Condensed Aerosol Fire Suppression Systems
Presented to FPE March 2014
Aerosol Technology - How it Works - Codes & Standards
Definition per NFPA 2010 Standard on Aerosol Fire-Extinguishing Systems
Solid particles > 10 Microns will tend to settle to form residue Solid particles < 10 Microns will tend to remain suspended in air
Particle Median Size Comparisons: Purple-K Dry Chemical Agent ~ 20 Microns High Pressure Watermist Droplet ~ 50 to 120 Microns Aerosol Agent < 1- 2 Microns
RELEVANT STANDARDS: NFPA: NFPA 2010 Standard on Aerosol Fire-Extinguishing Systems (2010 ed.) NFPA 70 National Electrical Code NFPA 72 National Fire Alarm and Signaling Code
CEN/ISO: CEN/TR 15276-1 Fixed Firefighting Systems Condensed Aerosol ISO 15779 Condensed Aerosol Fire Extinguishing Systems
AGENCIES: UL 2775 Fixed Condensed Aerosol Extinguishing System Units CSIRO ActvFire
Aerosol fire suppression systems are designed as: Engineered total flooding fire detection and fixed suppression systems Self-activating or remote (manual) operated fixed fire extinguishers c/w high
temperature fire detection
AEROSOL SYSTEM
WHAT IT IS Total flooding system for enclosed spaces
Listed extinguishant for Class A (surface), B,
C fire hazards
Aerosol with ultra-fine solid particles mixed with and propelled by low pressure N2 inert gas
Fire detection & extinguishing system (with FACP or stand-alone)
Environmentally friendly o zero ODP, ~zero GWP, zero ALT
EPA SNAP listed as a halon 1301
replacement for normally unoccupied areas
WHAT IT IS NOT NOT NFPA 17 Dry chemical system (>20m)
NOT NFPA 2001 Clean agent system
NOT HFC halocarbon gas
NOT suffocating gas
NOT pressurized storage gas system with
distribution piping network
NOT refillable
NOT listed for Class D fires
NOT toxic when designed as a total flooding system
6
Aerosol Fire Suppression Technology
Aerosol Agent & Inert Gas
Actuator Signal (electric, thermal,
or manual)
How a Generator Works 1) Signal energizes Actuator 2) Agent Compound reacts with Oxidation Block, generating 3) Aerosol agent and Inert Gas pass through Cooling Block, and out generator Exit Ports 4) Stat-X Agent suspension fills hazard area, suppressing fire
Fire Tetrahedron
Primary Extinguishing Mechanism: Aerosol free radicals react with flame free radicals and interfering with chemical reactions taking place in the fire
Fire Triangle
Huge population of suspended aerosol particles < 2m with very large total surface area to absorb heat
SOME HEAT ABSORBTION
Aerosol Extinguisher
Aerosol Agent & Inert Gas Suspension
1-2 m
8
K+
K+
K+
K+
K+
K+
K+
K+
Potassium Radicals From Aerosol Agent
Combustion Free Radicals
O- H O-
H+
H+
O- H
O
O- O- C K
+ K+
N2 N2
N2 N2
How Aerosol Agents Suppresses Fire 1) Aerosol Agent & Inert Gas Suspension discharge fills hazard volume (particle size 1-2 micron) 2) Potassium Radicals from Aerosol Agent mix with free radicals generated by combustion 3) Potassium chemically joins with Combustion Free Radicals, interrupting the fires reaction pathway and creating Stable Molecules 4) The interrupted fire reaction pathway can no longer sustain combustion and the fire is suppressed.
Stable Molecules
Condensed aerosol agent is ultra-fine particles propelled by self-generated inert gas
10
MCA machinery space performance certification fire test
APPLICATION DESIGN DENSITIES
11
Application Density Required per Published Listed Design Manuals. Application Density (g/m3) Product A Product B Class B 66.95 109.2 Class A 97.15 109.2
APPLICATION BASED PERFORMANCE TESTS
12
13
Ventilated high speed locomotive power compartment fire test (simulated air flow to 100 mph)
Belgian train motor compartment fire test (1YR in service)
14
Swedish SP bus engine compartment fire test
Middle East Civil Defense car engine fire test
15
Gas turbine compartment and auxiliary compartment fire test and volume inerting tests
Gas turbine bearing compartment fire test
16
MCA marine small vessel machinery compartment fire test
Naval diesel engine and flammable storage room fire test
Naval gas turbine fire test
17
Naval switch gear cabinet fire test
Transformer fire test man portable grenade
Naval man portable grenade evaluation tests
18
High speed train 1 year service endurance test
Army armored vehicle military standard qualification/endurance tests and actual Iraq/ Afghanistan combat service
CNC machine commissioning discharge test
How Aerosol Agent Compares
Aerosol Discharge
20
Agent Effectiveness: More Efficient
21
US Naval Research Lab performance fire tests show that aerosol fire suppression systems can outperform equivalent water mist systems in extinguishment time for all sizes of fires and at a fraction of the system weight.
