SHORT FORM SERVICE MANUAL - CIM 5 CONTROLLER

Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

Embed Size (px)

Citation preview

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 1/38

SHORT FORM SERVICE MANUAL - CIM 5 CONTROLLER

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 2/38

SHORT FORM SERVICE MANUAL

Operating temperature

-30˚C to +30˚C-22 F to +86 F

Ambient temperature

-30˚C to +50˚C-22 F to +122 F

Model: SC-MCI40-WC, SC-MCI40, SCI-40 and SCU-40

Refrigerant: R-134aCharged with 4.5 kg / 9.9 lb

[2]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 3/38

SHORT FORM SERVICE MANUAL

Controller box view

Phase direction

Phase direction

Heat element

Cond. fan low

Cond. fan high

Evap. fan low

Evap. fan high

FC/Compressor

Main circuit breaker

[3]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 4/38

SHORT FORM SERVICE MANUAL

Controller box view

Terminal block PCB

Power meas

Power in

Modem (if installed)

Transformer

[4]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 5/38

SHORT FORM SERVICE MANUAL

Controller box view

Controller connections

Fuses: 2x 0.4/0.63 Amp.

3x 10 Amp.

Fuse: 6.3 Amp.

Recommended to raise

F1 and F2 to 0.63 Amp.

[5]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 6/38

SHORT FORM SERVICE MANUAL

Unit rear side view

Tsuc sensor

Return air sensor

Humidity sensor

Evaporator sensor

Supply air sensors

[6]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 7/38

SHORT FORM SERVICE MANUAL

Replacement of Tsuc sensor

Remove PVC Cover to accessTsuc sensor

Cut cable tie (one pcs). Sensor can thenbe removed

When installing the new sensor, make sure toinsert properly in tube

[7]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 8/38

SHORT FORM SERVICE MANUAL

Replacement of air exchange sensor

Remove the two nger screws on thebutter y and remove cover plate

Remove the fourteen screws to loosenthe black cover where the air ex-sensoris mounted

Replace the sensor and install all thedismantled parts again

[8]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 9/38

SHORT FORM SERVICE MANUAL

Air exchange sensor calibration

Close fresh air buttery

In the service menu SO5; Con-

guration menu FO6; Press “Enter” twice

Calibration is completed

[9]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 10/38

SHORT FORM SERVICE MANUAL

Supply voltage measurements

Measure voltage output from themain circuit breaker

Measure voltage supplied to thepower meas PCB

Range -50 Hz: 335 – 460 VACRange -60 Hz: 390 – 525 VAC

[10]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 11/38

SHORT FORM SERVICE MANUAL

Supply voltage measurements

Measure the voltage output fromthe power meas PCB to the maincircuit

Range -50 Hz: 335 – 460 VACRange -60 Hz: 390 – 525 VAC

[11]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 12/38

SHORT FORM SERVICE MANUAL

Supply voltage measurements

Measure the voltage output fromthe power meas PCB to thetransformer

Range -50 Hz: 335 – 460 VACRange -60 Hz: 390 – 525 VAC

[12]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 13/38

SHORT FORM SERVICE MANUAL

Supply voltage measurements

Measure the voltage supplied tothe transformer

Range -50 Hz: 335 – 460 VACRange -60 Hz: 390 – 525 VAC

[13]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 14/38

SHORT FORM SERVICE MANUAL

Supply voltage measurements

Measure the voltage output of thetransformer 20 VAC

The output voltage depends onthe supply voltage

Range: 15.3 – 24.3 VAC

[14]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 15/38

SHORT FORM SERVICE MANUAL

Supply voltage measurements

Measure the voltage output fromthe transformer 24 VAC

The output voltage depends onthe supply voltage

Range: 18.9 – 30.0 VAC

[15]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 16/38

SHORT FORM SERVICE MANUAL

Check of 6,3 Amp fuse

Measure voltage from GND to top

of fuse

Fuse is ok

Range 18.9 - 30 VAC

Fuse is not ok

[16]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 17/38

SHORT FORM SERVICE MANUAL

Check power to ON/OFF PCB

Measuring from ground toterminal 4 (see picture) showsthat the controller is turned OFF

After turning ON, the voltage canbe measured

Range 18.9 – 30.0 VAC

[17]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 18/38

SHORT FORM SERVICE MANUAL

Check power to ON/OFF PCB

After turning ON you can read thevoltage supplied through the ”ON/OFF” PCB on terminal1 and 2

Range 15.3 – 24.3 VAC

[18]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 19/38

SHORT FORM SERVICE MANUAL

Check Frequency Converter

Frequency converter MUST alwayshave the black foil mounted forprotection of print, componentsand your safety

WARNING - HIGH VOLTAGE

[19]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 20/38

SHORT FORM SERVICE MANUAL

Check Frequency Converter

If deviation between phases ismore than 15 VAC:

Alarm ”523 FC phase loss” orAlarm ”516 FC Trip phase loss”

will be given

Range -50 Hz: 335 – 460 VACRange -60 Hz: 390 – 525 VAC

E.g. due to unstable power supplyfrom the genset

[20]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 21/38

SHORT FORM SERVICE MANUAL

Check Frequency Converter

A green light indicates FC is ok

A ashing green light indicates FCcommunicates with the controller

A red light indicates a problem

[21]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 22/38

SHORT FORM SERVICE MANUAL

Check Frequency Converter

If a red light is ON and alarm 500”FC missing” is displayed, the FChas an internal problem and mustbe replaced

The ”Warrenty repair report”must be lled out and submittedto Star Cool. The defect part mustbe properly tagged

[22]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 23/38

SHORT FORM SERVICE MANUAL

Emergency operation

Dismount the frequency converterand connect the FC power 1 cabledirectly to the compressor supplyterminals (W, V, U)

The 3 remaining terminals (Y, X,Z) have to be tted with a wire- jumper.

