sspfc converter ieee paper

Embed Size (px)

Citation preview

  • 8/10/2019 sspfc converter ieee paper

    1/12

    4882 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 56, NO. 12, DECEMBER 2009

    An Improved ACDC Single-Stage Full-BridgeConverter With Reduced DC Bus Voltage

    Pritam Das, Shumin Li, and Gerry Moschopoulos,Member, IEEE

    AbstractA new acdc single-stage voltage-fed pulsewidth-modulation (PWM) full-bridge converter is proposed in this paper.The converter can simultaneously perform input power factorcorrection and dcdc conversion using conventional phase-shiftPWM and can maintain a primary-side dc bus voltage of lessthan 450 V even at a high input line voltage of 265 Vrms. Thisis a combination of features that few, if any, other converters ofthe same type have. The proposed converter has these featuresdue to the novel implementation of an asymmetrical auxiliarytransformer winding that is placed in series with the input in-ductor and acts as a boost switch. In this paper, the operationof the proposed converter is explained in detail, its outstanding

    features are discussed, and a detailed design procedure is givenand demonstrated with an example. Experimental results thatconfirm the feasibility of the converter and its ability to meetIEC1000-3-2 Class D standards for electrical equipment are alsopresented in this paper.

    Index TermsACDC power conversion, full bridge, magneticswitch, power factor correction (PFC), single-stage converters.

    I. INTRODUCTION

    ACDC rectifiers are usually implemented with a boost

    converter that performs power factor correction (PFC)

    as the front-end converter and an isolated dcdc converter

    that produces the required output voltage. The dcdc converter

    is typically a flyback or a forward converter for low-powerapplications and a full-bridge converter for higher power appli-

    cations. ACDC rectifiers can be used as stand-alone converters

    or can be used as paralleled modules.

    Due to the cost and complexity involved in implementing two

    separate switch-mode converters, there has been considerable

    interest by power electronics researchers to try to combine

    both acdc PFC and isolated dcdc conversion into a single

    converter. As a result, there have been numerous publications

    on the topic of single-stage acdc converters, particularly for

    low-power (

  • 8/10/2019 sspfc converter ieee paper

    2/12

    DAS et al.: IMPROVED ACDC SINGLE-STAGE FULL-BRIDGE CONVERTER WITH REDUCED VOLTAGE 4883

    control, which makes it difficult to optimize their de-

    sign as they must be able to operate over a wide range

    of switching frequency. For example, the characteris-

    tics of the voltage-fed resonant converters proposed in

    [20][24] with respect to the dc bus capacitor voltage

    are dependent on the fine tuning of the resonant tank

    components.4) They are current-fed converters with a boost inductor

    connected to the input of the full-bridge circuit [24]

    [26]. They can achieve a near-unity input pf but lack

    an energy-storage capacitor across the primary-side dc

    bus. The absence of such a capacitor can result in the

    appearance of high voltage overshoots and ringing across

    the dc bus whenever a converter switch is turned off,

    unless some preventative measure is implemented, which

    results in a loss of efficiency. It also causes current-fed

    single-stage converters to have an output voltage with a

    large low-frequency 120-Hz ripple that restricts their use

    to applications where a tightly regulated output voltage is

    not required.

    In [27], a promising single-stage voltage-fed PWM full-

    bridge converter was proposed, but its characteristics were not

    well known, and thus, its strengths were not properly taken

    advantage of; this topology will be the focus of this paper.

    In this paper, the operation of the converter is explained and

    analyzed in detail, its outstanding features are discussed, and

    a detailed design procedure is given and demonstrated with

    an example. Experimental results that confirm the feasibility

    of the converter and its ability to meet IEC1000-3-2 Class D

    standards for electrical equipment [30] are also presented in

    this paper. The proposed single-stage voltage-fed PWM full-bridge converter has none of the aforementioned drawbacks

    and is, thus, superior to other previously proposed converters of

    the same typeincluding converters such as the ones proposed

    in [11], [16], [18], and [19] in previous editions of these

    transactions.

    II. CONVERTERO PERATION

    The converter shown in Fig. 1 operates like a standard PWM

    full-bridge converter. Energy is transferred from the dc bus

    capacitorCb whenever a pair of diagonally opposed switches

    is on. No energy is transferred when the converter is in afreewheeling mode of operation, where the two top switches or

    the two bottom switches are both on and the voltage across the

    transformer primary is zero. By appropriately alternating the se-

    quence of energy transfer and freewheeling modes, an ac square

    voltage is impressed across the transformer primary winding,

    which is then stepped down by the transformer, rectified by

    the output diodes, then filtered by the output inductorcapacitor

    (LC)filter to produce an output dc voltage.While it is performing dcdc conversion, the converter is

    also performing input PFC due to the transformer winding

    Naux, which is an auxiliary winding taken from the main powertransformer. A voltage is impressed across the main transformer

    primary winding whenever switches S2 and S3 are on. Thepolarity of this voltage is such that it causes a voltage with a

    Fig. 1. Proposed single-stage full-bridge converter.

