- 1 - Specification of DISMY heat pump 1.Air source heat pump DISMY air source heat pump includes: (1) air source heat pump for heating (for weather temperature min. -7, or weather temperature min. -25) (2) air source heat pump for heating/DHW (for weather temperature min. -7, or weather temperature min. -25) (3) air source heat pump for heating/cooling (for weather temperature min. -7, or weather temperature min. -25) (4) waste heat recovery air source heat pump for heating/cooling/DHW (for weather temperature min. -7, or weather temperature min. -25) (5) Swimming pool air source heat pump *The heating capacity of DISMY air source for domestic application can be from 2kw-60kw. *The heating capacity of DISMY air source for commercial application can be from 60kw-480kw. Split type monobloc type

Specification of DISMY heat pump 1.Air source heat pumpf03.s.alicdn.com/kf/HTB1l14lFVXXXXasXVXX.PRXFXXXM.pdf · 2019. 7. 30. · 1.Air source heat pump ... power/pc 80W 80W 120W 180W

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

  • - 1 -

    Specification of DISMY heat pump

    1.Air source heat pump DISMY air source heat pump includes: (1) air source heat pump for heating (for weather temperature min. -7, or weather temperature min. -25) (2) air source heat pump for heating/DHW (for weather temperature min. -7, or weather temperature min. -25) (3) air source heat pump for heating/cooling (for weather temperature min. -7, or weather temperature min. -25) (4) waste heat recovery air source heat pump for heating/cooling/DHW (for weather temperature min. -7, or weather

    temperature min. -25) (5) Swimming pool air source heat pump *The heating capacity of DISMY air source for domestic application can be from 2kw-60kw. *The heating capacity of DISMY air source for commercial application can be from 60kw-480kw.

    Split type monobloc type

  • - 2 -

    (1). air source heat pump for heating (for weather temperature min. -7, or weather temperature min. -25) (2). air source heat pump for heating/DHW (for weather temperature min. -7, or weather temperature min. -25)

    Performance parameter table

    Item

    DAR-60

    ASPA2-U

    DAR-80

    ASPA2-U

    DAR-100

    ASPA2-U

    DAR-120

    ASPA2-U

    DAR-150

    ASPB2-U

    DAR-150

    ASPA2-

    U

    DAR-200

    ASPB2-U

    DAR-200

    ASPA2-

    U

    DAR-250

    ASPB2-U

    heating

    capacity

    KW

    A7/W45 7.2 8.6 10.56 14.2 17.6 17.6 21.1 21.1 26.7

    heating power

    KW

    A7/W45 2.2 2.53 3.1 4.5 4.9 4.9 6.2 6.2 8.8

    heating

    capacity

    KW

    A2/W35 5.84 7.43 8.4 11.68 14.6 14.6 16.8 16.8 23.3

    heating power

    KW

    A7/W45 1.83 2.3 2.57 3.62 4.2 4.2 5.2 5.2 7.4

    heating

    capacity

    KW

    A-7/W35 4.1 5.37 6.13 8.2 11.2 11.2 12.3 12.3 17.3

    heating power

    KW

    A7/W45 1.86 2.19 2.6 3.68 4.12 4.12 5.3 5.3 7.39

    heating

    capacity

    KW

    A2/W50 5.26 6.82 8.7 10.52 12.5 12.5 14.9 14.9 22.1

    heating power

    KW

    A7/W45 2.34 3.1 3.54 4.64 5.6 5.6 7.2 7.2 9.6

    heating

    capacity

    KW

    A7/W35 7.4 8.9 10.8 14.8 17.9 17.9 21.8 21.8 27.3

    heating power

    KW

    A7/W45 2.39 3.2 3.98 4.78 5.53 5.53 7.97 7.11 8.9

    max. running

    current A 10.87 14.55 18.1 21.49 25.8 18.76 36.22 24.24 30.2

    start current A 27.175 36.375 45.25 53.725 69.9 23.45 117 30.3 82

    soft starter built-in built-in built-in built-in no built-in no built-in no

    power type 220V 220V 220V 220V 220V 380V 220V 380V 380V

    compressor scroll

    compressor

    qty. Pc 1 1 1 1 2 1 2 1 1

    refrigerant R407C R407C R407C R407C R407C R407C R407C R407C R407C

    ref. qty. Kg 1.8 2.4 3 2*1.8 2*2.3 4.6 2*3.0 5.8 7.5

    protection

    High or low pressure protection, electric current over loading protection, defrost protection, electrical short of phase

