22
KUWAIT OIL COMPANY K.S.C.) STANDARDS PUBLICATION KOCSTANDARD FOR LAYOUT, SPACING AND DIKING OF ABOVEGROUND PETROLEUM STORAGE TANKS DOC. NO. STANDARDS DIVISION

Standard for Layout, Spacing and Diking of Aboveground Petroleum Storage Tanks

  • Upload
    npwal

  • View
    264

  • Download
    22

Embed Size (px)

DESCRIPTION

Specification for storage tank and dykes

Citation preview

  • KUWAIT OIL COMPANY (K.S.C.)

    STANDARDS PUBLICATION

    KOCSTANDARD

    FOR

    LAYOUT, SPACING AND DIKING OF ABOVEGROUND PETROLEUM STORAGE TANKS

    DOC. NO.

    STANDARDS DIVISION

  • DOC. NO. KOC-L-027 1 Page 1 of 21 REV. 1

    KUWAIT OIL COMPANY (K.S.C.)

    STANDARDS PUBLICATION

    KOC STANDARD

    FOR

    LAYOUT, SPACING AND DIKING OF ABOVEGROUND PETROLEUM STORAGE TANKS

    DOC. NO. KOC-L-027

    STANDARDS DIVISION

  • KOC STANDARD

    FOR

    LAYOUT. SPACING AND DIKING OF

    ABOVEGROUND PETROLEUM STORAGE TANKS

    DOC. NO. KOC-L-027

    ISSUING AUTHORITY:

    STANDARDS DIVISION

  • TABLE OF CONTENTS

    FOREWORD

    SCOPE

    APPLICATION

    TERMINOLOGY

    REFERENCE STAND ARDS AND CODES

    ENVIRONMENTAL CONDITIONS

    HEALTH, SAFETY AND ENVIRONMENT

    BASIC DESIGN ClNSlDERATlONS

    TECHNICAL REQUIREMENTS

    TANK GROUPING

    TANK SPACING

    DIKES AND DIKED AREAS

    REMOTE IMPOUNDING

    DOCUMENTATION

    APPENDIX- I : MINIMUM TANK SPACING FROM OPERATING FACILITIES

    ACKNOWLEDGMENT

    Page No.

    4

    6

    6

    6

    8

    9

    9

    10

    10

    13

    13

    14

    18

    19

    20

  • FOREWORD

    It has been observed that the basic requirements for the tank field design are still v~~daly varying in various National Standards ( IP, NFPA, lFCl ) and International Oil Companies' practices and have no truly validated basis for the tank spacing except the concerns to minimize the adverse effects due to any potential fire. This was amply corroborated by the 'LASTFIRE" ( Large Atmospheric Storage Tank Fires ) project - a joint Oil Industry Project to Review the Fire Related Risks of Large, Open-top Floating Roof Storage Tanks.

    This document " KOC Standard for Layout, Spacing and Diking of Aboveground Petroleum Storage Tanks" is thus intended to provide the basic requirements for tank field design in KOC for safe containment of hydrocarbon in the event of spillage due to any accident.

    This Standard has been approved by the Standards Division, in consultation with Standard Technical Committee (STC), for use throughout the corporate engineering and operational functions of Kuwait Oil Company.

    This Standard sets out to achieve the following objectives: a) To define, from the current practices in the industry as well as from the

    international 1 national codes, the technical guidelines for use as KOC safety requirements, for inter tank spacing and tanks safe separation distances from operating facilities with a view to limiting the spread of hydrocarbon fire to the adjoining areas.

    b) To specify a set of design criteria for accessibility, drainage and impoundage in and around the tank field area in order to contain any adverse effects from spills, leaks and overfills as well as to improve the effectiveness of fire fighting efforts during any fire incident.

    C) To provide general technical guidance for developing layout drawings & specifications with a view to achieving safety, reliability and economy in the site specific tank field area.

