31
StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated Glazing - Single and Twin Span (Drawing numbers ie V8242 used as CAD detail reference only ) Table of Contents TM ELEV-StrMax-HR-250-Sgl-Span ELEV-StrMax-HR-250-Twin-Span H8141-Head-at-Sgl-Span H8141T-Head-at-Twin-Span H8142-Horizontal. H8143-Sill-at-Sgl-Span H8144-Horizontal. H8145-Single-Spn-Hd-Sill-Anchor H8146-Twin-Spn-Hd-Sill-Anchor H8147-90-OSC-Hd-Sill-Anchor H8148-Mull-Jamb-Splice H8149-Corner-Mull-Splice H8150-Mull-Splice-SSG H8151-Stl-Anchor-Jb-Mull H8152-Stl-Anchor-90-Crnr V8141-Jamb V8142-Jamb-w-AnchorBolt V8143-Jamb-w-Steel V8144-Jamb-2Pc-w-AnchBolt V8145-Jamb-2pc-w-AnchBolt V8146-Jamb-2Pc-w-Steel V8148-Vertical-Typical V8149-Vertical-Typ-w-Steel1 V8150-Vertical-Typ-w-Steel2 V8151-Vertical-Typ-w-Steel3 V8152-Vertical-Heavy V8153-90-Outside-Corner V8154-SSG-90-Outside-Corner V8157-SSG-Vertical V8158-SSG-Vertical-w-Steel

StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated Glazing - Single and Twin Span

(Drawing numbers ie V8242 used as CAD detail reference only )Table of Contents

TM

ELEV-StrMax-HR-250-Sgl-SpanELEV-StrMax-HR-250-Twin-SpanH8141-Head-at-Sgl-SpanH8141T-Head-at-Twin-SpanH8142-Horizontal.H8143-Sill-at-Sgl-SpanH8144-Horizontal.H8145-Single-Spn-Hd-Sill-AnchorH8146-Twin-Spn-Hd-Sill-AnchorH8147-90-OSC-Hd-Sill-AnchorH8148-Mull-Jamb-SpliceH8149-Corner-Mull-SpliceH8150-Mull-Splice-SSGH8151-Stl-Anchor-Jb-MullH8152-Stl-Anchor-90-Crnr

V8141-JambV8142-Jamb-w-AnchorBoltV8143-Jamb-w-SteelV8144-Jamb-2Pc-w-AnchBoltV8145-Jamb-2pc-w-AnchBoltV8146-Jamb-2Pc-w-SteelV8148-Vertical-TypicalV8149-Vertical-Typ-w-Steel1V8150-Vertical-Typ-w-Steel2V8151-Vertical-Typ-w-Steel3V8152-Vertical-HeavyV8153-90-Outside-CornerV8154-SSG-90-Outside-CornerV8157-SSG-VerticalV8158-SSG-Vertical-w-Steel

