58
... · .. ' . ' . l'nstallation Operation.· Maintenance Split System Air Handlers 5-20 Tons (R-410A) Model (60 Hz) Model (50 Hz) 1WE061D/E***A 1WE051D***A 1WE090D/E***A 1WE076D*** A 1WE120D/E***A 1WE101D/E***A 1WE150E***A 1WE126E***A 1WE180E***A 1WE156E***A 1WE240E***A 1WE201E***A November 2009 SSA-SVX06A-EN

Split System Air Handler

Embed Size (px)

Citation preview

Page 1: Split System Air Handler

... · .. ' . ' .

l'nstallation Operation.· Maintenance

Split System Air Handlers 5-20 Tons (R-410A)

Model (60 Hz) Model (50 Hz)

1WE061D/E***A 1WE051D***A 1WE090D/E***A 1WE076D*** A 1WE120D/E***A 1WE101D/E***A 1WE150E***A 1WE126E***A 1WE180E***A 1WE156E***A 1WE240E***A 1WE201E***A

November 2009 SSA-SVX06A-EN

Page 2: Split System Air Handler

Warnings, Cautions and Notices

Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at appropriate intervals throughout this manual. Warnings are provided to alert installing contractors to potential hazards that could result in personal injury or death. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.

Y9ur personal safety and the proper operation of this machine depend upon the strict observance Of these preCautiOns.

ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout this literature. Read these carefully.

,& WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

&cAUTION: lndicates·a potentially hazardous situation which, if not avoided, could result in minor' or moderate injury. It could also be used to alert against unsafe practices.

NOncE: Indicates a situation that could result in equipment or property-damage only accidents.

Important Environmental Concerns! Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozohe layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential-impact to the environment. Trane advocates the responsibl_e handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.

Responsible Refrigerant Practices! Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry .. AII technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

&wARNING R-410A Refrigerant under Higher Pressure than R-22! The unit described in this manual uses R-410A refrigerant which operates at higher pressures than R-22 refrigerant. Use ONLY R-410A rated service equipment or components with this unit. For specific handling concerns with R-410A, please contact your lOcal Trane representative. Failure to use R-410A rated service equipment or components could result in equipment or components exploding under R-410A high pressures which could resutt in death, serious injury, or equipment damage.

© 2009 Trane All rights reserved SSA-SVX06A-EN

Page 3: Split System Air Handler

SSA-SVX06A-EN

Warnings, Cautions and Notices

&WARNING Contains R-410A Refrigerant! System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives. Failure to follow proper procedures or the use of non-approved refrigerants, refrigerant substitutes. or refrigerant additives could result in death or serious injury or equipment damage.

Important: DO NOT release refrigerant to the atmosphere! If adding or removing refrigerant is required, the service technician must comply with all federal, state, and local laws.

Important: One copy of this document ships inside the control panel of each unit and is customer property. It must be retained by the unit's maintenance personnel.

&WARNING Personal Protective Equipment (PPE) Required! Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.

• Before installing/servicing this unit, technicians MUST put on all Personal Protective Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate MSDS and OSHA guidelines for proper PPE.

• When working with or around hazardous chemicals, ALWAYS refer to appropriate MSDS and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.

• If there is a risk of arc or flash, technicians MUST put on all Personal Protective Equipment (PPE) in accordance with NFPA70E for arc/flash ·prOtection PRIOR to servicing the unit.

Failure to follow recommendations could result in death or serious injury.

This booklet describes proper installation, operation, and maintenance procedures for air cooled systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.

It is important that periodic maintenance be performed to help assure trouble free operation. Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.

Important: All phases of this installation must comply with the NATIONAL, STATE & LOCAL CODES. In addition to local codes, the installation must conform with National Electric Code -ANSI!NFPA NO. 70 LATEST REVISION.

Any individual installing, maintaining, or servicing this equipment must be properly trained, licensed and qualified.

3

Page 4: Split System Air Handler

Table of Contents

Model Number Description .............................................. 5

General Information .................................................... 6 Installation Checklist ........................................... 6 Unit Inspection ............................................... 6 Initial Leak Test ............................................... 6 Lifting Recommendations ....................................... 6

Pre-Installation ......................................................... 8 Repositioning Drain Pan ............ , ........................... 8 Field Conversion to 460 Volt ..................................... 9 Refrigerant Piping ............................................ 11 Installations, Limitations and Recommendations .................. 12

Dimensional Data ...................................................... 13

Electrical Data ......................................................... 22

Installation ............................................................ 30 Horizontal Suspension ........................................ 30 Refrigerant Piping ............................................ 31 Condensate Piping · ........................................... 32 Filters ...................................................... 32 Duct Connections ............................................ 32

· AirFiow"settings .... -.-~---~ .................................... 32 Electrical Connections ......................................... 33 Checkout Procedure .......................................... 34 Installation Checklist .......................................... 34

Electrical Wiring .................................................. 34 Thermostat and Control Connections for Electromechanical Controls . 35 Thermostat and Control Connections for ReliaTei'M Controls ........ 36

Maintenance .......................................................... 38 Fan Belt Adjustment .......................................... 38 Monthly .................................................... 39 Annually (Cooling Season) ..................................... 40 Coil Cleaning ................................................ 40 Precautionary Measures ....................................... 41 First Aid Measures ........................................... 41 Maintenance Log ............................................. 42

Warranty ............................................................. 43

Central Air Conditioner ............................................ 43 Commercial Equipment Rated 20 Tons and Larger and Related Accessories (Parts Only) ................................................. 43

Wiring Diagram Matrix ................................................. 45

4 SSA-SVX06A-EN

Page 5: Split System Air Handler

Model Number Description

SSA-SVX06A-EN

TWE 240 E 3 00 B A

123 456 7 8 910 11 12

Model Number Description All products are identified by a multiple-character model number that precisely identifies a particular type of unit. An explanation of the alphanumeric identification code is provided. Its use will enable the owner/ operator, installing contractors, and service engineers to define the operation, specific components, and other options for any specific unit.

Note: When ordering replacement parts or requesting setvice, be sure to refer to the specific model number, serial number, and DL number (if applicable) stamped on the unit nameplate.

DIGITS 1 - 3: Product Type TWE ==Split System Heat Pump/Cooling Air Handler

DIGITS 4- 6: Nominal Gross Cooling Capacity (MBh)

061 = 5 Tons (60 Hz) 090 == 7% Tons (60Hz) 120 = 10 Tons (60Hz) 150 = 12V2 Tons (60Hz) 180 = 15 Tons (60Hz) 240 = 20 Tons (60 Hz)

051 = 4.6 Tons (50 Hz) 076 = 6.25 Tons (50 Hz) 101 = 8.33 Tons (50 Hz) 126 = 10.4 Tons (50 Hz) 156= 13 Tons (50 Hz) 201 = 16.7 Tons (50 Hz)

DIGIT 7: Major Development Sequence

D =Single Circuit E =Dual Circuit

DIGIT 8: Electrical Characteristics

1 = 208-230/60/1 w = 575/60/3 3 = 208-230/60/3 D = 380-415/50/3 4 = 460/60/3 K = 380/60/3

DIGITS 9 - 10: Factory Installed Options 00 = Packed Stock

DIGITS 11: Minor Design Sequence A & B =Current Design Sequence

DIGITS 12: Service Digit A= Current Service Digit

5

Page 6: Split System Air Handler

General Information

Installation procedures should be performed in the sequence that they appear in this manual. Do not destroy or remove the manual from the unit.

The manual should remain weather-protected with the unit until all installation procedures are complete.

Note: It is not the intention of this manual to cover alf possible variaUons in systems that may occur or to provide comprehensive information concerning every possible contingency that may be encountered during an installation. If additional information is required or if specmc problems arise that are not fully discussed in this manual, contact your focal sales office.

This manual covers installation of the TWE air handlers. These air handler models incorporate a single slab coil assembly, improved application flexibility, servicing, maintenance accessibility and an improved accessory line. They are fully convertible, (vertical to horizontal discharge) without fjeld removal of the coil assembly. They are shipped ready for horizontal installation.

All units have one drain pan that can be installed in any one of four positions. This allows for vertical or horizontal applications and right or left exit.

Important: All dual circuit (digit 7 =E) have an intertwined coil.

Installation Checklist

Unit Inspection

Initial Leak Test

An "Installation Checklist" is provided at the end of the installation section of this manual. Use the checklist to verify that all necessary installation procedures have been completed. Do not use the checklist as a substitute for reading the information contained in the manual. Read the entire manual before beginning installation procedures.

Inspect material carefully for any shipping damage. If damaged, it must be reported to, and claims made against the transportation company. Compare the information that appears on the unit nameplate with ordering and submittal data to ensure the proper unit was shipped. Available power supply must be compatible with electrical characteristics specified on component nameplates. Replace damaged parts with authorized parts only.

All TWE units are shipped with a holding charge of nitrogen in each circuit. Remove the access panel shown in Figure 13, p. 21. Locate the liquid line or suction line access valve for each circuit. Install gauges to determine if the circuits are still pressurized. If not, the charge has escaped. Repair as required to obtain a leak-free circuit.

Lifting Recommendations

&WARNING Improper Unit Lift!

6

Each of the cables (chains or slings) used to lift the unit must be capable of supporting the entire weight of the unit. lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements may cause equipment or property·only damage. Failure to properly lift unit could result in death or serious injury. Refer to Table 1 and Table 2 for unit weight.

NOTICE Equipment Damage! Use spreader bars to prevent straps from damaging the unit. Install the bars between lifting straps, both underneath the unit and above the unit. This will prevent the straps from crushing the ur'lit cabinet or damaging the unit finish.

SSA-SVX06A-EN

Page 7: Split System Air Handler

General Information

Before preparing the unit for lifting, estimate the approximate center of gravity for lifting safety. Because of placement of internal components, the unit weight may be unevenly distributed. Approximate unit weights are given in Table 1 and Table 2, p. 7.

The crated unit can be moved using a forklift of suitable capacity. For lifting the unit into an elevated mounting position, run lifting straps or slings underthe unit and attach securely to the lifting device.

Table 1. TWE Unit and Comer Weights- Jbs (60Hz)

Corner Weights - Vertical Corner Weights - Horizontal

Tons Model No. Shipping Max (lbs) Net Max (lbs) 1 2 3 4 A 8 c 0

5 TWE061D/E 263 232 55 71 51 55 54 67 50 61

?Y2 TWE090D/E 360 323 67 99 75 82 56 92 87 88

10 TWE120D/E 429 393 77 121 110 85 79 118 77 119

121/z TWE150E 730 676 168 192 181 135 196 164 145 171

15 TWE180E 729 675 167 192 181 135 196 163 145 "171

20 TWE240E 891 818 258 168 161 231 256 181 146 235

Table 2. TWE Unit and Comer Weights - kg (50 Hz)

Corner Weights- Vertical Corner Weights - Horizontal

Tons Model No. Shipping Max (kg) Net Max (kg) 1 2 3 4 A 8 c D

5 TWE0510/E 118 104 25 32 23 25 24 30 23 27

7'h TWE076D/E 162 145 30 45 34 37 25 41 39 40

10 TWE1010/E 193 177 35 54 so 38 36 53 35 54

12112 TWE126E 329 304 76 86 81 61 88 74 65 77

15 TWE156E 328 304 7s 86 81 61 88 73 65 77

20 TWE201E 401 368 116 76 72 104 115 81 66 106

SSA-SVX06A-EN 7

Page 8: Split System Air Handler

8

Pre-Installation The final position for the air handler must be dictated by required service access to it, weight distribution over structural supports, and by the locations of electrical, refrigerant and condensate drainage connections. After this is determined, the following preparations should be made.

Repositioning Drain Pan These air handlers come with one drain pan that can be installed in any one of four positions; this allows for vertical or horizontal application and right or left condensate line connection. The drain pan can also be easily removed for periodic cleaning.

Note: Important! AJI air handlers are shipped with the drain pan insta!Jed in the horizontal position and the connection on the left side (as shown in Figure 1. If an alternate position is required, the drain pan should be repositioned before setting the air handler.

Figure 1. Drain Pan Location

DRAIN PAN LOCATION j HORIZONTAL APPLICATION

ACCESS PLATE ALTERNATE DRAIN PAN LOCATION FOR VERTICAL APPLICATION

SSA-SVX06A-EN

Page 9: Split System Air Handler

Process for Drain Pan Relocation

1. Remove the access plate atthe opposite end ofthe drain connection. This plate secures and lifts the back end of the drain pan for sloping. It must be removed before the drain pan can be removed. This is done as follows:

a. Remove the screw

b. Lift the access plate up

c. Pull the plate out. If the drain pan is to be moved to the vertical position also remove the other two access plates.

2. Remove the screw securing the drain pan.

a. Lift the pan up

b. Slide the pan out

3. Install the drain pan into the new position.

a. Slide the drain pan into the opening

b. Lift the drain pan up

c. Push it in all the way

d. Drop it down over the lip of the opening, secure with screw

4. Install the access plate on the opposite end of the drain pain.

a. Slide the edge of the access plate under the drain pan

b. Lift the access plate and drain pan up

c. Push the access plate in

d. Drop the access plate down over the lip of the opening, secure with screw. If the drain pan is being moved to the vertical position, install the other access plates over the horizontal position opening.

