSTEM FOUNDATION SLAB … · 1.concrete slab/reinforcing as per nzs 3604, specific design or engineer (sed) reinforcing not shown for clarity 2.where insulation

STO uPVC VENTED

ADJUSTABLE FOOT TRAY

SCALE 1:5

6mm OVERHANG

RECOMMENDED TO

AVOID VARIANCES IN

FOUNDATION

TIMBER FRAMING

TO NZS 3604

DPC

INTERIOR LINING

225m

m M

IN

.

TO

U

NP

AV

ED

G

RO

UN

D LE

VE

L

50m

m

clad.

150m

m M

IN

.

TO

P

AV

ED

G

L

WALL UNDERLAY

STOTHERM RENDER SYSTEM

CAVITY SPACERS TO SUIT

FIXINGS

AS PER NZS 3604

STOTHERM PANEL

FIXING

6

STO RENDER SYSTEM

ON FOUNDATION

CONCRETE SLAB/REINFORCING

AS PER NZS 3604 OR ENGINEER

SPECIFIC DESIGN - NOT SHOWN

FOR CLARITY

DPM

INSULATION

AS PER NZBC

H1/AS1

100m

m M

IN

.

Sto P

laster

50m

m

Flexyl

STOTHERM 20mm VH

CAVITY BATTENS

STOTHERM PANEL

The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered

Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to

alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure

they have and use the current Sto details and specifications on site.

STOTHERM

SYSTEM

STOTHERM INSULATED FACADE SYSTEM

FOUNDATION SLAB-ON-GROUND

ST 200

2017

Page 2: STOTHERM INSULATED FACADE SYSTEM FOUNDATION SLAB … · 1.concrete slab/reinforcing as per nzs 3604, specific design or engineer (sed) reinforcing not shown for clarity 2.where insulation

SCALE 1:5

5mm MIN GAP

STO uPVC VENTED BASE CAP

6mm OVERHANG

RECOMMENDED TO AVOID

VARIANCES IN FOUNDATION

TIMBER FRAMING

TO NZS 3604

DPC

225m

m M

IN

.

TO

U

NP

AV

ED

G

RO

UN

D LE

VE

L

150m

m M

IN

.

TO

P

AV

ED

G

L

WALL UNDERLAY

STOTHERM 20mm VH CAVITY

BATTENS

STOTHERM RENDER SYSTEM

STOTHERM PANEL FIXING

CAVITY SPACERS TO SUIT FIXINGS

AS PER NZS 3604

5

STOTHERM PANEL

STO FLEXYL WATERPROOFING

TO REBATE

INSULATED FOUNDATION WITH

STOTHERM RENDER SYSTEM ON

STOFLEXYL WATERPROOFING

CONCRETE SLAB/REINFORCING

AS PER NZS 3604 OR ENGINEER

SPECIFIC DESIGN - NOT SHOWN

FOR CLARITY

DPM

INSULATION AS

PER NZBC -

Clause H1

100m

m M

IN

.

Sto R

ender

50m

m

Clad.

The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered

Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to

alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure

they have and use the current Sto details and specifications on site.

STOTHERM

SYSTEM

STOTHERM INSULATED FACADE SYSTEM

INSULATED SLAB-ON-GROUND

ST 201

2017

Page 3: STOTHERM INSULATED FACADE SYSTEM FOUNDATION SLAB … · 1.concrete slab/reinforcing as per nzs 3604, specific design or engineer (sed) reinforcing not shown for clarity 2.where insulation

SCALE 1:5

TIMBER FRAMING

TO NZS 3604

DPC

STO RENDER SYSTEM

INTERNAL LINING

DPM

AS PER NZS 3604

75mm

rebate

BUILDING UNDERLAY

20mm DRAINED CAVITY

STOTHERM PANEL

STO FLEXYL OR LIQUID DPM ON

REBATE

STO uPVC CONTROL JOINT OR

FINISHING EDGE AT JUNCTION

TO FOUNDATION

WEATHER PROTECTED VENTS

TO ACHIEVE MIN. VENTILATION

OF 1000mm²/LINEAL METER

POSITIONED HARD ON REBATE

10

INSULATION TO EXTERIOR

WALLS

CONCRETE SLAB/REINFORCING

AS PER NZS 3604 OR ENGINEER

SPECIFIC DESIGN - NOT SHOWN

FOR CLARITY

STOTHERM PANEL

FIXING

INSULATION AS

NZBC H1/AS1

100m

m M

IN

.