    Fig. 2. Discontinuous input current waveform.

    polarity that counteracts the dc bus voltage to appear across the

    auxiliary winding so that a net positive voltage is impressed

    across the input inductor and the input current rises. When the

    converter operates in a freewheeling mode of operation so that

    the voltage across the main primary transformer winding is zero

    or when switches S1 and S4 are on so that this voltage is ofdifferent polarity, then the net voltage across the input inductor

    is negative, and the input current falls.

    The rise and the fall of the inductor current during a converter

    switching cycle are analogous to that of the inductor current in

    a boost converter. Activating the asymmetric auxiliary winding

    will counteract the dc bus capacitor voltage, which is the same

    as turning the boost-converter switch on in a boost converter.

    Deactivating the asymmetric auxiliary winding will impress

    the dc bus capacitor voltage at the right-hand end of the input

    inductor in Fig. 1, and this is the same as turning the boost-

    converter switch off. The winding is asymmetric, as the input

    current rises only when switchesS2

    andS3

    are on. The inputcurrent in the proposed converter can be shaped to improve

    the input pf, as can be done in a standard acdc boost PFC

    converter. If the input current is made discontinuous, as shown

    in Fig. 2, then an excellent input pf can be achieved.

    The proposed converter goes through several modes of op-

    eration during a switching cycle. Typical converter waveforms

    for a single switching cycle with a discontinuous output current

    and a discontinuous input current are shown in Fig. 3, and

    the equivalent circuit diagrams for each mode of operation are

    shown in Fig. 4. The converter goes through the following

    modes of operation during a switching cycle.

    Mode 1 (t0t1): In this mode, S2 and S3 are on, and

    auxiliary diodeDaux1 and output diodeD1are forward biased.The current in the output inductor is rising and so does the input

  • 8/10/2019 sspfc converter ieee paper

    3/12

    4884 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 56, NO. 12, DECEMBER 2009

    Fig. 3. Typical waveforms describing the modes of operation.

    current ifvs,k > NxVbus(Nx = Naux : N1); otherwise, therewill be no current in the input inductor. The slope of the risinginput current can be expressed as

    diin,kdt

    = vs,k+ (Nx 1) Vb

    Lin. (1)

    At the end of this mode, the input current reaches a peak of

    Iin,k(t1) = [vs,k+ (Nx 1) Vb] D Tsw

    2Lin(2)

    where vs,k is the magnitude of the rectified input voltage atthek th switching period, Nx= Naux : N1, whereNaux is the

    number of turns on the auxiliary winding andN1is the numberof turns on the primary winding,Vbis the dc bus voltage acrossenergy-storage capacitor Cb, D is the duty ratio, and Tsw isthe switching period. The slope of the output current can be

    described by

    diout,kdt

    =VbN VoLo

    (3)

    and it reaches its peak value at the end of the interval when

    t= t1. The output current is discontinuous, and its peak valuecan be expressed by

    Iout,k(t1) = 12 V

    bN Vo

    DTswLo

    (4)

    where N is the turns ratio of the primary winding N1 to thesecondary windingN2,Vo is the regulated output voltage, andLois the output filter inductance current.

    Mode 2 (t1t2): At t1, S2 is turned off, and the primarycurrent starts to charge and discharge switch capacitors Cs2andCs1; this mode ends with fully charging and discharging ofCs2

    andCs1.Mode 3(t2t3): At the start of this mode, the output current

    starts freewheeling through D1 andD2 and so does the inputcurrent through Daux2 and Daux1, charging up the dc buscapacitor. In this mode, the input and the output currents are

    decreasing, and the transformer primary current freewheels

    throughS1 and S3. Sometime during this mode, S1 is turnedon with zero-voltage switching (ZVS). This mode ends with the

    output current reducing to zero. The negative voltage vs,k Vbacross inductor Lin forces the current to fall linearly with aslope of

    diin,k

    dt =

    vs,k Vb

    Lin . (5)

    The input currentIin,k(t2)att = t3is

    Iin,k(t3) =Iin,k(t2) +(vs,k Vb)(1 D)Tsw

    2Lin. (6)

    Also, during this interval, the output inductor current Iout,kfallswith a slope of

    diout,kdt

    = VoLo

    . (7)

    Mode 4(t3t4): In this mode, the input current continues todecrease, freewheeling through Daux1 andDaux2. This modeends with the turning off ofS3.

    Mode 5(t4t5): This mode begins with the primary currentcharging and discharging switch capacitors Cs3 and Cs4 andends with the full charging and discharging of these capacitors.

