General Description The Series TY-B, 5.6 K-factor, Horizon- tal and Vertical Sidewall Sprinklers de- scribed in this data sheet are standard response - standard coverage, deco- rative 5 mm glass bulb type spray sprinklers designed for use in light and ordinary hazard, commercial occupan- cies such as banks, hotels, shopping malls, etc.They are designed for instal- lation along a wall or the side of a beam and just beneath a smooth ceiling. Sidewall sprinklers are commonly used instead of pendent or upright sprinklers due to aesthetics or building construction considerations, where piping across the ceiling is not desir- able. The recessed version of the Series TY-B Horizontal Sidewall Sprinkler is intended for use in areas with a fin- ished wall. It uses a two-piece Style 10 Recessed Escutcheon. The Recessed Escutcheon provides 1/2 inch (12,7 mm) of recessed adjustment or up to 3/4 inch (19,1 mm) of total adjustment from the flush sidewall position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe nipples to the sprinklers must be cut. Corrosion resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be ob- tained when exposed to corrosive at- mospheres. Although corrosion resis- tant coated sprinklers have passed the standard corrosion tests of the appli- cable approval agencies, the testing is not representative of all possible cor- rosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corro- sive environment. The effects of ambi- ent temperature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed. WARNINGS The Series TY-B Sprinklers described herein must be installed and main- tained in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association, in addition to the standards of any other authorities hav- ing jurisdiction. Failure to do so may impair the performance of these de- vices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Model/Sprinkler Identification Numbers TY3351 - Horizontal TY3451 - Vertical Technical Data Approvals UL and C-UL Listed. FM, LPCB, and NYC Approved. (Refer to Table A for complete approval information including corrosion resis- tant status) Maximum Working Pressure 175 psi (12,1 bar) Discharge Coefficient K = 5.6 GPM/psi 1/2 (80,6 LPM/bar 1/2 ) Temperature Ratings Refer to Table A Finishes Sprinkler: Refer to Table A Recessed Escutcheon: White Coated, Chrome Plated, and Brass Plated Series TY-B — 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage Page 1 of 6 TFP161 JULY, 2004 Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 IMPORTANT Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.

Sprk Perdea

  • Upload
    danateo

  • View
    214

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Sprk Perdea

GeneralDescriptionThe Series TY-B, 5.6 K-factor, Horizon-tal and Vertical Sidewall Sprinklers de-scribed in this data sheet are standardresponse - standard coverage, deco-rative 5 mm glass bulb type spraysprinklers designed for use in light andordinary hazard, commercial occupan-cies such as banks, hotels, shoppingmalls, etc.They are designed for instal-lation along a wall or the side of a beamand just beneath a smooth ceiling.Sidewall sprinklers are commonlyused instead of pendent or uprightsprinklers due to aesthetics or buildingconstruction considerations, wherepiping across the ceiling is not desir-able.

The recessed version of the SeriesTY-B Horizontal Sidewall Sprinkler isintended for use in areas with a fin-ished wall. It uses a two-piece Style 10Recessed Escutcheon. The RecessedEscutcheon provides 1/2 inch (12,7mm) of recessed adjustment or up to3/4 inch (19,1 mm) of total adjustmentfrom the flush sidewall position. Theadjustment provided by the RecessedEscutcheon reduces the accuracy towhich the fixed pipe nipples to thesprinklers must be cut.

Corrosion resistant coatings, whereapplicable, are utilized to extend thelife of copper alloy sprinklers beyondthat which would otherwise be ob-tained when exposed to corrosive at-mospheres. Although corrosion resis-tant coated sprinklers have passed thestandard corrosion tests of the appli-cable approval agencies, the testing isnot representative of all possible cor-rosive atmospheres. Consequently, itis recommended that the end user beconsulted with respect to the suitabilityof these coatings for any given corro-sive environment. The effects of ambi-ent temperature, concentration ofchemicals, and gas/chemical velocity,should be considered, as a minimum,along with the corrosive nature of thechemical to which the sprinklers will beexposed.

WARNINGSThe Series TY-B Sprinklers describedherein must be installed and main-tained in compliance with this docu-ment, as well as with the applicablestandards of the National Fire Protec-tion Association, in addition to thestandards of any other authorities hav-ing jurisdiction. Failure to do so mayimpair the performance of these de-vices.