NOTICE System Component Damage!

Pre-Installation

Figure 2. Drain Pan Relocation

STEP T

These air handlers are shipped with a dry nitrogen holding charge in the coil. Depress or remove the access valve core to bleed off the nitrogen prior to brazing. Temporarily cap off tubes if the refrigerant line connections are to be made later.

Field Conversion to 460 Volt

.&wARNING

SSA-SVX06A-EN

Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer's literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.

9

Page 10: Split System Air Handler

Pre-Installation

10

.&.WARNING Grounding Required! Follow proper local and state electrical code on requirements for grounding. Failure to follow code could result in death or serious injury.

• Available power supply must agree with electrical data on component nameplate.

• Some air handlers are shipped wired for 208-230 volt applications and can be converted for 460 volt by rewiring the blower motor, see Figure 3. (This includes models TWE090D3, TWE090E3, TWE120D3, TWE120E3, TWE150E3 and TWE180E3).

Converting Motor to 460 Volt 1. Ensure power is disconnected to unit by following the warning above.

2. Remove unit access panels closest to motor.

3. Open terminal cover on lead end of motor.

4. Pull voltage selector plug from low voltage selection (see Figure 3).

5. Shift the plug (or rotate 180°) to align plug for high voltage selection and re-insert plug.

Important: When re-inserting voltage selection plug, ensure it is fully seated.

6. Replace terminal cover on lead end of motor.

7. Replace unit access panels.

Figure 3. Voltage Change Plug

VIEW OF TERMINAL END

TO CHANGE VOLTAGE, PULL PLUG, ROTATE 180' AND REINSERT

o'

MARATHON"

HIGH LOW

TO CHANGE VOLTAGE, PULL SELECTOR PLUG OUT, SHIFT PLUG TO AUGN ARROW TO 460V FOR HIGH VOLTAGE OR 230V FOR LOW VOLTAGE AS DESIRED. PUSH PLUG BACK IN.

GENERAL ELECTRIC"

;

~

0

0

@ <@

".<: @

HIGH

CONNECT LINES TO L 1, L2, L3 TO REVERSE ROTATION,

@ >@ >@

INTERCHANGE AtN TWO LINE CONNECTIONS

; 0

~ 0

LOW

SSA-SVX06A-EN

Page 11: Split System Air Handler

Pre-Installation

Refrigerant Piping

Evaporator Coil Orientation Important: Applies only to TWE/261150 and 7561180 when positioned for vertical upflow. Unit

is shipped in the horizontal position. If installing in the vertical position, the coil must be reoriented by rotating the coi/4 degrees (control box side) from the shipped position. See instructions and Figure 4 below.

Process for reorienting evaporator coil on TWE126, 150, 156 and 180 only. 1. Remove screws from top evaporator coil bracket (bracket that attaches coil to cabinet and runs

the length of the unit).

2. Rotate evaporator coil approximately 4 degrees clockwise- looking from the control box end (see Figure 4). When the evaporator coil is rotated, the lower set of evaporator coil bracket holes will align with the support bracket (from which it was originally fastened).

3. Reinsert screws in evaporator coil bracket.

Figure 4. Evaporator Coil Reorientation for TWE126, 150, 156, 180

Top bracket screws

Preparation

NOTICE Unit Damage!

Rotate 4° clockwise

Do not apply heat to remove seal caps until the gauge port cores have been removed. If seal caps are intact, application of heat may generate excessive pressure in the unit and result in damage to the coil or expansion valve.

The air handler is designed so that refrigerant piping can enter from either the right or left hand side. It is shipped with the intent that the refrigerant lines will enter from the left hand side. To convert to right hand entry, unbraze the elbow on the suction line and rotate 180° and rebraze.

Important: Access to refrigerant lines is limited in all horizontal and some vertical applications. Therefore, refrigerant lines should be stubbed out and temporarily capped prior to setting the air handler. Protect adjacent surfaces from heat damage when brazing in and around the air handler.

SSA-SVX06A-EN 11

Page 12: Split System Air Handler

Pre-Installation

Installations, Limitations and Recommendations

12

NOTICE System Component Damage! Properly insulate all refrigerant gas piptng to prevent possible water damage due to condensation and to prevent capacity loss and possible compressor damage.

The general location of the air handler is normally selected by the architect, contractor and/or buyer. For proper installation the following items must be considered.

• Available power supply must agree with electrical data on component nameplate.

• If external accessories are installed on the unit, additional clearances must be provided.

• All duct work should be properly insulated to prevent condensation and heat loss.

• Refrigerant gas piping must be insulated.

It is recommended that the outline drawings (Figure 6, p. 14- Figure 13, p. 21) be studied and dimensions properly noted and checked against the selected installation site. By noting in advance which features are to be used, proper clearance allowances can be made for installation and possible future service.

Important: When installing these units "free standing" with discharge grills and isolators, a top support with isolator should be added to prevent ti'pping. Support and isolator can be attached to a waff or other appropriate structure.

Important: If adding external accessories to the unit, additional clearances must be considered for the overa/J space needed.

For installation of accessories available forth is air handler, follow the instructions packed with each accessory.

SSA·SVXD6A·EN

Page 13: Split System Air Handler

Dimensional Data

Figure 5. TWE Quick Reference

60Hz H w D

TWE061 48-1/8 (1222.4) 39-5/8 (1006.5) 23-5/8 (600)

TWE090 54-1/8(1374.8) 49-1/8(1247.8) 26-1/2 (673.1)

TWE120 54-1/8 (1374.8) 65-118 (1654.2) 26-112 (673.1 I

TWE150, 180 69-1/8 (1756) 81-1/4(20637) 30 (762)

TWE240 71-7/8(18066) 94-1/4 (2394) 32-1/8 (816)

50 Hz H w D

TWE051 48-1/8 (1 222.4) 39-5/8 (1 0065) 23-5/8 (60~)

TWE076 54-1/8 (1374.8) 49-1/8{1247.8) 26-1/2 (673.1)

TvVElOl 54-1/8(1374.8) 65-1/8(16542) 26-1/2 (673.1)

TWE126, 156 69-1/8 (1756) 81-1/4(20637) 30 (762)

TWE201 71-7/8 (18066) 94-1/4(2394) 32-1/8 (816)

Note: Full dimensional data available on next pages.

SSA-SVXD6A-EN 13

Page 14: Split System Air Handler

Dimensional Data

Figure 6. TWE051, 061 Air Handler, Single Circuit

I-2H-

(571.5) 13114" (336.5) NOTES:

SUPPLY OPENING

HEATER VENTILATION

CONTROL WIRING

LlNE VOLTAGE

CONTROL BOX

ACCESS PANEL ---1!--/

DRAIN CONNECTION FOR HORIZONTAL (SEE NOTE 2.3,5)

FILTER ACCESS PANEL 22" (558.8) MIN. DISTANCE BOTH SIDE----_/

LIQUID LINES

SEE NOTES 2,3,4

11ffl"1 ~ (28.6)

,. .I

34 9!18" (877.9)

1116" " {1 220.8)

1<~i~16" (2 5.1)

14

35 SIS" (904.9)

3715116" (963.6)

1 PANEL DEPTH 112" (12.7) (TYP.ALL PANELS) 2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END

OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT.

3.1F PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT.

4. 1" (25.4) FEMALE SCHEO. 40 PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION 5. 1" (25.4) FEMALE SCHED. 40 PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.

BOTIOM RETURN 13 5116" (338.1)

32 112" (825.5)

L--:-;;:.:J

44.45)

2 3/4" (69.8)

COPPER LIQUID LINE FIELD CONNECTION

O.D. SUCTION LINE

COPPER SUCTION LINE FIELD CONNECTION

REMOTE BULB TXV

13 9/16" 12" {344.5)

(3tt8) J

[

5/16" (23.8)

1 318" (35)

3 3116" (81)

(4)- HOLE FOR HORIZONTAL SUSPENSION

17 5J16" (439.7) 161/B" 13 9116" 12"

1 {4l6) (7.5) (3 •. 8)

1~W {23.8~ 1 318" (35)

111116" (42.9)

311116"(93.6)

SUPPLY OPENING

SEE NOTES 2,3,4

(4) HOLE FOR HORIZONTAL SUSPENSION

SIDER ETURN

80

SUPPLY VERTICAL • RETURN HORIZONTAL/ RETURN VERTICAL

SUPPLY HORIZONTAL­RETURN VERTICAL I RETURN HORIZONTAL

SSA-SVX06A-EN

Page 15: Split System Air Handler

Dimensional Data

Figure Z TWE061 Air Handler, Dual Circuit

SUPPlY OPENING

HEATER VENTILATION

CONTROL WIRING

DRAIN CONNECTION FOR HORIZONTAL (SEE NOTE 2.3,5)

FILTER ACCESS PANEL 22" (558.8) MIN. DISTANCE BOTH SIOE----...J

SEE NOTES 2,3.4

1 5116" {33.3)

1 3715116"

(953.6)

7 9116" (192)

NOTES: 1 PANEL DEPTH 112" (12.7) (TYP.ALl PANELS}. 2_ REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END

OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION. PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OVT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTAllED AFTER SLIDING PAN DRAIN PAN BACK INTO UNIT.

3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED. ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN CONNECTION AT END OF UNIT.

4. 1" (25.4) FEMALE SCHED. 40 PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION. 5. 1" (25.4) FEMALE SCHED. 40 PVC PIPE DAAIN CONNECTION HORIZONTAL CONFIGURATION.

~ 3 9116"

- (963.6)

2 5.116" {58.7)

6 7/8 (174.6)

.20MRrn;;;

~--;;;::r

3 7/16" (87.3)

(2) REMOTE BULB TXV

SUCTION LINE

13 9116" 16118" 12" (344 5) (409.6)

13~ 8' l l

t:S/16" (23.8)

1 3/8" (35)

11116" (42.9)

3 JJ16" (81}

3 11116"' (93.7} (4)- HOLE FOR HORIZONTAL SUSPENSION

32112" {825.5)

CoPPER LIQUID LINE FIELD CONNECTION

COPPER SUCTION UNE FIELD CONNECTION

COPPER LIQUID LINE FIELD CONNECTION

44.45)

-32112" -- (825.5)-

SEE NOTES 2.3.4

15116" (23.8)

2 314" (69.8)

1 118• --j f-----35 S/8",---~ (28.6) I (904.9)

SUPPLY OPENING

(4) HOLE FOR HORIZONTAL SUSPENSION

48 1/16" (1220.8)

)[

34 9/16" (877.9}

107116" (265.1)

SSA-SVX06A-EN

SIDE RETURN

BOTTOM RETURN SUPPLY VERTICAL­RETURN HORIZONTAL/ RETURN VERTICAL

FILTER

SIDE RETURN

SUPPLY HORIZONTAL· RETURN VERTICAL I RETURN HORIZONTAL

15

Page 16: Split System Air Handler

Dimensional Data

Figure 8. TWE076, 090 Air Handler, Single Circuit

25%, ---, .. ,-, r 15 718" 3/4" (403.2) (19.05)

SUPPLY OPENING

HEATER CONTROL AND SINGLE POWER ENTRY WIRES

HEATER VENTILATIO

CONTROL WIRING

LINE VOLTAGE

CONTROL BOX ACCESS PANEL ----1!_,

,. (25.4)

DRAIN CONNECTION FOR HORIZONTAL

(SEE NOTE 2,3,5)

FILTER ACCESS PANEL 22" (558.8) MIN. DISTANCE BOTH SIDE ____ J

LIQUID LINES

SEE NOTES 2,3,4

13/16"l (30.2)

I 6 314"

(171.4)

J,.

14 3/B" {365.1)

47112" 18 3/4" (1206.5) (4762) I

13112"(89)

B 13.'16! (223.8} 1

45 118" (1146.2)

"" {406.4)

NOTES: 1 PANEL DEPTH 112" (12.7) (T'fP.ALL PANELS). 2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END

OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN ACCESS ?tATE ON THE END OF UNIT OPPOSITE DRI\IN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SLIDING DRI\IN PAN BACK INTO UNIT. IF PERIODIC DRI\IN PAN CLEANING IS REQUIRED. ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT.

4. 1" {25.4) FEMALE SCHED. 40 pVC PIPE DRI\IN CONNECTION VERTICAL CONFIGURATION. 5_ 1" {25.4) FEMALE SCHED. 40 PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURI\TION.