Page 2: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

MONOLITHIC LAMINATED GLAZING StormMax - 2 1/2" X 6 3/4" HURRICANE RESISTANT CURTAIN WALL

MODEL: Elev-StormMax-HR-250-SGL

NOTE: FOR SPECIFIC PRODUCT APPLICATIONS CONTACT ANOLDCASTLE BUILDING ENVELOPE REPRESENTATIVE™

H8145

HORIZ

SILLH8143

H8142H8144

V8149V8150

V8148

V8152

V8142V8144V8145V8146

Single Span

WET GLAZED SHOWN - DRY GLAZED OPTIONAL

H8145

V815390 OSC

H8145

H8145

HEADH8141

V8157V815490 OSC

V8158

SSG VerticalsWET GLAZED ONLY

V8141

H8145

H8145

Page 3: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

StormMax - 2 1/2" X 6 3/4" HURRICANE RESISTANT CURTAIN WALL

NOTE: FOR SPECIFIC PRODUCT APPLICATIONS CONTACT ANOLDCASTLE BUILDING ENVELOPE REPRESENTATIVE™

H8146

H8146

SILL

H8148V8149V8151

ANCHORH8151

HEAD

V815390 OSC

H8142H8144

V8143V8144V8145V8146

Twin Span

WET GLAZED SHOWN - DRY GLAZED OPTIONAL

H8146

H8146

MODEL: Elev-StormMax-HR-250-Twn

H8141T

H8143

V8157V815490 OSC

V8158

SSG VerticalsWET GLAZED ONLY

SPLICEH8149

CORNER

H8147

H8147

H8152CORNER

HORIZONTAL

MONOLITHIC LAMINATED GLAZING

H8150SSG

H8146H8147

H8147 H8146

Page 4: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

CW-1998 TRIMCW-1997 HEAD

CW-17 EXTERIOR GASKET

CW-2 FACE CAP & ZG-60 PRESSURE PLATE

ATTACH WITH FS-322 #12-14 X 1" HWH "TEK"W/SHOP INSTALLED CW-6 ISOLATOR. FIELD

STRUCTURAL SILICONE SEALANT (BY OTHERS)W/FG-5185 SPACER GASKET

SHIMS (BY OTHERS)BACKER ROD & SEALANT

HR-FP-1 MULL CAP

Head - H8141StormMax HR-250 - Wet GlazedTM

D.L

.O.

2 1/

2"1/

2"

CW-187 SPACER

SEAL TOP OF MULL AND FACE CAP BEYOND

ANCHOR BOLT (BY OTHERS)

6 3/4"

MONOLITHIC LAMINATED GLASS CW-2338 INTERIOR GASKETCW-2337 EXTERIOR GASKET

Dry Glazed Option

(BY OTHERS)

Page 5: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

CW-1998 TRIMCW-1997 HEAD

CW-17 EXTERIOR GASKET

CW-2 FACE CAP & ZG-60 PRESSURE PLATE

ATTACH WITH FS-322 #12-14 X 1" HWH "TEK"W/SHOP INSTALLED CW-6 ISOLATOR. FIELD

STRUCTURAL SILICONE SEALANT (BY OTHERS)W/FG-5185 SPACER GASKET

ANCHOR AT VERTICALS

HR-FP-1 MULL CAP

Head-at-Twin Span - H8141TStormMax HR-250 - Wet GlazedTM

D.L

.O.

2 1/

2"3/

4"

CW-187 SPACER

6 3/4"

MONOLITHIC LAMINATED GLASS CW-2338 INTERIOR GASKETCW-2337 EXTERIOR GASKET

Dry Glazed Option

ACCESS HOLES

BACKER ROD & SEALANT SEAL TOP OF MULL

AND FACE CAP BEYOND(BY OTHERS)

Page 6: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

Horizontal - H8142

6 3/4"

StormMax HR-250 - Wet Glazed

REF TOP VIEW

ON CW-2101 SETTING BLOCKS

TM

FOR WATER DIVERTER INFO.CW-2117

CW-1998MONOLITHIC LAMINATED GLASS

W/SHOP INSTALLED CW-6 ISOLATOR. FIELDATTACH WITH FS-322 #12-14 X 1" HWH "TEK"

CW-2 FACE CAP & ZG-60 PRESSURE PLATE

2 1/

2"

CW-17 EXTERIOR GASKETW/FG-5185 SPACER GASKET

STRUCTURAL SILICONE SEALANT (BY OTHERS)

CW-2338 INTERIOR GASKETCW-2337 EXTERIOR GASKET

Dry Glazed Option

Page 7: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

Sill-at-Single-Span - H8143StormMax HR-250 - Wet Glazed

6 3/4"

HR-FP-1 MULLION CAP

BACKER ROD & SEALANT(BY OTHERS)

TM

ANCHOR BOLT

CW-187 SPACER

CW-1997 SILL

SHIMS (BY OTHERS)

CW-1998 TRIM

W/SHOP INSTALLED CW-6 ISOLATOR. FIELDATTACH WITH FS-322 #12-14 X 1" HWH "TEK"

CW-2 FACE CAP & ZG-60 PRESSURE PLATE

2 1/

2"

STRUCTURAL SILICONE SEALANT (BY OTHERS)W/FG-5185 SPACER GASKET

CW-17 EXTERIOR GASKET

MONOLITHIC LAMINATED GLASS

(BY OTHERS)

ON CW-2101 SETTING BLOCK

CW-2338 INTERIOR GASKETCW-2337 EXTERIOR GASKET

Dry Glazed Option

Page 8: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

Horizontal - H8144

6 3/4"

StormMax HR-250 - Wet Glazed

REF TOP VIEW

TM

FOR WATER DIVERTER INFO.