    and contra dictionary phase protection, voltage too high or too low protection

    heat

    exchanger

    type plate/coaxial coil

    heating flow T/H 1.4 1.7 2 2.7 3.4 3.4 3.8 3.8 4.8 pressure drop

    of exchanger KPa 10 10 10 10 10 10 10 10 10

  • - 3 -

    heating

    connector 1"f 1"f 1"f 1"f 1-1/4"f 1-1/4"f 1-1/4"f 1-1/4"f 1-1/2"f

    fan qty. 1 1 1 1 1 1 2 2 2

    fan rate/pc M3/h 1420 1420 2830 3700 3700 3700 3700 3700 3700

    power/pc 80W 80W 120W 180W 180W 180W 180W*2 180W*2 180W*2

    fan direction top top top Top top top top top top

    Ambient

    condition -7 to 35 degree

    measure(L*W*

    H) 725×725×1000 725×1450×1000

    Noise dBA 56 56 56 60 60 60 60 60 60

    weight Kg 112 116 122 145 172 167 191 178 245

    Max.heating

    temperature ℃ 55 degree

    Recom.

    breaker 30(2P) 30(2P) 30(2P) 40(2P) 40(2P) 30(4P) 63(2P) 30(4P) 30(4P)

    Recom.power

    cable

    YCW2*4+

    1*2.5

    YCW2*4+

    1*2.5

    YCW2*4+

    1*2.5

    YCW2*6+

    1*4

    YCW2*6+

    1*4

    YCW3*4

    +1*2.5

    YCW2*10

    +1*6

    YCW3*4

    +1*2.5

    YCW3*4+

    1*2.5

    A35/W7 cooling condition: dry ball temperature 35℃, cooling water 7℃

    A7/W45 heating condition: dry ball temperature 7℃ and wet ball temperature 6℃, heating water 45℃

  • - 4 -

    (3). air source heat pump for heating/cooling (for weather temperature min. -7, or weather temperature min. -25)

    Performance parameter table

    Item

    DAR-60

    ASPA2-U

    DAR-80

    ASPA2-U

    DAR-100

    ASPA2-U

    DAR-120

    ASPA2-U

    DAR-150

    ASPB2-U

    DAR-150

    ASPA2-

    U

    DAR-200

    ASPB2-U

    DAR-200

    ASPA2-

    U

    DAR-250

    ASPB2-U

    COOLING

    CAPACITY

    KW

    A35/W7 6 7.8 9.6 12 15 15 19.2 19.2 25

    COOLING

    POWER

    KW

    A35/W7 2.1 2.79 3.4 4.3 5.4 5.4 6.8 6.75 8.96

    heating

    capacity

    KW

    A7/W45 7.2 8.6 10.56 14.2 17.6 17.6 21.1 21.1 26.7

    heating power

    KW

    A7/W45 2.2 2.53 3.1 4.5 4.9 4.9 6.2 6.2 8.8

    heating

    capacity

    KW

    A2/W35 5.84 7.43 8.4 11.68 14.6 14.6 16.8 16.8 23.3

    heating power

    KW

    A7/W45 1.83 2.3 2.57 3.62 4.2 4.2 5.2 5.2 7.4

    heating

    capacity

    KW

    A-7/W35 4.1 5.37 6.13 8.2 11.2 11.2 12.3 12.3 17.3

    heating power

    KW

    A7/W45 1.86 2.19 2.6 3.68 4.12 4.12 5.3 5.3 7.39

    heating

    capacity

    KW

    A2/W50 5.26 6.82 8.7 10.52 12.5 12.5 14.9 14.9 22.1

    heating power

    KW

    A7/W45 2.34 3.1 3.54 4.64 5.6 5.6 7.2 7.2 9.6

    heating

    capacity

    KW

    A7/W35 7.4 8.9 10.8 14.8 17.9 17.9 21.8 21.8 27.3

    heating power

    KW

    A7/W35 2.39 3.2 3.98 4.78 5.53 5.53 7.97 7.11 8.9

    max. running

    current A 10.87 14.55 18.1 21.49 25.8 18.76 36.22 24.24 30.2

    start current A 27.175 36.375 45.25 53.725 69.9 23.45 117 30.3 82

    soft starter built-in built-in built-in built-in no built-in no built-in no

    power type 220V 220V 220V 220V 220V 380V 220V 380V 380V

    compressor scroll

    compressor

    qty. Pc 1 1 1 1 2 1 2 1 1

    refrigerant R407C R407C R407C R407C R407C R407C R407C R407C R407C

    ref. qty. Kg 1.8 2.4 3 2*1.8 2*2.3 4.6 2*3.0 5.8 7.5

    protection

    High or low pressure protection, electric current over loading protection, defrost protection, electrical short of phase

