Upload
ana-bogdanovic-gagi
View
83
Download
3
Embed Size (px)
DESCRIPTION
eci
Citation preview
DC Power forBusiness-Critical Continuity™Standard Control Unit (SCU+)
Controller, SCU+M521B, M522B, M523B, M221B
The next generation Standard Control Unit (SCU+) is a powerful control unit used in DC power applications. The SCU+ enables remote monitoring of the telecom site's AC mains supply, DC power plant, battery backup, site environment, etc.
The SCU+ enables advanced battery management such as sophisticated boost charge control, remaining time prediction, constant current test, scheduled test and fast test. Furthermore, with basic energy saving function, the SCU is surely a cost-efficient product.
The information and alarms, from a specific site, can be monitored or checked by means of a simple web browser or special monitoring software. When using a web browser, no additional software is needed and the web browser login monitor the site is password protected.
Designed for global use, the SCU withstands high telecom standards, and provides great reliability and availability.
Features and Benefits■ Flexible and scalable to satisf y your
present and future needs■ Minimized installation time as a result of
easily configurable file upload/download■ Sophisticated boost charge management
gives long battery life-span■ Automatic battery test including advanced
scheduled test / constant test / fast test■ High quality failure information due to
intelligent alarm setup through using PLC1
■ Lower operating cost due to energy saving standby function for rectifier
1PLC = Programmable Logic Controller
Description
M221B
M521B
M522B
M523B (without Ethernet & RS232 Port )
DC Power forBusiness-Critical Continuity™
Business-Critical Continuity, Emerson Network Powerand the Emerson Network Power logo are trademarks
and service marks of Emerson Electric Co.©2008 Emerson Electric Co.
Emerson Network Power.The global leader in enablingBusiness-Critical Continuity™
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
Standard Control Unit (SCU+)
2008.11
Technical Specifications, SCU+
M521B M522B M523B M221B
Display LCD with 8X16 characters No display
Communication Interface RS232, Ethernet RS 232 RS232, Ethernet
Protocol
HTTP, SNMP √ √ √
YDN23, EEM, SocTpe, Rsoc
√ √ √ √
Inputs
Analog
2 battery currents, 1 load current, 1 bus voltage, 1 battery
voltage, 2 temperatures, 3 AC voltages
2 battery currents, 1 load current, 1 bus voltage, 1 battery voltage, 2 temperatures
Digital
12 load fuses, 6 battery fuses, 2 bi-stable
contactor statues, 2 user inputs
2 load fuses, 2 battery fuses,2 bi-stable contactor statues, 2 user inputs
Outputs2 LVD mono or bistable contactors, 2 user relay
outputs2 LVD mono or bistable contactors, 2 user relay outputs
Ethernet port
RS232 port
LCD
Green: Operating
Red: Major or critical alarm
Functional keys
Yellow: Minor alarm
Ethernet port
RS232 port
Green: Operating
Red: Major or critical alarmYellow: Minor alarm
M221B
M521B
M522B
M523B (without Ethernet & RS232 Port)
GeneralPower Supply 19 to 60VDCPower Consumption 5WOperating Temperature Range - 40℃ to + 75℃/- 40℉ to + 167℉Relative Humidity 0 to 90%EMC EN 300 386, 2001 class B, FCC part 15 class BSafety IEC 60950 -1, EN 60950 -1, UL 60950 -1Approvals CE, UL and NEBS level 3
Mechanical DataDimensions(H×W×D) 86.6×42×211.5mm/34.09×16.5×83.28inchStandard Installation Methods Hot pluggable in stand-alone or embedded power plantsWeight < 0.8 kg / 1.76 Ibs
Examples of Alarms DC Power Plant Alarms AC mains failure, Rectifier failure, DC/DC converter failure, High voltage shutdown,
Fan failure, Thermal derating (of rectifier output due to high temperature)
Inputs/Outputs
Ordering InformationDescription Product Name Product Code
Controller (SCU+) M521B 1M521BAXX M522B 1M522BAXX M523B 1M523BAXX M221B 1M221BAXX
Emerson Network Powerwww.emersonnetworkpower.comwww.emersonenergy.com (Energy Systems, Europe) www.emersonnetworkpower.com/energysystems (Energy Systems, North America)