VERIFY LOCATIONS OF ALL PUBLIC AND PRIVATE UNDERGROUND UTILITIES PRIOR TO PERFORMING ANY ELECTRICAL SITE WORK. COORDINATE ALL DIRECTIONAL BORING WORK WITH CITY.
AutoCAD SHX Text
B.
AutoCAD SHX Text
PROVIDE SCHEDULE 40 PVC FOR ALL UNDERGROUND CONDUITS INDICATED ON THIS PLAN. INSTALL UNDERGROUND CONDUITS A MINIMUM OF 24" BELOW FINISHED GRADE. PROVIDE A GROUNDING CONDUCTOR IN EACH CONDUIT. PROVIDE 1" MINIMUM SIZE FOR UNDERGROUND CONDUITS.
AutoCAD SHX Text
C.
AutoCAD SHX Text
PROVIDE #10 AWG MINIMUM CONDUCTORS FOR ALL SITE LIGHTING CONDUCTORS UNLESS NOTED OTHERWISE.
AutoCAD SHX Text
D.
AutoCAD SHX Text
PROVIDE DIMENSIONED LOCATION, FROM A PERMANENT BENCHMARK(e.g. BUILDING FOOTING/WALL), FOR ALL UNDERGROUND CONDUIT/CABLE ON THE RECORD DRAWINGS.
AutoCAD SHX Text
E.
AutoCAD SHX Text
PROVIDE LIGHT STANDARD BASE FOR EACH NEW POLE/FIXTURE SHOWN ON SITE PLAN. SEE POLE BASE DETAIL 1 AND LIGHT FIXTURE SCHEDULE ON SHEET E200.
AutoCAD SHX Text
PROVIDE NEW PARKING LOT LIGHTING FIXTURE(S), POLE, AND BASE AT THIS LOCATION. PROVIDE NEW CONDUIT, CIRCUITING, WIRING, CONTROLS, ETC. FROM NEAREST EXISTING 277V BUILDING MOUNTED CIRCUIT FOR CONNECTION OF NEW LIGHTING FIXTURE(S) AS INDICATED. REFER TO LIGHTING FIXTURE SCHEDULE AND POLE BASE DETAIL ON SHEET E200 FOR MORE DETAILS.
AutoCAD SHX Text
2
AutoCAD SHX Text
APPROXIMATE LOCATION OF EXISTING BUILDING MOUNTED LIGHTING FIXTURE. PROVIDE CIRCUITING FROM THIS FIXTURE TO NEW LIGHT POLE AS INDICATED.
AutoCAD SHX Text
3
AutoCAD SHX Text
PROPOSED ROUTING OF NEW ELECTRICAL BRANCH CIRCUIT WIRING FOR NEW PARKING LOT LIGHTING FIXTURE FROM EXISTING 277V BUILDING MOUNTED LIGHTING FIXTURE AND CONTROLS. PROVIDE 2#10 + 1#10GND TO FEED NEW LIGHTING AS INDICATED. PROVIDE CIRCUITING AND CONTROLS FROM BUILDING LIGHTING FIXTURE MOUNTED OUTSIDE OF RECEIVING ROOM, MAKE SPLICE CONNECTION INSIDE RECEIVING ROOM, ROUTE DOWN RECEIVING ROOM WALL INTERIOR AND MAKE PENETRATION THOUGH EXTERIOR WALL NEAR GROUND LEVEL WITH CONDUIT BODY, THEN PROVIDE DIRECTIONAL BORING OUT TO POLE MOUNTED LIGHTING FIXTURE. PROVIDE CUTTING AND PATCHING OF EXISTING EXTERIOR CONCRETE SIDEWALK. MAKE ALL FINAL CONNECTIONS AS REQUIRED. FIELD VERIFY OPTIMAL BRANCH CIRCUIT ROUTING THROUGH BUILDING.
AutoCAD SHX Text
4
AutoCAD SHX Text
PROVIDE NEW BOLLARD MOUNT CAR CHARGING STATION AT APPROXIMATE LOCATION SHOWN. PROVIDE CIRCUITING, CONDUIT, WIRING, ETC. AS INDICATED TO NEW CAR CHARGING STATION. PROVIDE NEW CONCRETE BASE WITH ANCHOR BOLTS PER MANUFACTURES RECOMMENDATIONS. VERIFY EXACT LOCATION OF CAR CHARGING STATION WITH CIVIL CONTRACTOR AND OWNER ON SITE. REFER TO SPECIFICATION SECTION FOR MORE DETAILS. PROVIDE CONCRETE BASE PER DETAIL 2 ON SHEET E200.