    Feedback as well as any comments or suggestions from the application of this Standard derived at any stage of conceptual design, engineering, field construction or operation are encouraged and should be directed to:

    The Supdt. Standards Division (Chairman, Standards Technical Committee) Engineering Group, KOC P.O. Box 9758, Ahmadi 61008 State of Kuwait

  • DOC. NO. KOC-L-027 I Page 5 of 21 REV. 1

    Task Force Responsible for this Standard

    The preparation of this Standard has been entrusted by the Standards Technical Committee (STC) to the Task Force No. (TF-LPl02) comprising of the following members:

    Mr. S, Kumar Mr. J. Masood Mr. Rafiq Khan Mr. F.Al-Qattan Mr. Faisal Mirza

    - Standards Div. - Team leader / Author - Engg Design Div. - Member - Gen. Proj. Div. - Member - Fire & Safety Div. - Member - Standards Div. - Member

  • DOC. NO. KOC-L-027 I Page 6 of 21 I REV. 1 SCOPE

    This Standard provides the basic technical requirements for the layout, spacing, diking and drainage of aboveground petroleum storage tanks, containing crude petroleum and flammable liquids, located at the KOC facilities in Kuwait.

    This Standard shall not be applicable to any underground storage and skid- mounted tanks.

    APPLICATION

    The design and construction of the tankage area ( layout, inter-tank spacing, drainage and impoundage ) shall conform to the requirements of this Standard and the reference standards 1 codes mentioned herein.

    Any exceptions or deviations from this Standard, along with their merits and justifications, shall be brought to the attention of KOC's Controlling Department for their review, consideration and amendment by Standards Division (if required).

    Compliance with this Standard does not of itself confer immunity from legal or statutory obligations.

    TERMINOLOGY

    Definitions

    For the purposes of this Standard, the following definitions apply.

    Aboveground Tank

    Atmospheric vertical, cylindrical, closed-top or open-top, steel tanks used for petroleum storage purposes, whose entire bottom is supported uniformly on the ground or completely on supports; and constructed as per API 650.

    Berm

    The annular area around the tank, inside the dike, normally used for access to the tank and the equipment surrounding it.

    Expulsion of crude oil (or certain other liquids) from burning tank in a prolonged fire. As the lighter fractions of the oil burn off, the heavier fractions become more dense than the hydrocarbon underneath it, sink as a hot zone and produce a heat wave which on reaching a water stratum

  • result in the violent expulsion of the overlying oil by the increase in volume of steaming water.

    Crude Petroleum

    Unrefined hydrocarbon mixtures having a flash point below 65.6OC (1 50F). Dike

    A bund wall of appropriate height and size, constructed of suitable materials and designed for safe containment of any major oil spillage from tank(s) to protect the natural environment and surrounding areas having process units, waterways and adjoining properties.

    Flash Point

    The lowest temperature of a liquid at which sufficient vapour is given off to form an ignitable mixture with air near the liquid surface as determined in the laboratory.

    Impounding Basin

    An enclosure, generally a large open area, for collecting liquid spillage from one or more sources, for example to collect spillage from two tank compounds.

    Tank Field Area

    Area comprising of one or multiple tanks, enclosed by dike wall(s) and having equipment which are located outside the dike walls but are meant for tank and fire fighting operations.

    Classification of Petroleum Liquids

    The classification of petroleum liquids (crude oil & hydrocarbon products) and its subdivision of classes are given below , based on the Institute of Petroleum (IP) : Model Code of Safe Practice- Part 19 :

    5

    IP Classification

    Class 0 - Liquefied Petroleum Gases (LPG ).

    Class I - Liquids with a closed cup flash point below 21C (69.8OF).

    Class II(1) - Liquids with a closed cup flash point from 21 OC (69.8OF) up to and including 55OC (131F), handled at a temperature below flash point.

  • DOC. NO. KOC-L-027 I Page 8 of 21 I REV. 1 Class Il(2) - Liquids with a closed cup flash point from 2I0C(69.8OF) up to

    and including 55OC (1 31 OF), handled at a temperature at or above flash point.