The owner is responsible for maintain-ing their fire protection system and de-vices in proper operating condition.The installing contractor or sprinklermanufacturer should be contactedwith any questions.

Model/SprinklerIdentificationNumbersTY3351 - HorizontalTY3451 - Vertical

TechnicalDataApprovalsUL and C-UL Listed.FM, LPCB, and NYC Approved.(Refer to Table A for complete approvalinformation including corrosion resis-tant status)

Maximum Working Pressure175 psi (12,1 bar)

Discharge CoefficientK = 5.6 GPM/psi1/2 (80,6 LPM/bar1/2)

Temperature RatingsRefer to Table A

FinishesSprinkler: Refer to Table ARecessed Escutcheon: White Coated,Chrome Plated, and Brass Plated

Series TY-B — 5.6 K-factorHorizontal and Vertical Sidewall SprinklersStandard Response, Standard Coverage

Page 1 of 6 TFP161JULY, 2004

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

IMPORTANTAlways refer to Technical DataSheet TFP700 for the “INSTALLERWARNING” that provides cautionswith respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and in-stallation can permanently damagea sprinkler system or its compo-nents and cause the sprinkler to failto operate in a fire situation or causeit to operate prematurely.

Page 2: Sprk Perdea

Physical CharacteristicsFrame . . . . . . . . . . . . . BronzeButton . . . . . . . . . Brass/CopperSealing Assembly . . . . . . . . . .

. . . . . Beryllium Nickel w/Teflon†Bulb . . . . . . . . . . . . . . . GlassCompression Screw . . . . . BronzeHSW Deflector . . . . . . . . BronzeVSW Deflector . . . . . . . . Copper

PatentsU.S.A. 5,810,263

OperationThe glass Bulb contains a fluid whichexpands when exposed to heat. Whenthe rated temperature is reached, thefluid expands sufficiently to shatter theglass Bulb, allowing the sprinkler toactivate and water to flow.

Page 2 of 6 TFP161

TYPE TEMP. BULBLIQUID

NATURALBRASS

CHROMEPLATED

WHITE***POLYESTER

155°F/68°C

175°F/79°C

200°F/93°C

SPRINKLER FINISH (See Note 10)

RECESSEDHORIZ.

SIDEWALL(TY3351)*Figure 3

135°F/57°C Orange

Red

Yellow

Green

1, 2, 3, 9

NOTES:1. Listed by Underwriters Laboratories, Inc. (UL) for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch (100 to 300 mm)

top of deflector to ceiling distance.2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) for use in Light and Ordinary Hazard Occupancies at a 4 to 12

inch (100 to 300 mm) top of deflector to ceiling distance.3. Approved by Factory Mutual Research Corporation (FM) for use in Light Hazard Occupancies at a 4 to 12 inch (100 to 300 mm)

top of deflector to ceiling distance.4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/05 & 007k/03) at a 4 to 6 inch (100 to 150 mm) deflector

to ceiling distance.5. Listed by Underwriters Laboratories, Inc. (UL) for use in Light and Ordinary Hazard Occupancies.6. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL:) for use in Light and Ordinary Hazard Occupancies.7. Approved by Factory Mutual Research Corporation (FM) for use in Light Hazard Occupancies.8. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/05 & 007k/03).9. Approved by the City of New York under MEA 354-01-E.10. Where Polyester Coated, Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be UL and C-UL Listed,

the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated, Wax Coated, and Wax over LeadCoated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers.

* Installed with Style 10 (1/2" NPT) 3/4" Total Adjustment Recessed Escutcheon.** 150°F/66°C Maximum Ceiling Temperature.*** Frame and deflector only. Listings and approvals apply to color (Special Order).