    Mode 6 (t5t6): During this mode, the primary currentflows through the body diodes of S1 and S4, and the inputcurrent continues to flow throughDaux2 due to the asymmetryof the transformer auxiliary winding. This mode ends with the

    turning on of S4 with ZVS. The slope of the input current,which is still decreasing in this mode, is given by

    diin,kdt

    = vs,k VbLin

    . (8)

    Mode 7(t6t7): The primary current flows through switchS1 and the body diode of S4 during this mode, while theinput current decreases as it flows through Daux2. This modeends with the body diode current in S4 reducing to zero andeventually flowing through the switch. The output capacitor

    feeds energy to the output load fromt3to t7.Mode 8(t7t8): During this mode, the output current rises

    again, flowing throughD2, and the input current still decreasesas it flows through Daux2. This mode ends with the inputcurrent reducing to zero.

    Mode 9 (t8t9): The output current continues to increaseduring this mode, and there is no current flowing in the input

  • 8/10/2019 sspfc converter ieee paper

    4/12

    DAS et al.: IMPROVED ACDC SINGLE-STAGE FULL-BRIDGE CONVERTER WITH REDUCED VOLTAGE 4885

    Fig. 4. Equivalent circuit diagrams for the modes of operation.

  • 8/10/2019 sspfc converter ieee paper

    5/12

    4886 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 56, NO. 12, DECEMBER 2009

    Fig. 5. Single-stage voltage-fed PWM converter proposed in [11].

    section of the converter. This mode ends with the turning

    off ofS1.Mode 10(t9t10): This mode begins with the transformer

    primary current charging and discharging switch capacitors Cs1andCs2 and ends with the complete charging and dischargingofCs1 and Cs2.

    Mode 11(t10t11): The output current freewheels throughD1 andD2 during this mode. This mode ends with the outputand the transformer primary currents reducing to zero. S2 isturned on with ZVS sometime during this mode.

    Mode 12 (t11t12): There is no current flowing in theconverters input section, the full-bridge circuit, and the output

    diodes during this mode; the output capacitor feeds the load.

    Sometime during this mode,S4 is turned off with zero-currentswitching (ZCS). This mode ends with S3 getting turned onwith ZVZCS, and a new switching cycle is commenced.

    III. CONVERTERC HARACTERISTICS

    The concept of using an auxiliary transformer winding to

    simulate a boost switch so that the input current can rise

    and fall appropriately to ensure a very good input factor has

    been proposed for use in a number of low-power single-stage

    acdc flyback and forward converters [2], [4], [10]. It has,

    however, never been implemented in a single-stage voltage-

    fed PWM full-bridge converter with the sole exception of the

    one proposed in [11]. It is the use of an auxiliary winding as a

    magnetic switch that allows standard phase-shift PWM control

    to be used, and the converter in [11] has been the only single-

    stage full-bridge converter that can operate with this control.

    The converter that was proposed in that paper, which is shown

    in Fig. 5, can only operate with a very high dc bus voltage thatwas almost 600 V under high-line conditions. The differences

    between these two converters will be explained in this section.

    A. Difference in Number of Auxiliary Windings

    The auxiliary windings in both the proposed converter and

    the converter proposed in [11] can be considered to be like

    switches that conduct current during the time that a voltage

    of appropriate polarity is impressed across the transformer

    primary.

    Consider the operation of the dcdc full-bridge section

    of both converters during a single switching cycle. In bothconverters, a voltage of one polarity is impressed across the

    transformer; then, a freewheeling mode occurs when no voltage

    is impressed; thereafter, a voltage of the opposite polarity

    is impressed across the transformer primary; finally, another

    freewheeling mode occurs.

    For the proposed converter, the sequence of events from the

    point of view of the converters input section that matches this

    sequence is as follows: The auxiliary winding switch Naux ison, the auxiliary winding switch is off, the auxiliary winding

    switch is off, and the auxiliary winding switch is off.

    For the converter proposed in [11], the sequence of events

    from the point of view of the converters input section that

    matches the sequence at the dcdc full-bridge section is as

    follows: The auxiliary winding switch Naux1 is on, bothauxiliary winding switches are off, the auxiliary winding

    switchNaux2 is on, and both auxiliary winding switchesare off.

    By referring to the typical waveforms shown in Fig. 3, it

    can be seen that the rise and the fall of the input current

    in the proposed converter occur once during a full switching

    cycle due to the fact that the converter has only one auxiliary

    winding switch. The rise and the fall in the current in the

    output inductor, however, occur twice during a switching cycle.

    For each rise and fall of the input inductor current, energy is

    transferred from the ac source to the dc bus capacitor, whereas,

    for each rise and fall of the output inductor current, energy is

    transferred from the dc bus capacitor to the output load. During

    each switching cycle, energy is transferred from the ac source

    to the dc bus once, whereas energy is transferred from the dc

    bus capacitor twice. It is a fact that there is only one auxiliary

    winding that causes this 1 : 2 ratio of energy input to the dc bus

    capacitor to energy output to exist.

    By comparison, the converter proposed in [11] has twoauxiliary windings so that the rise and the fall of the input

    current will occur twice in a switching cycle, just as the rise

    and the fall of the output inductor current does. It is a fact that

    there are two auxiliary winding switches that cause this 2 : 2

    (or 1 : 1) ratio of energy input to the dc bus capacitor to energy

    output to exist.

