Exponation AIA Provider Number: 70119700 Specifying Lighting and Building Management Systems (BMS) with BACnet, today and in the future LEDSSMW16-S#11 Scott Ziegenfus, Hubbell Lighting 11.15.16

Specifying Lighting and Building Management Systems … fileBACnet and Lighting History • Did you know? • BACnet is ANSI/ASHRAE SSPC 135 BACnet Standard • BACnet standard first

Embed Size (px)

Citation preview

ExponationAIA Provider Number: 70119700

Specifying Lighting and Building

Management Systems (BMS) with

BACnet, today and in the futureLEDSSMW16-S#11

Scott Ziegenfus, Hubbell Lighting11.15.16

Credit(s) earned on completion of

this course will be reported to AIA

CES for AIA members.

Certificates of Completion for both

AIA members and non-AIA

members are available upon

request.

This course is registered with AIA

CES for continuing professional

education. As such, it does not

include content that may be

deemed or construed to be an

approval or endorsement by the

AIA of any material of construction

or any method or manner of

handling, using, distributing, or

dealing in any material or product._______________________________________

Questions related to specific materials, methods,

and services will be addressed at the conclusion

of this presentation.

This session will cover the fundamentals of

BACnet, including a primer on BACnet

terminology, the items needed to specify for

BMS interoperability and conformance to the

BACnet standard. It will elaborate on the new

items developed by the Lighting Application

Working Group within BACnet to make

specifying lighting and BMS Integration easier

and what's next in BACnet standards

development for lighting.

Course

Description

Learning

Objectives

• Learn enough BACnet Basics to specify

successfully

• Showcase BMS integration with BACnet and how it

works with Lighting.

• Share what to include and where to include for

successful BMS integration with BACnet in

integration specifications.

• Highlight what has been done and is being done in

the future make it easier and more inclusive in

specifying Lighting for BMS and BACnet

integration.

IES Annual Conference

•Scott Ziegenfus CEM, CLEP, CDSM, GGP, GPCP, LEED AP

•Government and Industry Relations Manager

•Hubbell Lighting, Inc.

•701 Millennium Blvd.

•Greenville, SC 29607

•m: 484.225.6345

•e: [email protected]

•w: www.Hubbelllighting.com

• ASHRAE SSPC 135 BACnet Committee

Member since 2010

• SSPC 135 Data Modeling Working

Group Convener/Chair

• BACnet International Education

Committee Co-Chair

• BACnet International “Leader of the

Pack” Award recipient

BACnet and Lighting History

• Did you know?

• BACnet is ANSI/ASHRAE SSPC 135 BACnet Standard

• BACnet standard first committee meeting 1987

• BACnet standard first published in 1995

• BACnet achieved the status ISO 16484-5 in 2003

BUT

• 2001 was the first meeting of the Lighting Application –Working Group

• only 2 lighting Control Companies attended

Iconic BACnet Graphics by H. Michael Newman, “Father of BACnet”

BACnet BASICS

How to talk to an integrator

BACnet Communication Basics

CLIENT(A Side)

SERVER(B Side)

service

request (What, How, and for How Long)

response (the way the Client requests)

• DEVICES and OBJECTS = WHAT is Controlled

• SERVICES = HOW it is controlled

CLIENT CANNOT TALK TO CLIENT

OR

A side cannot talk to A Side

SERVER CANNOT TALK TO SERVER

OR

B side cannot talk to B Side

BACnet Communication Basics

Clause 12

OBJECTS = WHAT BACnet communicates

• The standard specifies 55 types of objects:

• Access Credential

• Access Door

• Access Point

• Access Rights

• Access User

• Access Zone

• Accumulator

• Alert Enrollment

• Analog Input: Sensor input

• Analog Output: Control output

• Analog Value

• Averaging

• Binary Input: Switch input

• Binary Lighting Output

• Binary Output

• Binary Value

• Bit String Value

• Calendar

• Channel Object

• Character String Value

• Command

• Credential Data Input

• Date Pattern Value

• Date Value

• Date Time Pattern Value

• Date Time Value

• Device

• Event Enrollment:

• Event Log

• File:

• Global Group

• Group

• Integer Value

• Large Analog Value

• Life Safety Point

• Life Safety Zone

• Lighting Output

• Load Control

• Loop

• Multi-state Input:

• Multi-state Output:

• Multi-state Value

• Network Security

• Notification Class

• Notification Forwarder

• Octet String Value

• Positive Integer Value

• Program

• Pulse Converter

• Schedule

• Structured-View

• Time Pattern Value

• Time Value

• Trend Log

• Trend Log Multiple

BACnet Communication Basics

SERVICES = HOW BACnet communicates

• BIBB = A service or collection of services

to perform a function

• BIBB Example 1) is the Dynamic Device Binding (DM-DDB) = In plain English is BACnet device

discovery using the WHO-IS and I-AM services. DM-DDB-A is the client side and DM-DDB-B is

the server side.

• BIBB Example 2) is the Change of Value (DS-COV) = In plain English is automatic real-time

feedback using the Subscribe COV, Confirmed COV Notification, and Unconfirmed COV

Notification services. DS-COV-A is the client side and DS-COV-B is the server side.

BACnet Communication Basics

DEVICE PROFILES = WHAT ARE YOU?STANDARD DEVICE Type

• Device Profile is defined by a minimum set of BIBBs (A and/or B side)

• standard types in Annex L of the ANSI/ASHRAE standard 135-2012, BACnet

BACnet Operator Workstation (B-OWS)

BACnet Advanced Operator Workstation (B-AWS)

BACnet Operator Display (B-OD)

BACnet Building Controller (B-BC)

BACnet Advanced Application Controller (B-AAC)

BACnet Application Specific Controller (B-ASC)

BACnet Smart Sensor (B-SS)

BACnet Smart Actuator (B-SA)

It’s ALL

about the

BIBBs

B-AWS B-OWS B-OD B-BC B-AAC B-ASC B-SA B-SS

Data Sharing DS-RP-A,B DS-RP-A,B DS-RP-A,B DS-RP-A,B DS-RP-B DS-RP-B DS-RP-B DS-RP-B

DS-RPM-A DS-RPM-A DS-RPM-A DS-RPM-B

DS-WP-A DS-WP-A DS-WP-A DS-WP-A,B DS-WP-B DS-WP-B DS-WP-B

DS-WPM-A DS-WPM-A DS-WPM-B DS-WPM-B

DS-AV-A DS-V-A DS-V-A

DS-AM-A DS-M-A DS-M-A

Alarm & Event Mgmt AE-N-A AE-N-A AE-N-A AE-N-I-A AE-N-I-A

AE-ACK-A AE-ACK-A AE-ACK-B AE-ACK-B

AE-INFO-B AE-INFO-B

AE-ESUM-B

AE-AS-A AE-AS-A

AE-AVM-A AE-VM-A

AE-AVN-A AE-VN-A AE-VN-A

AE-ELVM-A

Scheduling SCHED-AVM-A SCHED-VM-A SCHED-E-B SCHED-I-B

Trending T-VMT-I-A T-V-B T-VMT-I-B

T-ATR-B

Device and Network Management DM-DDB-A,B DM-DDB-A,B DM-DDB-A,B DM-DDB-A,B DM-DDB-A,B DM-DDB-B DM-DDB-B DM-DDB-B

DM-ANM-A

DM-ADM-A

DM-DOB-B DM-DOB-B DM-DOB-B DM-DOB-B DM-DOB-B DM-DOB-B DM-DOB-B DM-DOB-B

DM-DCC-A DM-DCC-B DM-DCC-B DM-DCC-B

DM-MTS-A DM-MTS-A

DM-TS-B

or

DM-UTC-B

DM-TS-B

or

DM-UTC-B

DM-OCD-A

DM-RD-A DM-RD-B DM-RD-B

DM-BR-A DM-BR-B

Operator Work Stations Controllers

Operator Work

Stations

Controllers

BACnet Communication Basics

• Changes in the Device Profiles• Profile Families

• A fundamental shift is happening to make specifying easier without the need for a PhD level of

understanding in BACnet because of a new “family” approach to BACnet device profiles. This

new approach just appeared in the newly available 2016 publishing of the BACnet standard.