    Class III(1) - Liquids with a closed cup flash point from 55OC (1 31 OF) up to and including 100C (21 2OF), handled at a temperature below flash point.

    Class lIl(2) - Liquids with a closed cup flash point from 55OC (1 31 OF) up to and including 100C ( 21 2OF ), handled at a temperature at or above flash point.

    Unclassified -Liquids with closed cup flash point above 1 OOC (21 2OF). Abbreviations

    HSE Health, Safety and Environment

    KOC Kuwait Oil Company ( K.S.C )

    REFERENCE STANDARDS AND CODES

    Conflicts

    In the event of conflicts between this Standard and the standards / codes referenced herein, or other contractual requirements, the most stringent requirement shall apply. In case further clarifications are required, the subject shall be brought to the attention of KOCts Controlling Department. In general, the sequence of precedence shall be followed as :

    a. Kuwait Governmental Rules and Regulations b. KOC Technical Specifications c. This KOC Standard ( KOC-L-027 ) d. International codes and standards e. Contractor's standards and specifications

    List of Standards and Codes

    The latest edition of the following standards, codes and specifications shall apply:

    4.2.1 International 1 National Standards

    API 650 Welded Steel Tanks for Oil Storage.

    API 2610 Design, Construction, Operation, Maintenance and Inspection of Terminal & Tank Facilities.

  • lFCl International Fire Code Institute-Uniform Fire Code, Vol. 1

    IP Model Code : Refining Safety Code. of Safe Practice Part 3

    IP Model Code : Fire Precautions at Petroleum Refineries and Bulk Storage of Safe Practice Installations Part 19

    NFPA 30 Flammable and Combustible Liquids Code.

    OSHA 29 CFR 191 0.106 Flammable and Combustible Liquids

    4.2.2 KOC Standards

    KOC-C-005 KOC Standard for Materials and Workmanship - Site Preparation and Earth works.

    KOC-C-026 KOC Standard for Storage Tank Foundation.

    KOC-C-033 KOC Standard for Materials and Workmanship - Bund Wall for Storage Tanks.

    KOC-G-002 KOC Standard for Hazardous Area Classification.

    KOC-G-007 KOC Standard for Basic Design Data.

    KOC-L-009 KOC Standard for Fire and Safety Equipment

    KOC-MV-007 KOC Standard for Field Erected Storage Tanks.

    KOC Fire & Safety Regulations

    5.0 ENVIRONMENTAL CONDITIONS

    5.1 The environmental conditions in Kuwait are severe. Due regard should be given to the consistently high levels of solar radiation experienced in Kuwait, which may develop surface temperatures of over 80 C (1 76' F) in exposed materials, the accompanying high evaporation rates and the significant periods under light breeze or calm conditions.

    5.2 Refer to KOC Standard for " Basic Design Data " (KOC-G-007) which provides the detailed design information regarding the environmental, site and utility supply conditions prevailing throughout the KOC facilities.

    6.0 HEALTH, SAFETY AND ENVIRONMENT

    6.1 The designer / contractor shall assure the compliance of necessary HSE design requirements to minimize the consequences and impacts of hazards on the surrounding environment and adjoining facilities.

  • DOC. NO. KOC-L-027 Pane 10 of 21 I REV. 1 I

    All relevant safety requirement of the KOC Fire & Safety Regulations and the KOC Health, Safety and Environment (HSE) policy shall be adhered to within KOC areas.

    BASIC DESIGN CONSIDERATIONS

    The basic design concepts of tank field area and tank layout should consider the following objectives to achieve : a.

    b.

    C.

    d.

    e.

    f.

    Site the

    Good accessibility, and smooth movement of personnel and mobile fire fighting equipment in the tank field area during a fire incident.

    Reduction of the risk of fire escalation to I from nearby facilities, equipment, buildings and public properties.