    The dc bus voltage in single-stage converters is uncontrolled,

    as these converters have only one controller that is used to

    regulate the output voltage. This voltage is, instead, depen-

    dent on the energy equilibrium that must exist at the dc bus

    capacitorthe amount of energy or charge that is fed into this

    capacitor must be equal to the amount of energy or charge thatis removed from the capacitor during a half line cycle (half of

    a 60-Hz cycle because the input line is rectified by the diode

    rectifier).

    The fact that the proposed converter has a 1 : 2 ratio of energy

    input to the dc bus capacitor to energy output instead of a 1 : 1

    ratio, which is what the converter proposed in [11] has, means

    that this capacitor is allowed to discharge more frequently than

    it is allowed to be charged. This affects its energy equilibrium

    so that its voltage is lower than that of the converter proposed in

    [11]. In summary, the use of a single auxiliary winding, instead

    of the two that are used in the converter proposed in [11], helps

    reduce the dc bus voltage so that it is easier to ensure that it

    does not exceed the 450-Vdcstandard that has been accepted inthe literature.

  • 8/10/2019 sspfc converter ieee paper

    6/12

    DAS et al.: IMPROVED ACDC SINGLE-STAGE FULL-BRIDGE CONVERTER WITH REDUCED VOLTAGE 4887

    Fig. 6. Input voltage waveform and input current envelope showing the deadangle .

    B. Difference in Auxiliary Winding/Transformer Primary

    Winding Turns Ratio

    Unlike the converter proposed in [11], the auxiliary winding

    in the proposed converter is designed so that it does not com-

    pletely cancel out the voltage across the dc bus capacitor. This

    means that some, but not all, of the diode bridge rectifier output

    voltage is placed across the input inductor. This can reduce the

    amount of energy placed in the input inductor when switches S2and S3are on, which, in turn, reduces the amount of energy thatis transferred to the dc bus capacitor during the time when both

    these switches are not on. The reduction in energy placed into

    the input inductor affects the energy equilibrium of the dc bus

    capacitor in a way that reduces the dc bus voltage and makes it

    lower than what it is in the converter proposed in [11].

    The input section of the converter is made to operate indiscontinuous current mode so that a high pf is achieved.

    Making the number of auxiliary winding turns different from

    the number of transformer primary winding turns, however,

    introduces deadband regions in the zero-crossing sections of the

    input current waveform, as shown in Fig. 6. This is because the

    diode-bridge diodes are reverse biased when the input voltage

    is low, and current is not allowed to flow in the input inductor

    as the dc bus voltage is not fully cancelled out by the auxiliary

    winding.

    This means that a compromise must therefore be made

    between the input pf and the dc bus voltage reductionthe dc

    bus voltage of the proposed converter can be kept lower than450 Vdc but with some current distortion. The converter can

    be designed to operate with a near-unity pf but with a dc bus

    voltage which may be greater than 450 Vdc yet still lower than

    that of the converter proposed in [11].

    C. Transformer Primary Current DC Offset

    The fact that the proposed converter has a single auxiliary

    winding means that its transformer primary current will have

    some dc offset. Current can flow through the auxiliary winding

    when the voltage across the transformer forward biases Daux1and reverse biases Daux2, but current cannot flow through

    the winding when the voltage across the transformer windingforward biasesDaux2 and reverse biasesDaux1.

    When current flows through the auxiliary winding, the trans-

    former primary current is the sum of the reflected current

    from the secondary and that from the auxiliary winding. When

    current does not flow through the auxiliary winding, the pri-

    mary current is only the reflected current from the secondary.

    The transformer should be designed to accommodate this dc

    offset like any other transformer that must operate without fulldemagnetization.

    Due to the presence of the auxiliary winding and the way it

    is implemented, the proposed converter is currently the only

    voltage-fed single-stage acdc full-bridge converter that can

    operate with standard phase-shift PWM and with a dc bus

    voltage that does not exceed the standard accepted voltage of

    450 Veven if its input voltage is the maximum high line

    voltage of 265 Vrms.

    IV. CONVERTERD ESIGN

    A procedure for the design of the converter is presented

    in this section and is demonstrated with an example. For the

    example, the converter is to be designed according to the fol-

    lowing specifications: output voltageVo= 48V, input voltageVin = 90265Vrms, output power Po = 600W, and switchingfrequency fsw = 1/Tsw = 50kHz. The dc bus capacitor shouldnot exceed 450 V for any operating condition. Since the design

    will follow IEC1000-3-2 Class D standards for harmonic con-

    tent, a pf ranging between 0.88 and 0.95 and a total harmonic

    distortion (THD) that is less than or equal to 45% will be

    considered acceptable [2].