Iconic BACnet Graphics by H. Michael

Newman, “Father of BACnet”

Proper / Required Documentation• Protocol Implementation Conformance Statement

• REQUIRED Documentation (not a sell sheet or spec sheet)

• It is exact detailed information on WHAT and HOW your device communicates using BACnet

(not just a list of objects)

• Blank PICS in ANNEX A of the standard

• Downloadable blank PICS available at www.bacnet.org/DL-Docs

• It is a specific 2 page questionnaire

Who ARE

you?

What are

your BIBBs ?

What type of

infrastructure

Security?

Networking?

Do I know

your

Device

Profile?

What Verison

of BACnet?

Your objects

are What?

Tested by 3rd Party Testing

• 4 Labs have license to test BACnet MBS GmbH SoftDEL Systems Private

Germany India

DIAL GmbH iHome Lab

Germany Germany

• Testing Mark Administration• BTL Listing through BACnet International

DOMESTIC

http://www.bacnetinternational.net/btl/

• WSPCert Certification through BACnet Interest Group-EUROPE (BIG-EU)

INTERNATIONAL

http://www.big-eu.org/en/products/certified-products/

• Testing Follows the ASHRAE SSPC 135.1 testing standard

• Each device based on its profile will be tested

• Must PASS Minimum 70 tests for a Simple Sensor (B-SS) to a

BACnet Controller (B-BC) 360+ testsB-AWS B-OWS B-OD B-BC B-AAC B-ASC B-SA B-SS

300 240 110 360 210 100 80 70

Points List

Example from Trane

Chiller Integration guide

“The industry has long used the general-purpose term "points", which

could refer to sensor inputs, control outputs or control values, with

different characteristics according to manufacturer”Bill Swan, Alerton Technologies, Inc

• The PICs are the technical specifications for BMS

• Points lists are WHAT each object does in your system

• No points list is like you asking what a lighting system does and they tell you it is distributed

and has an IP 65 rating, YES but what does it do?!

Some Rules of Thumb

• INSIST ON A PICS• If a company does not have the 2 page required document that

has a blank downloadable form and is REQUIRED by the standard that they can just fill out, what else did they miss in the 1000+ page standard that might be a long and costly issue on a project?

• MAKE SURE IT IS TESTED • The BACnet standard is over 1300+ page book of technical

instructions, do not rely on any engineer reading it all correctly or the same as another engineer. Even the committee members that write the standard argue about the standard!

SPECIFYING BACnet

In the Lighting world

Specifying BACnet for Lighting

• Coordination Issues

• Traditionally Building Management Systems has been under the

Mechanical Engineer sometimes putting all the integration

specifications under Division 23 (HVAC).

• Lighting under Division 26 means trades may never see it.

• Specifiers and installers understand the functionality and workings of

systems they are responsible for but may not be invested in or

understand what is involved in the integration to the BMS

• Leading to general statements in CSI Specs like “Building integrator shall

provide integration of the lighting control system with Building

Automation Systems using BACnet.”

Specifying BACnet for Lighting

25 13 00 Integrated Automation Control and Monitoring Network

All control systems to be integrated with the Building Management

System (BMS) shall conform to ANSI/ASHRAE Standard 135,

BACnet standard.

• CSI Recommendations

• Use Division 25 - Integrated Automation !!!!

• Added in the CSI Master Spec as a "place holder" for integration but

not used today (or used VERY little)

• A central place for all Integration and communication specifications

between systems

• Add all common protocol requirements to Lighting Division

- 26 09 43 System Integration (Division 26 Lighting)

- Controller and operator interface communication shall conform to

ANSI/ASHRAE Standard 135, BACnet/IP Annex J standard

Lighting system should have a Sequence of Operation for

Integration for BMS Integration

• WHO DOES WHAT?

