F I A M M . C O M
SSLA
SSLA Battery Range
UPS
SECurity SyStEmS and EmErGEnCy liGhtinG
Light tRACtiON
LEISURE
MAIN APPLICATIONS:THE SSLA BATTERY RANGE HAS BEEN DESIGNED TO
COVER A WIDE RANGE OF APPLICATIONS. THE FOOTPRINT
OF BATTERIES IS ALSO IDEAL FOR CRITICAL INSTALLATIONS.
CONNECTION IS SIMPLE ON SMALLER MODELS SIZES THANKS
TO THE EASY ‘FAST-ON’ TERMINALS.
THE FIAMM SSLA RANGE HAS FOUR DIFFERENT PRODUCT
FAMILIES. EACH ONE IS SPECIFICALLY DESIGNED TO OPTIMISE
THE BEST SOLUTION FOR THE APPLICATION.
FG DESIGNED TO MEET MEDIUM TO LONG DISCHARGE RATES
AND WITH A DESIGN LIFE OF 5 YEARS. THE RANGE IS AVAILABLE
IN 6V OR 12V BLOCKS WITH A CAPACITY RANGE OF 1.2 - 70AH.
FGH DESIGNED FOR MAXIMUM PERFORMANCE IN CRITICAL
POWER APPLICATIONS SUCH AS UPS. THE RANGE IS AVAILABLE
IN 12V BLOCKS WITH A CAPACITY RANGE OF 5 - 18AH.
FGHL CLASSIFIED “LONG LIFE” ACCORDING EUROBAT INDUSTRY
STANDARD, WHICH MEANS 10 YEARS DESIGN LIFE. THE RANGE
IS AVAILABLE WITH A CAPACITY RANGE OF 5AH TO 12AH.
FGC AN IDEAL SOLUTION FOR CYCLIC APPLICATIONS WITH A
DESIGN LIFE OF 5 YEARS. RANGE IS AVAILABLE FROM 12 – 42AH.
THESE PRODUCTS ARE DESIGNED TO GIVE A WIDE RANGE OF
SOLUTIONS TO ALL APPLICATIONS AND OFFER UNSURPASSED
PROVEN RELIABILITY, COMPLIANT WITH THE HIGHEST
RECOGNISED INTERNATIONAL STANDARDS. SSLA USES
VRLA TECHNOLOGY WITH 99% INTERNAL RECOMBINATION
EFFICIENCY, IS NON-SPILLABLE AND MAINTENANCE FREE
THEREFORE REQUIRES NO TOPPING UP OF ELECTROLYTE
DURING ITS FLOAT-LIFE. SSLA RANGE IS NON-HAZARDOUS
FOR AIR/SEA/RAIL/ROAD TRANSPORTATION AND IS 100%
RECYCLABLE. SLA HAS A SELF-DISCHARGE RATE LESS THAN
2% PER MONTH, GUARANTEEING LONG SHELF-LIFE.
*SSLA (SMALL SEALED LEAD ACID) ARE BATTERIES WITH CAPACITY (AH) TILL MAX
24AH. THE FIAMM SSLA FIAMM RANGE CONTAINS SOME SIZES THAT EXCEED THIS
LIMIT. HOWEVER SOME SIZES ARE OF A LARGER CAPACITY DUE TO APPLICATIONS.
Ø5.56.35 M5 M64.75 Ø6.5
TECHNOLOGY
F I A M M S S L A R A N G E U S E A G M ( A B S O R B E D G L A S S M AT ) T E C H N O L O G Y. T H E E L E C T R O LY T E I S A B S O R B E D I N F I B E R G L A S S S E PA R AT O R S W I T H 9 9 % I N T E R N A L G A S R E C O M B I N AT I O N E F F I C I E N C Y. B L O C S A R E G R A N T S N O N - S P I L L A B L E A N D M A I N T E N A N C E F R E E T H E R E F O R E R E Q U I R E S N O T O P P I N G U P O F E L E C T R O LY T E D U R I N G I T S W H O L E L I F E . L O W S E L F - D I S C H A R G E A L L O W S 6 M O N T H S S H E L F L I F E .
Terminal Pillar Internal Strap
Separators
Negative Flat Plate
The image is for illustrative purposes only.