[23]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 24/38

SHORT FORM SERVICE MANUAL

Emergency operation

Go to Service menu andselect “Conguration” (S05)

In “Conguration” menuscroll down to “FC type”

(F03)

Then press return and select “NONE”

Note: remember to switchback to “Danfoss” in the “FC

type” setting when a new FCis mounted

[24]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 25/38

SHORT FORM SERVICE MANUAL

Contactor check

Measure Ω between terminalA1 and A2

Contactor is ok

Contactor is not ok

Deviation in resistance due tochange in temperature

[25]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 26/38

SHORT FORM SERVICE MANUAL

Temperature sensor check

Disconnect X1 on the controllerdoor

All temperature readings mustdrop to -70˚C within approxi-

mately 5-10 minutes

If one or more temperatures donot drop to -70˚C, the control-ler must be replaced

The ”Warrenty repair report”

must be lled out and sub-mitted to Star Cool. The defectpart must be properly tagged

[26]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 27/38

SHORT FORM SERVICE MANUAL

Temperature sensor check

Dismount the current defect sensor(s)according to the wiring diagram insidethe controller door

[27]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 28/38

SHORT FORM SERVICE MANUAL

Temperature sensor check

Measure the voltage between thetwo terminals on the PCB

Correct range: 4.80 > 5.05 VDC

[28]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 29/38

SHORT FORM SERVICE MANUAL

Temperature sensor check

Measure the resistance of thedisconnected sensor

Value must be according to theresistance table in the ”Operation

and Service manual”

E.g. 32.65 kΩ = 0˚C /32 F

[29]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 30/38

SHORT FORM SERVICE MANUAL

Temperature sensor check

Place the bulb in ice-waterand stir the sensor in theice-water

The displayed temperature in

the controller should be: 0˚C+/- 0.5˚C (32 F +/- 1.25 F)otherwise replace the sensor

[30]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 31/38

SHORT FORM SERVICE MANUAL

Pressure transmitter check

Disconnect X1 on the controller door

Psuc (and Peco) value must goto 14.7 or 12.0 Bar

Pdis value must go to 45.0or 32.0 Bar

Values depends on transmittertype congured in conguration menu menu (FO7 and FO8) (NSK, AKS)

If the above mentioned values are not reached within 5-10 minutes, the control-

ler module must be replacedThe ”Warrenty repair report” must be lled out and submitted to Star Cool. Thedefect part must be properly tagged

[31]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 32/38

SHORT FORM SERVICE MANUAL

Pressure transmitter check

Dismount the current defecttransmitter according to thewiring diagram inside thecontroller door

[32]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 33/38

SHORT FORM SERVICE MANUAL

Pressure transmitter check

Measure voltage between GNDand 5 VDC for the transmitter.(According to the electricalwiring diagram)

Correct range:4.80 > 5.05 VDC

[33]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 34/38

SHORT FORM SERVICE MANUAL

Pressure transmitter check

Reconnect GND and 5 VDC wiresfor the transmitter

Measure voltage between signalwire and GND

Check signal output from trans-mitter. Compare it to gaugereading/value found in relevanttable in the “Operational andService manual”.

[34]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 35/38

SHORT FORM SERVICE MANUAL

Check of heat elements

Measure the voltage(across each heater pair)

Measure the resistancevalue of each disconnected heater:

210 Ω (105 Ω as a pair)Value for tray heater: 400 ΩRange: +/- 10 Ω

5

4

Y/G

3

1

6

2

10

32

1211

98

76

Hevap

45

1

14Y/G

13

X601

5

3 2

6

5

8

1

7

3

4

12

2

4

4

4

6 6

2

4

6

(15 x 0,75mm2 / 15 x AWG 18)

Hevap

23

45

67

8

9

1011

1213

14

K3

[35]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 36/38

SHORT FORM SERVICE MANUAL

Change of parts

Always make sure to turn OFFthe main circuit breaker anddisconnect the power cable

[36]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 37/38

SHORT FORM SERVICE MANUAL

Notes

[37]

8/10/2019 Star-Cool-Short-form-Manual-CIM-5-Version-3.pdf

http://slidepdf.com/reader/full/star-cool-short-form-manual-cim-5-version-3pdf 38/38

SHORT FORM SERVICE MANUAL

Contacts

Internet

www.starcool.dk

Spare parts / orders

[email protected]

Service

[email protected]

Logistic

[email protected]

Technical Hot line 24/7

+45 73 64 35 00

[38]