    and contra dictionary phase protection, voltage too high or too low protection

    heat

    exchanger plate/coaxial coil

  • - 5 -

    type

    heating flow T/H 1.4 1.7 2 2.7 3.4 3.4 3.8 3.8 4.8

    pressure drop

    of exchanger KPa 10 10 10 10 10 10 10 10 10

    heating

    connector 1"f 1"f 1"f 1"f 1-1/4"f 1-1/4"f 1-1/4"f 1-1/4"f 1-1/2"f

    fan qty. 1 1 1 1 1 1 2 2 2

    fan rate/pc M3/h 1420 1420 2830 3700 3700 3700 3700 3700 3700

    power/pc 80W 80W 120W 180W 180W 180W 180W*2 180W*2 180W*2

    fan direction top top top Top top top top top top

    Ambient

    condition -7 to 35 degree

    measure(L*W*

    H) 725×725×1000 725×1450×1000

    Noise dBA 56 56 56 60 60 60 60 60 60

    weight Kg 112 116 122 145 172 167 191 178 245

    Max.heating

    temperature ℃ 55 degree

    Recom.

    breaker 30(2P) 30(2P) 30(2P) 40(2P) 40(2P) 30(4P) 63(2P) 30(4P) 30(4P)

    Recom.power

    cable

    YCW2*4+

    1*2.5

    YCW2*4+

    1*2.5

    YCW2*4+

    1*2.5

    YCW2*6+

    1*4

    YCW2*6+

    1*4

    YCW3*4

    +1*2.5

    YCW2*10

    +1*6

    YCW3*4

    +1*2.5

    YCW3*4+

    1*2.5

    A35/W7 cooling condition: dry ball temperature 35℃, cooling water 7℃

    A7/W45 heating condition: dry ball temperature 7℃ and wet ball temperature 6℃, heating water 45℃

  • - 6 -

    (4). waste heat recovery air source heat pump for heating/cooling/DHW (for weather temperature min. -7, or weather temperature min. -25) The air-to-water heat pump is intended for use in existing or newly built heating systems. The heat pump is designed for the cooling, heating for heating purposes and the supply of domestic hot water! The heat pump is suitable for mono-energetic and bivalent operation. Defrosting of the evaporator is automatic. In winter, the air is the heating source, the heat pump can get heat from the heat source by the compressor circuit, and the heat can be transferred into the room through water, so the room becomes warm. In summer, the air is the cooling source, the heat pump can get heat from room by the compressor circuit, and the heat can be transferred into the cooling source through water, so the room becomes cool. The heat pump can supply domestic hot water every time, even if when cooling. In summer, DHW is heated from the waste heat that should be sent to air, so the heat of DHW is free. DDR series heat pump delivers heat up to a fixed temperature level. This is called “fixed condensing”. DDR series heat pump can be docked to an external unit with its own heating controls, for example, room thermostat for floor heating system or thermostatic valve for radiator. 1. Characteristics ●The new renewable energy technology DISMY ground heat pumps use the earth's surface shallow geothermal energy as a source of hot and cold, for energy conversion of heating and cooling air-conditioning system, geothermal energy from the shallow surface area has much advantages, such as no resource constraints, limitless area, abundance, everywhere, almost unlimited. DISMY ground heat pump use earth’s surface shallow renewable resources, have opened up a new way to clean energy. ●Multifunctional DISMY ground source heat pump can supply cooling, floor heating and domestic hot water, it is a multi-purpose. ●The super hot water function 1, When cooling in summer, the waste heat will be recovered to get free DHW, hot water temperature can reach 55-60 ℃. 2, When no heating and cooling needed, it will become hot water heat pump and make DHW, hot water temperature can reach 55-60 ℃. 3, When heating in winter, DHW is provided at the same time, hot water temperature can reach 55-60 ℃. ●Built-in Hydraulic module, easy installation(Optional) Hydraulic module (flow switch, expansion tank, water pumps) is built-in.