W/SHOP INSTALLED CW-6 ISOLATOR. FIELDATTACH WITH FS-322 #12-14 X 1" HWH "TEK"

CW-2 FACE CAP & ZG-60 PRESSURE PLATE

2 1/

2"

CW-17 EXTERIOR GASKETW/FG-5185 SPACER GASKET

STRUCTURAL SILICONE SEALANT (BY OTHERS)

CW-2000 HORIZONTAL

CW-2338 INTERIOR GASKETCW-2337 EXTERIOR GASKET

Dry Glazed Option

ON CW-2101 SETTING BLOCKSMONOLITHIC LAMINATED GLASS

Page 9: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

HEAD

JAMB SILL

HEAD

SILL

4" 4"4"

MULLION

Anchors-at-Single-Span - H8145StormMax Curtain Wall

2 1/

2"

Page 10: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

HR-FP-24 ANCHOR HR-FP-25 ANCHOR

SILL

HEAD

Anchors-at-Twin-Span - H8146StormMax Curtain Wall

HR-FP-15 ANCHOR SLEEVEHR-FP-16 ANCHOR SLEEVE

SILL

HEADACCESS HOLE

JAMB MULLION

Page 11: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

HR-FP-22 ANCHOR

HEAD

SILL

90 OUTSIDE CORNER

Anchors-at-Twin-Span - H8147StormMax Curtain Wall

PLAN VIEW AT HEAD

HR-FP-23 ANCHORHR-FP-22 ANCHOR

HR-FP-23 ANCHOR

ACCESS HOLE

Page 12: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

CW-1995

HR-FP-20SPLICE

CW-2001 CW-2002

HR-FP-18 SPLICE

HR-FP-14SPLICE

Mullion Splices - H8148StormMax HR-250 - Curtain WallTM

CENTER LINE AT PRESSURE PLATE

4"

2"

CENTER LINE AT SPLICE

CE

NTE

R L

INE

FA

CE

CAP

1/2"

FS-8 STOP SCREW

3 3/

4"3

3/4"

1/2"

SEAL AND TOOL JOINT

SEAL TOP OF FACE CAP TO PRESSURE PLATE

SEALTOP OF PRESSURE PLATE

1/2"

TO MULLION-SEE INSTALLATION MANUAL

Page 13: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

CW-2018

HP-FP-29SPLICE

CW-2019

HR-FP-21 SPLICE

3 3/

4 "

FS-8 STOP SCREW

SEAL AND TOOL JOINT

CENTER LINE AT SPLICE

1/2"

3 3/

4"3

3/4"

Corner Mullion Splices - H8149StormMax - Curtain WallTM

Page 14: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

CW-1999

HR-FP-30 SPLICE

SSG-Mullion Splice - H8150StormMax - Curtain WallTM

CENTER LINE AT SPLICE

FS-8 STOP SCREW

3 3/

4"3

3/4"

1/2"

SEAL AND TOOL JOINT

STOP SCREW

Page 15: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

TAP PLATE W/TAPPED HOLESFOR ANCHOR BOLT

Steel Anchor @ Floor Slab - H8151

TMStormMax - Curtain Wall

1/16" NYLON SLIPPADBY INSTALLER

WELD AS REQUIRED BY INSTALLER

Jamb

Mullion

ANCHOR BOLT (BY OTHERS)

Plan View

Plan View

HOLE IN ANCHOR AT DEAD LOADSLOT IN ANCHOR AT WIND LOAD

STEEL ANCHORFLOOR SLAB

Side ViewANCHOR BOLT (BY OTHERS)

