SSC-02 Multi-standard outdoor macro base station Next-generation site in a cabinet The SSC-02 Site Solution Cabinet sup- plies -48 V DC power to Main-remote (M-R) radio base stations and auxiliary equipment. Physical space as well as prioritized power for auxiliary equipment such as transmission is also supported. To provide security against AC power supply interruptions, battery backup functionality is ensured by built-in batteries or via connection to a BBS 6101 (for applications requiring very long battery autonomy or for cyclic battery operation). Flexibility The SSC-02 is configurable to suite both small and large M-R configurations. DC output capability ranges from 2,0 kW to 8 kW. DC load circuit breakers are available from 2A up to 32A ,ensuring that virtually any M-R site configuration can be supported. The system supports one battery circuit breaker connected to the built-in battery bank. For very large backup needs, the bat- tery bank can be daisy-chained to an exten- sion BBS cabinet. The cabinet features 9 HU of space for auxil- iary 19” mountable auxiliary equipment. All equipment, connections and the climate system are easily accessed via the lockable front door.

Ssc-02 Data Sheet 1_287 01 - Fgc 101 0344 Rev A

Embed Size (px)

Citation preview

Page 1: Ssc-02 Data Sheet 1_287 01 - Fgc 101 0344 Rev A

SSC-02Multi-standard outdoor macro base station

Next-generation site in a cabinet

the SSC-02 Site Solution Cabinet sup-plies -48 V DC power to Main-remote (M-R) radio base stations and auxiliary equipment. Physical space as well as prioritized power for auxiliary equipment such as transmission is also supported.

To provide security against AC power supply interruptions, battery backup functionality is ensured by built-in batteries or via connection to a BBS 6101 (for applications requiring very long battery autonomy or for cyclic battery operation).

Flexibility The SSC-02 is configurable to suite both small and large M-R configurations. DC output capability ranges from 2,0 kW to 8 kW. DC load circuit breakers are available from 2A up to 32A ,ensuring that virtually any M-R site configuration can be supported.

The system supports one battery circuit breaker connected to the built-in battery bank. For very large backup needs, the bat-tery bank can be daisy-chained to an exten-sion BBS cabinet.

The cabinet features 9 HU of space for auxil-iary 19” mountable auxiliary equipment.

All equipment, connections and the climate system are easily accessed via the lockable front door.

Page 2: Ssc-02 Data Sheet 1_287 01 - Fgc 101 0344 Rev A

Telefonaktiebolaget LM Ericssonwww.ericsson.com

1/287 01 - FGC 101 0344 Rev A© Telefonaktiebolaget LM Ericsson 2010

TECHNICAL SPECIFICATIONS SSC-02

Overall, including protruding roof: 1460 x 660 x 930 mmFootprint: 660 x 700 mm 9HU of 19” rack space210 kg excluding rectifier and batteries

88 – 280 VAC two or three phase (HVD High Voltage Disconnect activates at 300V ± 10V) 220 – 280 VAC single phase (HVD High Voltage Disconnect activates at 300V ± 10V)50-60 Hz ±5%400 V AC single phase to the PBC 6100 system310 ±10 / 285 ±10 VAC system disconnect / reconnect level0.99Better than 91% (184 V AC and higher for 40 - 100% load)15 kA (L-N), 50 kA (N-PE, Nominal surge current, 10/350 us) SPD class I/B (IEC/VDE)

-48 VDC (-15% / +20%)Via temp.-stable electro-hydraulic circuit breakers (CB).Main load distribution: 10 x 13 mm wide CB positionsPriority load distribution: 14 x 13 mm wide CB positionsAvailable CB ratings (A): 32, 25, 20, 16, 10, 6, 2

Rectifier capacity: 2.0 kWSystem capacity: Up to 4 rectifiers, i.e. 8 kW For up to 6 external DC outputs (RRU’s)

200 and 63 A (200A if battery expansion in BBS6101)1 (for battery expansion in BBS6101), Optional

TBD W typical consumption for heating / cooling

Normal operation: -33 to +50 °C Transportation (< 3 months), excl. batteries: -40 to +70 °C Normal operation: 15 – 100 %Transportation (< 3 months), excl. batteries: 5 – 100 %IEC 60 950-1, EN 60 950-1 and UL 60 950-1CE, CB, UL, CSACISPR 22/EN 55022, FCC part 2 15, GR-1089-CORE, ICES-003IP55IEC 60721-3-3 class 1M2 and ETSI EN 300 019-1-3 class 3.1 according to IEC 60068-2-57, assuming proper installation and usage of BBS 6101 appr. batteries and accessories only.

Default setting: 8 binary alarm outputs. Major power alarm, minor power alarm, CSU failure (power system), CLU failure, high battery temperature, door alarm and 2 un-defined alarms.On power system controller, rectifiers, climate systemLCD display and keypadVia the system controller’s RS232 or optional Web-interface

MECHANICAL External dimensions (HxWxD)

Internal space for auxiliary equipment:System weight:

AC InputInput voltage:

Line frequency: Non-destruction voltage:

Power factor, rectifiers:Efficiency, rectifiers:AC Surge protection:

DC OutputOutput voltage:DC Distribution:

Output power and current:

DC Surge protection:

BATTERy INTERFACESAvailable battery circuit breakers (CB):Number of surge protected CB positions:

CLIMATE SySTEM POWER CONSUMPTIONHeat-Exchanger power consumption:

EnvIrOnmEntAlTemperature range:

Relative humidity:

Safety:Approval:EMC:Enclosure:Optional earthquake proofing:

SupErvISIOn AnD COntrOlBinary Alarm Outputs

LED indicatorsLocal interfaceRemote access

To facilitate operations, maintenance and spare parts han-dling, the power system modules are the same as in the indoor system PBC 6200.

Climate Control SystemThe heat exchanger climate system ensures a suitable interior climate for the 19” equipment and power system. For the battery compartment an energy efficient active cooling system is used to ensure maximum battery lifetime and performance. Bothe climate systems works without air exchange with the ambient environment.

EnvironmentEarthquake Zone 4 capability is available as an option at a later date.

Supervision and ControlThe power system controller features an LCD display and key pad for quick access to power system information at the site. The same information and more can be accessed remotely. Binary alarms can be connected to the network supervision system, via the site’s alarm collecting system. The power system controller’s binary outputs also supports a diesel generator On&Off control.