    Prevention of flames from a full surface fire on a tank from impinging on an adjacent tank. Diking to provide secondary containment of any major spillage by impounding the boil-over of any tank holding flammable liquids for the protection of environment and surrounding areas.

    Proper drainage of any spillage, accidental leaks and overfills of flammable liquids, to minimize the adverse effects on other tanks and associated equipment.

    An acceptable level of safety associated with adequate preventive measures and fire protection systems.

    specific reviews of the risk assessment analysis shall be conducted on t I basis of stock characteristics, type of storage tanks ( floating roof I

    fixed roof ), proximity of other KOC facilities, public or private properties, topography, and prevailing wind direction during the initial design stage.

    TECHNICAL REQUIREMENTS

    Location & Layout

    The location and layout of aboveground petroleum tanks and tank field area shall be decided on the basis of number of factors including but should not be limited to the following :

    a. Operating Requirements, b. Topographical Features, c. Fire Protection, d. Accessibility, e. Drainage, f. Capacity Limitation, g. Safe Separation Distances.

  • DOC. NO. KOC-L-027 I Page 11 of 21 I REV. 1 Operating Requirements

    a. Tank field area should be located close to or remote from the units, which it serves, on the basis of operating requirements.

    b. Tanks shall normally be placed away and uphill from their transfer pumps to facilitate flooded suctions of the pump(s).

    c. Sometimes, tanks limited in size need to be located close to the units, which it serves, to meet certain processingloperating conditions (stock characteristics, quality control or other factors) rather than storage requirements.

    Topographical Features

    a. Generally, topography of the tank field area shall be flat level ground as much as possible with a gentle slope. However, elevation, drainage, grading, excavation costs, and soil characteristics shall be considered to use the surrounding natural features to the maximum advantage.

    b. The tank field area should, preferably, not be located at levels higher than processing units in the same catchment area.

    c. Storage tanks holding flammable liquids shall be installed in such a way that any spill shall not flow towards a process area or any other source of ignition.

    Fire Protection

    For fire protection, the fixed fire extinguishing systems shall be installed on each tank in accordance with KOC Standard for " Fire and Safety Equipment" (KOC-L-009) and other protective devices specified in KOC Standard for " Field Erected Storage Tanks " (KOC-MV-007). For fire mitigation and effective fire fighting in the tankage area, the following factors as specified below shall be given prime importance in the layout.

    Accessibility

    a. Unobtrusive access of emergency vehicles shall be provided for a reasonable operating distance (18 m to 45 m) of hazards in the tank field area for effective fire fighting efforts.

    b. All-weather roads shall be provided around the perimeter of each dike, on at ieast two sides, for ready access to all tanks and shall be connected to the main access road system in the tankage areas. Compacted gatch roads may be acceptable in Gathering Centers and Booster Stations.

    c. These roads shall be of minimum width of 7 m; and should be located generally upwind of the tanks in the prevailing direction of wind.

  • DOC. NO. KOC-L-027 P a ~ e 12 of 21

    Where an access road is located between two adjacent tank compounds in a tank farm, the minimum distance between the liquefied walls (i.e. boundaries of classified zones) of each tank should be 24 m ( 75 f t ) as recommended in Appendix Ill (Note 4) of KOC Standard for " Hazardous Area Classification " (KOC-G-002). Turnouts shall be provided at convenient intervals to accommodate multiple vehicles involved in handling any emergency. Hard standing should also be considered at strategic locations for emergency traffic in large tank farm areas.

    Access ramps shall be provided for large compounds to assist maintenance work and to aid fire fighting in certain situations. Maintenance vehicles shall be allowed for access into these areas with necessary KOC's permits.

    8.1.5 Drainage

    Natural features of the topography (elevation, gradient, water channels etc.) shall be given due consideration in the layout from the initial design stage showing existing, new and future tankage in the area.

    Drainage paths shall be provided to quickly remove spills and leaks away from the tanks to nearby drain pits, sumps or impounding basins so that any KOC facilities including pumps, valve manifolds, electrical or any other equipment in the tank field shall not be endangered.