  • - 7 -

    DHW outlet

    DHW inlet

    heating/cooling inlet

    heating/cooling outlet

  • - 8 -

    Itme Unit

    DAR-120A

    SPA1-FP

    A

    DAR-120A

    SPB1-FP

    A

    DAR-150A

    SPA1-FP

    A

    DAR-150A

    SPB1-FP

    A

    DDR-200AS

    PB1-FPA

    DDR-250AS

    PB1-FPA

    Cooling capacity KW

    A35/W7 12 15 20 25

    Cooling power KW

    A35/W7 4.3 5.4 6.75 8.96

    heating capacity KW

    A7/W45 14.2 17.6 21.1 26.7

    heating power

    KW

    A7/W45 4.5 4.9 6.2 8.8

    heating capacity KW

    A2/W35 11.68 14.6 16.8 23.3

    heating power

    KW

    A7/W45 3.62 4.2 5.2 7.4

    heating capacity KW

    A-7/W35 8.2 11.2 12.3 17.3

    heating power

    KW

    A7/W45 3.68 4.12 5.3 7.39

    heating capacity KW

    A2/W50 10.52 12.5 14.9 22.1

    heating power

    KW

    A7/W45 4.64 5.6 7.2 9.6

    heating capacity KW A7/W35 14.8 17.9 21.8 27.3

    heating power KW A7/W35 4.78 5.53 7.11 8.9

    water flow T/H 2.7 3.4 3.8 4.8

    DHW water flow T/H 2.7 3.4 3.8 4.8

    DHW output L/H

    △35℃ 340 470 600 710

    Compressor type scroll scroll scroll Scroll

    Compressor qty. pc 2 1 2 1 2 2

    Refrigerant R407C/R417A R407C/R417A R407C/R417

    A

    R407C/R417

    A

    Ref. qty. kg 1.3*2 2.5 1.5*2 2.9 2.3*2 2.5*2

    DHW connector 1"F 1"F 1"F 1"F

    Heating connector 1-1/4"F 1-1/4"F 1-1/4"F 1-1/4"F

    Measure mm 1100*500*1

    572

    1100*470*1

    572

    1100*500*1

    572

    1100*470*1

    572 1540*540*1642 1540*540*1642

    Fan discharge side side side side side side

    Weight kg 200 200 270 330

    Noise dBA 48 48 48 48

    Max. heating temp. ℃ 55 55 55 55

    Power 230V/50H

    z

    380V/3N/5

    0Hz

    230V/50H

    z

    380V/3N/5

    0Hz 380V/3N/50Hz

  • - 9 -

    Soft starter Built-in no Built-in no no no

    Cooling start

    current A 56 30 69 36 45 51.2

    Heating start

    current A 60 32 78 41 50 56.8

    Cooling running

    Current A 19.5 7.5 23 9.0 11.0 12.5

    Heating running

    Current A 21.2 8.0 26 10.3 12.2 13.8

    Recom. Breaker 30(2P) 16(4P) 30(2P) 16(4P) 20(4P) 20(4P)

    Recom. cable YCW2*4+

    2*2.5

    YCW3*2.5

    +2*2.5

    YCW2*6+

    2*4

    YCW3*4+

    2*2.5

    YCW3*4+2*

    4

    YCW3*4+2*

    4

    A35/W7 cooling condition: dry ball temperature 35℃, cooling water 7℃

    A7/W45 heating condition: dry ball temperature 7℃ and wet ball temperature 6℃, heating water 45℃