1~16" 16 I 4i)

/REnJ~ \,,. 16 14 2r-6)

~ 39.7) Y4" 2

(69.8)

(4)-HOlEFOR HORIZOI>.'TAL SUSPENSION

.,. (1066.8)

" I 46) ,!16-j Y4" 2

(69.8)

COPPER LIQUID LINE FIELD CONNECTION

COPPER SUCTION LINE FIELD CONNECTION

17318" 1611116" (441.3) (423.9)

SUPPLY OPENING

/MR~

42" (1066.8)

SEE NOTES 2,3,4

(4) HOLE FOR HORIZONTAL SUSPENSION

1116" (936.6) SIDER EnJRN

" 113

16

73.2)

10 116" (26 ~-;, B

SUPPLY VERTICAL­RETURN HORIZONTAL f RETURN VERTICAL

SU?PL Y HORIZONTAL­RETURN VERTICAL f RETURN HORIZONTAL

SSA-SVX06A-EN

Page 17: Split System Air Handler

Dimensional Data

Figure 9. TWE090 Air Handler, Dual Circuit

SUPPLY OPENING

HEATER CONTROL MID SINGLE POWER ENTRY WIRES

HEATER VENTILATION

CONTROL WIRING

2514 --,647.7~

3.14" (19.05)

14 318" (365.1)

47 112" 18314"(1206.5) {476.2)

NOTES: 1 PANEL DEPTH 112" (12.7) (TYPALL PANELS). 2. REMOVABLE DRAIN PAN AND ATIACHED DRAIN CONNECTION MAY BE INSTALLED ON END

OF UNIT IN EITI--!ER THE VERTICAL OR HORIZONTAL CONFIGURATION, PlASTIC DRAIN PAN ACCESS PlATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT.

3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT.

4. 1" (25.4) FEMALE SCHED. 40 PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION. 5. 1" (25.4) FEMALE SCHED. 40 PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.

t16" " { 4f8)

9 39.7) 3/4" 2

(69.8)

/HETU~

·~ (1066.8)

6 t/8" ·y-6) ' ,,

J,~j (46)

2 3/4" (69.8)

?MRE~

,,. (1066.8)

LINE VOLTAGE

CONTROL BOX

r-3 1/2" (89)

81311J. (223.8)1 COPPER LIQUID UNE FIELD CONNECTION

ACCESS PANEL ----.jj~

DRAIN CONNECTION FOR HORIZONTAL

(SEE NOTE 2,3,5)

Fll TER ACCESS PANEL 2.2" (558.8) MIN. DISTANCE BOTH SIDE-

1/16" 54 ,, 373.2)

SEE NOTES 2,3,4

13/1~--(30.2)

I 6 3/4" (171.4)

36 718" {936.6}

1a;pr (26 .1)

SSA-SVX06A-EN

45 118" (1146.2)

"" (406.4)

(2) REMOTE BULB TXV

16 1/4" (412.8)

I

SIDER

16 3/4" (425.4)

I 19 1116" (464.2)

I

(4)- HOLE FOR HORIZONTAL SUSPENSION

ETURN

SUPPLY VERTICAL­RETURN HORIZONTAL/ RETURN VERTICAL

20 1116" (509.6) 16 3/4"

1 (42r)

161/4" 13 3/4" (412.8) (349.2)

j ,L~ (33.3)

3 518" (92)

SUPPLY OPENING

SIDE RETURN

1 518" (41.3)

SEE NOTES 2,3.4

(4) HOLE FOR HORIZONTAL SUSPENSION

SUPPLY HORIZONTAL­RETURN VERTICAL I RETURN HORIZONTAL

17

Page 18: Split System Air Handler

Dimensional Data

Figure 10. TWE101, 120 Air Handler, Single Circuit

SUPPLY OPENING

HEATER VENTILATION

CONTROL WIRING

LINE VOLTAGE

CONTROL BOX

n;;7~-,-15 15/16 (404.6)

ACCESS PANEL ---.JIL

SEE NOTES 2,3,4

~·· (19.05)

22114" {565.1)

18 15116" (451)

L2 ,,4. (57.1)

~6 13116" (173)

NOTES: 1 PANEL DEPTH 112" (12.7) {TYPALL PANELS). 2. REMOVABLE DRAIN PAN AND A IT ACHED DRAIN CONNECTION MAY BE INSTALLED ON END

OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT.

3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED. ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT.

4. 1" (25.4) FEMAlE SCHEO. 40 PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION. 5. 1" (25.4) FEMALE SCHEO. 40 PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.

-.......

,1,,s. 15 ,, 'I'' ~RETUR~ 6~/6" 2e) ' (4 ~OMR~

' ( '9 42.9)

2 314" (69.6)

sa· (1473.2)

,l,j (46)

3/4" 2 {69.8)

COPPER LIQUID LINE FIELD CONNECTION

sa· (1473.2)

SEE NOTES 2,3,4

'"""R (1612.9)

1 3116" 61116"

I (30.2) (1552.6)

{4)- HOLE FOR HORIZONTAL SUSPENSION

SUPPLY OPENING

(4) HOLE FOR HORIZONTAL SUSPENSION

4 1116" 5 ,, 373.2)

18

6 3/4" (171.4

J/8. (936.6)

10 7116" t!265.1)

SlOE RET URN

B OTTOM RETURN

SUPPLY VERTICAL­RETURN HORIZONTAL I RETURN VERTICAL

SUPPLY HORIZONTAL­RETURN VERTICAL I RETURN HORIZONTAL

SSA-SVX06A·EN

Page 19: Split System Air Handler

Dimensional Data

Figure 11. TWE101, 120 Air Handler, Dual Circuit

SUPPLY OPENING

HEATER VENTILATION

CONTROL WIRING

LINE VOLTAGE

CONTROL BOX ACCESS PANEL

' 1!16" 54 (1 373.2)

SEE NOTES 2,3,4

13116"1 I (30.21

(~l~~)_

,1 (936.6)

'

10 7/16" \>(265.1)

SSA-SVX06A-EN

I

25 ~ --(647.7)

15 15/16" 3J4" (404.8} (19.05)

611/!1" (1552.6)

221/4" (565.1)

NOTES: 1 PANEL DEPTH 112" (12.7){TYP.ALL PANELS). 2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END

OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION. PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT.

J.IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT.

4. 1" (25.4) FEMALE SCHEO. 40 PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION. 5.1" (25.4) FEMALE SCHEO. 40 PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.

--..._

ls1w s\ffl. 15 (4 ·~4.8) ~RETUR~ ,

(4 ·y·6l ~OM RET~

,t,,J 42.9)

, (

,l,j (46)

2 314" sa· (69.8) (1473.2)

~4' 2 (69.8)

COPPER LIQUID LINE FIELD CONNECTION

sa· (1473.2)

(2) REMOTE BULB TXV

SUCTION LINE

16114" {412.7)

I

SIDE

( 4)- HOLE FOR HORIZONTAL SUSPENSION

RETURN

BOTTOM RETURN

SUPPLY VERTICAL­RETURN HORIZONTAL I RETURN VERTICAL

1 5116" (33.3j

1 518" (41.3)

3 SIS" {92.1)

(4) HOLE FOR HORIZONTAL SUSPENSION

SEE NOTES 2.3.4

SUPPLY HORIZONTAL­RETURN VERTICAL I RETURN HORIZONTAL

19

Page 20: Split System Air Handler

Dimensional Data

Figure 12. TWE126, 150, 156, 180 Air Handler, Dual Circuit

SUPPLY OPENING -<

HEATER CONT AND SINGLE P ENTRVWIRES

ROL OWER

CONTROL WIRING

CONTROL BOX ACCESS PANEL

-28118"-(714.4)

-..1 16"-(406.4)

~

0

/_

4 5/16"-<> (109.5)

j--3 1/16" (7 7.8)

-----, 141 •. (~ 8)

113 1~1 16" 7) (4~4.

13~/ (~12.

,. ,, 181~/ 16" (47t 7)

L"ro· (308)

NOTES: 1 PANEL DEPTH 1!2" (12.7) (TYPALL PANELS). 2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END

OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION. PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST SE REMOVED TO SLIDE DMIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SUDING DRAIN PAN BACK INTO UNIT.

3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT

4. 1" (25.4) FEMALE SCHED. 40 PVC PIPE DRAIN CDNNECTIONVERTICAL CONFIGURAllON 5. 1" (25.4) FEMALE SCHED. 40 PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.

-...._

;riB. 1 I r) /RE~ /ERE~

TQ-9;-3) 19 (4 /MR~ /MR~

3 ( 'l 5116" 84.1)

2 3/4" (70)

(2) REMOTE BULB TXV

SUCTION LINE

18 5116" (465.1)

I 18 1i116" (474.6)

I

74 118" (1882.8)

{4)- HOLE FOR HORIZONTAL SUSPENSION

7116"j 7.3)

"" 3 (8

2 {70)

COPPER LIQUID LINE FIELD CONNECTION

74 1/8" (1882.8)

15 13/16" (401.6}

I

2"(50.8)j 2 5116" (58.7)

4 118" (104.8)

SEE NOTES 2.3.4

r------,(~~25~~~),--------1 1 3116"-lf-------77 3116"'------11 (JO.Z) (1950.6)

(4) HOLE FOR HORIZONTAL SUSPENSION

9 518" (244.5)

48" 69 1116" (1219.2) (1754.2)

117116"(290.5)

20

SIDE RETURN

SUPPLY VERTICAL· RETURN HORIZONTAL/ RETURN VERTICAL

SUPPLY HORIZONTAL· RETURN VERTICAL I RETURN HORIZONTAL

SSA-SVX06A-EN

Page 21: Split System Air Handler

Dimensional Data

Figure 13. TWE201, 240 Air Handler, Dual Circuit

SUPPLY OPENING

CONTROL WIRING

liNE VOLTAGE

CONTROL BOX

ACCESS PANEL -----~--•

DRAIN CONNECTION FOR HORIZONTAL

(SEE NOTE 2,3,5)

7 (1

LIQUID LINES

SEE NOTES 2.3.4

111116.(42.9)-<-

I 9 518"

(244.5) ·,! 1 7/8"

(1290.6)

825.6)

11 ~6:--(290.5)

I

SSA-SVX06A-EN

1811/16" (474.6)

92 9116" (2351)

89 3116" (2265.4)

2015/16" (531.8)

rJ 3' (76.2)

4 3/4" (120.6)

NOTES: 1 PANEL DEPTH 112" (12.7) (TYPALL PANELS). 2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END

OF UNIT IN EITHER THE VERTICAL OR HORIZONTAl CONFIGURATION, PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO SUDE DRAIN PAN OUT OF UNIT CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT.

3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED.ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT.

4. 1" (25.4} FEMALE SCHED. 40 PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION. 5. 1" (25.4) FEMALE SCHED.40 PVC PIPE DRAIN CONNECTION HORIZONTAl CONFIGURATION.

SIDE RETURN SIDE RETURN

1-----831/8"':-----4 (2111.4)

~ 1.8) 20 (5

2 I 74.6) ,t,d 314" 4

(120.6)

COPPER LIQUID LINE FIELD CONNECTION

4) ·HOLE FOR HORIZONTAL SUSPENSION /'

SIDE RETURN

BOTIOM RET URN

SUPPLY VERTICAL­RETURN HORIZONTAL I RETURN VERTICAL

BOTIOM RETURN BOTIOM RETURN

831/8" (2111.4)

SEE NOTES 2.3,4

(4) HOLE FOR HORIZONTAL SUSPENSION

SUPPLY HORIZONTAL­RETURN VERTICAL I RETURN HORIZONTAL

21

Page 22: Split System Air Handler

Electrical Data

Table 3. Electrical Characteristics - Standard and Low Static Motors - 60Hz Air Handlerl•l

Standard Evaporator Fan Motor

Tons Unit Model Number No. Volts Phase

TWE06101, El 1 . 208 1

TWE061D1, El 1 230 1

TWE061D3, E3 1 208 3 5

TWE06103, E3 1 230 3

TWE061D4, E4 1 460 3

TWE061DW 1 575 3

TWE090Dl, El 1 208 1

TWE090D1, El 1 230 1

71/z TWE090D3, E3 1 208 3

TWE090D3, E3 1 230 3

TWE09003, EJ(b) 1 460 3

TWE09DDW 1 575 3

TWE120Dl, El 1 208 1

TWE120Dl, El 1 230 1

10 TWE120D3, E3 1 208 3

TWE120D3, E3 1 230 3

TWE12003, EJ(b) 1 460 3

TWE120DW, EW 1 575 3

TWE150E3 1 208 3

TWE150E3 1 230 3 12Y2

TWElSOEJ(b} 1 460 3

TWElSOEW 1 575 3

TWE180E3 1 208 3

TWE180E3 1 230 3 15

TWE180E3(b) 1 460 3

TWE180EW 1 575 3

TWE240E3 1 208 3

TWE240E3 1 230 3 20

TWE240E4 1 460 3

TWE240EW 1 575 3

Contmued on next page

(a) For additional information contact product support. (b) Field wired for 460V.