TERMINALS TYPE
Faston 4.8 Faston 6.3 Flag Ø 5.5 Flag Ø 6.5 Round M5 Round M6
SPECIFICATIONS
High purity lead calcium tin grid plates, designed to resist corrosion and provide short recharge time
VRLA AGM technology using low resistance high microporous fiberglass separators
Leak resistant post seal, faston, flag and threaded female, terminals with high conductivity and maximum torque resistance
One-way safety relief valves allow gas to escape and prevent the ingress of oxygen
ABS plastic (for FGHL range flame retardant ABS plastic to IEC 707 FV0 and UL94 FV0 - LOI greater than 28%)
Installation in any orientation (excluding permanently inverted)
FIAMM reserves the right to change or revise without notice any information or detail given in this publication SSLA Battery Range_2016_06_15
BATTERYTYPE
VDS*
NOMINALVOLTAGE
(V)
CAPACITY (Ah) NOMINAL DIMENSIONS (mm) TYPICALWEIGHT
(kg)
TERMINAL TYPE
20 H to 1.75 VPC at 25°C
Length Width Height Tot. Height**
FG 10121 6 1.2 97 24 51 58 0.28 Faston 4.8
FG 10301 • 6 3.0 134 33 60 66 0.60 Faston 4.8
FG 10381 6 3.8 66 33 119 125 0.61 Faston 4.8
FG 10451 6 4.5 70 47 101 106 0.72 Faston 4.8
FG 10721 6 7.2 150 34 94 100 1.2 Faston 4.8
FG 11201 • 6 12 151 50 93 99 1.8 Faston 4.8
FG 11202 • 6 12 151 50 93 99 1.8 Faston 6.3
FG 20121 • 12 1.2 97 48 51 57 0.54 Faston 4.8
FG 20121A 12 1.2 97 43 51 58 0.52 Faston 4.8
FG 20201 • 12 2.0 178 35 60 65 0.80 Faston 4.8
FG 20271 12 2.7 79 56 99 105 1.1 Faston 4.8
FG 20341 12 3.4 134 65 60 66 1.3 Faston 4.8
FG 20451 12 4.5 90 70 101 107 1.5 Faston 4.8
FG 20721 • 12 7.2 151 65 95 101 2.3 Faston 4.8
FG 20722 • 12 7.2 151 65 95 101 2.3 Faston 6.3
FG 21201 • 12 12 151 98 95 100 3.8 Faston 4.8
FG 21202 • 12 12 151 98 95 100 3.8 Faston 6.3
FG 21803 • 12 18 181 76 167 167 5.5 Flag Ø5.5
FG 22703 • 12 27 166 175 125 125 8.7 Flag Ø5.5
FG 24204 • 12 42 197 165 170 170 13.5 Flag Ø5.5
FG 27004 • 12 70 350 166 174 174 23.3 Flag Ø6.5
* Model available also with VDS
**Tot. Height = total height including terminals
FG
BATTERYTYPE
NOMINALVOLTAGE
(V)
CAPACITY (Ah)INTERNAL
RESISTANCE (mOhm)
NOMINAL DIMENSIONS (mm) TYPICALWEIGHT
(kg)
TERMINAL TYPE
20 H to 1.75 VPC at 25°C
IEC 60896 21-22 Length Width Height Tot. Height*
FGC 21202 12 12 13 151 98 95 100 4.0 Faston 6.3
FGC 21803 12 18 12 181 76 167 167 6.3 Flag Ø5.5
FGC 22705 12 27 11 166 175 125 125 9.2 Round M5
FGC 23505 12 35 6.5 197 132 170 170 12.2 Round M5
FGC 24207 12 42 7.5 196 165 169 169 13.2 Round M6
*Tot. Height = total height including terminals
FGC
ELECTRICAL CHARACTERISTICS
Float Voltage: 2.25-2.30 V/cell at 25°CBoost Voltage for cyclic use: 2.40-2.50 V/cell at 25°CFloat Voltage Compensation with Temperature: -2.5 mV/cell/°CSelf-Discharge at 25°C: <2%/month
STANDARDS