  • - 10 -

    Itme Unit DAR-300ASPB1-F

    PA

    DAR-400ASPB1-F

    PA

    DDR-500ASPB1-F

    PA

    DDR-600ASP

    B1-FPA

    Cooling capacity KW

    A35/W7 30 40 50 60

    Cooling power KW

    A35/W7 10.2 12.4 14.4 20.4

    Heating capacity KW

    A7/W45 38.5 49 56 76

    Heating power KW

    A7/W45 11.6 13.8 16 23.2

    Heating water flow T/H 5.2 7 8 4.3

    DHW water flow T/H 6.2 8.2 10.4 12.4

    DHW output L/H

    △ ℃35 930 1200 1400 1800

    Compressor type scroll scroll scroll scroll

    Compressor qty. pc 2 2 2 2

    Refrigerant R407C/R417A R407C/R417A R407C/R417A R407C/R417A

    Ref. qty. kg 2.9*2 4.5*2 5.2*2 6.2*2

    DHW connector 1"F 1"F 1"F 1"F

    Heating connector 1-1/4"F 1-1/4"F 1-1/4"F 1-1/4"F

    Measure mm 1484*854*1253 1531*894*1403 1631*934*1403 1817*994*1403

    Fan discharge top top top top

    Weight kg 320 425 530 620

    Noise dBA 48 48 48 48

    Max. heating temp. ℃ 55 55 55 55

    Power 380V/3N/50Hz 380V/3N/50Hz 380V/3N/50Hz 380V/3N/50Hz

    Soft starter no no no No

    Cooling start

    current A 45 55 65 90

    Heating start

    current A 50 60 70 100

    Cooling running

    Current A 18 21.9 25.4 36

    Heating running

    Current A 20.5 24.6 28.2 41

    Recom. Breaker 30(4P) 40(4P) 60(4P) 100(4P)

    Recom. cable YCW3*6+2*2.5 YCW2*6+2*4 YCW3*10+2*6 YCW3*16+2*1

    0

    A35/W7 cooling condition: dry ball temperature 35 , cooling water 7℃ ℃

    A7/W45 heating condition: dry ball temperature 7 and wet ball temperature 6 , heating water 45℃ ℃ ℃

  • - 11 -

    (5) Swimming pool air source heat pump

  • - 12 -

    2. Ground source heat pump DISMY ground source heat pump includes: (1) ground source heat pump for heating(brine to water) (2) ground source heat pump for heating/DHW(brine to water) (3) ground source heat pump for heating/cooling(brine to water) (4) waste heat recovery ground source heat pump for heating/cooling/DHW (5) ground source heat pump with built-in tank for heating/DHW (6) water source heat pump for heating(water to water) (7) water source heat pump for heating/DHW(water to water) (8) water source heat pump for heating/cooling(water to water) (9) screw compressor ground source heat pump for commercial application *The heating capacity of DISMY ground source for domestic application can be from 2kw-100kw. *The heating capacity of DISMY ground source for commercial application can be from 100kw-2000kw.

    Model definition

    DDR – 112 G S P B 2 – U

    1 2 3 4 5 6 7 8

    1. Heat pump type, DDR means DISMY ground source heat pump

    2. Cooling or heating class

    3. Condensation type, W means ground water as heat source, G means Soil, rock or lake as heat source

    4. Compressor type, S means scroll compressor

    5. Heat exchanger type, P means plate heat exchanger

    6. Power type, A means 220-240V/1N/50Hz, B means 380-415V/3N/50Hz

    7. Refrigerant type, 2 means R407C

    8. Optional:

    F: full waste heat recovery

    R: half waste heat recovery

    M: module type

    U: single heating function only

    V: 3-way valve in-built for DHW

    A: water pump and expansion tank in-built

    P: flow switch in-built

    O: outside house installation, without “O” means inside house installation

  • - 13 -

    (1) ground source heat pump for heating(brine to water) (2) ground source heat pump for heating/DHW(brine to water)

    Ground source heat pump technology implements transferring the low-temperature from earth's

    surface shallow water (river, lake, sea)and Soil that absorption of solar energy and geothermal energy,

    to high-temperature by importing a little of electricity. Ground source heat pump can supply cooling,

    heating and domestic hot water.

    DISMY ground source heat pump is a heating system which is designed for operation as brine/water

    heat pump. The heat pump extracts energy from the heat source medium at a low temperature level.

    This extracted energy is then transferred to the heating water at a higher level, enriched with the

    energy transferred by the compressor. Subject to the heat source temperature, the heating water can

    be heated up to a flow temperature of 55 .℃

    A three-way valve built-in(optional) have been integrated for diverting the flow either to the heating

    circuit or the DHW circuit. DHW is heated by pumping the heating water, which has been heated by

    the heat pump, through a heat exchanger into the DHW cylinder, where it transfers its energy to the

    DHW. DM2066 DHW thermostat can be used to start DHW function instant or by timing.

    DDR series heat pump delivers heat up to a fixed temperature level. This is called “fixed condensing”.