TABLE ALABORATORY LISTINGS AND APPROVALS

WAX OVERLEAD COATED

LEADCOATED

WAXCOATED

N/A

1, 2, 3, 9 1, 2, 3, 9

1**, 2**, 3**, 9** 1**, 2**, 3**, 9**

1, 2, 3, 9

N/A

K

5.61/2"NPT

HORIZ.SIDEWALL(TY3351)

135°F/57°C Orange

155°F/68°C Red

175°F/79°C Yellow

200°F/93°C Green

286°F/141°C Blue

360°F/182°C Mauve

1, 2, 3, 4, 9

5.61/2"NPT

VERTICALSIDEWALL(TY3451)InstalledPendent

orUpright

135°F/57°C

155°F/68°C

175°F/79°C

200°F/93°C

286°F/141°C

360°F/182°C Mauve

Blue

Green

Yellow

Red

Orange

1, 2, 4, 9

4, 5, 6, 7, 8, 9

4, 5, 6, 8, 9

5, 6, 7, 9 5, 6, 7, 9 5, 6, 7, 9

5**, 6**, 7**, 9** 5**, 6**, 7**, 9**

N/A

1, 2, 3, 9

1, 2, 9

†D

uPon

tReg

iste

red

Tra

dem

ark

Page 3: Sprk Perdea

DesignCriteriaThe Series TY-B Horizontal and Verti-cal Sidewall Sprinklers are intendedfor fire protection systems designed inaccordance with the standard installa-tion rules recognized by the applicableListing or Approval agency (e.g., ULListing is based on the requirements ofNFPA 13, and FM Approval is basedon the requirements of FM’s Loss Pre-vention Data Sheets). Only the Style10 Recessed Escutcheon is to be usedfor recessed horizontal installations.

InstallationThe Series TY-B Sprinklers must beinstalled in accordance with the follow-ing instructions:

NOTESDo not install any bulb type sprinkler ifthe bulb is cracked or there is a loss ofliquid from the bulb. With the sprinklerheld horizontally, a small air bubbleshould be present. The diameter of theair bubble is approximately 1/16 inch(1,6 mm) for the 135°F/57°C to 3/32inch (2,4 mm) for the 360°F/182°Ctemperature ratings.

A leak tight 1/2 inch NPT sprinkler jointshould be obtained with a torque of 7to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-mum of 21 ft. lbs. (28,5 Nm) of torquemay be used to install sprinklers with1/2 NPT connections. Higher levels oftorque may distort the sprinkler inletand cause leakage or impairment ofthe sprinkler.

Do not attempt to make-up for insuffi-cient adjustment in the escutcheonplate by under- or over-tightening thesprinkler. Readjust the position of thesprinkler fitting to suit.

The Series TY-B Horizontal and Ver-tical Sidewall Sprinklers must be in-stalled in accordance with the follow-ing instructions.

Step 1. Horizontal sidewall sprinklersare to be installed in the horizontalposition with their centerline of water-way perpendicular to the back wall andparallel to the ceiling. The word “TOP”on the Deflector is to face towards theceiling.

Vertical sidewall sprinklers are to beinstalled in the pendent or upright po-sition with the arrow on the Deflectorpointing away from the wall.

Step 2. With pipe thread sealant ap-plied to the pipe threads, hand tightenthe sprinkler into the sprinkler fitting.

Step 3. Tighten the sprinkler into thesprinkler fitting using only the W-Type6 Sprinkler Wrench (Ref. Figure 4),except that an 8 or 10 inch adjustableCrescent wrench is to be used for waxcoated sprinklers. With reference toFigure 1 or 2, the W-Type 6 SprinklerWrench or the Crescent wrench, asapplicable, is to be applied to thewrench flats.

When installing wax coated sprinklerswith the adjustable Crescent wrench,additional care needs to be exercisedto prevent damage to the wax coatingon the sprinkler wrench flats or framearms and, consequently, exposure of

bare metal to the corrosive environ-ment. The jaws of the wrench shouldbe opened sufficiently wide to passover the wrench flats without damag-ing the wax coating. Before wrenchtightening the sprinkler, the jaws of thewrench are to be adjusted to just con-tact the sprinkler wrench flats. Afterwrench tightening the sprinkler, loosenthe wrench jaws before removing thewrench.