AutoCAD SHX Text
5
AutoCAD SHX Text
PROVIDE 1"C FROM NEW LP-1-1 PANEL OUT TO APPROXIMATE LOCATION SHOWN FOR FUTURE CAR CHARGING STATIONS. PROVIDE CONDUIT AND JUNCTION BOX MOUNTED ABOVE FROM LP-1-1 IN RECEIVING ROOM, ROUTE FROM RECEIVING ROOM WALL INTERIOR AND MAKE PENETRATION THOUGH EXTERIOR WALL NEAR GROUND LEVEL WITH CONDUIT BODY, THEN PROVIDE DIRECTIONAL BORING OUT TO GRASS AREA INDICATED AND LEAVE CONDUIT BURIED UNDERGROUND. CAP EACH ENDS OF CONDUIT FOR FUTURE USE AND LABEL JUNCTION BOX INSIDE LABELED "FUTURE CAR CHARGING STATION". PROVIDE CUTTING AND PATCHING OF EXISTING EXTERIOR CONCRETE SIDEWALK. FIELD VERIFY OPTIMAL BRANCH CIRCUIT ROUTING THROUGH BUILDING. FOR FUTURE CAR CHARGING STATIONS, CAP ENDS OF CONDUIT AND WIRING FOR FUTURE CONNECTIONS.
AutoCAD SHX Text
6
AutoCAD SHX Text
APPROXIMATE LOCATION OF EXISTING DATA/IT ROOM. VERIFY EXACT LOCATION IN FIELD.
AutoCAD SHX Text
7
AutoCAD SHX Text
APPROXIMATE LOCATION OF EXISTING ELECTRICAL ROOM. VERIFY EXACT LOCATION IN FIELD.
AutoCAD SHX Text
8
AutoCAD SHX Text
APPROXIMATE LOCATION OF EXISTING MSB 800A MAIN ELECTRICAL SWITCHGEAR IN ELECTRICAL ROOM. VERIFY EXACT LOCATION IN FIELD.
AutoCAD SHX Text
9
AutoCAD SHX Text
APPROXIMATE LOCATION OF EXISTING DATA RACK IN DATA ROOM. VERIFY EXACT LOCATION IN FIELD.
AutoCAD SHX Text
10
AutoCAD SHX Text
PROVIDE NEW 208/120V LP-1-1 PANEL AT APPROXIMATE LOCATION SHOWN IN RECEIVING ROOM ALONG OPEN WALL SPACE ALONG EXTERIOR WALL. VERIFY EXACT LOCATION IN FIELD AND WITH OWNER. REFER TO SHEET E200 FOR MORE DETAILS.
AutoCAD SHX Text
11
AutoCAD SHX Text
PROVIDE NEW 112.5KVA TRANSFORMER AT APPROXIMATE LOCATION SHOWN IN RECEIVING ROOM ALONG OPEN WALL SPACE ALONG EXTERIOR WALL. VERIFY EXACT LOCATION IN FIELD AND WITH OWNER. REFER TO SHEET E200 FOR MORE DETAILS.
AutoCAD SHX Text
12
AutoCAD SHX Text
PROPOSED ROUTING OF NEW ELECTRICAL BRANCH CIRCUIT WIRING FOR NEW CAR CHARGING STATION(S) FROM NEW 208/120V LP-1-1 PANELBOARD. PROVIDE 40A/2P BREAKER IN NEW PANELBOARD, 1"C 4#6 + 1#10GND TO FEED NEW CHARGING STATION AS INDICATED. PROVIDE SPARE 1" EMPTY CONDUIT WITH PULL STRING ROUTED PARALLEL TO POWER FEED FOR FUTURE LOW VOLTAGE. STUB INTO BASE AS SHOWN ON BASE DETAIL. PROVIDE CIRCUITING FROM PANELBOARD MOUNTED IN RECEIVING ROOM, ROUTE FROM RECEIVING ROOM WALL INTERIOR AND MAKE PENETRATION THOUGH EXTERIOR WALL NEAR GROUND LEVEL WITH CONDUIT BODY, THEN PROVIDE DIRECTIONAL BORING OUT TO CAR CHARGING STATION. PROVIDE CUTTING AND PATCHING OF EXISTING EXTERIOR CONCRETE SIDEWALK. MAKE ALL FINAL CONNECTIONS AS REQUIRED. FIELD VERIFY OPTIMAL BRANCH CIRCUIT ROUTING THROUGH BUILDING.
AutoCAD SHX Text
13
AutoCAD SHX Text
PROVIDE SAW CUTTING AND PATCHING OF EXISTING EXTERIOR CONCRETE SIDEWALK AT ONE LOCATION NEAR EXTERIOR WALL PENETRATIONS FOR ALL FEEDERS TO EITHER CHARGING STATIONS OR LIGHTING FIXTURE(S). PROVIDE DIRECTIONAL BORING AS REQUIRED.