Page 16: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

Steel Anchor @ Floor Slab - H8152

TMStormMax - Curtain Wall

Plan View - 90 Corner0

BY INSTALLERWELD AS REQUIRED

ANCHOR BOLT (BY OTHERS)

1/16" NYLON SLIPPADBY INSTALLER

HOLE IN ANCHOR AT DEAD LOADSLOT IN ANCHOR AT WIND LOAD

STEEL ANCHORFLOOR SLAB

Side View

Page 17: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

CW-1996 FILLER

CW-1995 JAMB

ATTACH W/FS-322CW-2005 POCKET FILLER

CW-17 GASKET

SEALANT (BY OTHERS) W/FG-5185STRUCTURAL SILICONE

ASSEMBLY SCREW (TYP)FS-8 #14 X 1" HHSTS

Jamb- V8141

CW-2 FACE CAPZG-60 PRESSURE PLATE

SEALANT (BY OTHERS)BACKER ROD &

StormMax HR-250 - Wet Glazed

MONOLITHIC LAMINATED GLASS

SPACER GASKET

CW-2338 INTERIOR GASKETCW-2337 EXTERIOR GASKET

Dry Glazed Option

Page 18: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

CW-1996 FILLER

CW-1995 JAMB

ASSEMBLY SCREW (TYP)FS-8 #14 X 1" HHSTS

(BY OTHERS)ANCHOR BOLT

Jamb- V8142StormMax HR-250 - Wet Glazed

ATTACH W/FS-322CW-2005 POCKET FILLER

CW-17 GASKET

SEALANT (BY OTHERS) W/FG-5185STRUCTURAL SILICONE

CW-2 FACE CAPZG-60 PRESSURE PLATE

SEALANT (BY OTHERS)BACKER ROD &

MONOLITHIC LAMINATED GLASS

SPACER GASKET

CW-2338 INTERIOR GASKETCW-2337 EXTERIOR GASKET

Dry Glazed Option

Page 19: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

RS-25 STEEL REINF

CW-1996 FILLER

CW-1995 JAMB

ASSEMBLY SCREW (TYP)FS-8 #14 X 1" HHSTS

LOCATE @ HD/SILL& INTERMEDIATE HORIZONTALS

Jamb- V8143StormMax HR-250 - Wet Glazed

ATTACH W/FS-322CW-2005 POCKET FILLER

CW-17 GASKET

SEALANT (BY OTHERS) W/FG-5185STRUCTURAL SILICONE

CW-2 FACE CAPZG-60 PRESSURE PLATE

SEALANT (BY OTHERS)BACKER ROD &

MONOLITHIC LAMINATED GLASS

SPACER GASKET

CW-2338 INTERIOR GASKETCW-2337 EXTERIOR GASKET

Dry Glazed Option

Page 20: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

HR-FP-2/3 WATER DIVERTER

CW-2001 JAMB CW-2002 JAMB

(2) FS-7 ATHORIZONTALS AND12" O.C. BETWEENHORIZONTALS

ANCHOR BOLT(BY OTHERS)