Cost-Effective to Own No agent level checks
or container weighing No disassembly and
vessel hydro-testing Hermetically sealed,
tough stainless steel Stable, long-lived agent
(10+ years) Keep spares handy to
Restore system fast after fire is suppressed
No waiting for resupply when at sea or remote sites
23
Approvals, Listings & More - Recognized Worldwide
US EPA SNAP LIST
Meets US EPA Significant New Alternatives Policy (SNAP) as substitute for ozone-depleting chemicals (e.g. halon)
25
Recognized Worldwide Underwriters Laboratories (UL), Underwriters Laboratories Canada (ULC) American Bureau of Shipping (ABS) U.S. Environmental Protection Agency (EPA) TUV (Germany) ECB (Europe) Bureau Veritas (France) RINA (Italy) Swedish Fire Protection Association (SBF 128) Oman and Emirates Civil Defence SSI Israel Taiwan Fire Authority Japanese Authority (METI) Malaysian Fire Authority (BOMBA) CSIRO/ActivFire and Australia Maritime Authority
26
Examples - Actual Installations - Protecting Critical Infrastructure Worldwide
Power Generation - Refinery Retrofit GE Frame 5 gas turbine for electrical power generation (aerosol suppression replacing decommissioned CO2 system) Turbine, accessory, & gear compartments protected
28
Generator Enclosure & Room Protection
Generator Enclosure Automatic fire detection & suppression
Power Utility: Switch Gear & MCC Electrical switch gear, motor control center (MCC) rooms Unoccupied, locked, high ceilings Solu t ion 500g, 250g (6 units) Spot detection
30
Modular configuration covers total space
Switch Gear & MCC Protection
31
Wind Turbine: Phu Qui, Vietnam Wind turbine nacelles, electrical cabinets Extreme weather, vibration, difficult access;
hydraulic oils, electrical cabinets Solu t ion Models: Electric and thermal operated units Aspirating detection
32
Dangerous and difficult access, multiple hazards
Telecom & Data: Cell Shelters Unoccupied cell site shelters Protection of electrical power, sources,
transceivers, GPS Solu t ion Model: Thermal operated 30g
33
Remote location is difficult to service
Telecom & Data: Electronic Cabinets Small individual cabinets, limited space Agent suspension easily vented Solu t ion Electric operated 100g & 250g Spot detection, FACP
34
Spot detection for addressability
Public Works: Boston Lift Bridge Two tower spaces, harsh environment Electric motors, diesel engines protected Solu t ion Model: Electric operated 2500g (56 units) 53,634 ft3 protected space
Releasing panels for 2500E activation
35
CNC & Machine Tool: Smith & Richardson Numerically controled milling, turning, boring & grinding machines Enclosures with flammable lubricating oils; downtime is expensive Solu t ion Model: Electric operated 60g or 100g Linear detection for fast
response, low install cost
Actual post-fire photo: damage minimal, clean-up easy!
36
Mining & Tunnel: Gdansk Motorway Earth tunneling machines for subways, roadways, rail lines Motor and electrical control spaces for engine Solu t ion Model 100g (1 unit/cabinet) Spot detection
37
Individual cabinets protected to focus on specific hazards
Specialty Vehicle: NASA Crawlers Space vehicle launch transporters Control areas, machine rooms,
communications rooms Solu t ion Models: Electric operated units Aspiration & triple IR detection
Aerosol units mounted in numerous
hazard areas
38
Specialty Vehicle: U.S. Military Mine-resistant
vehicles serving in Iraq & Afghanistan
High temperatures, vibration & isolated locations
Solu t ion 100g (standard
commercial unit) Linear detection
39
Military tested and approved for use on current and next generation vehicles
Specialty Vehicle: Oslo Snow Removal Airport snow removal vehicle Engine compartment Solu t ion Model: Electric operated 250g Linear detection, manual pull
250g units rated down to 40 C/F
40
Rolling Stock: Public Transportation Eurostar diesel/electric in test Engine compartments, allow safe egress 1000 Stagecoach buses Solu t ion Models: Electric operated 100g & 250g Linear detection
41
Suppression buys time for evacuation of public, especially handicapped
Duct Protection
42
Protection of duct work of manufacturer of roofing materials
Duct coated with flammable materials
Solution External mounted electric
operated units injecting into ductwork
Marine and Offshore: Hovercraft Workboats, law enforcement, tugs, ferries, offshore platforms Engine, machinery & storage spaces;
typically small with obstructions Solu t ion Electric operated aerosol units Linear & flame detection
Mounting accommodates
most obstructions
43
LCAC AVCO LYCOMING/VERICOR POWER TF-40 GT MODULE
LCAC
SSC
US Navy LCU Landing Craft Utility
Diesel Engine Room Test Enclosure
Flammable Liquid Storage Enclosure
Al Adaaam 96 Fire
Engine compartment extinguished by aerosol fire suppression system
Hand-held aerosol units for utilities, first responders, fire service, military, police and security
Manhole & vault fires, need for safer egress & entrance, knockdown fire
Solu t ion Portable aerosol grenade Like a smoke grenade,
except generates fire suppression agent
Plus: Hand-Held Fire Suppression
48
Hand Held Aerosol Units
49
100% made in USA to ISO 9001:2008
Electric operated generators integrated with UL listed fire alarm control panel. Available in 30E, 60E, 100E, 250E, 500E, 1000E, 1500E, and 2500E sizes. All stainless steel construction.
Automatic units with fixed temperature heat Sensor. Available in 30T, 60T, 100T, 250T, and 500T sizes. Patented Thermal Actuator in 70C (158F), 95C (203F), and 123C (253F) settings with manual cable pull. All stainless steel construction.
Available as 500 gram units. Special cases to carry and store 1 to3 First Responders.
ENGINEERED
PRE-ENGINEERED
HAND HELD
Questions?
THANK-YOU
www.statx.com 19200-001 Rev A 11-12