PROVIDE CHARGEPOINT CAR CHARGING STATION ON CONCRETE BASE
AutoCAD SHX Text
GROUND ALL GROUNDING CONDUCTORS AND GROUND ROD TO GROUND LUG
AutoCAD SHX Text
PROVIDE SPARE 1" PVC CONDUIT STUBBED OUT 12" FROM BASE. CAP CONDUIT.
AutoCAD SHX Text
PROVIDE GAP UNDER STATION TO ALLOW DRAINAGE FROM STATION
AutoCAD SHX Text
PROVIDE 45 DEGREE CHAMFERED EDGE
AutoCAD SHX Text
PROVIDE ANCHOR BOLTS 3" ABOVE BASE. COORDINATE WITH POLE MANUFACTURER FOR SIZE, TYPE AND MOUNTING CONFIGURATION/TEMPLATE.
AutoCAD SHX Text
TIE ANCHOR BOLTS TO VERTICAL REINFORCEMENT RODS
AutoCAD SHX Text
PROVIDE SONOTUBE FORM
AutoCAD SHX Text
24"
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
PROVIDE 4#4 REINFORCEMENT RODS
AutoCAD SHX Text
TYPICAL 1" NOM. DIA. RIGID PVC CONDUIT
AutoCAD SHX Text
24" MIN.
AutoCAD SHX Text
60" MIN.
AutoCAD SHX Text
PROVIDE 3/4" X 15' COPPER COATED GROUND ROD. EXTEND ROD 2" ABOVE CONCRETE BASE.
AutoCAD SHX Text
PROVIDE #3 HORIZONTAL TIES ON 1'-0" CENTERS
AutoCAD SHX Text
4000 PSI CONCRETE AFTER 28 DAYS
AutoCAD SHX Text
PROVIDE 1" PVC CONDUIT AND WIRING STUBBED OUT 12" FROM BASE.
AutoCAD SHX Text
12" MIN.
AutoCAD SHX Text
3" MIN.
AutoCAD SHX Text
FIRST FLOOR
AutoCAD SHX Text
1
AutoCAD SHX Text
MECH/ELEC ROOM
AutoCAD SHX Text
EXIST. MSB 800A
AutoCAD SHX Text
NUMBER
AutoCAD SHX Text
1 1/2"C. 3#3/0 & 1#6 GND.
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
1
AutoCAD SHX Text
EXISTING 800A MAIN SWITCHGEAR (MSB). MSB IS A GE MSB IS A GE SPECTRA SERIES SWITCHBOARD WITH SPECTRA RMS BREAKERS. REFER TO E100 FOR APPROXIMATE REFER TO E100 FOR APPROXIMATE LOCATION. PROVIDE NEW 112.5KVA TRANSFORMER. SEE SCHEDULE ON THIS SHEET FOR DETAILS. COORDINATE WITH CONTRACTOR ON SITE FOR EXACT MOUNTING LOCATION. PROVIDE NEW 400A 208/120V 3PH, 4W PANELBOARD. SEE PANELBOARD SUMMARY SCHEDULE ON THIS SHEET FOR DETAILS. COORDINATE WITH CONTRACTOR ON SITE FOR EXACT MOUNTING LOCATION. PROVIDE 4" CONCRETE HOUSEKEEPING PAD FOR THIS PIECE OF EQUIPMENT. PROVIDE NEW 200A/3P BREAKER IN EXISTING 800A MSB SWITCHBOARD OPEN SPACE. MSB IS A GE SPECTRA SERIES SWITCHBOARD WITH SPECTRA RMS BREAKERS. EXISTING UTILITY TRANSFORMER SHOWN FOR REFERENCE ONLY.
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
A.
AutoCAD SHX Text
FIELD VERIFY OPTIMAL ROUTING OF ALL NEW FEEDERS THROUGHOUT EXISTING BUILDING.
AutoCAD SHX Text
1
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
RATING
AutoCAD SHX Text
LOCATION
AutoCAD SHX Text
NAME
AutoCAD SHX Text
VOLTS
AutoCAD SHX Text
MOUNTING
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
MAINS
AutoCAD SHX Text
AMP
AutoCAD SHX Text
QUANTITY OF BREAKERS
AutoCAD SHX Text
1-POLE
AutoCAD SHX Text
2-POLE
AutoCAD SHX Text
3-POLE
AutoCAD SHX Text
SPACES
AutoCAD SHX Text
TOTAL
AutoCAD SHX Text
POLES
AutoCAD SHX Text
A.I.C.