After installation, the sprinkler wrenchflats and frame arms must be in-spected and the wax coating re-touched (repaired) whenever the coat-ing has been damaged and bare metal

TFP161 Page 3 of 6

FIGURE 15.6 K-FACTOR STANDARD RESPONSE

SERIES TY-B HORIZONTAL SIDEWALL (TY3351) SPRINKLERS

1 - Frame2 - Button3 - Sealing

Assembly4 - Bulb5 - Compression

Screw6 - Deflector

* Temperature rating is indicated on deflector or adjacent to orifice seat on frame.**Pipe thread connections per ISO 7/1 can be provided on special request.

24

5

6

PLATE SEATINGESCUTCHEON

(11,1 mm)NOMINALMAKE-IN

SURFACE

13

2-7/8" DIA.

ESCUTCHEON

STYLE 10RECESSED

(73,0 mm)

WRENCHFLATS

1-1/2"(38,1 mm)

2-3/16"(55,6 mm)

7/16"1-13/16"(46,0 mm)

CENTERLINE

WATERWAYOF SPRINKLER

HATDEFLECTOR

1/2"NPT

*

9/16"(14,3 mm)

**

Page 4: Sprk Perdea

is exposed. The wax coating on thewrench flats can be retouched by gen-tly applying a heated 1/8 inch diametersteel rod to the areas of wax that havebeen damaged, to smooth it back overareas where bare metal is exposed.

NOTESOnly retouching of the wax coating ap-plied to the wrench flats and framearms is permitted, and the retouchingis to be performed only at the time ofthe initial sprinkler installation.

The steel rod should be heated only tothe point at which it can begin to meltthe wax, and appropriate precautionsneed to be taken, when handling theheated rod, in order to prevent theinstaller from being burned.

If attempts to retouch the wax coatingwith complete coverage are unsuc-cessful, additional wax can be orderedin the form of a wax stick (the end ofwhich is color coded). Only the correctcolor coded wax is to be used, andretouching of wrench flats and framearms is only permitted at the time ofinitial sprinkler installation. With thesteel rod heated as previously de-scribed, touch the rod to the area re-quiring additional wax with the rod an-gled downward, and then touch thewax stick to the rod approximatelyone-half inch away from the area re-quiring retouching. The wax will meltand run down onto the sprinkler.

The Series TY-B Recessed Horizon-tal Sidewall Sprinklers must be in-stalled in accordance with the follow-ing instructions.

Step A. Recessed horizontal sidewallsprinklers are to be installed in thehorizontal position with their centerlineof waterway perpendicular to the backwall and parallel to the ceiling. Theword “TOP” on the Deflector is to facetowards the ceiling.

Step B. After installing the Style 10Mounting Plate over the sprinklerthreads, hand tighten the sprinkler intothe sprinkler fitting.

Step C. Tighten the sprinkler into thesprinkler fitting using only the W-Type7 Recessed Sprinkler Wrench (Ref.Figure 5). With reference to Figure 1,the W-Type 7 Recessed SprinklerWrench is to be applied to the sprinklerwrench flats.

Step D. After the ceiling has been in-stalled or the finish coat has been ap-plied, slide on the Style 10 Closureover the Series TY-B Sprinkler andpush the Closure over the MountingPlate until its flange comes in contactwith the ceiling.

Care andMaintenanceThe Series TY-B Sprinklers must bemaintained and serviced in accord-ance with the following instructions:

NOTESBefore closing a fire protection systemmain control valve for maintenancework on the fire protection system thatit controls, permission to shut down theaffected fire protection system must beobtained from the proper authoritiesand all personnel who may be affectedby this action must be notified.

Absence of an escutcheon, which isused to cover a clearance hole, maydelay the time to sprinkler operation ina fire situation.

Sprinklers that are found to be leakingor exhibiting visible signs of corrosionmust be replaced.

Automatic sprinklers must never be bepainted, plated, coated or otherwisealtered after leaving the factory. Modi-fied sprinklers must be replaced.Sprinklers that have been exposed to

corrosive products of combustion, buthave not operated, should be replacedif they cannot be completely cleanedby wiping the sprinkler with a cloth orby brushing it with a soft bristle brush.

Care must be exercised to avoid dam-age to the sprinklers - before, during,and after installation. Sprinklers dam-aged by dropping, striking, wrenchtwist/slippage, or the like, must be re-placed. Also, replace any sprinkler thathas a cracked bulb or that has lostliquid from its bulb. (Ref. InstallationSection).