    Step 1Establish Appropriate Value for Maximum

    Converter Duty Cycle Dmax: The maximum duty cycles

    Dmax that the converter can operate with are determined bythe switch and the controller that are used. A typical value of

    Dmax would be 0.7, as many controllers for phase-shift PWMfull-bridge converters use current-sensing transformers that

    require a certain amount of time to reset [2], [11], [29]. The

    value ofDmaxthat will be used in this example is Dmax= 0.7.Step 2Determine Value for Output Inductor Lo: The

    output inductor should be designed so that the output current is

    made to be discontinuous under all operating conditions. This is

    to avoid the possibility of the primary-side dc bus voltageVbusto exceed 450 V, which may happen under certain operating

    conditionsparticularly if the input inductor is designed so

    that the input current is made to be always discontinuous andthus bounded by a sinusoidal envelope. This phenomenon is

    common to all voltage-fed single-stage acdc converters and is

    explained in detail in [15].

    The maximum value ofLo should be the value ofLo withwhich the converters output current will be on the boundary be-

    tween being continuous and discontinuous when the converter

    is operating with minimum input voltage, maximum duty cycle

    (Dmax), and full load (Po,max). If this condition is met, thenthe output current will be discontinuous for all other converters

    operating conditions. The maximum value ofLo can thereforebe determined to be

    Lo,max= V2o

    Po,max(1 Dmax)

    2Tsw

    2 . (9)

  • 8/10/2019 sspfc converter ieee paper

    7/12

    4888 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 56, NO. 12, DECEMBER 2009

    Substituting Po,max= 600W, Vo = 48V, Tsw = 20 s, andDmax = 0.7 established in Step 1 gives Lo,max = 6 H. Thevalue ofLoshould be close to the maximum to try to minimizethe output peak current but slightly lower to provide some

    margin; therefore, a value ofLo = 5H is chosen.Step 3Determine Values for Turns Ratio of Auxiliary

    TransformerNx: Nx should be made to be less than one toavoid placing the full input voltage across Lin when energy isto be placed in this inductor. As was explained in the previous

    section, not placing the full input voltage acrossLin results inan energy equilibrium at Cbthat results in a lower value ofVbus.IfNxis made to be too low, however, then the input current willbecome very distorted and unable to meet the desired harmonic

    standards, as current cannot flow through L in when the inputvoltage is less than (1 Nx) Vbus. The input current willtherefore be a discontinuous waveform that will be confined to

    an envelope with deadbands as shown in Fig. 6. The deadband

    anglecan be written as

    = sin1

    (1 Nx)VbusVm

    (10)

    whereVmis the peak value of the input voltage andVbus is thedc bus voltage.

    If it is assumed that the most significant input current har-

    monics will be low-order harmonics that are dependent on the

    shape of the envelope, then a Fourier series analysis of the

    envelope waveform can be performed to derive the following

    equations for input pf and THD, as was done in [28]:

    pf=2 1

    2sin 2

    A2(11)

    where

    A=

    2

    3

    2sin2 + ( 2)sin2 (12)

    pf= 1THD100

    2+ 1

    . (13)

    Graphs of the input pf and the THD versus Nx, such asthe ones shown in Fig. 7, can be generated for Vin = 100 and230 Vrms using (11)(13). Vin = 100 and 230 Vrms are thestandard voltages for which harmonic measurements are made

    to confirm compliance with IEC1000-3-2 specifications. Thecurves in Fig. 7 will be valid no matter what the load is, as

    theVbus in a single-stage voltage-fed converter will not changewith the load ifVin is fixed and if both the input and the outputinductor currents are discontinuous [11], [15].

    The values of Vm= 100 1.414 = 141.14 V and Vbus =180 V are used for the 100-Vrms curves, and the values ofVm= 230 1.414 = 325V and Vbus = 360V are used for the230-Vrms curves for the graphs in Fig. 7. TheVbus values thatare used to generate the curves are estimated values but are valid

    estimates, as the dc bus voltage must always be just slightly

    higher (3040 V) than the input voltage if the Vbus < 450 Vcriterion is to be met over the universal input line range. The

    actual values ofVbusmay be slightly higher or lower, and thus,the graphs in Fig. 7 will not be much different. A value of

    Fig. 7. Variation of THD (in percent) and pf for different values of auxiliarywinding turns ratio at input voltages of 100 and 230 Vrms.

    Nx= 0.7is chosen from these graphs, as it is the highest valueofNxthat ensures that the input current satisfies the harmonicstandard requirements.

    Step 4Determine Value for Turns Ratio of Main

    TransformerN: The value ofNaffects the primary-side dcbus voltage, as it determines how much reflected load current

    is available at the transformer primary to discharge the bus

    capacitor Cb. If N is high, then Vbus can be low, but theprimary current may be too high to be practicaldepending

    on the switching and conduction losses. If a lower value ofNis used to reduce the primary current, then the primary current

    that is available to discharge Cb may be low, and thus, Vbus

    may become excessive under certain operating conditions (i.e.,high line).

    The minimum value ofNcan be found by considering thecase when the converter must operate with minimum input line

    and, thus, minimum primary-side dc bus voltage Vbus,min andmaximum duty cycle Dmax. If the converter can produce the re-quired output voltage and can operate with discontinuous input

    and output currents in this case, then it can do so for all cases.