ASSEMBLY SCREW (TYP)FS-8 #14 X 1" HHSTS

Jamb- V8144

TMStormMax HR-250 - Wet Glazed

CW-17 GASKET

SEALANT (BY OTHERS) W/FG-5185STRUCTURAL SILICONE

CW-2 FACE CAPZG-60 PRESSURE PLATE

SEALANT (BY OTHERS)BACKER ROD &

MONOLITHIC LAMINATED GLASS

SPACER GASKET

CW-2338 INTERIOR GASKETCW-2337 EXTERIOR GASKET

Dry Glazed Option

Page 21: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

CW-2001 JAMB CW-2002 JAMB

(2) FS-7 ATHORIZONTALS AND12" O.C. BETWEENHORIZONTALS

WATER DIVERTER

ASSEMBLY SCREW (TYP)FS-8 #14 X 1" HHSTS

(BY OTHERS)ANCHOR BOLT

HR-FP-2/3

Jamb- V8145StormMax HR-250 - Wet GlazeTM

CW-17 GASKET

SEALANT (BY OTHERS) W/FG-5185STRUCTURAL SILICONE

CW-2 FACE CAPZG-60 PRESSURE PLATE

SEALANT (BY OTHERS)BACKER ROD &

MONOLITHIC LAMINATED GLASS

SPACER GASKET

CW-2338 INTERIOR GASKETCW-2337 EXTERIOR GASKET

Dry Glazed Option

Page 22: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

CW-2001 JAMB CW-2002 JAMB

(2) FS-7 ATHORIZONTALS AND12" O.C. BETWEENHORIZONTALS

HR-FP-2/3

FG-5000-PP-8 STEEL REINF.ATTACH WITH FS-322

ASSEMBLY SCREW (TYP)FS-8 #14 X 1" HHSTS

Jamb- V8146StormMax HR-250 - Wet GlazedTM

CW-17 GASKET

SEALANT (BY OTHERS) W/FG-5185STRUCTURAL SILICONE

CW-2 FACE CAPZG-60 PRESSURE PLATE

SEALANT (BY OTHERS)BACKER ROD &

MONOLITHIC LAMINATED GLASS

SPACER GASKET

CW-2338 INTERIOR GASKETCW-2337 EXTERIOR GASKET

Dry Glazed Option

Page 23: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

CW-2 FACE CAP

CW-1996 FILLER

CW-1995 MULLION

STRUCTURAL SILICONE SEALANT(BY OTHERS) W/FG-5185 SPACER GASKET

CW-17 GASKET

ASSEMBLY SCREW (TYP)FS-8 #14 X 1" HHSTS

Mullion - V8148

ATTACH WITH FS-322CW-6 ISOLATOR. FIELD

WITH SHOP INSTALLEDZG-60 PRESSURE PLATE

#12-14 X 1" HWH "TEK"@ 12" O.C.

StormMax HR-250 - Wet GlazedTM

MONOLITHIC LAMINATED GLASS

CW-2338 INTERIOR GASKETCW-2337 EXTERIOR GASKET

Dry Glazed Option

LOCATE @ INTERMEDIATEHORIZONTALS

Page 24: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

ATTACH WITH FS-322CW-6 ISOLATOR. FIELD

WITH SHOP INSTALLEDZG-60 PRESSURE PLATE

#12-14 X 1" HWH "TEK"@ 12" O.C.

CW-2 FACE CAP

CW-1995 MULLION

CW-1996 FILLER

(BY OTHERS) W/FG-5185 SPACER GASKETSTRUCTURAL SILICONE SEALANT

CW-17 GASKET

RS-25 STEEL REINF

ASSEMBLY SCREW (TYP)FS-8 #14 X 1" HHSTS

Mullion - V8149StormMax HR-250 - Wet GlazedTM

MONOLITHIC LAMINATED GLASS

CW-2338 INTERIOR GASKETCW-2337 EXTERIOR GASKET

Dry Glazed Option

LOCATE @ INTERMEDIATEHORIZONTALS

Page 25: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

CW-2 FACE CAP

CW-1995 MULLION

RS-16 STEEL REINF

CW-1996 FILLER

(BY OTHERS) W/FG-5185 SPACER GASKETSTRUCTURAL SILICONE SEALANT

CW-17 GASKET

ASSEMBLY SCREW (TYP)FS-8 #14 X 1" HHSTS

Mullion - V8150StormMax HR-250 - Wet GlazedTM

ATTACH WITH FS-322CW-6 ISOLATOR. FIELD

WITH SHOP INSTALLEDZG-60 PRESSURE PLATE

#12-14 X 1" HWH "TEK"@ 12" O.C.

