Specifications Sakya Generator

Embed Size (px)

Citation preview

  • 8/9/2019 Specifications Sakya Generator

    1/10

    Technical Specifications400kVA Prime Rated

    Generator

    Technical Specifications

    TENDER FOR SUPPLY, INSTALLATION AND COMMISSIONING OF400 k VA (PRIME), AMF TYPE GENERATOR AND ACCESSORY EQUIPMENT

    ItemNo

    Item Description Specification CompliedYes/No

    Remarks

    1. Make of Engine/country of Origin _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

    (Contactor to specify)

    2. Model of Engine_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

    (Contactor to specify)

    3. Make of Alternator

    _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _(Contactor to specify)4. Model of Alternator

    _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _(Contactor to specify)

    5. General Shall be of shipped and delivered to site as complete unitassembled in manufacturers facility

    Yes/No

    Shall be the exclusive agent for the generator unit offered andmay be responsible for after sales service

    Yes/No

    Generator control panel shall be from the same generatormanufacturer and shall be shipped assembled/wired at themanufacturers facility

    Yes/No

    All component and accessories for complete generatorinstallation shall be supplied and installed by the bidder

    Yes/No

    Page 1 of 10

  • 8/9/2019 Specifications Sakya Generator

    2/10

    Technical Specifications400kVA Prime Rated

    Generator

    ItemNo

    Item Description Specification CompliedYes/No

    Remarks

    Price shall include testing and commissioning of the complete

    unit including load testing.

    Yes/No

    Price shall include testing and commissioning of the completeunit including load testing. Necessary loads and fuel shall besupplied by the bidder without any cost to the client.

    Yes/No

    Contractor shall investigate the site conditions, drawings andspecifications for selecting the most suitable solution for theproposed location.

    Yes/No

    All documents, drawings, catalogues, instructions, etc.,

    relating to this bid shall be in English and in SI Units.

    Yes/No

    Generator Unit and associated equipment shall be designedfor operation in the following environment conditions:Ambient Temperature : 6 deg. C to 42 deg. CRelative humidity : 90%, non condensing

    Yes/No

    All documents, drawings, catalogues, instructions, etc.,relating to this bid shall be in English and in SI Units.

    Yes/No

    6. Rating Shall be of Power output of 400kVA, (Prime) or higher at 0.8power factor

    Yes/No

    Shall be of Self Excited, 50Hz, 1500rpm, 3 phase, 400/230V Yes/No

    Page 2 of 10

  • 8/9/2019 Specifications Sakya Generator

    3/10

    Technical Specifications400kVA Prime Rated

    Generator

    ItemNo

    Item Description Specification CompliedYes/No

    Remarks

    7. Scope Supply, installation, testing and commissioning of generator

    unit complete with Deisel Engine, Alternator, and all otherequipment for fully operational unit.

    Yes/No

    Shall be with digital protection and control panel, mounted onthe Unit, wired and tested at the manufacturers facility

    Yes/No

    Shall be with unit mounted fuel tank with capacity not lessthan 750 liters. Please indicate the capacity.

    Yes/No Capacity :

    Shall be supplied and installed with bulk fuel tank of capacitynot less than 2500 liters with level indicator, filling pipe

    connections. Please indicate the capacity.

    Yes/No Capacity :

    Shall be supplied and installed with sound attenuationenclosure including unit cooling ductwork. Maximum allowablesound level at 1m distance shall not be more than 75dB.

    Yes/No

    Shall include with the proposal a detail proposal of soundattenuation enclosure and cooling duct work, including adrawing.

    Yes/No

    Shall provide necessary cabling and connections fromgenerator panel to ATS panel including conduiting,terminations, and accessories.

    Yes/No

    Shall provide and supplied with start up battery, battery rack,cabling & connections, battery charger, complete.

    Yes/No

    Page 3 of 10

  • 8/9/2019 Specifications Sakya Generator

    4/10

    Technical Specifications400kVA Prime Rated

    Generator

    ItemNo

    Item Description Specification CompliedYes/No

    Remarks

    8. Features Shall be delivered as Complete System Designed and built at

    ISO 9001 Certified manufacturing facility

    Yes/No

    Shall be factory tested to design specifications at full loadcondition and certified test report submitted

    Yes/No

    9. Engine Shall be of Industrial water cooled diesel engine Yes / No

    Shall be with Electronic Governor and with Electronic Speedcontrol

    Yes / No

    Start up electrical system shall be 12V dc or 24V dc complete

    with Battery Rack & cabling

    Yes / No

    Air filter shall be of dry type Yes / No

    Fuel and oil filter shall be of Cartridge type Yes / No

    Shall be with engine cooling system with coolant drain valve Yes / No

    10. Alternator Shall be of revolving field single bearing brushless typealternator and Insulation shall be of class H

    Yes / No

    Shall be of drip proof generator enclosure with cooling airintake (IP 23)

    Yes / No

    Electrical design shall be in Accordance with BS 5000 part 99 Yes / No

    Shall be with in-built heaters and provided with space heaters Yes / No

    Page 4 of 10

  • 8/9/2019 Specifications Sakya Generator

    5/10

    Technical Specifications400kVA Prime Rated

    Generator

    ItemNo

    Item Description Specification CompliedYes/No

    Remarks

    11. Control panel Shall be with sheet steel enclosure with hinged lockable door

    fitted to the generator body with vibration isolators

    Yes / No

    Standard control panel shall contain instrument, Protection,Indicators and controls indicated below:

    Yes / No

    12. Control & Display Functions

    General

    Automatic Voltage Regulation Yes / NoElectronic governor Control Yes / No

    Faulty condition / fault history indicator Yes / NoGlow plug control Yes / No

    Operator control Interface Functions/Features

    Manual/Automatic Mode Selector Switch Yes / NoManual start/stop Switch Yes / NoEmergency Stop Press Button Yes / NoManual/Auto LED Indicators Yes / NoCommon Shutdown LED Yes / NoCommon Warning LED Yes / NoEmergency Stop LED Yes / NoAlphanumeric LED Screen display Yes / NoFault Reset function Yes / No

    Page 5 of 10

  • 8/9/2019 Specifications Sakya Generator

    6/10

    Technical Specifications400kVA Prime Rated

    Generator

    ItemNo

    Item Description Specification CompliedYes/No

    Remarks

    Measurements and Indicators

    EngineLubricating Oil Pressure Yes / NoLubricating Oil Temperature Yes / NoCooling Water Temperature Yes / NoEngine Speed Yes / NoHour meter indication Yes / NoNumber of starts Yes / NoStart up battery voltage Yes / NoBattery Charging Ammeter Yes / No

    AlternatorLine to line voltage, Line to neutral voltage Yes / NoFrequency Yes / NoLine current with line selector Yes / NokWh meter, per phase and total Yes / NokVA meter, per phase and total Yes / NoPower factor per phase and total Yes / No

    Page 6 of 10

  • 8/9/2019 Specifications Sakya Generator

    7/10

    Technical Specifications400kVA Prime Rated

    Generator

    ItemNo

    Item Description Specification CompliedYes/No

    Remarks

    13. Protection & protection Shutdown Function

    Shutdown Protection

    Engine

    Low Fuel Level Trip Yes / NoHigh Fuel Level Trip Yes / NoLow Oil Pressure Trip Yes / NoHigh Engine Cooling WaterTemperature Trip Yes / NoOver speed Trip Yes / No

    Alternator

    Under & Over Voltage Trip Yes / NoUnder & Over Frequency Trip Yes / NoOver Current Trip Yes / NoEarth Leakage Trip Yes / NoReverse Power Trip Yes / NoReverse AVr Trip Yes / No

    Page 7 of 10

  • 8/9/2019 Specifications Sakya Generator

    8/10

    Technical Specifications400kVA Prime Rated

    Generator

    ItemNo

    Item Description Specification CompliedYes/No

    Remarks

    14. Protection Shutdown Indication

    Shutdown Protection & Indicatoion

    Engine

    Low Fuel Level Trip Indication Yes / NoHigh Fuel Level Trip Indication Yes / NoLow Oil Pressure Trip Indication Yes / NoHigh Engine Coolant Temperature Trip Indication Yes / NoOver speed Trip Indication Yes / NoFail to Crank Shutdown Indication Yes / No

    Over Crank Indication Yes / No

    Alternator

    Under & Over Voltage Trip Indication Yes / NoUnder & Over Frequency Trip Indication Yes / NoOver Current Trip indication Yes / NoEarth Leakage Trip Indication Yes / NoReverse Power Trip indication Yes / NoReverse AVr Trip Indication Yes / No

    Page 8 of 10

  • 8/9/2019 Specifications Sakya Generator

    9/10

    Technical Specifications400kVA Prime Rated

    Generator

    ItemNo

    Item Description Specification CompliedYes/No

    Remarks

    15. Generator breaker, Power and Earth Connections

    50 kA, 630A, minimum, 4 poleEFR Tripping current to be adjustable from 0-300mA

    Yes / No

    Power connection from generator Panel to ATS (only the ATSsupplied by others)

    Yes / No

    Ear thing of Generator Unit (Generator Neutral with CopperRod and Tap, 25mm X 3mm Connection)

    Yes / No

    16. Mounting Arrangement

    Heavy duty fabricated steel base with lifting points and Antivibration pads to ensure vibration isolation

    Yes / No

    Engine coupled to generator with flexible disc coupling or asper manufacturers standard design

    Yes / No

    17. Exhaust System and Cooling Air System

    Heavy duty industrial capacity exhaust silencer(Heat resisting materials shall be covered with Aluminiumcladding)

    Yes / No

    Necessary extention of exhaust discharge system Yes / No

    Cooling air system complete with hot air discharge system Yes / No

    Page 9 of 10

  • 8/9/2019 Specifications Sakya Generator

    10/10

    Technical Specifications400kVA Prime Rated

    Generator

    ItemNo

    Item Description Specification CompliedYes/No

    Remarks

    18. Literature

    Manufacturers technical literature for engine Yes / No

    Manufacturers technical literature for alternator Yes / No

    Circuit Diagram for generator control panel Yes / No

    19. Warranty

    3 years comprehensive,(Parts, Labour and Transport)

    Yes / No

    3 Nos. free service including oil, filters and labour

    Draft service and maintenance agreement after completion of3 year warranty period

    Yes / No

    Page 10 of 10