Sto R

ender

50m

m

flexyl

50m

m

Clad.

100m

m

to paving

STOTHERM RENDER

SYSTEM

STO uPVC END CAP

The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered

Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to

alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure

they have and use the current Sto details and specifications on site.

STOTHERM

SYSTEM

STOTHERM INSULATED FACADE SYSTEM

REBATED SLAB-ON-GROUND - RENDERED FINISH

ST 202

2017

Page 4: STOTHERM INSULATED FACADE SYSTEM FOUNDATION SLAB … · 1.concrete slab/reinforcing as per nzs 3604, specific design or engineer (sed) reinforcing not shown for clarity 2.where insulation

SCALE 1:5

50m

m

cladding

150m

m to paving

225m

m unpaved G

L

DPC

GL

WALL UNDERLAY

STOTHERM PANEL

FIXING

STOTHERM PANEL

STO uPVC VENTED

BASE CAP

STOTHERM 20mm VH

CAVITY BATTENS

STOTHERM RENDER

SYSTEM

CAVITY SPACERS TO

SUIT FIXINGS

RIBRAFT POLYSTYRENE POD

INSTALLATION IN ACCORDANCE TO FIRTH

RIBRAFT CONSTRUCTION DETAILS

85

220

CONCRETE SLAB/REINFORCING

AS PER NZS 3604, SPECIFIC

DESIGN OR ENGINEER (SED)

Reinforcing not shown for clarity

300

The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered

Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to

alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure

they have and use the current Sto details and specifications on site.

STOTHERM

SYSTEM

STOTHERM INSULATED FACADE SYSTEM

RIBRAFT FLOOR SYSTEM / EDGE DETAIL

ST 203

2017

Page 5: STOTHERM INSULATED FACADE SYSTEM FOUNDATION SLAB … · 1.concrete slab/reinforcing as per nzs 3604, specific design or engineer (sed) reinforcing not shown for clarity 2.where insulation

225m

m unpaved G

L

SCALE 1:5

CONCRETE FOOTING AS

PER NZS 3604 OR ENGINEER

SPECIFIC DESIGN

CONCRETE SLAB/REINFORCING

AS PER NZS 3604 OR ENGINEER

SPECIFIC DESIGN

DPC

NOTE:

SHELL OF BLOCK CAN SUPPORT

BOTTOM PLATE WHEN SLAB IS

TIED TO FOUNDATION

50m

m

cladding

150m

m to paved

GL

INSULATION AS PER

NZBC - Clause H1

DPM

STO uPVC VENTED

BASE CAP

WALL UNDERLAY

STOTHERM 20mm VH

CAVITY BATTENS

STOTHERM RENDER

SYSTEM

STOTHERM PANEL

FIXING

STOTHERM PANEL

CAVITY SPACERS TO

SUIT FIXINGS

The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered

Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to

alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure

they have and use the current Sto details and specifications on site.

STOTHERM

SYSTEM

STOTHERM INSULATED FACADE SYSTEM

CONC.BLOCK FOUNDATION EDGE DETAIL

ST 204

2017

Page 6: STOTHERM INSULATED FACADE SYSTEM FOUNDATION SLAB … · 1.concrete slab/reinforcing as per nzs 3604, specific design or engineer (sed) reinforcing not shown for clarity 2.where insulation

SCALE 1:5

CONCRETE FOOTING AS

PER NZS 3604 OR ENGINEER

SPECIFIC DESIGN

DPM REQUIRED ON

FOUNDATION FOR POORLY

DRAINED SITES OTHERWISE

TERMINATE AT BOTTOM

EXTERNAL CORNER OF

FOUNDATION

CONCRETE SLAB/REINFORCING

AS PER NZS 3604 OR ENGINEER

SPECIFIC DESIGN

DPC

NOTE:

INSTALL STOFLEXYL UNDER DPM AT TRANSITION IF REQUIRED FOR POORLY

DRAINED SITES.

STO uPVC VENTED BASE

CAP - 5mm MIN.GAP

WALL UNDERLAY

STOTHERM 20mm VH

CAVITY BATTENS

STOTHERM RENDER

SYSTEM

STOTHERM PANEL

FIXING

STOTHERM PANEL

CAVITY SPACERS TO

SUIT FIXINGS

DPM

INSULATION AS PER

NZBC - Clause H1

STOFLEXYL WATERPROOFING

TO REBATE, CONTINUE TO

50mm PAST STO RENDER

TERMINATION POINT

100m

m

Sto R

ender

50m

m

Flexyl

50m

m

cladding

150m

m

TO

P

AV

ED

G

L

225m

m

TO

U

NP

AV

ED

G

RO

UN

D LE

VE

L

The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered

Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to

alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure

they have and use the current Sto details and specifications on site.