Frequent visual inspections are rec-ommended to be initially performed forcorrosion resistant coated sprinklers,after the installation has been com-pleted, to verify the integrity of the cor-rosion resistant coating. Thereafter,annual inspections per NFPA 25should suffice; however, instead of in-specting from the floor level, a randomsampling of close-up visual inspec-tions should be made, so as to betterdetermine the exact sprinkler condi-tion and the long term integrity of thecorrosion resistant coating, as it maybe affected by the corrosive conditionspresent.

Page 4 of 6 TFP161

FIGURE 25.6 K-FACTOR STANDARD RESPONSE

SERIES TY-B VERTICAL SIDEWALL (TY3451) SPRINKLERS

1 - Frame2 - Button

3 - SealingAssembly

4 - Bulb5 - Compression

Screw

6 - Deflector7- Ejection Spring

* Temperature rating is indicated on deflector or adjacent to orifice seat on frame.**Pipe thread connections per ISO 7/1 can be provided on special request.

PLATE SEATINGESCUTCHEON

WRENCHFLATS

(11,1 mm)NOMINALMAKE-INSURFACE

NPT1/2"

SECTIONPENDENT UPRIGHTCROSS

3

1

2

5

4

6*

7

(55,6 mm)2-3/16"

(38,1 mm)1-1/2"

SHOWNSHOWN

**

FROM AND BEPERPENDICULAR

POINT AWAY

TO THE BACKWALL SURFACE

ARROW MUST

7/16"

2-3/16"(55,6 mm)

Page 5: Sprk Perdea

The owner is responsible for the in-spection, testing, and maintenance oftheir fire protection system and de-vices in compliance with this docu-ment, as well as with the applicablestandards of the National Fire Protec-tion Association (e.g., NFPA 25), inaddition to the standards of any otherauthorities having jurisdiction. The in-stalling contractor or sprinkler manu-facturer should be contacted relative toany questions.

It is recommended that automaticspr inkler systems be inspected,tested, and maintained by a qualifiedInspection Service in accordance withlocal requirements and/or nationalcodes.

LimitedWarrantyProducts manufactured by Tyco FireProducts are warranted solely to theoriginal Buyer for ten (10) yearsagainst defects in material and work-manship when paid for and properlyinstalled and maintained under normaluse and service. This warranty will ex-pire ten (10) years from date of ship-ment by Tyco Fire Products. No war-ranty is given for products orcomponents manufactured by compa-nies not affiliated by ownership withTyco Fire Products or for products andcomponents which have been subjectto misuse, improper installation, corro-sion, or which have not been installed,maintained, modified or repaired in ac-cordance with applicable Standards ofthe National Fire Protection Associa-tion, and/or the standards of any otherAuthorities Having Jurisdiction. Mate-rials found by Tyco Fire Products to bedefective shall be either repaired orreplaced, at Tyco Fire Products’ soleoption. Tyco Fire Products neither as-sumes, nor authorizes any person to

assume for it, any other obligation inconnection with the sale of products orparts of products. Tyco Fire Productsshall not be responsible for sprinklersystem design errors or inaccurate orincomplete information supplied byBuyer or Buyer’s representatives.

IN NO EVENT SHALL TYCO FIREPRODUCTS BE LIABLE, IN CON-TRACT, TORT, STRICT LIABILITY ORUNDER ANY OTHER LEGAL THE-ORY, FOR INCIDENTAL, INDIRECT,SPECIAL OR CONSEQUENTIALDAMAGES, INCLUDING BUT NOTLIMITED TO LABOR CHARGES, RE-GARDLESS OF WHETHER TYCOFIRE PRODUCTS WAS INFORMEDABOUT THE POSSIBILITY OF SUCHDAMAGES, AND IN NO EVENTSHALL TYCO FIRE PRODUCTS’ LI-ABILITY EXCEED AN AMOUNTEQUAL TO THE SALES PRICE.

THE FOREGOING WARRANTY ISMADE IN LIEU OF ANY AND ALLOTHER WARRANTIES EXPRESS ORIMPLIED, INCLUDING WARRANTIESOF MERCHANTABILITY AND FIT-NESS FOR A PARTICULAR PUR-POSE.