22

Amps

Hp FLA LRA MCA

0.75 6.0 41.0 7.5

0.75 5.9 45.0 7.4

0.75 2.5 16.4 3.1

0.75 2.4 16.4 3.0

0.75 1.2 8.2 1.5

0.75 1.3 6.1 1.6

1.50 6.8 31.5 8.5

1.50 6.2 31.5 7.8

1.50 5.3 34.3 6.6

1.50 5.0 34.3 6.3

1.50 2.5 17.0 3.1

1.50 1.8 13.6 2.3

2.00 8.5 57.4 10.6

2.00 7.7 57.4 9.6

2.00 6.2 33.9 7.8

2.00 5.8 33.9 7.3

2.00 2.9 33.9 3.6

2.00 2.3 14.4 2.9

2.00 5.95 23.0 7.4

2.00 5.5 23.0 6.9

2.00 2.75 23.0 3.4

2.00 2.2 18.0 2.8

3.00 9.4 74.9 11.8

3.00 9.2 74.9 11.5

3.00 4.6 39.3 5.8

3.00 3.4 24.6 4.3

5.00 14.5 98.0 18.1

5.00 14.3 98.0 17.9

5.00 6.7 47.0 8.4

5.00 5.2 . 6.5

Low Static Evaporator Fan Motor

Amps

MFS No. Volts Phase Hp FLA LRA MCA MFS

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

20 N/A N/A N/A N/A N/A N/A N/A N/A

20 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

25 1 208 3 3.00 9.4 74.9 11.8 20

25 1 230 3 3.00 9.2 74.9 11.5 20

15 1 460 3 3.00 4.6 39.3 5.8 15

15 1 575 3 3.00 3.4 24.6 4.3 15

SSA-SVX06A-EN

Page 23: Split System Air Handler

Electrical Data

Table 4. Electrical Characteristics - High and Ultra-High Static Motors - 60Hz Air Handlerl•l

High Static Evaporator Fan Motor

Tons Unit Model Number No. Volts Phase

TWE061D1, El 1 208 1

TWE061Dl, El 1 230 1

TWE061D3, E3 1 208 3 5

TWE06103, E3 1 230 3

TWE06104, E4 1 460 3

TWE061DW 1 575 3

TWE09001, El 1 208 1

TWE090Dl, El 1 230 1

TWE090D3, E3 1 208 3 71f2

TWE09003, E3 1 230 3

TWE090D3, EJ(b) 1 460 3

TWE090DW 1 575 3

TWE12001, El N/A N/A N/A

TWE12001, El N/A N/A N/A

TWE120D3, E3 1 208 3 10

TWE120D3, E3 1 230 3

TWE120D3, EJ(b) 1 460 3

TWE120DW, EW 1 575 3

TWE150E3 1 208 3

TWE150E3 1 230 3 12Y2

TWElSOEJ{b) 1 460 3

TWElSOEW 1 575 3

TWE180E3 1 208 3

TWE1BOE3 1 230 3 15

TWE180EJ(bl 1 460 3

TWE180EW 1 575 3

TWE240E3 N/A N/A N/A

TWE240E3 N/A N/A N/A 20

TWE240E4 N/A N/A N/A

TWE240EW N/A N/A N/A

(a) For addLtLonalmformatLon contact product support. (b) Field wired for 46DV.

SSA-SVX06A·EN

Amps

Hp FLA LRA MCA

1.50 6.8 31.5 8.5

1.50 6.2 31.5 7.8

1.50 5.3 34.3 6.6

1.50 5.0 34.3 6.3

1.50 2.5 17.0 3.1

1.50 1.8 13.6 2.3

2.00 8.5 57.4 10.6

2.00 7.7 57.4 9.6

2.00 6.2 33.9 7.8

2.00 5.8 33.9 7.3

2.00 2.9 33.9 3.6

2.00 2.3 14.4 2.9

N/A N/A N/A N/A

N/A N/A N/A N/A

3.00 9.4 74.9 11.8

3.00 9.2 74.9 11.5

3.00 4.6 39.3 5.8

3.00 3.4 24.6 4.3

3.00 9.4 74.9 11.8

3.00 9.2 74.9 11.5

3.00 4.6 39.3 5.8

3.00 3.4 24.6 4.3

5.00 14.5 98.0 18.1

5.00 14.3 98.0 17.9

5.00 6.7 47.0 8.4

5.00 5.2 . 6.5

N/A N/A N/A N/A

N/A N/A N/A N/A

N/A N/A N/A N/A

N/A N/A N/A N/A

Ultra-High Static Evaporator Fan Motor

Volts I Phase

Amps

MFS No. Hp FLA LRA MCA MFS

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 1 208 3 3.00 9.4 74.9 11.8 20

15 1 230 3 3.00 9.2 74.9 11.5 20

15 1 460 3 3.00 4.6 39.3 5.8 15

15 1 575 3 3.00 3.4 24.6 4.3 15

N/A N/A N/A N/A N/A N/A N/A N/A N/A

N/A N/A N/A N/A N/A N/A N/A N/A N/A

20 N/A N/A N/A N/A N/A N/A N/A N/A

20 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

20 1 208 3 5.00 14.5 98.0 18.1 25

20 1 230 3 5.00 14.3 98.0 17.9 25

15 1 460 3 5.00 6.7 47.0 8.4 15

15 1 575 3 5.00 5.2 .• 6.5 15

25 N/A N/A N/A N/A N/A N/A N/A N/A

25 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A

N/A 1 208 3 7.50 20 114.0 25.0 35

N/A 1 230 3 7.50 17.6 126.0 22.0 35

N/A 1 460 3 7.50 9.0 61.4 11.3 20

N/A 1 575 3 7.50 7.2 49.8 9.0 15

23

Page 24: Split System Air Handler

Electrical Data

24

Table 5. Unit Wiring - Air Handler - 60Hz

Tons Unit Model Number

TWE06Dl, El

TWE06103, E3

5 TWE06104, E4

TWE061DK

TWE061DW

TWE090Dl, El

TWE090D3, EJ(b)

?V2 TWE090D3, E3(c)

TWE090DK

TWE090DW

TWE120D1, El

TWE120D3, EJ(b)

10 TWE12003, E3(c)

TWE120DK

TWE120DW, EW

TWE150E3

lZY2 TWE1SOE3(c)

TWElSOEK

TWElSOEW

TWE180E3

TWE180E3(c) 15

TWE180EK

TWE180EW

TWE240E3

TWE240E4 20

TWE240EK

TWE240EW

(a) HACR type Clrcutt breaker per NEC. (b) When wired for 208-230 volt. (c) When wired for 460 volt.

Unit Operating Voltage Range

187-253

187-253

414-506

342-418

518-632

187-253

187-253

414-506

342-418

518-632

187-253

187-253

414-506

342-418

518-632

187-253

414-506

342-418

518-632

187-253

414-506

342-418

518-632

187-253

414-506

342-418

518-632

Maximum Fuse Minimum Circuit or HACR Circuit

Ampacity Breaker Size(a)

7.5 15

3.1 15

1.5 15

1.4 15

1.6 15

8.5 15

6.6 15

3.1 15

3.8 15

2.3 15

10.6 15

7.8 15

3.6 15

4.1 15

2.9 15

7.4 15

3.4 15

4.1 15

2.8 15

11.8 20

5.8 15

9.8 15

4.3 15

18.1 25

8.4 15

10.4 15

6.5 15

SSA-SVX06A-EN

Page 25: Split System Air Handler

Electrical Data

Table 6. Unit Wiring with Electric Heat (Single Point Connection) - 5, 7Yz and 10 Ton Air Handlers - 60Hz

Maximum Maximum Fuse or Fuse Heater Unit Power Minimum Circuit HACR Circuit

Tons Used With Heater Model No. KW Rating(a) Supply Control Stages Ampacity<bl Breaker Size(b)(c)

BAYHTRL106A 4.33/5.76 I 33/37 35/40

TWE061Dl BAYHTRL112A 8.65/11.52 5

208-230/1/60 I 59/67 60/70

TWE061El BAYHTRL117A 12.98/17.28 I 85/97 90/100

BAYHTRL123A 17.30/23.04 2 111/127(d) 125/150

BAYHTRL106A 4.33/5.76 I 34/38 35/40

BAYHTRL112A 8.65/11.52 I 60/681dl 60/70

71/z TWE090Dl BAYHTRL117A 12.98/17.28 208-230/1/60 I 86/98 90/100

TWE090E1 BAYHTRL123A 17.30/23.04 2 112/1281'1 125/150

BAYHTRL129A 21.65/28.80 2 138/lSS(d) 150/175

BA YHTRLl 06A 4.33/5.76 I 37/41 40/45

BAYHTRL112A 8.65/11.52 I 63/?t(d) 70/80

10 TWE120D1 BAYHTRL117A 12.98/17.28 208-230/1/60 I 89/101 90/110

TWE120El BAYHTRL123A 17.30/23.04 2 115/131idl 125/150

BAYHTRL129A 21.65/28.80 2 141/161(d) 150/175

BAYHTRL305A 3.75/5.00 I 17/19 20/20

TWE061D3 5

BAYHTRL310A 7.45/9.96 208-230/3/60 I 30/34 30/35

TWE061E3 BAYHTRL315A 11.25/14.96 I 43/49 45/50

BAYHTRL325A 18.71/24.92 2 69/79{d) 70/80

BAYHTRL305A 3.75/5.00 I 20/22 20/25

BAYHTRL310A 7.45/9.96 I 33/37 35/40

71/2 TWE090D3 BAYHTRL315A 11.25/14.96 208-230/3/60 I 46/52 50/60

TWE090E3 BAYHTRL325A 18.71/24.92 2 72/B2(d) 80/90

BAYHTRL335A 26.20/34.88 2 97/112(e) 100/125

BAYHTRL305A 3.75/5.00 I 21/23 25/25

BAYHTRL310A 7.45/9.96 I 34/38 35/40

10 TWE120D3 BAYHTRL315A 11.25/14.96 208-230/3/60 I 47/53 50/60

TWE120E3 BA YHTRL325A 18.71/24.92 2 73/SJ(dl 80/90

BAYHTRL335A 26.20/34.88 2 98/113(e) 100/125

BAYHTRL405A 5 I 10 15

TWE06104 BAYHTRL410A 9.96 460/3/60 I 17 20 5

TWE061E4 BAYHTRL415A 14.96 I 25 25

BAYHTRL425A 24.92 2 40 40

BAYHTRL405A 5 I II 15

BAYHTRL410A 9.96 I 19 20

7Y2 TWE090DJ(f) BAYHTRL415A 14.96 460/3/60 I 26 30

TWE090EJ(f) BAYHTRL42SA 24.92 2 41 45

BAYHTRL435A 34.88 2 56 60

BAYHTRL40SA 5 I 12 15

BAYHTRL410A 9.96 I 20 20

10 TWE1200J(f) BAYHTRL41SA 14.96 460/3/60 I 27 30

TWE120EJ(f) BAYHTRL425A 24.92 2 42 45

BAYHTRL43SA 34.88 2 57 60

SSA-SVX06A-EN 25

Page 26: Split System Air Handler

Electrical Data

Table 6. Unit Wiring with Electric Heat (Sing.le Point Connection) - 5, 7% and 10 Ton Air Handlers - 60 Hz

Maximum Fuse Heater Unit Power

Tons use'd With Heater Model No. KW Rating(a) Supply Control Stages

BAYHtRLWOSA 5

BAYHTRLWlOA 9.96 5

TWE061DW BAYHTRLWlSA 14.96

BAYHTRLW25A 24.92

BAYHTRLWOSA 5

BAYHTRLWlOA 9.96

lV2 TWE090DW BAYHTRLW15A 14.96

BAYHTRLW25A 24.92

BAYHTRLW35A 34.88

BAYHTRLWOSA 5

BAYHTRLWlOA 9.96

10 TWE120DW BAYHTRLWlSA 14.96

TWE120EW BAYHTRLW25A 24.92

BAYHTRLW3SA 34.88

(a} kW ratmgs are at: 208/240V for 208-230V a1r handlers. 480V for 460V air handlers 600V for 57SV air handlers

575/3/60

575/3/60

575/3/60

For other than rated voltage, capacity= (Voltage/Rated Voltage)Z x Rated capacity. (b) Any power supply and circuits must be wired and protected In accordance with local codes. (c) The HACR circuit breaker is for U.S.A. installations only. (d) Fleld wire must be rated at least 75°(. (e) Field wire must be rated at least 90°(. (f) With motor field converted to 460V.

