Safety Technology International, Inc. 2306 Airport Road • Waterford, Michigan 48327-1209 Phone: 248-673-9898 • Fax: 248-673-1246 Toll Free: 800-888-4784 • E-mail: [email protected] Web: www.sti-usa.com Safety Technology International (Europe) Ltd. Unit 49G Pipers Road • Park Farm Industrial Estate • Redditch Worcestershire • B98 0HU • England • Tel: 44 (0) 1527 520 999 Fax: 44 (0) 1527 501 999 • Freephone: 0800 085 1678 (UK only) E-mail: [email protected] • Web: www.sti-europe.com INSTALLATION OF SS-2000 FIRE SERIES STOPPER ® STATION All specifications and information shown were current as of publication, and are subject to change without notice. SHEET 1 10277IS JAN99 .69 in. (17mm) SUB-102722-R PLASTIC SPACER MOLDED IN RED (OPTIONAL) TERMINAL BLOCK ASSEMBLY BACKPLATE ASSEMBLY WITH STAINLESS STEEL GROUND PLATE AND LUG MOLDED BUTTON WITH KEY RESET MOLDED POLYCARBONATE FACEPLATE TURN CLOCKWISE ONE QUARTER TURN TO RESET 19001 HOUSING RETENTION SCREW #8-32 x 3/8 in. (1) PROVIDED 19015 3/32 in. ALLEN WRENCH (1) PROVIDED BUTTON LOCK NUT F F I I R R E E P U S h H E R E STANDARD SINGLE OUTLET BOX NOTE: TO MOUNT STOPPER STATION SS-2000F ON A STANDARD OUTLET BOX SUB-102722-R IS REQUIRED 19030 KEY (2) PROVIDED 10197H CONTACT HOLDER SCREWS (2) PROVIDED 19010 #6-32 x 1 in. WITHOUT SUB-102722-R 19045 #6-22 x 1 1/2 in. WITH SUB-102722-R TO PROVIDE ADEQUATE CLEARANCE FOR INSTALLATION TO ANY STANDARD SINGLE GANG OUTLET BOX, THE SUB-102722-R SPACER IS REQ 2.25 in. (57mm) 1.62 in. (41mm) 4.87 in. (124mm) 3.25 in. (82mm) PRODUCT DIMENSIONS PRY BACK LEVER 'A' IN DIRECTION OF ARROW THEN USING A FLATHEAD SCREW DRIVER, INSERT AS SHOWN AND ROTATE UPWARD. REMOVAL OF TERMINAL BLOCKS A INSERT TERMINAL BLOCK NOTCH AS SHOWN AND ROTATE UPWARD. INSTALLATION OF TERMINAL BLOCKS ADA compliant Electronic warranty form at www.sti-usa.com/wc14

STI SS-2000F Instruction Manual

Embed Size (px)

DESCRIPTION

Buy the STI SS-2000F at JMAC Supply!https://www.jmac.com/STI_SS_2000F_p/sti-ss-2000f.htm?=scribd

Citation preview

  • Safety Technology International, Inc.2306 Airport Road Waterford, Michigan 48327-1209Phone: 248-673-9898 Fax: 248-673-1246Toll Free: 800-888-4784 E-mail: [email protected]: www.sti-usa.com

    Safety Technology International (Europe) Ltd.Unit 49G Pipers Road Park Farm Industrial Estate RedditchWorcestershire B98 0HU England Tel: 44 (0) 1527 520 999Fax: 44 (0) 1527 501 999 Freephone: 0800 085 1678 (UK only)E-mail: [email protected] Web: www.sti-europe.com

    INSTALLATION OF SS-2000 FIRE SERIES STOPPER STATIONAll specifications and information shown were current as of publication, and are subject to change without notice. SHEET 1

    10277IS JAN99

    .69 in.(17mm)

    SUB-102722-RPLASTIC SPACER MOLDEDIN RED (OPTIONAL)