    Since Lo was designed in Step 2 to make the output currentdiscontinuous but close to being continuous when the converter

    is operating under these conditions, the following constraint

    based on standard full-bridge operation can be placed on N:

    N Vbus,min

    VoDmax. (14)

  • 8/10/2019 sspfc converter ieee paper

    8/12

    DAS et al.: IMPROVED ACDC SINGLE-STAGE FULL-BRIDGE CONVERTER WITH REDUCED VOLTAGE 4889

    TABLE ICOMPONENTVALUES FOR PROPOSEDCONVERTER ANDCONVERTER IN [11]

    A value ofVbus = 160 V can be estimated for Vin = 90Vrmsusing the reasoning described in Step 3. Substituting

    Vbus = 160 V, Vo = 48 V, and Dmax= 0.7 into (14)results inN 2.3. A value ofN= 2.5is chosen.

    With a value of N established, the actual value of Vbuscan now be determined more precisely by using the following

    equation, which is based on standard full-bridge operation with

    a discontinuous output current:

    Vbus,min = NVo+

    V2o +

    16Po,maxLoTswD2max

    2

    . (15)

    Substituting Vin = 90 Vrms, Po= 600 W, and Dmax = 0.7 intothis equation givesVbus,min = 166V.

    Step 5Determine Value for Input InductorLin: The valuefor L in should be low enough to ensure that the input currentis fully discontinuous under all operating conditions, but not so

    low as to result in excessively high peak currents. For the case

    whereLin is such that the input current remains discontinuousfor all operating conditions, then the average input power can

    be expressed as

    Pin =

    1

    |vs,k|is,kdSut (16)

    where is calculated from (10), |vs,k| =Vm| sin2fSutk| isthe magnitude of the rectified input voltage at the kth switchinginterval,fSu is the input ac frequency, and

    tk= kTsw (17)

    is,k=1

    8

    D2NxLinfsw

    |vs,k| + (Nx 1)Vbus

    1 |vs,k |Vbus

    for |vs,k| >(1 Nx)Vbus = 0

    for |vs,k|

  • 8/10/2019 sspfc converter ieee paper

    9/12

    4890 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 56, NO. 12, DECEMBER 2009

    TABLE IIPERFORMANCE FACTOR C OMPARISON BETWEENPROPOSEDCONVERTER ANDCONVERTER IN [11]

    Fig. 8. Typical input voltage and current waveforms.Vin = 110Vrms; Po =600W; scale: V = 75V/div., I = 10A/div., and t = 4ms/div.

    over the full line cycle but would become continuous at

    certain parts of the cycle. This would make the input cur-

    rent even more distorted and would reduce the input pf.

    4) The switches in the converter proposed in [11] operatewith greater rms currents because the reflected currents

    from both the main and the auxiliary windings of the

    transformer are higher due to the lower turns ratios of the

    main and the auxiliary transformer windings.

    5) The secondary output diodes in the converter proposed in

    [11] operate with a higher peak voltage because of the

    lower main transformer winding turns ratio.

    V. EXPERIMENTALR ESULTS

    An experimental prototype was built to verify the feasibility

    of the proposed converter. It was designed for the follow-ing specifications: input voltage Vin = 90265 Vrms, outputvoltageVo = 48V, maximum output power Po,max = 600 W,and switching frequency fsw = 50 kHz. The converter wasimplemented with the following parameters: Lin = 16 H,Lo = 5H,N =N1 : N2 = 2.5, andNx= Naux : N1 = 0.7.IRFP460 MOSFETs were used for switches S1S4, andDaux1 and Daux2 are implemented with GaAs Schottky diodesDGSK40-025A, while output rectifier diodes are implemented

    with GaAs Schottky diodes DGS20-018A. A standard UC3879

    IC was used as the controller.

    Fig. 8 shows the input voltage and the input current wave-

    forms when the converter is operating with Vin = 110 Vrms

    and Po = 600W. Fig. 9 shows the transformer primary voltagewaveform when the converter is operating with Vin = 110Vrms

    Fig. 9. Typical transformer primary voltage, input inductor current, and outputcurrent at 110-Vrms input and 600-W output. Scale: Vpri = 100 V/div.,ILin = 10A/div., ILo = 5A/div., and t = 10

    s/div.

    Fig. 10. Typical transformer primary voltage and current waveform.Vin =110 Vrms; Po = 600 W; scale: V = 125 V/div., I = 15 A/div., and t =

    5 s/div.

    andPo = 600W, along with the input and the output inductorcurrent waveforms. From the waveforms in Fig. 9, it can be

    seen that the frequency of the input inductor current is half that

    of the output inductor current; this difference in frequency is

    due to the asymmetrical auxiliary winding. Fig. 10 shows the

    typical transformer primary voltage and current waveforms.

    Fig. 11 shows a typical dc bus voltage waveform. Fig. 12

    shows the typical auxiliary diode waveforms. Fig. 13 shows the

    experimental converter efficiency, which is around 92% at full

    load. This is comparable to that of a conventional two-stage

    converter.