    Difference in elevation shall be used at a particular site in meeting drainage requirements.

    However, impounding and drainage areas for tanks handling flammable liquids with flash points below 37.8OC (lOOF) including crude oil, shall not be located at higher elevations than other facilities. This should minimize the migration of spillage or leakage through the soil to resurface at lower elevations, creating fire risks to the facilities and surroundings.

    8.1.6 Capacity Limitation

    a. Single Floating roof tanks, holding all classes of liquids including crude oil, shall be restricted to the maximum total capacity of 1,000,000 BBLS ( 158,900 m3 within a single diked compound.

    b. Fixed roof tanks above 45 m diameter, staring / handling crude oils within a single dike shall be subject to KOC's review and approval.

    8.1.7 Safe Separation Distances

    The requirements for the safe separation distances of the tanks holding crude oil I petroleum liquids from the operating facilities and the boundaries

  • of other adjoining tanks as well as for drainage and impoundage shall conform to the following clauses from 9.0 to 12.0 of this Standard.

    TANK GROUPING

    Tanks of diameter up to 10 m and height of 1 4 m or less shall be considered as small tanks; and when grouped together with the aggregate capacity of the group not exceeding 8000 m3 ( 50,346 BBLS 1, may be regarded as one tank for the consideration of tank spacing or diking in accordance with IP-19.

    The distance between individual tanks in such above group shall be governed by constructional and operating convenience, but shall not be less than 3.0 m.

    Floating/ Fixed roof tanks not meeting the above criteria in clause 9.1 shall be located individually within a single diked compound.

    Tanks should, preferably, not be grouped with different classes of liquids and different types in the same dike.

    TANK SPACING

    General

    The spacing requirements between tanks and between tanks and dikes / property lines are recommended on the basis of prevailing experiences for design guidance and for preliminary layout under normal conditions. However, the suggested distances are made conservative as exceptions to IP 19 or NFPA 30, to meet KOC's safety requirements.

    NOTE : LASTFIRE project of 16 m#or oil companies reviewing the risks associated with large diameter (> 40 m) open-top floating roof storage tanks, concludes that there is no truly validated basis except experience behind the spming requirements in the current standards to minimize the risks of fire escdstrbn 8s odined in clause 7. I of this Standard.

    Risk Assessment Studies

    The safe distances of tank(s) from other facilities and adjoining tanks shall be determined by using KOC approved and tested computerized models of the heat radiation and risk assessment analysis with site specific information in accordance with clause 7.2 of this Standard.

    Inter Tank Spacing (Shell-To-Shell) 10.3.1 The final inter tank spacing shall be decided, considering the proper scale

    of fire protection facilities and associated risks involved, on the basis of risk assessment analysis. However, i n absence of reliable analysis or modeling, the inter tank safe distances between shell to shell shall not be less than

  • DOC. NO. KOC-LQ27 I Page 14 of 21 I REV. 1 1.5 times the largest tank diameter in order to ensure safety with minimum performance/flow rate from deluge water pumps.

    Whenever the risk assessment studies determine the safe inter tank (shell- to-shell) distances less than the largest diameter, the minimum shell-to-shell distance shall be provided not less than 1.0 times the largest tank diameter.

    Distance from Property Lines 81 Public Roadways

    The following criteria shall be taken into consideration for the safe distances of aboveground tanks with respect to the property lines and public roadways :

    a. Pressure limitation of tanks under emergency venting conditions. b. Type of liquid stored and its characteristics under fire conditions. c. Type of tank and protection for exposures available. d. Proximity of high traffic public ways, degree of occupation ( low /

    medium / high ) and any important facilities. e. Alternate use of the area near the property line for tanks containing

    iquids with flash points above 60C (140F) to reduce the potential risk.