STOTHERM

SYSTEM

STOTHERM INSULATED FACADE SYSTEM

EPS BLOCK FOUNDATION DETAIL

ST 205

2017

Page 7: STOTHERM INSULATED FACADE SYSTEM FOUNDATION SLAB … · 1.concrete slab/reinforcing as per nzs 3604, specific design or engineer (sed) reinforcing not shown for clarity 2.where insulation

SCALE 1:5

50m

m

cladding

150m

m to paved

225m

m unpaved G

L

INSULATION AS PER

NZBC - Clause H1

DPM

DPC

10mm INSULATION

IF REQUIRED

GL

CONCRETE SLAB/REINFORCING

AS PER NZS 3604 OR SPECIFIC

ENGINEER DESIGN (SED)

Varies

refer to N

ZS

3604 or S

ED

WALL UNDERLAY

STOTHERM PANEL FIXING

STOTHERM PANEL

STO uPVC VENTED

BASE CAP

STOTHERM 20mm VH

CAVITY BATTENS

STOTHERM RENDER

SYSTEM

CAVITY SPACERS TO

SUIT FIXINGS

The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered

Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to

alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure

they have and use the current Sto details and specifications on site.

STOTHERM

SYSTEM

STOTHERM INSULATED FACADE SYSTEM

SOLID CONC.FOUNDATION EDGE DETAIL

ST 206

2017

Page 8: STOTHERM INSULATED FACADE SYSTEM FOUNDATION SLAB … · 1.concrete slab/reinforcing as per nzs 3604, specific design or engineer (sed) reinforcing not shown for clarity 2.where insulation

SCALE 1:5

TIMBER FRAMING/STUCTURE

TO NZS 3604

DPC

STO uPVC VENTED

ADJUSTABLE FOOT TRAY

SELECTED

FLOORING

50

NOTE:

1. CONTINUOUS PERIMETER FOUNDATION

WALL WITH VENTILATION OPENINGS

2. CLEARANCE BETWEEN CLADDING AND

ADJACENT GROUND - REFER NZS3604

SED - Specific Engineer Design

100mm DRAPE TO DBL SIDED

PERFORATED FOIL INSUL.R = 0.9

- REFER NZBC - Clause H1

as per N

ZS

3604

or S

ED

as per N

ZS

3604

or S

ED

CGL

FGL

as per NZS3604

MA

X.H

EIG

HT

- N

ZS

3604 6.11.2

MIN

.H

EIG

HT

6.11.2

WALL UNDERLAY

STOTHERM 20mm VH CAVITY

BATTENS

STOTHERM RENDER SYSTEM

STOTHERM PANEL

FIXING

STOTHERM PANEL

The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered

Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to

alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure

they have and use the current Sto details and specifications on site.

STOTHERM

SYSTEM

STOTHERM INSULATED FACADE SYSTEM

CONC.CONTINOUS PERIMETER FOUND.WALL

ST 207

2017

Page 9: STOTHERM INSULATED FACADE SYSTEM FOUNDATION SLAB … · 1.concrete slab/reinforcing as per nzs 3604, specific design or engineer (sed) reinforcing not shown for clarity 2.where insulation

DPC

WALL UNDERLAY

STOTHERM PANEL FIXING

STOTHERM PANEL

STO uPVC VENTED BASE CAP

20mm DRAINED CAVITY

STOTHERM RENDER

SYSTEM

CAVITY SPACERS TO SUIT

FIXINGS

1. CONCRETE SLAB/REINFORCING AS PER NZS 3604, SPECIFIC DESIGN OR

ENGINEER (SED)

Reinforcing not shown for clarity

2. WHERE INSULATION OS BELOW GROUND, APPLY TWO (2) COATS OF

STOFLEXYL TO MAXRAFT INSULATION BEFORE COMMENCING

3. 150mm MIN. CLEARANCE FROM SLAB LEVEL TO EXTERIOR PAVING,

225mm MIN. CLEARANCE FROM SLAB LEVEL TO UNPAVED GROUND TO

E2/AS1

4. AS REQUIRED, SECURE THE DPM TO THE MAXRAFT EDGE INSULATION

USING AN EIFS FLASHING TAPE 50mm ON MAXRAFT AND 100MM ONTO

UNDERSLAB DPM

SOLID COMPACTION 800mm

MIN.PAST EDGE OF

FOUNDATION

100

100

50

250

50

10

450

STOMULTI SCREED MESHED

BASECOAT FINISHED IN

1.0mm FLOAT or STOLIT K

FINISHING RENDER,

PAINTED IN STOCOLOR

MAXICRYL

SCALE 1:10

DPM REFER NOTE 4

The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered

Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to

alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure

they have and use the current Sto details and specifications on site.