    TERMINAL BLOCK ASSEMBLY

    BACKPLATE ASSEMBLYWITH STAINLESS STEELGROUND PLATE AND LUG

    MOLDED BUTTONWITH KEY RESET

    MOLDEDPOLYCARBONATEFACEPLATE

    TURN CLOCKWISEONE QUARTER TURNTO RESET

    19001 HOUSINGRETENTION SCREW#8-32 x 3/8 in.(1) PROVIDED

    19015 3/32 in. ALLENWRENCH (1) PROVIDED

    BUTTON LOCK NUT

    FF II RREEP

    U Sh

    H E R E

    STANDARD SINGLE OUTLET BOXNOTE: TO MOUNT STOPPER STATION SS-2000F ON A STANDARD OUTLET BOX SUB-102722-R IS REQUIRED

    19030 KEY(2) PROVIDED

    10197H CONTACT HOLDER

    SCREWS (2) PROVIDED19010 #6-32 x 1 in. WITHOUT SUB-102722-R19045 #6-22 x 1 1/2 in. WITH SUB-102722-R

    TO PROVIDE ADEQUATECLEARANCE FOR INSTALLATIONTO ANY STANDARD SINGLEGANG OUTLET BOX,THE SUB-102722-R SPACER IS REQ

    2.25 in.(57mm)

    1.62 in.(41mm)

    4.87 in. (124mm)

    3.25 in. (82mm)

    PRODUCT DIMENSIONS

    PRY BACK LEVER 'A' INDIRECTION OF ARROWTHEN USING A FLATHEADSCREW DRIVER, INSERTAS SHOWN AND ROTATEUPWARD.

    REMOVAL OF TERMINAL BLOCKS

    A

    INSERT TERMINALBLOCK NOTCH ASSHOWN AND ROTATEUPWARD.

    INSTALLATION OF TERMINAL BLOCKS

    ADAcompliant

    Electronic warranty form at www.sti-usa.com/wc14

  • IF LASTSTATION ON

    CIRCUIT,CONNECT E.O.L.

    RESISTOR

    12-18 AWG

    CLOSE ONALARM

    SINGLE DEVICE

    DIAGRAM DEPICTINGMULTIPLE DEVICES

    12-18 AWG

    CLOSE ONALARM

    SUPERVISED LOOP (SEE CAUTION NOTE)

    CLOSE ONALARM

    BE SURE ALL ELECTRICALPOWER IS DISCONNECTED

    BEFORE STARTING THE INSTALLATION.NOTE: JUMPER NOT PROVIDED

    AVIEW IN DIRECTIONS OF ARROWINSTALLATION AND REMOVAL OF TERMINAL BLOCKS ANDTERMINAL BLOCK ASSEMBLY FROM BUTTON ASSEMBLY

    TO SEPARATE TERMINALAND BUTTON ASSEMBLY

    GRASP TERMINAL HOUSING, USINGTHUMB APPLY PRESSUREDOWNWARD, REMOVE TERMINALHOUSING AS SHOWN.

    REMOVAL OF TERMINAL BLOCKFROM TERMINAL HOUSING

    INSERT SMALL SCREWDRIVERAS SHOWN AND PRYUPWARD, REMOVE TERMINAL.

    BACKPLATE ASSEMBLY

    INSERT NOTCHAS SHOWN THENROTATE UPWARD

    TERMINAL BLOCK RELEASE LEVERMUST FACE UPWARDAS SHOWN FOR SWITCHTO FUNCTION CORRECTLY.

    ELECTRICAL TERMINAL1, 2, OR 3 TERMINALSMAY BE USED

    STRIP 1/4 in. OF WIRE INSULATION,INSERT IN TERMINAL (AS SHOWN).THEN USING A PHILLIPS SCREWDRIVERTURN CLOCKWISE UNTIL TIGHT.

    AVIEW IN DIRECTIONS OF ARROWINSTALLATION OF ELECTRICALWIRE INTO TERMINAL BLOCK

    OUTGOING

    INCOMING

    BUTTON LOCK NUT

    10196 N.O. TERMINAL BLOCK(2) PROVIDED UP TO 3TERMINALS MAY BE USED FOREACH STATION ASSEMBLY.

    A

    AN UNINSULATED SECTION OF A SINGLECONDUCTOR SHOULD NOT BE LOOPEDAROUND THE TERMINAL AND SERVE ASTWO CONNECTIONS.THE WIRE MUST BE SEVERED, THEREBYPROVIDING SUPERVISION OF THECONNECTION IN THE EVENT THE WIREBECOMES DISLODGED FROM THE DEVICE.

    CAUTION

    METAL WASHER

    ALL TERMINALS ACCEPT TWO 12 TO 18 (AWG)

    VOLTAGE RATED AVERAGE CURRENT

    250 VDC 1 AMP24 VAC 3 AMP

    SAFETY TECHNOLOGY INTERNATIONAL, INC. 2306 AIRPORT ROAD WATERFORD MICHIGAN 48327-1209 PHONE: 248-673-9898 FAX: 248-673-1246 INFO @ www.sti-usa.comSHT. 2

    10277IS JAN99