    As a minimum, the safe distances of the nearest floating / fixed roof tank(s) shall be not less than 300 m (1000 ft) from the public or private property lines; and shall not be less than 60 m (200ft) from the public roadways respectively.

    Tank Spacing from Operating Facilities

    The spacing requirements between tanks and other operating equipment (separators, pressure vessels, heat exchangers, compressors, pumps, heaters, etc.) including operating facilities shall be decided as per the minimum distances specified in Appendix- I.

    DIKES AND DIKED AREAS

    General

    Dikes shall be provided around tank(s) for protection of important facilities, adjoining surroundings, waterways and nearby properties from any accidental discharge of liquids pertaining to the IP classification of Class I, II & Ill as per clause 3.2.1 of this Standard.

    Dikes shall be designed with sufficient height, as measured from the outside ground level, to afford protection for personnel when engaged in fire-fighting; but shall not restrict ventilation in the tankage area.

    Diked areas located in extremely porous soils may require special treatment to prevent seepage of hazardous quantities of liquids (Class 1) to low lying areas.

  • DOC. NO. KOC-L-027 I Page 16 of 21 I REV. 1 I

    Dikes shall be liquid-tight, impervious to the liquid and shall be designed to withstand a full hydrostatic head.

    Capacity

    Dikes shall be sized to contain the greatest amount of liquid that can be released from the largest tank within the diked area, assuming 11 5% of tank rated capacity.

    The net retention capacity of the diked area enclosing more than one tank, shall be calculated by deducting the following from the total capacity of the enclosed area :

    a. the volume of all tanks, other than the largest, below the height of the dike (excluding the freeboard); and

    b. the volume of all intermediate dikes.

    Height

    The average interior height of the diked area shall not be more than 1800 mm (6ft) above the interior grade level unless as described in the following clauses 11.3.2 lh11.3.3.

    Greater height than 1800 mm shall be permitted, where special provisions are provided for normal access and necessary emergency access to tanks, valves and other equipment, and safe exit from the diked area.

    Where the average height of the dike containing flammable liquids (Class I) is over 3600 mm (12 ft) from the interior grade level, special design features such as remote operated valves, elevated walkways or similar arrangements shall be provided.

    An allowance of freeboard shall be provided below the actual dike height for the capacity calculation to account for future consolidation, settlement or possible erosion as given below :

    a. 150 mm for dikes up to an effective height of 1200 mm; b. 300 mm for dikes of an effective height of 1800 mm; c. 600 mm for dikes up to an effective height of 3600 mm.

    Fire Walls

    Each diked area, if containing two or more tanks, shall be subdivided at least by fire walls (intermediate dikes) in order to prevent small spills from endangering adjacent tanks within the same compound in compliance with the requirements of NFPA 30.

  • Alternately, drainage channels between the tanks may also be used for quick disposal of the spilled liquid by gravity to a remote impounding basin.

    Fire walls, where used, shall not be less than 450 mm in height if formed of earth, and at least 300 mm high if made of concrete.

    Dike Construction

    Dikes shall normally be of earth construction with suitable KOC approved fill materials, and shall be stabilized and protected from erosion by one of the following approved protective lining in conformity with " KOC Standard for Materials and Workmanship - Bund Wall for Storage Tanks " ( KOC-C- 033) :- a. Asphalt lining, or b. Bitumen sand lining, or c. Concrete lining.

    Other materials of construction (concrete or masonry ) may be used in any special case for small dikes and small areas but shall be subject to KOC's review and approval for its application.

    Earthen dikes shall be constructed in compliance with the requirements specified in KOC Standard KOC-C-033 .

    For earthen dikes, the slopes shall be consistent with the angle of repose of the fill materials for stability and safe maintenance.

    Earthen dikes shall have a minimum flat top width of 600 mm for heights up to 1200 mm; and minimum 900 mm above heights of 1200 mm as a walkway on top.

    Whenever the dike height exceeds 1200 mm from the toe, stairway access shall be provided to the inside of dike area at least from one convenient location of each side of the dike from the roads for ease of entry. No ladder shall be provided for access.