� Time clock BMS or Lighting or combination or Scheduling Object?

� BMS building sweep covers lighting and what about areas with

Occupancy Sensors?

� Does the lighting system need to provide real time feedback to the

BMS with no polling required?

� How much control vs monitoring does the BMS systems have over the

lighting system?

� Sharing DATA does your Occupancy area correlate to HVAC zones?

CSI Recommendations

1.01 Lighting BACnet Interface Object Creation Requirements

1.01.1 Equipment Supplier shall create objects using the table below based on the following requirements:

1.01.1.1 The individual lighting device is called a ZONE. Lighting devices such ballasts, occupancy/vacancy sensors, daylight sensors and local controllers are considered ZONEs. Create all lighting devices as a separate ZONEs.

1.01.1.2 There are one or more ZONEs grouped into AREAs. An AREA is normally the space that is served by one HVAC Air Terminal Unit. If a VAV box serves more than one office, each office shall be set up as an AREA. If there is more than one lighting device (i.e., ballasts, occupancy/vacancy sensors, daylight sensors and local controllers) in a given AREA, create each lighting device as a separate ZONE.

1.01.1.3 The group of AREAs that are served by one HVAC Air Terminal Unit is called a DOMAIN. AREAs may or may not be contiguous. 1.01.1.4 The graphic below shows the relationship between the ZONEs, AREAs and the DOMAIN for typical group of offices found in the Work.

Examples supplied by Appin Associates, Grant Wichenko President

Gateways vs Embedded

• 3rd Party Gateways• 3rd Party Gateways are protocol translators translating each

command from BACnet to a protocol known by the lighting system

• Used many times as the initial entry into BMS integration

• Using a gateway, like any translation, information maybe lost and

many times does not have the same meaning making them a

negative condemnation for BMS integrators.

• Embedded BACnet stack puts the responsibility of BACnet on the

company embedding it.

• PICS needs to be Company Specific not of the entire gateway.

Translating two computer languages is like translating two human

languages. Words don’t mean exactly the same thing from one language to

another and it takes extra time waiting for everything to be translated. Try

using Google to translate a letter and then give that letter to someone who

can speak the other language fluently and watch the expression on their

face. They will probably break up laughing.

The Term Native

• Native

� Industry term not a technical term usually means embedded

� Not defined in the BACnet Standard or by an authoritative source

� Is nowhere in the 1300+ page BACnet standard (ANSI/ASHRAE

standard 135-2012, BACnet)

� “Native” is relative for your frame of reference

� May or may not be conformant with the BACnet standard!

What is the meaning of 'natural' on the label of food?

From a food science perspective, it is difficult to define a food product that is 'natural' because the

food has probably been processed and is no longer the product of the earth. That said, FDA has

not developed a definition for use of the term natural or its derivatives. However, the agency has

not objected to the use of the term if the food does not contain added color, artificial flavors, or

synthetic substances.

http://www.fda.gov/aboutfda/transparency/basics/ucm214868.htm

Like a food labeled “Natural”???

Conformance to the Standard

• Is a clause in the BACnet standard

� Has exact requirements

� It is clear in the “Table of Contents”

� It insists on a PICS

� Asks to be tested

� Only 4 pages

IT’S IN

THERE

Changes for Lighting

Within BACnet

Lighting Specific Objects

• Lighting Output Object (analog) - The new object is made specifically for Lighting

offering features used in lighting applications, such as:

- Blink-warn for Afterhours

- Continuous control of lighting level

- Ramping to a level at a fixed rate of change Fading to a level time

- Incremental stepping values up and down.

- Feedback for actual value of physical lighting

- Total Power and Instantaneous power of loads

- Min and Mav value for High and Low end trim

• Lighting Output Object (Binary) – Same as analog Plus functions that have clear

equivalencies to similar functions in DALI-based lighting systems such as:

• Elapsed Time and Reset indicated accumulated number of seconds that the light was ON

• Strike_Count and Reset the number of times the light has transitioned from OFF to ON

(Approved October 27, 2012.)