26

1

1

1

2

1

1

1

2

2

1

1

1

2

2

Maximum Fuse or Minimum Circuit HACR Circuit

Ampacity(b} Breaker Size(b)(c)

8 15

15 15

21 25

33 35

11 15

17 20

23 25

36 40

48 50

10 15

16 20

22 25

35 35

47 50

SSA-SVX06A-EN

I ' I ' I i I ,I

I

I I I

' I I

\

Page 27: Split System Air Handler

Table 7. Unit Wiring with Electric Heat (Single Point Connection) - 12'1>- 20 Ton Air Handlers

Heater Heater KW Tons Used With Model No. Rating(a)

BAYHTRM310A 7.50/10.00

BAYHTRM320A 14.96/19.92 121/z TWE150E3

BAYHTRM330A 22.50/29.92

BAYHTRM350A 37.42/49.84

BAYHTRM310A 7.50/10.00

BAYHTRM320A 14.96/19.92 IS TWE180E3

BAYHTRM330A 22.50/29.92

BAYHTRM350A 37.42/49.84

BAYHTRM310A 7.50/10.00

BAYHTRM320A 14.96/19.92 20 TWE240E3

BAYHTRM330A 22.50/29.92

BAYHTRM350A 37.42/49.84

BAYHTRM410A 10

TWE150E3(e) BAYHTRM420A 19.92

lZY2 BAYHTRM430A 29.92

BAYHTRM4SOA 49.84

BAYHTRM410A 10

BAYHTRM420A 19.92 15 TWE1BOE3(e)

BAYHTRM430A 29.92

BAYHTRM450A 49.84

BAYHTRM410A 10

BAYHTRM420A 19.92 20 TWE240E4

BAYHTRM430A 29.92

BAYHTRM450A 49.84

BAYHTRMWlOA 10

BAYHTRMW20A 19.92 12V2 TWE150EW

BAYHTRMW30A 29.92

BAYHTRMW50A 49.84

BAYHTRMWlOA 10

BAYHTRMW20A 19.92 IS TWE180EW

BAYHTRMW30A 29.92

BAYHTRMW50A 49.84

BAYHTRMW10A 10

BAYHTRMW20A 19.92 20 TWE240EW

BAYHTRMW30A 29.92

BAYHTRMW50A 49.84

(a) kW ratmgs are at: 208/240V for 208-230V a1r handlers. 480V for 460V air handlers 600V for 575V air handlers

Unit Power Supply

208-230/3/60

208-230/3/60

208-230/3/60

460/3/60

460/3/60

460/3/60

575/3/60

575/3/60

575/3/60

For other than rated voltage, capacity= (Voltage/Rated Voltage)2 x Rated Capacity.

Control Stages

1

1

2

2

1

I

2

2

1

1

2

2

I

I

2

2

1

I

2

2

1

1

2

2

1

I

2

2

I

1

2

2

1

1

2

2

(b) Any power supply and circuits must be wired and protected in accordance with local codes. (c) The HACR circuit breaker is for U.S.A. installations only. (d) Held wire must be rated at least 90°C. (e) With motor field wired for 460V.

SSA-SVX06A-EN

Minimum Circuit An'lpacity(b}

33/37

59/67

85/97

137/157

38/42

64/72

90/102

142/162(d)

45/49

71/79

97/109

149/169(d)

19

34

49

79

21

36

51

81

24

39

54

84

IS

27

39

63

17

30

42

67

20

32

45

70

Electrical Data

Maximum Fuse or HACR Circuit

Breaker Size(b)(c)

35/40

60/70

90/100

150/175

40/45

70/80

90/110

150/175

50/50

80/80

100/110

150/175

20

35

so 80

25

40

60

90

25

40

60

90

20

30

40

70

20

30

45

70

25

35

45

70

27

Page 28: Split System Air Handler

Electrical Data

Table 8. Electrical Characteristics - Standard Motor - 50 Hz Air Handler

I Standard Evaporator Fan Motor

Amps

Tons Unit Model Number No. Volts Phase FLA LRA

1 380

I 3 1.4 8.0

4.5 nJ\/EOSlDD, ED 1 415 3 1.0 8.36

1 380 3 3.1 17 6.25 TVVE076DD, ED

1 415 3 3.2 16.8

1 380 3 3.4 17.3 8.33 TWE101DD, ED

1 415 3 3.2 19

1 380 3 3.2 35 10.4 TWE126ED

1 415 3 3.1 35

1 380 3 4.0 33.1 13.0 TWE156ED

1 415 3 4.0 36.1

1 380 3 7.8 40 16.7 TWE201ED

1 415 3 7.6 45

Table 9. Unit Wiring - Air Handler - 50 Hz

Minimum Maximum Fuse Unit Unit Operating Circuit Size or Maximum

Tons Model No. Voltage Range Ampacity Circuit Breaker

4.5 TWE051DD 380/415 4 15

6.25 TWE076DD 380/415 5 15

8.33 TWE101DD, ED 380/415 5 15

10.4 TWE126ED 380/415 5 15

13.0 TWE156ED 380/415 6 15

16.7 TWE201ED 380/415 10 15

28 SSA-SVX06A-EN

I

I I

I I I

I I I

J I

I I

I

I I I

I I '·

Page 29: Split System Air Handler

SSA-SVX06A-EN

Electrical Data

Table 10. Unit Wiring With Electric Heat (Single Point Connection) -Air Handlersl•llbl

Heater Heater To Use Model No. kW Rating( c) with Unit

BAYHTRL40SA 5.00

BAYHTRL410A 9.96 TWEOSlDD

BAYHTRL415A 14.96

BAYHTRL42SA 24.92

BAYHTRL405A 5.00

BAYHTRL410A 9.96

BAYHTRL415A 14.96 TWE076DD

BAYHTRL42SA 24.92

BAYHTRL435A 34.88

BAYHTRL40SA 5.00

BAYHTRL410A 9.96

BAYHTRL415A 14.96 TWE101DD, TWE101ED

BAYHTRL425A 24.92

BAYHTRL435A 34.88

BAYHTRM410A 10.00

BAYHTRM420A 19.92 TWE126ED

BAYHTRM430A 24.92

BAYHTRM450A 49.84

BAYHTRM410A 10.00

BAYHTRM420A 19.92 TWE156ED

BAYHTRM430A 24.92

BAYHTRM450A 49.84

8AYHTRM410A 10.00

BAYHTRM420A 19.92 TWE201ED

BAYHTRM430A 24.92

BAYHTRM450A 49.84

(a) Field wire must be rated at least 167°F (75°C). (b) Field wire must be rated at least 194°F (90°C).

Minimum Control Circuit Stages Ampacity (d)

1 13

1 22

1 31

2 49

1 14

1 23

1 32

2 50

2 68

1 14

1 23

1 32

2 50

2 68

1 19

1 41

2 59

2 94

1 23

1 41

2 59

2 95

1 29

1 46

2 65

2 100

(c) kW ratings are at 400v for 3 phase, 400v air handlers For other than rated voltage, Capacity= (Voltage/Rated Voltage)2 x Rated Capacity and kW =(Voltage/Rated Voltage) 2 Rated kW.

Maximum Fuse Breaker

Size 2

15

25

35

50

15

25

35

50

70

15

25

35

50

70

20

45

60

100

25

45

60

100

30

50

70

100

(d) Any power supply and circuits must be wired and protected in accordance with lo<:al codes. MCA and Maximum Fuse Size is based on 400V.

29

Page 30: Split System Air Handler

Installation

Horizontal Suspension

30

If the air handler will be suspended, use a suspension mounting kit to isolate the unit from the structure. This is usually accomplished through the use of spring or rubber isolators, which are offered as an accesSory. Mounting rods must be field supplied. Isolator selection is dependent upon total unit weight including accessories. Approximate unit weights are provided in Table 1 and Table 2, p. 7.

NOTICE Equipment Damage! Before hanging the unit on suspension rods, reinforce the cabinet around the suspension holes by using a large washer inside the cabinet. Washers should be between the skin of the air handler and the nut on the suspension rod.

Align holes in the cabinet with structural supports and secure suspension rods to the structure, then to the air handler cabinet. If hole locations do not permit proper alignment with existing structure, it may be necessary to field fabricate cross members on existing structural beams.

Note: When other than bottom return is to be used, side panel removed for return duct installation must be secured over the bottom opening.

Leveling This air handler has a double sloped drain pan. In order to assure proper drainage along the length of the drain pan, it is important to have the unit properly leveled. Be sure the air handler is level.

Auxiliary Drain Pan A field fabricated, auxiliary drain pan should be installed under the unit for all horizontal applications and when air handlers are installed above ceilings or in other locations where condensate overflow may cause damage. This drain pan will eliminate any excess condensation that may be due to extreme humidity or an obstructed drain in the primary drain pan. Drain lines from this pan must be installed, but should not be connected to the primary drain line from the unit. Isolate the auxiliary drain pan from both the air handler and the structure.

&WARNING Fiberglass Wool! Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respiratory, skin or eye irritation.

Precautionary Measures • Avoid breathing fiberglass dust.

• Use a NIOSH approved dust/mist respirator.

• Avoid contact with the skin or eyes. Wear long-sleeved, loose-fitting clothing, gloves, and eye protection.

• Wash clothes separately from other clothing: rinse washer thoroughly.

• Operations such as sawing~ blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respirator in these situations.

SSA-SVX06A-EN

I

I I

I I I

I ' I I I I

Page 31: Split System Air Handler

Installation

First Aid Measures

Eye Contact- Flush eyes with water to remove dust. If symptoms persist. seek medical attention.

Skin Contact - Wash affected areas gently with soap and warm water after handling.

Refrigerant Piping

SSA-SVX06A-EN

Installation, brazing, leak testing and evacuation of refrigerant Jines are covered in the installation instructions packaged with the outdoor unit. Read the instructions before beginning installation of refrigerant lines.

Locate cloth bag(s) attached to the refrigerant tube of the coil that contains a stainless steel clamp and insulation material (approximately 9" long by 4" wide) for each refrigerant circuit. This is for attaching and insulating the expansion valve bulb (s) to the suction line(s).

On air handlers that will have refrigerant lines entering the cabinet from the left side, remove the split rubber grommet from the knockout in the end of the air handler. Uncoil the cap tube with the bulb attached at the expansion valve and place the grommet on the cap tube. With the grommet around the tube, push the bulb through the hole and position the grommet back into its original position (one bulb and cap tube on single circuit units and two bulbs and cap tubes on dual circuit units).

Attach the bulb(s) on a horizontal section oftube where the entire length ofthe bulb is in contact with the tube, (see Figure 14, p. 31) approximately 45 degrees off vertical (a 10 or 2 o'clock position), 10 to 12 inches outside of the air handler.

On air handlers that will have refrigerant lines entering the cabinet from the right side, the bulb(s) should be attached to the suction tube(s) inside the cabinet in the sam·e manner as above. approximately 10" from the right end of the unit.

After attaching to the suction line{s), either inside or outside of the cabinet, wrap the insulation around the bulb(s) and suction tube(s). Refrigerant piping should be insulated.

NOTICE Equipment Damage!

Figure 14. Remote Bulb Installation

Between /10 and 2 O'Clock"-...,.

Bulb Retaining Clip

Ensure that the refrigerant lines passing through the cabinet are not resting on sharp sheet metal edges and that the bulb(s) are attached to the suction line of the same circuit.

31

Page 32: Split System Air Handler

Installation

Condensate Piping

Filters

The drain pan condensate connection is a female slip joint type for 1" Schedule 40 PVC pipe. Use PVC cement and tubing as required (field supplied) to construct a trap. A union or flexible tubing and clamps may be installed if the drain pan is to be removed periodically for cleaning.

Important: When air handler is instafled in the vertical position and close proximity trapping of condensate is required, use of a subbase accessory to raise the air handler for clearance of the drain trap is recommended. See Figure 15 for a typical drain trap assembly.

Figure 15. Typical Drain Trap Assembly

VENT

DRAIN

Materials 2 each- TEE 2 each- go• Ell 1 each- PLUG 2 each- 6" NIPPLE 2 each- 2'NIPPLE 1 each -l"NPTto PVC or

COPPER ADAPTER

Air handlers are shipped with throwaway filters Figure 16. Filter Replacement installed. For replacement filters consult the air handler service facts for correct size and number.

To replace filters from the end of the unit, remove lower access panel (either end) and slide old filters out and replace with new ones. To replace from the front of the unit, remove one "L' shaped angle. Remove and replace filters and reinstaii"L' shaped angle. See Figure 16.

To convert from 1" filter to a 2" filter on units so equipped, remove lower access panels from both ends of the air handler. Remove screws and rotate the "L' shaped angles from both the top and bottom ofthefiltertrack 180°to increase the width of the filter opening.

Frame

Duct Connections

The supply and return ducts should be connected to the unit with flame retardant duct connectors to reduce vibration transmission. The return duct should be sized to the same dimensions as the return inlet of the unit.

Important: Duct flanges are provided for attachment of the duct work and are packaged on the outside of the cabinet for TWE150, 180 and 240 and TWE126, 156 and 201. The duct flanges are fastened to the top coil support bracket in the TWE051, 061, 076, 090, 101 and 120 models.

Air Flow Settings

32

Unit is shipped for nominal airflow with nominal static pressure. Please refer to fan performance table in either the product catalog or unit service facts and select the proper drive package for each application. Failure to do so could result in improper airflow causing coil frosting or condensate management problems. Condensate management problems such as water blow off could be the

SSA-SVX06A-EN

I I i i I

I I I f I i I

I I

i

I I

Page 33: Split System Air Handler

Installation

result of too great of air face velocity across the coil. To ensure proper operation refer to fan belt adjustment procedures, p. 38.

Electrical Connections

&wARNING

SSA·SVX06A-EN

Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer's literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.

&wARNING Grounding Required! Follow proper local and state electrical code on requirements for grounding. Failure to follow code could result in death or serious injury.