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
%%C/WIRE
AutoCAD SHX Text
LP-1-1
AutoCAD SHX Text
RECEIVING
AutoCAD SHX Text
SURFACE
AutoCAD SHX Text
(5) 40A
AutoCAD SHX Text
14
AutoCAD SHX Text
208/120V
AutoCAD SHX Text
MCB
AutoCAD SHX Text
400
AutoCAD SHX Text
30
AutoCAD SHX Text
10,000
AutoCAD SHX Text
3%%C/4W
AutoCAD SHX Text
NEW
AutoCAD SHX Text
LP-1-1
AutoCAD SHX Text
400A
AutoCAD SHX Text
3"C. 4#500 & 1#3 GND.
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
RECEIVING ROOM
AutoCAD SHX Text
TRANSFORMER
AutoCAD SHX Text
2
AutoCAD SHX Text
4
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
(6) 20A
AutoCAD SHX Text
PRIMARY OVERCURRENT DEVICE
AutoCAD SHX Text
PROVIDE 4" CONCRETE HOUSE KEEPING PAD FOR TRANSFORMER. REFER TO SPECIFICATION SECTION 26.05.60 FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
1.
AutoCAD SHX Text
TRANSFORMER SCHEDULE NOTES:
AutoCAD SHX Text
200A
AutoCAD SHX Text
MSB
AutoCAD SHX Text
480V DELTA
AutoCAD SHX Text
T-1
AutoCAD SHX Text
112.5
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
LOCATION
AutoCAD SHX Text
NAME
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
PRIMARY
AutoCAD SHX Text
1
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
K4
AutoCAD SHX Text
208/120V, 3P, 4W, WYE
AutoCAD SHX Text
MOUNTING
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
K-RATING
AutoCAD SHX Text
SECONDARY
AutoCAD SHX Text
GROUND ALL TRANSFORMERS AS PER SPECIFICATION SECTION 26.05.26 AND THE NEC.
AutoCAD SHX Text
1.
AutoCAD SHX Text
TRANSFORMER SCHEDULE NOTES:
AutoCAD SHX Text
5
AutoCAD SHX Text
5
AutoCAD SHX Text
TRANSFORMER
AutoCAD SHX Text
6
AutoCAD SHX Text
EXIST. UTILITY
AutoCAD SHX Text
6
AutoCAD SHX Text
112.5KVA
AutoCAD SHX Text
11,200 AFC
AutoCAD SHX Text
11,109 AFC
AutoCAD SHX Text
7191 AFC
AutoCAD SHX Text
T-1
AutoCAD SHX Text
1
AutoCAD SHX Text
POLE BASE DETAIL
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
PROVIDE POLE WITH HANDHOLE W/GASKETED COVER
AutoCAD SHX Text
PROVIDE IN-LINE FUSE KIT ACCESSIBLE FROM HANDHOLE
AutoCAD SHX Text
GROUND ALL GROUNDING CONDUCTORS AND GROUND ROD TO GROUND LUG
AutoCAD SHX Text
PROVIDE SPARE 3/4" PVC CONDUIT STUBBED OUT 6" FROM BASE. CAP CONDUIT.
AutoCAD SHX Text
PROVIDE BASE COVER
AutoCAD SHX Text
PROVIDE GAP UNDER POLE TO ALLOW DRAINAGE FROM POLE
AutoCAD SHX Text
PROVIDE 45 DEGREE CHAMFERED EDGE
AutoCAD SHX Text
PROVIDE ANCHOR BOLTS. COORDINATE WITH POLE MANUFACTURER FOR SIZE, TYPE AND MOUNTING CONFIGURATION/TEMPLATE.
AutoCAD SHX Text
TIE ANCHOR BOLTS TO VERTICAL REINFORCEMENT RODS
AutoCAD SHX Text
PROVIDE SONOTUBE FORM
AutoCAD SHX Text
24"
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
6"
AutoCAD SHX Text
PROVIDE 4#4 REINFORCEMENT RODS
AutoCAD SHX Text
TYPICAL RIGID PVC CONDUIT (SEE PLAN FOR SIZE)
AutoCAD SHX Text
6"
AutoCAD SHX Text
24" MIN.
AutoCAD SHX Text
6'-0" MIN.
AutoCAD SHX Text
PROVIDE 3/4" X 15' COPPER COATED GROUND ROD. EXTEND ROD 2" ABOVE CONCRETE BASE.
AutoCAD SHX Text
PROVIDE #3 HORIZONTAL TIES ON 1'-0" CENTERS
AutoCAD SHX Text
4000 PSI CONCRETE AFTER 28 DAYS
AutoCAD SHX Text
1.
AutoCAD SHX Text
PROVIDE FIXTURE MOUNTED TO NEW POLE AS INDICATED ON NEW CONCRETE BASE PER DETAIL 1 ON THIS SHEET.