    Fig. 14 shows the dc bus voltage Vbus versus the output loadfor various input voltages; it can be seen that the dc bus voltage

  • 8/10/2019 sspfc converter ieee paper

    10/12

    DAS et al.: IMPROVED ACDC SINGLE-STAGE FULL-BRIDGE CONVERTER WITH REDUCED VOLTAGE 4891

    Fig. 11. Typical dc bus voltage measured at 265-Vrms input and 100-Woutput (V = 60V/div. and t = 10ms/div.).

    Fig. 12. (a) Typical voltage and current through auxiliary diode Daux1(V = 60V/div., I = 5A/div., and t = 5 s/div.) and (b) typical voltage andcurrent through auxiliary diode Daux2 (V = 60 V/div., I = 8 A/div., andt = 5 s/div) at 110-Vrmsinput and 600-W output.

    Vbus can be kept below 450 V over the required range. Fig. 15shows the input current harmonics when Vin = 100V and Po =600W, which was determined to be the worst case condition forthe harmonic content. It can be seen that the converter can meet

    the IEC1000-3-2 Class D standards for electrical equipment. It

    was confirmed that the standards were met when Vin = 230V.

    The range of the input pf was measured to be in the range of0.890.94 throughout the operating range.

    Fig. 13. Experimental efficiency versus output power.

    Fig. 14. Experimental dc bus voltage versus output power.

    Fig. 15. Input current harmonics compared to IEC1000-3-2 Class D standardwith an output power of 600 W and an input voltage of 100 Vrms.

    VI. CONCLUSION

    A new acdc single-stage voltage-fed full-bridge converter

    has been proposed in this paper. The converter can perform

    input PFC using an auxiliary winding taken off of the main

    power transformer that acts as a switch. This switch iseither on, causing the input current to rise, or off, causing the

  • 8/10/2019 sspfc converter ieee paper

    11/12

    4892 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 56, NO. 12, DECEMBER 2009

    input current to fall. The winding itself is asymmetrical and is

    designed so that the input current frequency is half that of the

    output current and so that the switch does not allow the full

    input voltage to be impressed across the input inductor.

    This novel winding scheme has made the proposed converter

    to be the only known single-stage voltage-fed full-bridge con-

    verter that can operate with standard phase-shift PWM control,meet the IEC1000-3-2 standards for electrical equipment, yet

    maintains a primary-side dc bus voltage of less than 450 V,

    regardless of line and load conditions.

    In this paper, the operation of the converter has been de-

    scribed in detail, and a procedure for the design of the converter

    has been given and demonstrated with an example. Experi-

    mental results obtained from a prototype have confirmed the

    feasibility of the proposed converter.

    REFERENCES

    [1] R. Redl, L. Balogh, and N. O. Sokal, A new family of single-stage iso-

    lated power-factor correctors with fast regulation of the output voltage,inProc. IEEE PESC Conf. Rec., 1994, pp. 11371144.

    [2] J. Qian, Q. Zhao, and F. C. Lee, Single-stage single-switch power-factor-correction AC/DC converters with DC-bus voltage feedback for universalline applications,IEEE Trans. Power Electron., vol. 13, no. 6, pp. 10791088, Nov. 1998.

    [3] L. Huber, J. Zhang, M. M. Jovanovic, and F. C. Lee, Generalized topolo-gies of single-stage input-current-shaping circuits, IEEE Trans. Power

    Electron., vol. 16, no. 4, pp. 508513, Jul. 2001.[4] Q. Zhao, F. C. Lee, and F.-S. Tsai, Voltage and current stress reduction

    in single-stage power factor correction AC/DC converters with bulk ca-pacitor voltage feedback, IEEE Trans. Power Electron., vol. 17, no. 4,pp. 477484, Jul. 2002.

    [5] H.-F. Liu and L.-K. Chang, Flexible and low cost design for a flybackAC/DC converter with harmonic current correction, IEEE Trans. Power

    Electron., vol. 20, no. 1, pp. 1724, Jan. 2005.

    [6] S. Luo, W. Qiu, W. Wu, and I. Batarseh, Flyboost power factor correctioncell and a new family of single-stage AC/DC converters, IEEE Trans.Power Electron., vol. 20, no. 1, pp. 2534, Jan. 2005.

    [7] Y. Jang, M. M. Jovanovic, and D. L. Dillman, Soft-switched PFC boostrectifier with integrated ZVS two-switch forward converter,IEEE Trans.Power Electron., vol. 21, no. 6, pp. 16001606, Nov. 2006.

    [8] D. D.-C. Lu, H. H.-C. Iu, and V. Pjevalica, A single-stage AC/DCconverter with high power factor, regulated bus voltage, and outputvoltage, IEEE Trans. Power Electron., vol. 23, no. 1, pp. 218228,Jan. 2008.