1. All electrical lines, sizing, protection, and grounding must be in accordance with the National Electric Code and local codes.

2. Isolate conduit whenever vibration transmission may cause a noise problem within the building structure.

3. Ensure all connections are tight and no wires exposed.

4. All accessories must be installed and wired according to the instructions packaged with that accessory.

For air handler power entry only, or for dual power entry {power entry for air handler and power entry for electric heats), the electrical connections are made in the fan control box located in the right side of the air handler and electric heater respectively. Wiring entrance is through holes provided in the end of the air handler cabinet, Figure 17. Breaker or fuse size can be ·selected using the nameplates attached to the unit and electric heater (see Table 6, p. 25).

Table 11. Recommended T'stat Wire Size

Figure 17. Electrical Entries

Wire Size (Gauge)

Maximum Wire Length Physical distance between Unit & T'stat

22

20

18

16

14

30 Feet

SO Feet

75 Feet

125 Feet

200 Feet

33

Page 34: Split System Air Handler

Installation

Checkout Procedure Complete the following "installation checklist" once installation of field wiring connections is complete. All operational checks (unit running) must be made after the outdoor unit is installed and system interconnection is complete.

Installation Checklist

&WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

Complete this checklist once the unit is installed to verify that all recommended procedures have been accomplished before the system is started. Operational checks cannot be performed until the outdoor unit is installed and system interconnection is complete.

1. Verify that the unit electrical power is disconnected.

2. Inspect all field wiring connections. All connections should be clean and tight.

3. Inspect unit ground connection(s). Ground must comply with all applicable codes.

4. Inspect unit suspension arrangement (if used). Unit position must be secure. Remove any tools or debris found in or near the unit.

5. Inspect duct outlets. Outlets must be open and unrestricted.

6. Inspect unit drain lines. Pipe connections must be tight and drain line unrestricted.

7. Inspect fan assembly to insure all moving parts move freely.

8. If unit is horizontally mounted, make sure secondary drain pan has been installed.

9. Inspect unit for proper filters, securely installed and not touching the coil surface. All cabinet panels must be secure.

10. Instruct owner/operator on proper system operating and maintenance procedure.

Electrical Wiring

&wARNING

34

Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer's literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.

Note: For additional information regarding the safe discharge of capacitors, see PROO-SVB06A­EN or PROD-SVB06A-FR

&WARNING Grounding Required! Follow proper local and state electrical code on requirements for grounding. Failure to follow code could result in death or serious injury.

SSA-SVX06A-EN

I I !

I i

' I

\

I

I i

Page 35: Split System Air Handler

Installation

Thermostat and Control Connections for Electromechanical Controls

SSA-SVX06A-EN

Wiring shown with dashed lines is to be furnished and installed by the customer. All customer­supplied wiring must be copper only and must conform to NEC and local electrical codes. Codes may require line of sight between disconnect switch and unit.

1. Observe all notes on the wiring diagrams.

2. Mount the thermostat in the desired location.

3. Install color coded low voltage cables between outdoor unit, indoor unit and thermostat.

4. Connect low voltage control wiring to the low voltage terminal board located on the side of the fan control box per the typical interconnecting wiring diagrams.

Note: When electric heater accessory is used, single point power entry or dual point power entry is field optional. Single point power entry option is through electric heater only.

Figure 18. Thermostat and Control Connections - Electromechanical Controls

Disconnect Switch

!Byothecs)~

it'\,

60Hz - ITA!TWE TTA073DfTWE090D TTA090DfTWE090D TTA090DfTWE120D TTA120DfTWE120D TTA120EfTWE120E TTA120FfTWE120D

'

50 Hz - ITA!TWE TTA061DDfTWE076DD TTA076DDfTWE076DD TTA076DDfTWE101DD TTA086DDfTWE101 DD TTA101 DDfTWE101DD TTA 101 EDfTWE101 ED

TTA150EfTWE150E TTA180EfTWE180E TTA 180FfTWE180Eial TTA 180EfTWE240E TTA240EfTWE240E TTA240FfTWE240Eial

TTA101FDfTWE101 DD TTA126EDfTWE126ED TTA156EDfTWE156ED TTA 156FDfTWE156EDial TTA156EDfTWE201ED TTA201 EDfTWE201 ED

{2) TTA073DfTWE150E {2) TTA090DfTWE180E {2) TTA 120DfTWE240E {2) TTA 120FfTWE240E

TTA201 FDfTWE201 EDial {2) TTA061DDfTWE126ED {2) TTA076DDfTWE156ED {2) TTA 101DDfTWE201 ED {2) TTA 101 FDfTWE201 ED

(a) Need to manifold the dual circuit indoor unit when connecting to a Manifolded outdoor unit.

Continued on next page

35

Page 36: Split System Air Handler

Installation

Field Wiring:

A. 3 power wires. Line voltage for 3 phase (2 wires for single phase)

B. 3 power wires. Line voltage for 3 phase (2 wires for single phase)

C. Cooling only thermostat: 3 to 7 wires depending on stages of electric heat

D. 3 to 7 wires depending on type of outdoor unit(s)

Thermostat and Control Connections for ReliaTel™ Controls

36

Wiring shown with dashed lines is to be furnished and installed by the customer. All customer­supplied wiring must be copper only and must conform to NEC and local electrical codes. Codes may require line of sight between disconnect switch and unit.

1. Observe all notes on the wiring diagrams.

2. Mount the thermostat in the desired location.

3. Install color coded low voltage cables between outdoor unit, indoor unit and thermostat.

4. Connect low voltage control wiring to the low voltage terminal board located on the side of the fan control box per the typical interconnecting wiring diagrams.

Notes:

1. When electric heater accessory is used, single point power entry or dual point power entry is field optional. Single point power entry option is through electric heater only.

2. ***Choose only one of the following; Thermostat, Zone Sensor, or NSB Panel.

Figure 19. Thennostat and Control Connections - ReliaTel™ Controls

Disconnect Switch (By others) )f) . Note2

' '

I

' @ T'stat

it\ Electric Heater

Accessory

I

" [j 01

Zone Sensor

60Hz - TTAITWE TTA073Dn\NE090D TTA090Dn\NE090D TTA090Dn\NE120D TTA120DnlNE120D TTA120En\NE120E TTA120Fn\NE120D

Continued on next page

Panel

;;t'~~DI•ooooect Swltoh (By others) Note 2

;---o;'"'""''"Switch (By others)

TTA150En\NE150E TTA180En\NE180E TTA 180FnlNE180Eial TTA 180En\NE240E TTA240En\NE240E TTA240FnlNE24QEial

(2) TTA073Dn\NE150E (2) TTA090DfTWE180E (2) TTA120DnlNE240E (2) TTA120Fn\NE240E

SSA-SVX06A-EN

I !

I I I \

I I

I

Page 37: Split System Air Handler

SSA-SVX06A-EN

Installation

50 Hz- 1TAITWE TIA061 DDITWE076DD TIA076DDITWE076DD TIA076DDITWE101 DD TIA086DDITWE101 DD TIA101DDITWE101 DD TIA 101 EDITWE101 ED

60Hz - TWA/TWE TWA073DITWE090D TWA090DITWE090D TWA120DITWE120D

50 Hz - TWAITWE TWA061 DDITWE076DD TWA076DDITWE076DD

TIA101FDITWE101 DD TIA126EDITWE126ED TIA156EDITWE156ED TIA 156FDITWE 156EDial TIA156EDITWE201ED TIA201EDITWE201ED

TWA180EITWE180E TWA240EITWE240E (2)TWA073DITWE150E

TWA 101 DDITWE101 DD TWA 156EDITWE156ED

TIA201 FDITWE201 EDial (2) TIA061 DDITWE126ED (2) TIA076DDITWE156ED (2) TIA 101 DDITWE201 ED (2) TIA 101 FDITWE201 ED

(2) TWA090DITWE180E (2) TWA120DITWE240E

TWA201 EDITWE201 ED

{a) Need to manifold the dual circuit indoor unit when connecting to a Manifolded outdoor unit.

Field Wiring:

A. 3 power wires, line voltage for 3 phase, (2 power wires for single phase)

B. 3 power wires, line voltage for 3 phase, (2 power wires for single phase)

C. Cooling only thermostat: 3 to 7 wires depending on stages of electric heat Zone Sensor: 4 to 10 wires depending on zone sensor model 1

D. 3 to 7 wires depending on type of outdoor unit(s).

1 See Zone Sensor wiring instructions for wir'1ng information IReliaTel Controls only).

37

Page 38: Split System Air Handler

Maintenance Perform all of the indicated maintenance procedures at the intervals scheduled. This will prolong the life of the unit and reduce the possibility of costly equipment failure.

Fan Belt Adjustment

38

.&WARNING Rotating Components! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

The fan belts must be inspected periodically to assure proper unit operation.

Replacement is necessary if the belts appear frayed or worn.

When removing or installing the new belts, do not stretch them over the sheaves. Loosen the belts using the belt tension adjustment bolts on the motor mounting base.

Once the new belts are installed, using a Browning or Gates tension gauge (or equivalent) illustrated in Figure 20; adjust the belt tension as follows;

1. To determine the appropriate belt deflection;

a. Measure the center-to-center shaft distance (in inches) between the fan and motor sheaves.

b. Divide the distance measured in Step 1a by 64; the resulting value represents the amount of belt deflection that corresponds to the proper belt tension.

2. Set the large 0-ring on the belt tension gauge at the deflection value determined in Step 1 b.

3. Set the small 0-ring at zero on the force scale of the gauge plunger.

4. Place the large end of the gauge at the center of the belt span; then depress the gauge plunger until the large 0-ring is even with the top of the next belt or even with a straightedge placed across the fan and motor sheaves.

5. Remove the belt tension gauge. The small 0-ring now indicates a number other than zero on the plunger's force scale. This number represents the force {in pounds) required to give the needed deflection.

6. Compare the "force" scale reading (Step 51 with the appropriate "force" value listed in Table 12, p. 39. lfthe "force" reading is outside the range, readjust the belt tension.

Note: Actual belt deflection "force" must not exceed the maximum "force" value shown in Figure 20.

Recheck the belt tension at least twice during the first 2 to 3 days of operation. Belt tension may decrease until the new belts are "run in':

Figure 20. Belt tension gauge

Deflection = Belt Span (in) 64

Deflection = Belt Span {mm)

\

!52

Small 0-Rmg I Belt Span

(~)~t. 0-Rmg

SSA-SVX06A-EN

I

I

I I I. I

Page 39: Split System Air Handler

Monthly

SSA~SVX06A~EN

Maintenance

Table 12. Belt Tension Measurement and Deflection

Deflection Force (lbs.) Small Pitch

Standard V-Belt Belts Cross Diameter V-Belt with Molded Notches

Section Range Min. Max. Min.

3.0 ~ 3.6 3 4 1/2 3 7/8

A 3.8- 4.8 3 1/2 5 4 1/2

5.0- 7.0 4 5 1/2 5

3.4- 4.2 4 5 1/2 5 3/4

8 4.4 - 5.6 5 1/8 7 1/8 6 1/2

5.8 - 8.8 6 3/8 8 3/4 7 3/8

Conduct the following maintenance inspections once per month.

The following warning complies with State of California law, Proposition 65.

&.WARNING Fiberglass Wool!

Max.

5 1/2

6 1/4

6 7/8

8

9 1/8

10 1/8

Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respiratory, skin or eye irritation.

&.WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer's Hterature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.

NOTICE Operating Under Vacuum Do not operate or apply power to the compressor while under a vacuum. Failure to follow these instructions will result in compressor failure.

1. Inspect air filters and clean (or replace) if necessary.

2. Check unit wiring to ensure all connections are tight and that the wiring insulation is intact.

3. Check drain pans and condensate piping to insure they are free of obstacles.

4. Manually rotate the indoor fan to ensure proper operation.

5. Inspect the evaporator coils for dirt and debris. If the coils appear dirty, clean them.

6. Observe indoor fan operation and correct any unusual or excessive vibration. Clean blower wheels as needed.

39

Page 40: Split System Air Handler

Maintenance

Annually (Cooling Season}

Coil Cleaning

40

The following maintenance procedures must be performed at the beginning of each cooling seiason to ensure efficient unit operation.

1. Perform all of the monthly maintenance inspections.

2. With the unit operating, check unit superheat and record the reading in the "Maintenance Log:'

3. Remove any accumulation of dust and/or dirt from the unit casing.

4. Remove corrosion from any surface and repaint. Check the gasket around the control panel door to ensure it fits correctly and is in good condition to prevent water leakage.

5. Inspect the evaporator fan belt. If it is worn or frayed, replace it.

6. Inspect the control panel wiring to ensure that all connections are tight and that the insulation is intact.

7. Check refrigerant piping and fittings for leaks.

8. Inspect the evaporator coils for dirt and debris. If the coils appear dirty, clean them.

Regular coil maintenance, including annual cleaning-enhances the unit's operating efficiency by minimizing:

- compressor head pressure and amperage draw;

- water carryover;

- fan brake horsepower and

- static pressure losses.