STOTHERM

SYSTEM

STOTHERM INSULATED FACADE SYSTEM

MAXRAFT FLOOR SYSTEM / EDGE DETAIL

ST 208

2017

Page 10: STOTHERM INSULATED FACADE SYSTEM FOUNDATION SLAB … · 1.concrete slab/reinforcing as per nzs 3604, specific design or engineer (sed) reinforcing not shown for clarity 2.where insulation

MIN. H1.2 TREATED

FLOOR JOISTS

20

20

50

100mm DRAPE TO

DOUBLE-SIDED PERFORATED

FOIL INSULATION R = 0.9 -

REFER NZBC - Clause H1

2/NAIL LAMINATED FLOOR JOISTS

UNDER LOAD BEARING WALLS

STO uPVC VENTED

ADJUSTABLE FOOT TRAY

WALL UNDERLAY

STOTHERM 20mm VH CAVITY

BATTENS

STOPOREN RENDER SYSTEM

STOTHERM PANEL

FIXING

STOTHERM PANEL

H4 TREATED BASEBOARDS

WITH 20mm CONTINUOUS SUB

FLOOR VENTILATION GAP

BETWEEN

H3.2 TREATED BEARER, H5

TREATED PILE - REFER NZS 3604

FOR TIMBER & PILE SETOUT

STOTHERM PANEL

FIXING

NOTE:

FOR CLEARANCE BETWEEN

CLADDING AND ADJACENT GROUND

- REFER NZS3604

SCALE 1:5

STOTHERM RENDER

SYSTEM

The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered

Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to

alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure

they have and use the current Sto details and specifications on site.

STOTHERM

SYSTEM

STOTHERM INSULATED FACADE SYSTEM

TIMBER PILE/SUBFLOOR VENTILATION (Parallel Wall)

ST 209

2017

Page 11: STOTHERM INSULATED FACADE SYSTEM FOUNDATION SLAB … · 1.concrete slab/reinforcing as per nzs 3604, specific design or engineer (sed) reinforcing not shown for clarity 2.where insulation

50

100mm DRAPE TO

DOUBLE-SIDED PERFORATED

FOIL INSULATION R = 0.9 -

REFER NZBC - Clause H1

MIN. H1.2 TREATED

FLOOR JOISTS

TRIMMER JOIST

20

20

H4 TREATED BASEBOARDS

WITH 20mm CONTINUOUS SUB

FLOOR VENTILATION GAP

BETWEEN

SELECTED FLOORING

TIMBER FRAMING

TO NZS 3604

WALL UNDERLAY

STOTHERM 20mm VH CAVITY

BATTENS

STOTHERM RENDER SYSTEM

STOTHERM PANEL

FIXING

STOTHERM PANEL

STO uPVC VENTED

ADJUSTABLE FOOT TRAY

H5 TREATED PILE - REFER

NZS 3604 FOR TIMBER & PILE

SET OUT

SCALE 1:5

STOTHERM PANEL

FIXING

NOTE:

FOR CLEARANCE BETWEEN

CLADDING AND ADJACENT

GROUND - REFER NZS3604

The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered

Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to

alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure

they have and use the current Sto details and specifications on site.

STOTHERM

SYSTEM

STOTHERM INSULATED FACADE SYSTEM

TIMBER PILE/SUBFLOOR VENTILATION (Right Angled Wall)

ST 210

2017

Page 12: STOTHERM INSULATED FACADE SYSTEM FOUNDATION SLAB … · 1.concrete slab/reinforcing as per nzs 3604, specific design or engineer (sed) reinforcing not shown for clarity 2.where insulation