    [9] A. Lazaro, A. Barrado, M. Sanz, V. Salas, and E. Olias, New power factorcorrection ACDC converter with reduced storage capacitor voltage,

    IEEE Trans. Ind. Electron., vol. 54, no. 1, pp. 384397, Feb. 2007.[10] J.-Y. Lee, Single-stage AC/DC converter with input-current dead-zone

    control for wide input voltage ranges,IEEE Trans. Ind. Electron., vol. 54,no. 2, pp. 724732, Apr. 2007.

    [11] P. K. Jain, J. R. Espinoza, and N. Ismail, A single-stage zero-voltage

    zero-current-switched full-bridge DC power supply with extended loadpower range, IEEE Trans. Ind. Electron., vol. 46, no. 2, pp. 261270,Apr. 1999.

    [12] L. Rosetto and S. Buso, Single-phase AC/DC integrated PWMconverter, inProc. IEEE INTELEC Conf. Rec., 2000, pp. 411418.

    [13] K. L. Fontoura, J. A. C. Pinto, V. J. Farias, L. C. de Freitas, andJ. B. Vieira, Jr., Application of the non-dissipative snubber in the AC/DCfull-bridge converter and high power factor application, in Proc. IEEE

    INTELEC Conf. Rec., 2000, pp. 665669.[14] T.-S. Kim, G.-B. Koo, G.-W. Moon, and M.-J. Youn, A single-stage

    power factor correction AC/DC converter based on zero voltage switch-ing full bridge topology with two series-connected transformers, IEEETrans. Power Electron., vol. 21, no. 1, pp. 8997, Jan. 2006.

    [15] G. Moschopoulos, M. Qiu, H. Pinheiro, and P. K. Jain, PWM full-bridgeconverter with natural input power factor correction,IEEE Trans. Aerosp.

    Electron. Syst., vol. 39, no. 2, pp. 660674, Apr. 2003.

    [16] G. Moschopoulos, A simple ACDC PWM full-bridge converter withintegrated power-factor correction, IEEE Trans. Ind. Electron., vol. 50,no. 6, pp. 12901297, Dec. 2003.

    [17] S. Li and G. Moschopoulos, A simple ACDC PWM full-bridge con-verter with auxiliary transformer winding, in Proc. IEEEINTELEC Conf.

    Rec., 2003, pp. 216223.[18] G. Moschopoulos and P. Jain, Single-phase single-stage power-factor-

    corrected converter topologies,IEEE Trans. Ind. Electron., vol. 52, no. 1,pp. 2335, Feb. 2005.

    [19] A. K. S. Bhat and R. Venkatraman, A soft-switched full-bridge single-stage AC-to-DC converter with low line current harmonic distortion,

    IEEE Trans. Ind. Electron., vol. 52, no. 4, pp. 11091116, Aug. 2005.[20] M. H. Kheraluwala, R. L. Steigerwald, and R. Gurumoorthy, A fast-response high power factor converter with a single power stage, in Proc.

    IEEE PESC Conf. Rec., 1991, pp. 769779.[21] M. J. Schutten, R. L. Steigerwald, and M. H. Kheraluwala, Characteris-

    tics of load resonant converters operated in a high-power factor mode,IEEE Trans. Power Electron., vol. 17, no. 2, pp. 304314, Apr. 1992.

    [22] R. Liu and C. Q. Lee, A unified approach to the design of resonantpower factor correction circuits, in Proc. IEEE PESC Conf. Rec., 1992,pp. 181188.

    [23] M. G. Egan, D. L. OSullivan, J. G. Hayes, M. J. Willers, and C. P. Henze,Power-factor-corrected single-stage inductive charger for electric vehiclebatteries, IEEE Trans. Ind. Electron., vol. 54, no. 2, pp. 12171226,Apr. 2007.

    [24] H. Benqassmi, J. P. Ferrieux, and J. Barbaroux, Current-source resonantconverter in power factor correction, in Proc. IEEE PESC Conf. Rec.,1997, pp. 378384.

    [25] V. Yakushev, V. Meleshin, and S. Fraidlin, Full-bridge isolated currentfed converter with active clamp, inProc. IEEE APEC Conf. Rec., 1999,pp. 560566.

    [26] J. G. Cho, J. W. Baek, D. W. D. I. Song, and G. H. Rim, Zero-voltage-transition isolated PWM boost converter for single stage power factorcorrection, inProc. IEEE APEC Conf. Rec., 1997, pp. 471476.

    [27] S. Li and G. Moschopoulos, An ACDC single-stage PWM full-bridgeconverter with a magnetic switch, in Proc. IEEE PESC Conf. Rec.,Jun. 2005, pp. 467473.

    [28] M. K. Nalbant, Power factor calculations and measurement, in Proc.IEEE APEC Conf. Rec., 1990, pp. 543552.

    [29] J. A. Sabate, V. Vlatkovic, R. B. Ridley, F. C. Lee, and B. H. Cho,Design considerations for high-voltage high-power full-bridge zero-voltage-switched PWM converter, in Proc. IEEEAPEC Conf. Rec., 1990,pp. 275284.

    [30] Limits for Harmonic Current Emissions (Equipment Input Current