At least once each year-or more often if the unit is located in a "dirty" environment-clean the coil using the instructions outlined below. Be sure to follow these instructions as closely as possible to avoid damaging the coils. To clean refrigerant coils, use a soft brush and a sprayer. Contact your local Parts Center for appropriate detergents.

1. Remove enough panels from the unit to gain safe access to coil.

.&WARNING No Step Surface! Do not walk on the sheet metal base. Walking on the base could cause the supporting metal to collapse. Failure of the base could result in death or serious injury.

2. Straighten any bent coil fins with a fin comb.

3. Remove loose dirt and debris from both sides of the coil with a soft brush.

4. Mix the detergent with water according to the manufacturer's instructions. If desired, heat the solution to 150° F maximum to improve its cleansing capability.

5. Pour the cleaning solution into the sprayer.

6. Spray the leaving-airflow side of the coil first; then spray the opposite side ofthe coil. Allow the cleaning solution to stand on the coil for five minutes.

7. Rinse both sides of the coil with coot clean water.

8. Inspect both sides of the coil; if it still appears to be dirty, repeat Steps 7 and 8.

9. Reinstall all of the components and panels removed in Step 1; then restore power to the unit.

10. Using a fin comb, straighten any coil fins that were inadvertently bent during the cleaning process.

SSA-SVX06A-E N

Page 41: Split System Air Handler

Maintenance

Precautionary Measures

• Avoid breathing fiberglass dust.

• Use a NIOSH approved dust/mist respirator.

• Avoid contact with the skin or eyes. Wear long-sleeved, loose-fitting clothing, gloves, and eye protection.

• Wash clothes separately from other clothing: rinse washer thoroughly.

• Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respirator in these situations.

First Aid Measures

SSA-SVX06A-EN

Eye Contact- Flush eyes with water to remove dust. If symptoms persist, seek medical attention.

Skin Contact - Wash affected areas gently with soap and warm water after handling.

41

Page 42: Split System Air Handler

1:> Maintenance Log

Ambient Evaporator Entering Air Compressor

Temp. .Dry Wet Suction Pressure Discharge Pressure

rn rn 1> rn

Date (Of) Bulb

-

Bulb (Cl) (C2)

L__

~ Note: Perform each inspection once per month (during cooling season) while unit is operating 0

"' )>

in z

(Cl)

~~---~-~--

(C2)

Superheat (°F) (at compressor)

Circuit #1 Circuit #2

Subcooling (°F) (at service valve)

Circuit #1 Circuit #2

.

s "' 5' ; "' "' "' n <D

Page 43: Split System Air Handler

Warranty

Central Air Conditioner TWE

This warranty is extended by Trane to the original purchaser and to any succeeding owner of the real property to which the Air Conditioner is originally affixed, and applies ~o products purchased and retained for use within the U.S.A. and Canada. There is no warranty against corrosion, erosion or deterioration.

Warrantor warrants for a period of 12 months from initial start-up or 18 months from date of shipment, whichever is less, that the products covered by this warranty {1) are free from defects in material and manufacture, and (2) have the capacities and ratings set forth in catalogs and bulletins; provided, that no warranty is made against corrosion, erosion or deterioration. Warrantor's obligations and liabilities under this warranty are limited to furnishing, F.O.B. factory replacement parts {or equipment at the option of Warrantor) for all Warrantor's products not conforming to this warranty. Warrantor shall not be obligated to pay for the cost of lost refrigerant. No liability whatever shall attach to Warrantor until said products have been paid for and then said liability shall be limited to the purchase price of the equipment shown to be defective.

THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS OR IMPLIED, IN LAW OR IN FACT. INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR USE, AND IN NO EVENT SHALL WARRANTOR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.

Some states do not allow limitations on how long an implied warranty lasts or do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

Trane, 2701 Wilma Rudolph Blvd., Clarksville, TN 37040-1008

Attention: Manager, Product Service

TW-338-0597

*This warranty is for commercial usage of said equipment and not applicable when the equipment is used for a residential application. Commercial use is any application where the end purchaser uses the product for other than personal, family or household purposes.

Commercial Equipment Rated 20 Tons and Larger and Related Accessories (Parts Only)

SSA-SVX06A-EN

Products Covered - This warranty is extended by Trane and applies only to commercial equipment rated 20tons and larger and related accessories purchased and retained for use within the U.S.A. and Canada.

Warrantor warrants for a period of 12 months from initial start-up or 18 months from date of shipment, whichever is less, that the products covered by this warranty ( 1} are free from defects in material and manufacture, and (2) have the capacities and ratings set forth in catalogs and bulletins; provided, that no warranty is made against corrosion, erosion or deterioration. Warrantor's obligations and liabilities under this warranty are limited to furnishing, F.O.B. factory replacement parts (or equipment at the option of Warrantor} for all Warrantor's products not conforming to this warranty. Warrantor shall not be obligated to pay for the cost of lost refrigerant. No liability whatever shall attach to Warrantor until said products have been paid for and then said liability shall be limited to the purchase price of the equipment shown to be defective.

THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS OR IMPLIED, IN LAW OR IN FACT. INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR USE, AND IN NO EVENT SHALL WARRANTOR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.

43

Page 44: Split System Air Handler

Warranty

44

Some states do not allow limitations on how long an implied warranty lasts or do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

Trane -Warrantor, 2701 Wilma Rudolph Blvd., Clarksville, TN 37040

GW-598-4799

SSA-SVX06A-EN

\

Page 45: Split System Air Handler

Wiring Diagram Matrix DIAGRAM NO. DIAGRAM TYPE UNIT MODEL NO'S

TWE051DDOOAA, TWE061D300AA, lWE061D400AA, TWE061DKOOAA, TWE061DWOOAA, lWE076DDOOAA, 2313-0401 Power/Control Diagram TWE090D300AA, TWE090DKOOAA, TWE090DWOOAA, TWE101DDOOAA, TWE1200300AA, TWE120DKOOAA,

TWE120DWOOAA

2313-0402 Power/Control Diagram TWED61D100AA, TWE0900100AA, TWE120D100AA

TVVE061E300AA, TVVE061E400AA, TVVE090E300AA, TVVE0101EDOOAA, TWE120E300AA,

2313-0431 Power/Control TWE120EK00AA, TWE120EW00AA, TVVE126EDOOAA, TWE150E300AA, TWE150EKOOAA,

Diagram TWE150EWOOAA, TWE156EDOOAA, TWE180E300AA, TWE180EKOOAA, TWElBOEWOOAA, TVVE201ED00AA, TWE240E300AA, TWE240E400AA, TWE240EK00AA, TWE240EWOOAA

2313-0432 Power/Control

TVVE061E100AA,TWE090E100AA, TWE120E100AA Diagram

.. Note: W1rmg d1agrams are avatlable through e-Library or by contactmg your local sales office

SSA-SVX06A·EN 45

Page 46: Split System Air Handler

literature Order Number SSA-SVX06A-EN

Date November 2009

Supersedes SSA-SVX06A-EN (August 2009)

The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this literature.

Page 47: Split System Air Handler
Page 48: Split System Air Handler

Service Facts

Split System Air Handler Convertible 15 .Tons-60Hz, R;.410A

1WE180E300AA 1WE180EKOOAA 1WE180EWOOAA

November 2009 SSA-SVF06A-EN

Page 49: Split System Air Handler

Warnings, Cautions and Notices

-----:;:r--

Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at appropriate intervals throughout this manual. Warnings are provided to alert installing contractors to potential hazards that could result in personal injury or death. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, While notices indicate a situation that could result in equipment or property-damage-only accidents.

Your personal safety ~nd the proper operation of thi~ machine depend upqn the strict observance of these precautions.

ATIENTION: Wcirnings, Cautions and Notices appear afappi-oPr"iate sections throughout this literature. Read these carefully. . · .

&, WARNING: Indicates a potentiallY hazardous situation which, if not avoided, could result in death or serious injury. · -: · ·· · · ..

&.cAUTION: Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert agairist unsafe practices.

NOTICE: Indicates a situation that could result in equipment or property~damage only accidents.

Important Environmental Concerns!

Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, F.luorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.

Responsible Refrigerant Practices!

Trane believes that responsible refrigerant practices are important to the environment. our customers, and the air conditioning industry. All. technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipmentthatis used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them .

.&.wARNING Contains R-410A Refrigerant! System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use .non-approved refrigerants, refrigerant substitutes, or refrigerant additives. Use ONLY R-410A rated service equipment or components with this unit. For specific handling concerns with R-410A, please contact your local Trane representative. Failure to use R-410A rated service equipment or components and/or failure to follow proper procedures or the use of non-approved refrigerants, refrigerant substitutes, or refrigerant additives could result in death or serious injury or equipment damage.

© 2009 Trane All rights reserved SSA-SVF06A-EN

Page 50: Split System Air Handler

SSA-SVFOSA-EN

Warnings, Cautions and Notices

&WARNING Personal Protective Equipment (PPE) Required! Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.

• Before installing/servicing this unit; technicians MUST put on all Personal Protective Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate MSDS and OSHA guidelines for proper PPE.

• . When working .with or around hazardous chemicals, ALWAYS refer to appropriate MSDS and OSHA guidelines for infonnation on allowable personal exposure levels, proper respiratory p~~ection and handling recommendations.

' • If there is a risk of arc or flash, technicians MUST put on all Personal Protective Equipment (PPE) in accordance with NFPA70E for arc/flash protection PRIOR to servicing the unit.

Failure to follow recommenda1:i6ns could result in death or serious injury. . ~ .

3

Page 51: Split System Air Handler

4

Accessories

Table 1. List of Available Accessories - TWE180

MODEL

Base (SUbbaSe) BAYBA_SE012A

Drip Kit BAYDRKT009A

Return Air Grille BAYGRLE004A

High ·static Motor

BAYHSMT119A

BAYHSMT120A

BAYHSMT121A

Electric Heaters BAYHTRM310A

BAYHTRM320A BAYHTRM330A BAYHTRM350A

BAYHTRM410A

BAYHTRM420A

BAYHTRM430A

BAYHTRM450A

BAYHTRMW10A

BAYHTRMW20A

BAYHTRMW30A

BAYHTRMWSOA

Isolators BAYISLT009A

BAYISLT012B

BAYISLT021A

BAYISLT030A

Plenum BAYPLNMOlBB

BAYPLNM033A

Water Kits BAYWATR025A

BAYWATR030A

(a) When used with 460V applications.

USED WITH

TW.E180E

TWE180E

. TWE18DE

TWE180E3

TWE18DE3(a) ·

TWE!BOEW

TWE180E3

TWE180E3

TWE180E3

.TWE180E3

TWE180E3(a)

TWE180E3(a)

TWE180E3(a)

TWE180EW

TWElBOEW

TWE180EW

TWElBOEW

TWE180EW

TWE180E

TWE180E

TWE180E

TWE180E

TWElBOE

TWElBOE

TWElBOE

TWE!BOE

DESCRIPTION

Subbase

Dlip K!t

Return Air. Grille

5 HP (230/3) wf lVPSOL motor""s;heave w/ BKSS fan sheave w/ BXSS belt

5 HP ( 460/3) w/ 1 VPSbL rilotor sheave w/ BKBS fan sheave . ·w/ BXSB belt

5 HP.(575/3) w/ lVPSOL.nlotor Sheave w/ BKBS fan sheave w/ BXSS belt

7.50/10.0 KW Heater 208/230 3 Phase

14.96/19.92 KW Heater 208/230 3 Phase

22.50/29.92 KW Heater 208/230 3 Phase

37.42/49.84 KW Heater 208/230 3 Phase

10.0 KW Heater 460/3 Phase

19.92 KW Heater 460/3 Phase

29.92 KW Heater 460/3 Phase

49.84 KW Heater 460/3 Phase

10.0 KW Heater 575/3 Phase

~9.92 KW Heater 575/3 Phase

29.92 KW Heater 575/3 Phase

49.84 KW Heater 575/3 Phase

Rubber Isolator Kit

Steel Spring Isolator Kit

Discharge Plenum & Grille

Electric Heat Discharge Plenum & Grille.

Steam Coil Enclosure

Hot Water Coil Enclosure

(b) When used with BAYWATR accessories, please see the Vibration Mounting Installation Guide on e-!ibrary (or by calling product support).

SSA-SVF06A-EN

Page 52: Split System Air Handler

Product Specifications

Table 2. General Data - TWE180- 60Hz

15 Tons Dual Circuit, TWE180E3, EW, EK

System Data No. Refrigerant Circuits

Suction Line Connection (in.) OD

Liquid Line Connection (in.) OD

Indoor Coil - Type Tube Size (ln.)

Face Area (sq. ft.) Rows/FPI.

Refrigerant Control

Drain Connection Size (in.)

Indoo~. Fan -Type No. Used/Diameter x Width (in.)