    DDR series heat pump can be docked to an external unit with its own heating controls, for example,

    room thermostat for floor heating system or thermostatic valve for radiator.

  • - 14 -

    Back pipe connection:

    Single heating(DDR-U) Heating/DHW(DDR-UV)

    Performance parameter table---- Back pipe connection (brine to water)

    Item Unit DDR-78GSPA2

    -UB(UV)

    DDR-112GSPA2-

    UB(UV)

    DDR-162GSPB2-UB

    (UV)

    DDR-192GSPB

    2-UB(UV)

    DDR-221GSPB2-UB

    (UV)

    Heating capacity KW B0/W35 6.4 9.5 14.2 15.9 18.2 Heating power KW B0/W35 1.6 2.3 3.5 3.8 4.2 Heating capacity KW B0/W50 5.6 8.5 13.3 14.8 16.6 Heating power KW B0/W50 2.1 2.9 4.8 5.1 5.8 Heating capacity KW B8/W35 7.3 11.1 15.6 18.2 20.8 Heating power KW B8/W35 1.6 2.3 3.2 3.7 4.6 Heating capacity KW B8/W50 6.6 10.3 14.2 16.5 18.8 Heating power KW B8/W50 2.2 3.2 4.5 5.3 6.4

    Brine flow T/H 1 1.5 2.1 2.5 2.8 Heating flow T/H 1.3 1.9 2.7 3.1 3.6 Evaporator pressure drop

    KPa 10 10 10 10 10

    Condenser pressure drop

    KPa 10 10 10 10 10

    Compressor SCROLL SCROLL SCROLL SCROLL SCROLL Compressor qty. Pc 1 1 1 1 1 Refrigerant R407C R407C R407C R407C R407C Refrigerant qty. kg 1.6 1.8 2.7 3.2 3.6

    DHW connector 1"F 1"F 1"F 1"F 1"F

    Brine/heating Connector

    1-1/4"F 1-1/4"F 1-1/4"F 1-1/4"F 1-1/4"F

  • - 15 -

    Recommendatory heating pipe

    DN32 DN32 DN32 DN32 DN40

    Measure(L*W*H) mm 500*679*900 500*679*900 500*679*900 500*679*900 500*679*900 Weight kg 120 180 185 210 225 Noise dBA 48 48 48 48 48 Brine inlet range ℃ -5 to +25 -5 to +25 -5 to +25 -5 to +25 -5 to +25 Max. heating temperature

    ℃ 55 55 55 55 55

    Soft starter Built-in Built-in No No No Heating start current

    A 24 45 45 54 60

    Cooling running current

    A 7.8 16.4 8.2 9.9 11

    Heating running current

    A 9.6 17.9 9 10.8 12

    Recom. breaker 30(2P) 40(2P) 30(4P) 40(4P) 40(4P) Recom. power cable

    YCW2*4+1*2.5

    YCW2*10+1*6 YCW3*6+1*4 YCW3*6+1*4

    YCW3*6+1*4

    Power 230V/1N/50Hz 380V/3N/50Hz B0/W35 heating: Brine inlet temperature is 0 degree, heating flow temperature is 35 degree.

  • - 16 -

    (3) ground source heat pump for heating/cooling(brine to water) Ground source heat pump technology implements transferring the low-temperature from earth's surface shallow water (groundwater, river, lake, sea)and Soil that absorption of solar energy and geothermal energy, to high-temperature by importing a little of electricity. Ground source heat pump can supply cooling, heating and domestic hot water. DISMY ground source heat pump is a heating system which is designed for operation as brine/water or water/water heat pump. The heat pump extracts energy from the heat source medium i.e. brine at a low temperature level. This extracted energy is then transferred to the heating water at a higher level, enriched with the energy transferred by the compressor. Subject to the heat source temperature, the heating water can be heated up to a flow temperature of 55 .℃ In winter, the underground water or ground is the heating source, the heat pump can get heat from the heat source by the compressor circuit, and the heat can be transferred into the room through water, so the room becomes warm. The heat pump also can produce sanitary hot water; In summer, the underground water or ground is the cooling source, the heat pump can get heat from room by the compressor circuit, and the heat can be transferred into the cooling source through water, so the room becomes cool. DDR series heat pump delivers heat up to a fixed temperature level. This is called “fixed condensing”. DDR series heat pump can be docked to an external unit with its own heating controls, for example, room thermostat for floor heating system or thermostatic valve for radiator.