IEC 60896 Part 21 - VRLA methods of testingIEC 60896 Part 22 - VRLA requirementsBS 6290 Part 4 - specifications for VRLA classificationEurobat “3-5 years standard commercial” for FG FGH FGC and “10-12 years long life” for FGHLUL Recognized
BATTERYTYPE
NOMINALVOLTAGE
(V)
CAPACITY (Ah)INTERNAL
RESISTANCE (mOhm)
NOMINAL DIMENSIONS (mm) TYPICALWEIGHT
(kg)
TERMINAL TYPE
20 H to 1.75 VPC at 25°C
IEC 60896 21-22 Length Width Height Tot. Height*
12 FGHL 22 12 5.0 37 90 70 101 107 2.1 Faston 6.3
12 FGHL 28 12 7.2 24.6 151 65 95 101 2.7 Faston 6.3
12 FGHL 34 12 9.0 23.6 151 65 95 101 2.8 Faston 6.3
12 FGHL 48 12 12 24.8 151 98 95 100 4.2 Faston 6.3
*Tot. Height = total height including terminals
BATTERYTYPE
NOMINALVOLTAGE
(V)
CAPACITY (Ah)INTERNAL
RESISTANCE (mOhm)
NOMINAL DIMENSIONS (mm) TYPICALWEIGHT
(kg)
TERMINAL TYPE
20 H to 1.75 VPC at 25°C
IEC 60896 21-22 Length Width Height Tot. Height*
12 FGH 23 slim 12 5.0 37 151 51 95 102 2.2 Faston 4.8
12 FGH 23 12 5.0 37 90 70 101 107 2.1 Faston 6.3
12 FGH 36 12 9.0 23.6 151 65 95 101 2.7 Faston 6.3
12 FGH 50 12 12 14.8 151 98 95 100 4.2 Faston 6.3
12 FGH 65 12 18 9.8 181 76 167 167 6.2 Flag Ø5.5
*Tot. Height = total height including terminals
FGH
FGHL
F I A M M S . p . A .
V i a l e E u ro p a , 7 5 - 3 6 0 7 5 M o n t e c c h i o M a g g i o re ( V I ) - I TA LY
T E L + 3 9 0 4 4 4 7 0 9 3 1 1 - F a x + 3 9 0 4 4 4 6 9 4 1 7 8
e - m a i l : i n f o . s t a n d b y @ f i a m m . c o m
w w w. f i a m m . c o m
f i a m m . b a t t e r i e s
f i a m m b a t t e r i e s
y o u t u b e . c o m / u s e r / F I A M M v i d e o
CERTIFICATIONS
I S O 9 0 0 1Q u a l i t y M a n a g e m e n t S y s t e m
I S O 1 4 0 0 1 E n v i ro n m e n t a l M a n a g e m e n t S y s t e m
O H S A S 1 8 0 0 1Wo r k p l a c e S a f e t y & H e a l t h
Battery Voltage (V)
Charging Current (A)
5 10 20 250
Charging time (h)
Cha
rgin
g Vo
ltage
(V)
13
0
10
11
12
14
15
15Discharge 100%50%
Cha
rgin
g C
urre
nt (A
)
Rec
harg
ed C
apac
ity (%
)
140
60
100
80
120
40
20
0
0.10 C10
0.05 C10
0
Recharged Capacity (%)
40°C
5°C
30°C 25°C
0 2 4 6 8 10 12 14 16 18 20
40
60
80
100The battery can be
used without refreshing charge
Refreshing charge at 2.4 Vpc for 24 hours (at 20-25°C) must be
applied as soon as possible.
Refreshing charge of 2.4 Vpc may be
insuf�cient to recover the battery capacity.
It is important to avoid this area
Storage Time (months)
Rem
aini
ng C
apac
ity (%
)
Battery Voltage and Charge Time for Standby Use (at 25°C) Capacity loss during storage at various temperatures
Discharge time (min)
Bat
tery
Vol
tage
(V/c
ell)
1.5
1.6
1.8
1.7
2.0
1.9
2.1
2.2
1 10 100 1.000 10.000
2.60 C 2 C 1.22 C 0.68 C
0.26 C0.10 C
0.05 C
DISCHARGE CuRvES at different current / final voltage (at 25°C)
TYPICAL CHARGE CuRvES STORAGE
The above discharge curves are typical. For more detailed information please see the specific product sheets.