MONOLITHIC LAMINATED GLASS

CW-2338 INTERIOR GASKETCW-2337 EXTERIOR GASKET

Dry Glazed Option

LOCATE @ INTERMEDIATEHORIZONTALS

Page 26: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

CW-2 FACE CAP

CW-1995 MULLION

CW-1996 FILLER

(BY OTHERS) W/FG-5185 SPACER GASKETSTRUCTURAL SILICONE SEALANT

RS-17 STEEL REINF

CW-17 GASKET

FS-8 #14 X 1" HHSTSASSEMBLY SCREW (TYP)

Mullion - V8151StormMax HR-250 - Wet GlazedTM

ATTACH WITH FS-322CW-6 ISOLATOR. FIELD

WITH SHOP INSTALLEDZG-60 PRESSURE PLATE

#12-14 X 1" HWH "TEK"@ 12" O.C.

MONOLITHIC LAMINATED GLASS

CW-2338 INTERIOR GASKETCW-2337 EXTERIOR GASKET

Dry Glazed Option

LOCATE @ INTERMEDIATEHORIZONTALS

Page 27: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

ATTACH WITH FS-322CW-6 ISOLATOR. FIELD

WITH SHOP INSTALLEDZG-60 PRESSURE PLATE

#12-14 X 1" HWH "TEK"@ 12" O.C.

CW-2 FACE CAP

CW-2097 HEAVY MULLION

CW-1996 FILLER

(BY OTHERS) W/FG-5185 SPACER GASKETSTRUCTURAL SILICONE SEALANT

CW-17 GASKET

ASSEMBLY SCREW (TYP)FS-8 #14 X 1" HHSTS

Mullion - V8152StormMax HR-250 - Wet GlazedTM

MONOLITHIC LAMINATED GLASS

CW-2338 INTERIOR GASKETCW-2337 EXTERIOR GASKET

Dry Glazed Option

LOCATE @ INTERMEDIATEHORIZONTALS

Page 28: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

CW-2003 PRESSURE PLATE

CW-2004 FACE CAP

CW-2019

CW-2020

FS-322 @36" O.C.

SEALANT BYINSTALLER

HR-FP-7

FG5000-FP-8

CW-2018

ASSEMBLY SCREW (TYP)FS-8 #14 X 1" HHSTS

90 Deg Corner - V8153StormMax HR-250 - Wet GlazedTM

CW-2338 INTERIOR GASKETCW-2337 EXTERIOR GASKET

Dry Glazed Option

& INTERMEDIATE HORIZONTALSLOCATE @ HD/SILL

LOCATE @ INTERMEDIATEHORIZONTALS

Page 29: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

CW-2019

CW-2020

FS-322 @36" O.C.

FG5000-FP-8

CW-2018

ASSEMBLY SCREW (TYP)FS-8 #14 X 1" HHSTS

HR-FP-7 MULLION CAP

SSG 90 Deg Corner - V8154StormMax HR-250 - Wet GlazedTM

& INTERMEDIATE HORIZONTALSLOCATE @ HD/SILL

LOCATE @ INTERMEDIATEHORIZONTALS

Page 30: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

CW-1999 MULLION

CW-1996 FILLER

(BY OTHERS) W/FG-5185 SPACER GASKETSTRUCTURAL SILICONE SEALANT

ASSEMBLY SCREW (TYP)FS-8 #14 X 1" HHSTS

BACKER ROD & STRUCTURALSILICONE SEALANT (BY OTHERS)

HR-FP-11 MULL CAP@ HEAD & SILL LAMINATED GLASS

SSG Mullion - V8157StormMax HR-250 - Wet GlazedTM

Page 31: StormMax- HR-250 - 2-1/2” x 6-3/4” - Monolithic Laminated

CW-1999 MULLION

RS-25 STEEL REINF

CW-1996 FILLER

(BY OTHERS) W/FG-5185 SPACER GASKETSTRUCTURAL SILICONE SEALANT

ASSEMBLY SCREW (TYP)FS-8 #14 X 1" HHSTS

INTERMEDIATE HORIZONTALSLOCATE @ HD/SILL &

BACKER ROD & STRUCTURALSILICONE SEALANT (BY OTHERS)

HR-FP-9 CONVOLUTEDWATER DIVERTER BRIDGE @INTERMEDIATE HORIZONTALS LAMINATED GLASS

StormMax HR-250 - Wet GlazedSSG Mullion - V8158

TM