(Approved July 3, 2014.)

Lighting Specific Objects Coming

• Staged Value Object

- Changing thresholds between scenes with deadband availability. Common use is

Daylighting

• Color Value Object

- Describe color using X and Y model coordinates on the CIE chromaticity diagram

• Color Temperature Object

– the Lighting Output (LO) object is based on a white light with variable intensity from 0 to

100% luminance.. A given lighting output must be capable of varying its color temperature

over a range of color temperatures.

(Just voted to 2nd Public Review)

(In full Committee SSPC )

(In working Group )

Lighting Specific BIBBs

• Data Sharing-Lighting Output-A (DS-LO-A)

• Data Sharing-Advanced Lighting Output-A (DS-ALO-A)

• Data Sharing-Lighting Output-B (DS-LO-B)

• Data Sharing-Binary Lighting Output-B (DS-BLO-B)

• Device Management – Lighting Output Management-A (DM-LOM-A)

• Data Sharing-Lighting View-A (DS-LV-A)

• Data Sharing-Lighting Advanced View-A (DS-LAV-A)

• Data haring-Lighting Modify-A (DS-LM-A)

• Data Sharing-Lighting Advanced Modify-A (DS-LAM-A)

BIBB = A service or collection of services to

perform a function

(Just voted to 2nd Public Review)

Lighting Specific Device Profiles

• Lighting Operator Interfaces- BACnet Advanced Lighting Workstation (B-ALWS)

- BACnet Lighting Operator Display (B-LOD)

• Lighting Control Stations - BACnet Advanced Lighting Control Station (B-ALCS)

- BACnet Lighting Control Station (B-LCS)

• Lighting Controllers - BACnet Lighting Supervisor (B-LS)

- BACnet Lighting Device (B-LD)

(In 2nd Public Review)

Lighting Control / Monitor Software

Smart switch or dimmer

Touchscreen

Keypads

Changes for IoT

Within BACnet

BACnet /IPv6

• NEW in the 2016 publication

• Now BACnet /IP = IPv4 and BACnet /IPv6 = IPv6

BACnet /NL Stack

BVLL

ARCNETEIA-485

ISO 8802-3(IEEE 802.3)Ethernet

ISO 8802-2 (IEEE 802.3)Type 1

EIA-232

MS/TP PTP

LonTalk

UDP/IPv4

ZVLL

ZigBee CBA

IEEE 802.15.4

BVLL IPv6

UDP/IPv6

IP Datalink

= Current BACnet Definitions

BACnet Application

BACnet Application Layer

BACnet Network Layer

BACnet /IT

• BACnet over HTTP

• Gets BACnet out of the transportation business moving the message

• Can use standard Network security protocols like TLS.

• Just voted into advisory public review (APR)

BACnet Web Services

• NEW in the 2016 publication

• HTTP REST (REpresentational State Transfer) model

• eXtensible Data Structures used

- Control Systems Markup Language (CSML) “Native XML” • Choice of XML or JSON

• defining, transmitting, and storing BMS and other application data.

• Security is provided by TLS (https:) and a profile of OAuth 2.0

• Uses URIs (e.g. https://bws.example.com/path/to/data) to access data

• The data model and services are protocol independent, and can therefore be used to model and access data from any source,. CLASIC BACNETT KNX T LONWORKS TETC

Points to Remember

� Must have a Proper PICS

� Should be 3rd Party certified

� Make sure you supply a points list

� Sequence of operation defining Lightings role vs BMS role

in lighting and how they work together

� Use division 25 it is for integration

� Lighting is getting easier should be more defined within the

next 12 to 24 months

� BACnet /WS and BACnet /IT is being built for IoT and

those systems talking IoT

IES Annual Conference

QUESTIONS

This concludes The American Institute of Architects