SCALE 1:5

OVERHANG TRIMMER JOIST

TO ALLOW CLADDING TO LAP

SUBFLOOR CLADDING

100mm DRAPE TO

DOUBLE-SIDED PERFORATED

FOIL INSULATION R = 0.9 -

REFER NZBC - Clause H1

JACK FRAMING IN AS PER

NZS3604 6.10.2

DPC

WALL UNDERLAY

STOTHERM 20mm VH CAVITY

BATTENS

STOTHERM RENDER SYSTEM

STOTHERM PANEL

STO uPVC VENTED

ADJUSTABLE FOOT TRAY

PROVIDE SHEET BRACING

MATERIAL and VENTILATION AS PER

NZS 3604

STOTHERM PANEL

FIXING

STOTHERM PANEL

FIXING

NOTE:

FOR CLEARANCE BETWEEN

CLADDING AND ADJACENT

GROUND - REFER NZS3604

The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered

Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to

alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure

they have and use the current Sto details and specifications on site.

STOTHERM

SYSTEM

STOTHERM INSULATED FACADE SYSTEM

TIMBER SUBFLOOR WITH JACK STUDS

ST 211

2017

Page 13: STOTHERM INSULATED FACADE SYSTEM FOUNDATION SLAB … · 1.concrete slab/reinforcing as per nzs 3604, specific design or engineer (sed) reinforcing not shown for clarity 2.where insulation

SCALE 1:10

STO FLEXYL MESHED WATERPROOFING

FROM 150mm ABOVE GROUND AND

DOWN OVER COMPRESSION BAR

SLAB-ON-GROUND FLOOR & CONC.MASONRY WALLS AS PER NZS

4210/4229/4230 & AND ENGINEERS DRAWINGS

ALLOW ADEQUATE TIME FOR BLOCK TO DRY/STABALISE BEFORE

PLASTERING NORMALLY FROM 4-8 WEEKS IN AVERAGE DRYING

CONDITIONS.

STOARMAT RENDER SYSTEM

TIMBER FRAMING

TO NZS 3604

50m

m

DPC

SELECTED

INTERIOR LINING

CONCRETE FLOOR SLAB,

FOOTING & WALL TO SPECIFIC

DESIGN

SELECTED INTERIOR

RENDER/FINISH

FILTER FABRIC

SLOTTED DRAIN LAID

TO A FALL

WALL UNDERLAY

NOMINAL 20x45mm H3.1 TIMBER

CAVITY BATTENS

STOTHERM PANEL FIXING

STOTHERM PANEL

STOTHERM RENDER SYSTEM

STO uPVC VENTED

ADJUSTABLE FOOT TRAY

NOTE:

FOR CLEARANCE BETWEEN

CLADDING AND ADJACENT

GROUND - REFER NZS3604:2011

TANKING SEALANT

COMPRESSION BAR MECHANICALLY

FIXED TO CONC.BLOCK. TRANSITION

APPROX 100mm BELOW GROUND

GRANDULAR FILL RECOMMENDED

SELECTED BITUMOUS PEEL &

STICK TANKING MEMBRANE WITH

PROTECTION MATERIAL

INSULATE BLOCKWORK IF

NEEDED

The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered

Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to

alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure

they have and use the current Sto details and specifications on site.

STOTHERM

SYSTEM

STOTHERM INSULATED FACADE SYSTEM

MASONRY CONC.BLOCK IN-GROUND WALL

ST 212

2017

Page 14: STOTHERM INSULATED FACADE SYSTEM FOUNDATION SLAB … · 1.concrete slab/reinforcing as per nzs 3604, specific design or engineer (sed) reinforcing not shown for clarity 2.where insulation

SCALE 1:2

STOFLEXYL WATERPROOFING TO

CONCRETE REBATE SURFACES AND

RENDER INTO REBATE

STOARMAT RENDER SYSTEM

TIMBER FRAMING

TO NZS 3604

DPC

NOTE:

CUT SLOPE AT 15° OR CUT

REBATE AND PLASTER 15°

SLOPE IN.

WALL UNDERLAY

STOTHERM 20mm VH CAVITY

BATTENS

STOTHERM RENDER SYSTEM

STOTHERM PANEL FIXING

STOTHERM PANEL

STO uPVC VENTED BASE

CAP

50m

m

REINFORCED CONCRETE BLOCK

WALLS IN ACCORDANCE WITH NZS

4230, 4229, 4218 & 4210

The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered

Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to

alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure

they have and use the current Sto details and specifications on site.

STOTHERM

SYSTEM

STOTHERM INSULATED FACADE SYSTEM

CONCRETE BLOCK INTER-STOREY DRAINED JUNCTION

ST 213