Drive Type/No. Speeds

CFM

No. Motors

Motor HP - Standard/Oversized Motor RPM

Motor Frame Size

filters- Type/Furnished (No.)/Size Recommended

Table 3. Fan Drives - TWE180

2

1 3/8

1/2

Lanced

0.375

16.3

4/14 Expansion Valve

1 PVC

Centrifugal

2/15 X 15

Belt/Adjustable

6000 - 1

3.0/5.0

1728/1750

56HZ

ThrowaWay/Yes

(B) 15 X 20 X 2

15 Ton TWE180 Low Static Drive with Field Supplied Sheave and Belt{a) 15 Ton - TWE180 -Standard Drive

Motor Sheave Turns Open

0 1

2

3

4

5

Nominal RPM

649

613

557

500

444

469

Motor Sheave Tums Open

0 1

2

3 4

5

Nominal RPM

845

812

728 745

711

678

15 Ton TWE180 High Static Drive

15 TOn TWE180 High Static Drive with Field Supplied Sheave(b)

Motor Sheave Turns Open

0

1

2 3-

4

5

Nominal RPM

1024

989

953

918

882

847

(a)TWE180 3HP Lo~static w/ field Installed belt and sheaves

Motor Sheave Turns Open

0

1

2

3

4

5

Field Supplied Components Required: · Motor Sheave: Variable Pitch {2.4- 3.4 Inch Pitch Diameter), 0.875 Inch Bore, Single Groove, Browning 1Vl40 Blower Sheave: Fixed Pitch (9.5 Inch Pitch Diameter), 1.4375 Inch Bore, Single Groove, Browning AX59

(b)TWE180 SHP HI-Static w/ field installed belt and sheaves Reid Supplied Components Required: Motor Sheave: Variable Pitch (3.4- 4.4 Inch Pitch Diameter), 1.125 Inch Bore, Single Groove, Browning 1VP50 Blower Sheave: Fixed Pitch (6.6 Inch Pitch Diameter), 1.4375 Inch Bore, Single Groove, Browning BK72 Belt: Browning BX58

SSA-SVF06A-EN

Nominal RPM

1217

117S

1118

1062

1006 964

,.

5

Page 53: Split System Air Handler

Product Specifications

Table 4. Evaporator Fan Performance - TWE180 - Air Handler

External St~tic Pressure (Iriches of Water Gauge)

.1o" .20" .30" .40" .so:· .60" .70" .8o" .9o" LOO"

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Low Static Drive w 1 Field Supplied Sheave & Belt 3 HP Standard Drive

4800 492 0.80 539 0.94 583 1.08 624 1.21 663 1.34 701 1.49 738 1.66 774 1.82 807 1.98 839 2.14

5100 517 0.95 562 1.08 604 1.24 644 1.38 681 1.52 718 1.67 753 1.83 788 2.00 853 2.35

5400 542 1.11 585 1.25 625 1.41 663 1.57 700 1.71 735 1.86 769 2.02 802 866 2.57

5700 567 1.29 647 1.60 684 1.78 719 1.93 753 2.08 786 2.24 818 881 2.80

6000 593 1.48 669 1.80 705 1.99 739 2.16 773 2.32 804 2.48 2.84 895 3.04

6300 619 1.70 692 2.03 726 2.22 760 2.42 792 2.59 823 2.75 3.12 910 3.31

6600 644 1.94 681 2.11 715 2.28 748 2.48 811 2.87 841 3.04 3.22 899 3.40 927 3.60

6900 670 2.20 705 2.37 739 2.55 771 2.75 832 3.18 861 3.36 3.54 917 3.72 944 3.92

7200 696 2.49 730 2.66 763 2.85 794 3.05 853 3.49 881 3.70 909 3.89 936 4.08 963 4.28

5 HP High Static Drive Kit External Static Pressure (Inches of Water Gauge)

1.10" 1.20" 1.30" 1.40" 1.50" 1.60" 1.70" 1.80" 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Motor & Sheaves 2.46 926 2.62 953 2.77 979

2.69 940 2.86 965 3.02 992

2.93 953 3.11 980 3.29 1005

3.19 966 3.38 993

5 HP Ultra High Static w/ Field Supplied Sheave & Belt 2.93 1004 3.08 1029 3.24 1051 3.38 1075 3.54 1097 3.69

1017 3.36 1042 3.52 1065 3.68 1088 3.84 1111 4.02

1031 3.65 1055 3.82 1078 3.99 1102 4.17 1123 4.34

1044 3.94 1068 4.13 1092 4.32 1114 4.50 1137 4.69

4800

5100

5400

5700

6000

6300

869 2.30 897

883 2.52 911

897 2.75 925

910 2.99 940

924 3.25 953

939 3.52 967

'-"'~~ 1057 4.26 1081 4.45 1105 4.66 1129 4.86 1150 5.05

4.37 1071 4.59 1095 4.79 1119 5.01

3.45 980 3.65 1008

3.73 995 3.95 ~~~ 4.71 1085 4.93 6600 954 3.81 981 4.02 1009 4.25

6900 971 -4.13 . 998 4.35 1022 4.57

7200 988 4.48 "1014 "4.70 1039 4.93 4.81 1074 5.04

5.15

External Static Pressure (Inches of Water Gauge)

2.10" 2.20" 2.30" 2.40" CFM RPM BHP RPM BHP RPM BHP RPM BHP

5 HP Ultra High Static wf Field Supplied Sheave & Belt

4800 1120 3.84 1141 3.99 1162 4.14 1183 4.30

5100 1132 4.17 1154 4.33 1175 4.49 1196 4.66

5400 1146 4.52 1167 4.69 11~8 4.86 1209 5.04 5700 1159 4.87· 1180. 5.061 6000

6300

6600

6900

7200

Notes: 1. Data Includes pressure drop due to wet coil and 1 ~ filter. 2. Fan motor heat (MBh) == 3.15 x BHP. 3. Factory supplied mot_o~s, in co~mercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously

at all cataloged con?1t1ons. Usmg the full horsepower range of our fan motors as shown In our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

4. For TWE180 Fan Drives use Table 3, p. 5.

SSA·SVF06A·EN

Page 54: Split System Air Handler

Product Specifications

Table 5. Static Pressure Drop Through Accessories (inches of water column)l•l - TWE180

Discharge Electric Heaters (kW) Hydronic COils Return Plenum and

Tons Unit Model No. CFM Grille Grille(b) 5-10 15-20 25-30 35-50 Steam Hot Water 4800 0.09 0.23 0.03 0.03 0.06 0.08 .46 .38

15 TWElBOE 6000 0.15 0.34 0.06 0.06 0.12 0.17 .64 .54 7200 0.2 0.49 0.08 0.08 0.16 0.24 .82 .72

(a) Retum a1r filter ESP Included m Fan Performance Table data. (b)At louver opening angle of 42 degrees. For ESP at other angle openings, see accessory installation guide.

Table 6. Electrical Characteristics - TWE1Soi•J

Standard Evaporator Fan Motor Low Static Evaporator Fan Motor

Amps

Phasel Hp

Amps

Tons Unit Model Number No. Volts Phase Hp FLA LRA MCA MFS No. Volts FLA LRA MCA MFS

TWE180E3 1 208 3 3.00 9.4 74.9 11.8 20 N/A N/A N/A N/A N/A N/A N/A N/A

TWE180E3 1 230 3 3.00 9.2 74.9 11.5 20 N/A N/A N/A N/A N/A N/A N/A N/A 15

TWE180EJ(b) 1 460 3 3.00 4.6 39.3 5.8 15 N/A N/A N/A N/A N/A N/A N/A N/A

TWE180EW 1 575 3 3.00 3.4 24.6 4.3 15 N/A N/A N/A N/A N/A N/A N/A N/A

High Static Evaporator Fan Motor Ultra-High Static Evaporator Fan Mot~r

Amps

Tons Unit Model Number No. Volts Phase

TWE180E3 1 208 3

TWE180E3 1 230 3 15

TWE180E3(b) 1 460 3

TWE180EW 1 575 3

(a) For additional mformatLon contact product support. (b) Field wired for 460V.

Hp FLA

5.00 14.5

5.00 14.3

5.00 6.7

5.00 5.2

Table 7. Unit Wiring - TWE180

SSA-SVF06A·EN

Tons Unit Model Number

TWE180E3

TWE180E3(b) 15

TWE180EK

TWE180EW

(a) HACR type c1rcu1t breaker per NEC. (b) Field wired for460V.

LRA

98.0

98.0

47.0

.

MCAIMFS

Amps

No. Volts Phase Hp FLA LRA MCA MFS

18.1 25 N/A N/A N/A N/A N/A N/A ,

N/A N/A

17.9 25 N/A N/A N/A N/A N/A N/A N/A N/A

8.4 15 N/A N/A N/A N/A N/A N/A N/A N/A

6.5 15 N/A N/A N/A N/A N/A N/A N/A N/A

Maximum Fuse Unit Operating Minimum Circuit or HACR Circuit Voltage Range Ampacity Breaker Size(a)

187-253 11.8 20

414-506 5.8 15

342-418 9.8 15

518-632 4.3 15

7

Page 55: Split System Air Handler

8

Product Specifications

Table 8. Unit Wiring with Electric Heat (Single Point Connection) - TWE180

Heater Heater KW Unit Power Control Tons Used With Model No. Rating(a) Supply Stages

BAYHTRM310A 7.50/10.00

BAYHTRM320A 14.96/19.92 15

TWE180E3 BAYHTRM330A 22.50/29.92

BAYHTRM350A 37.42/49.84

BAYHTRM410A 10

BAYHTRM420A 19.92 15

TWE180E3(e) BAYHTRM430A 29.92

BAYHTRM450A 49.84

BAYHTRMWlOA 10

BAYHTRMW20A 19.92 15

TWElBOEW BAYHTRMW30A 29.92

BAYHTRMWSOA 49.84

(a) kW ratmgs are at: 208/240V for 208~230V a1r handlers. 480V for 460V air handlers

208-230/3/60

460/3/60

575/3/60

.. 600V for 575V air handlers 'For other than rated voltage, capacity= (Voltage/Rated Voltage)2 x Rated Capacity.

(b)Any power supply and cirOJits must be wired and protected in accordance with local codes. (c) The HACR circuit breaker is for U.S.A. installations only. (d) Field Wire must be rated at least 90°C. {e) Field wired for460V.

1

1

2

2

1

1

2

2

1

1

2

2

Maximum Fuse or Minimum Circuit HACR Circuit

Ampacity(b) Breaker Size(b)(c)

38/42 40/45

64/72 70/80

90/102 90/110

142/162(d) 150/175

21 25

36 40

51 60

81 90

17 20

30 30

42 45

67 70

SSA-SVF06A-EN

Page 56: Split System Air Handler

' I

Refrigerant Circuit

SSA-SVF06A-EN

Figure 1. Refrigerant Circuit

~-~ALIZER TXV BULB I LTUBE /-

TO OUTDOOR SECT I ON { !BRAZE CONNECTIONS)

1 ) I r /

'

----'-----,---, I CHECK

VALVE

EXPANSION-+--...../ VALVE

-"" -w 0-' uo z o:< O:I:

go: z­-<

I I

L...-.....+--ou NOTE A: ONLY ONE INDOOR COIL ENTRY/EXIT CIRCUIT IS SHOWN: All MODELS HAVE MULTIPLE ENTRY/EXIT CIRCUITS.

8726818

9

Page 57: Split System Air Handler

Troubleshooting

:;; :z: ,. .a· ~ ,. ~ "' ~ 0 < 0 ~ 0 n ~ ;:; ,. ~ ~ ~ ~ "' n ~ ~

" ., ~

3 .,

:;· 0 < 5' Q.

"' ~

Head Pressure Too low

Suction Pressure Too High

suction Pressure Too Low

Indoor Coil Frosting

Liquid Floodback {TXV)

g "' m

r- r- :z: ~ "' X

"' "' 0 :z: n .... 0 .a· ~ ~ n ~ ~ ~ n ~ ~ ~ ~ ~

~ ~ :;· ~ ,. ,. ~ ~ ~ ~

~ .... ~ ,

"' ., ~ ~· ~- ~ ~ ~ < ~

,. "· ~ n ~ ~ ~ 5' 5' ;;:· < ~ ~ 0 ~ ~ ~ c iii n 3 Q. Q. c: ~ ;;· ;;· ;:; ~ ~ 6' ;;: ~ < ~ ~ ~ ~ 3 "' < ;;:

!!. 0 0 ~ o· o· "'

~ ~ i> C' ~ 0 ~ ~ Q. ~ ~ ~ ~ 0

i> ;;; , ~ n ~ < ~ ~ ~ ~ ~ ~ c ~ ~

~ 5' ~ , n '!' ii '=t ~ 0' ~ 3 ~ ~

" " ~ 0 ,. :!: ~ ~ ~ ~

~

~ ~ ~ n X ~ 3 ~ ~ ~ ~ ~. < ~ ~

"' ro ~

p p

p p

p p p p p p p

literature Order Number SSA-SVFOBA-EN

Date November 2009

Supersedes SSA-SVF06A-EN (August 2009)

The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.

Page 58: Split System Air Handler