    Stairway shall be made of either precast concrete sleepers with handrails which shall be properly embedded into the dike slopes; or of steel construction with galvanized serrated treads and handrails. Stairway(s) shall be at least 1000 mm wide with steps not less than 300 mm in width. Step heights should be either not less than 150 mm or not more than 200 mm depending on dike height.

    Within the dikes, berms shall be made with sufficient width and slope around the tank(s) in accordance with KOC Standard for " Storage Tank Foundation" (KOC-C-026) for access to hatches, appurtenances and equipment mounted on or near the tank.

  • DOC. NO. KOC-L-027

    Any cutting or opening in the existing dike wall shall be subject to the written approval from KOC Loss Prevention Group and shall be rectified in conformity with the requirements of KOC Standard KOC-C-033.

    Drainage

    The areas inside the dike shall be graded with a slope away from the tank(s), piping and other equipment for surface drainage towards drain pit(s) or sump(s) or any impounding basin. The minimum slope shall be not less than 1 % from the edges of tank berm around the tanks for at least either 15 m or to the dike base whichever is less.

    Drain pit(s) or sump(s) shall be provided within the dike area at the farthest locations from the nearest tank. Drain pits should preferably be minimum two (2) Nos. located diagonally on the opposite corners, having safe access from outside clear areas.

    The drainage system shall also be sized to handle the surface runoff of storm water, fire water and accidental overfill, leak or spill of flammable or combustible liquid from any tank and if required, shall use shallow 1 deep ditches and/or diversion channels for quick disposal.

    Oil interceptors of adequate sizes should be considered in the drainage system of the dikes so that no hydrocarbon will be discharged into any watercourses or adjoining lands.

    Piping and Equipment

    Piping

    a. Piping inside the dikes shall be restricted solely to the lines which are directly associated with tank(s) in that area. All other piping shall be located outside the diked area. Piping for any tank or a group of tanks shall not run through other diked areas but may cross fire walls within that group, if necessary.

    b. The main pipe way to the tank(s) should preferably be under ground. But if run above ground, it shall be on concrete or steel supports and be at a minimum distance of 7.5 m (25 ft) from any tank in the diked area. Manifolds shall be located outside the dikes. Steel pipe supports shall be fireproofed for a 2 hour fire exposure.

    c. Piping or conduits should not pass through dike walls; but if they penetrate, they shall be designed to prevent buildup of excessive stresses on pipes or conduits as a result of settlement or fire exposure.

  • d. Pipelines passing through the earthen dikes shall be adequately protected from external corrosion by use of coatings and pipe sleeves. Pipe sleeves are normally preferred for ease of maintenance. The annular space around the pipes or conduits in the dike wall shall be properly sealed.

    e. Penetration of dikes (except drains) shall be kept to a minimum to prevent leakage paths through the dike.

    11.7.2 Equipment

    a. Pump(s) serving only one tank or one group of tanks in a common diked area shall be located outside the dike at least a minimum distance of 7.5 m (25 ft) from the dike wall.

    b. Deluge valves to be used for fire fighting shall be located outside of the diked area to provide protection from and access to during a fire incident or a spill.

    c. Block valves for drainage shall be located outside the diked area to be safely operated during an emergency. These valves shall be normally closed and secured.

    d. All electrical equipment to be installed inside the hazardous zones 1 dike areas shall conform to the relevant parts of KOC Recommended for " Selection, Installation and Maintenance of Electrical Equipment in Hazardous Areas" (KOC-E-004). The extent of hazardous zones shall be classified in accordance with " KOC Standard for Hazardous Area Classifications " (KOC-G-002).

    e. Electrical equipment, not complying with KOC-E-004, shall be located outside the diked area away from the drainage pats and impounding areas so that they are unlikely to be damaged in case of any spill fire.