TFP161 Page 5 of 6

FIGURE 3SERIES TY-B RECESSED HORIZONTAL SIDEWALL SPRINKLER

WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENTSTYLE 10 RECESSED ESCUTCHEON

FIGURE 4W-TYPE 6 SPRINKLER WRENCH

WRENCH RECESS(END "A" USED FOR1/2" NPT MODELS)

FIGURE 5W-TYPE 7 RECESSEDSPRINKLER WRENCH

RECESSWRENCH

WITH SPRINKLERENGAGEMENTIN TO ENSURE

WRENCHING AREA

PUSH WRENCH

MOUNTING

3/4" (19,1 mm)

1-1/4" (31,8 mm)

PLATE

CLOSURE

SURFACEMOUNTING

(73,0 mm)

2-1/4" DIA.(57,2 mm)

1/4" (6,4 mm)

3/4" (19,1 mm)

(3,2 mm)1/8"

5/8±1/4"

FACE OF

FITTINGSPRINKLER

(15,9±6,4 mm)

2-7/8" DIA.

SERIESTY-B

Page 6: Sprk Perdea

OrderingProcedureWhen placing an order, indicate the fullproduct name. Refer to the Price Listfor complete listing of Part Numbers.

Contact your local distributor for avail-ability.

Sprinkler Assemblies with NPTThread Connections:Specify: (Specify Model/SIN), Stand-ard Response, (specify K-factor),(specify temperature rating), SeriesTY-B (specify Horizontal Sidewall orVertical Sidewall) Sprinkler with (spec-ify type of finish or coating), P/N (spec-ify from Table B).

Recessed Escutcheon:Specify: Style (specify) Recessed Es-cutcheon with (specify finish), P/N(specify).

1/2" (15 mm)Style 10Chrome Plated . . . . . . . . . P/N 56-701-9-010

1/2" (15 mm)Style 10White ColorCoated . . . . . . . . . . . . . . . P/N 56-701-4-010

1/2" (15 mm)Style 10White RAL9010* . . . . . . . P/N 56-701-3-010

1/2" (15 mm)Style 10Brass Plated . . . . . . . . . . . P/N 56-701-2-010

* Eastern Hemisphere sales only.

Sprinkler Wrench:Specify: W-Type 6 Sprinkler Wrench,P/N 56-000-6-387.

Specify: W-Type 7 Sprinkler Wrench,P/N 56-850-4-001.

Wax Sticks:(for retouching wrench damagedwax coating)Specify: (Specify color) color codedWax Stick for retouching (specify tem-perature rating) temperature rated Se-ries TY-B Sprinklers, P/N (specify).

Black for 135°F . . . . . . . . . . . . P/N 56-065-1-135Red for 155°F . . . . . . . . . . . . . P/N 56-065-1-155Yellow for 175°F . . . . . . . . . P/N 56-065-1-175Blue for 200°F and

286°F . . . . . . . . . . . . . . . . . P/N 56-065-1-286

NOTESEach wax stick is suitable for retouch-ing up to twenty-five sprinklers.

The wax used for 286°F sprinklers isthe same as for 200°F sprinklers, and,therefore, the 286°F sprinkler is limitedto the same maximum ceiling tempera-ture as the 200°F sprinkler (i.e.,150°F).

Page 6 of 6 TFP161

TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446

P/N 57 — XXX — X — XXX

360°F/182°C

155°F/68°C

360

155

TEMPERATURERATING

135°F/57°C1351

SPRINKLER

TABLE BPART NUMBER SELECTION

SERIES TY-B HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS

175°F/79°C

286

200°F/93°C200

286°F/141°C

175

WHITE POLYESTER

NATURAL BRASS

9

4

MODEL/SIN

CHROME PLATED

7 LEAD COATED

6 WAX COATED286°F/141°C MAX.

8 WAX OVER LEAD286°F/141°C MAX.

578 HORIZONTAL SIDEWALL

575 VERTICAL SIDEWALL

TY3351

TY3451

3 WHITE (RAL9010)*

* Eastern Hemisphere sales only.