    REMOTE IMPOUNDING

    Remote impounding shall also be considered, if the site topography permits, to contain any spills from the tank field(s), where impounding by diking is not provided fully.

    As a minimum, the impounding area shall be designed to hold the contents of the largest tank in the tank field or at least 10% of the total contents of all tanks of that group, whichever is greater.

    At basin capacity, the impounded liquid shall be at least 300 m away from the nearest tank and from any property line that can be built on.

  • correspondence, instructions, data sheets, drawings or any other itten information shall be in English language. In case of dual languages,

    language shall be English.

    dimensions, units of measurement, physical constants etc. shall be in SI unless otherwise specified. ( Nominal bore pipe sizes to be generally

    in inches ).

    All documents (text, data sheets, specifications etc.) shall be provided with el I ctronic files in the approved and widely used software ( MS Word,

    AutoCad etc.).

  • 14.0 APPENDIX-I : MINIMUM TANK SPACING FROM OPERATING FACILITIES

    2

    3

    4

    6 Small Product Tanks from Exchangers, 15 m (50 ft) Drums, Transformers, Loading Racks

    7 Tanks 1 Tanks Impounding Basins from the Flares : a. Elevated a. 300 m (1 000 ft)

    Diesel Tanks from the Operating Facility

    B

    b. Ground 1 Burn Pit b. 150 m (500 ft) 8 Flow or Storage Tanks from Oil Well 300m (1000ft)

    Tanks from the Electrical Substations and Fire Water Pumping Stations Tanks from the Operation Control

    To be confirmed by Flare Heat Radiation.

    30 m (100 ft)

    5

    - Do -

    60 m (200 ft) 150 m (500 ft)

    - Do -

    - Do - Building Tanks from Heaters 60m (150ft) - Do -

  • DOC. NO. KOC-L-027 I Page 2 1 of 21 REV. 1 ACKNOWLEDGEMENT

    This Standard has been approved by the Standards Technical Committee ( STC ) consisting of the following :-

    Mr. Ali H. Baba ( Standards Div.) Chairman Mr. Mohd. Emam ( Insp.& Corr. Div.) Deputy Chairman Mr. S. Kumar ( Standards Div.) Secretary1 Member Dr. Mohammad llyas ( Standards Div.) Member Mr. Khalid S. AI-Ali ( Maint. Proj. Div.) Member Mr. Henry S. Hill ( Maint. Plng. Div.) Member Mr. Jassem Al- Quraini ( PMD- North ) Member

    The draft of this Standard has been circulated to the KOC User Departments for their review and responses were received from the following :-

    ENGINEERING GROUP

    Gen. Supdt. Engg. Services Gen. Supdt. Proj. Mgmt ( N&W )

    PROD.& EXPORT OPNS. GROUP

    Gen. Supdt. Prod. Services Gen. Supdt. Prod. Opns ( N&W ) Gen. Supdt. Mar.& Export Opn.

    MAJOR PROJECTS GROUP LOSS PREVENTION GROUP

    Gen. Supdt. Engg. Projects ( N&E ) Gen. Supdt. Fire & Safety

    MAINTENANCE GROUP INDUSTRIAL SERVICES GROUP

    Gen. Supdt. Maint. Services. Gen. Supdt. Maint. (S&E) Gen. Supdt. Maint. (N&W)

    Gen. Supdt. Ahmadi Services Gen. Supdt. Transport & Plant

    This KOC Standard for " Layout, Spacing and Diking of Petroleum storage Tanks " has been prepared by the Task Force (TF-LPl02) comprising of the following members :-

    Mr. S, Kumar - Standards Div. - Team LeaderIAuthor Tel. No. 61407 Mr. J. Masood - Engg Design Div. - Member Tel. No. 61322 Mr. Rafiq Khan - Gen. Proj. Div. - Member Tel. No. 61 356 Mr. F.Al-Qattan - Fire & HSE Div. - Member Tel. No. 67389 Mr. Faisal Mirza - Standards Div. - Member Tol. No. 61 151