  • - 17 -

    Back pipe connection:

  • - 18 -

    Performance parameter table---- Back pipe connection (brine to water)

    Item Unit DDR-78GSPA2

    -B

    DDR-112GSPA

    2-B

    DDR-162GSPB

    2-B

    DDR-192GSPB

    2-B

    DDR-221GSPB

    2-B

    Cooling capacity KW W25/W7

    7.2 10.6 16.5 19.82 22.1

    Cooling power KW W25/W7

    1.6 3.32 4.62 5.55 6.17

    Heating capacity KW B0/W35

    6.4 9.5 14.2 15.9 18.2

    Heating power KW B0/W35

    1.6 2.3 3.5 3.8 4.2

    Heating capacity KW B0/W50

    5.6 8.5 13.3 14.8 16.6

    Heating power KW B0/W50

    2.1 2.9 4.8 5.1 5.8

    Heating capacity KW B8/W35

    7.3 11.1 15.6 18.2 20.8

    Heating power KW B8/W35

    1.6 2.3 3.2 3.7 4.6

    Heating capacity KW B8/W50

    6.6 10.3 14.2 16.5 18.8

    Heating power KW B8/W50

    2.2 3.2 4.5 5.3 6.4

    Cooling source flow T/H 1.5 2.3 3.4 3.9 4.5 Cooling flow T/H 1.3 2 2.8 3.3 3.8 Evaporator pressure drop

    Pa 10 10 10 10 10

    Condenser pressure drop

    Pa 10 10 10 10 10

    Compressor SCROLL SCROLL SCROLL SCROLL SCROLL Compressor qty. Pc 1 1 1 1 1 Refrigerant R407C R407C R407C R407C R407C Refrigerant qty. kg 1.6 1.8 2.7 3.2 3.6

    DHW connector 1"F 1"F 1"F 1"F 1"F

    Connector 1-1/4"F 1-1/4"F 1-1/4"F 1-1/4"F 1-1/4"F

    Recommendatory heating pipe

    DN32 DN32 DN32 DN32 DN40

    Measure(L*W*H) mm 500*679*900 500*679*900 500*679*900 500*679*900 500*679*900 Weight kg 120 180 185 210 225 Noise dBA 48 48 48 48 48 Brine inlet range ℃ -5 to +25 -5 to +25 -5 to +25 -5 to +25 -5 to +25 Max. heating temperature

    ℃ 55 55 55 55 55

    Soft starter Built-in Built-in No No No Cooling start current

    A 19.5 41 41 49.5 55

    Heating start current

    A 24 45 45 54 60

    Cooling running current

    A 7.8 16.4 8.2 9.9 11

  • - 19 -

    Heating running current

    A 9.6 17.9 9 10.8 12

    Recom. breaker 30(2P) 40(2P) 30(4P) 40(4P) 40(4P) Recom. power cable

    YCW2*4+1*2.5

    YCW2*10+1*6

    YCW3*6+1*4

    YCW3*6+1*4

    YCW3*6+1*4

    Power 230V/1N/50Hz 380V/3N/50Hz W25/W7 cooling: ground loop inlet temperature is 25 degree, cooling flow temperature is 7 degree. B0/W35 heating: Brine inlet temperature is 0 degree, heating flow temperature is 35 degree.

  • - 20 -

    (4) waste heat recovery ground source heat pump for heating/cooling/DHW (brine to water) Ground source heat pump technology implements transferring the low-temperature from earth's surface shallow water (groundwater, river, lake, sea)and Soil that absorption of solar energy and geothermal energy, to high-temperature by importing a little of electricity. Ground source heat pump can supply cooling, heating and domestic hot water. DISMY ground source heat pump is a heating system which is designed for operation as brine/water or water/water heat pump. The heat pump extracts energy from the heat source medium i.e. brine at a low temperature level. This extracted energy is then transferred to the heating water at a higher level, enriched with the energy transferred by the compressor. Subject to the heat source temperature, the heating water can be heated up to a flow temperature of 55 .℃ In winter, the underground water or ground is the heating source, the heat pump can get heat from the heat source by the compressor circuit, and the heat can be transferred into the room through water, so the room becomes warm. The heat pump also can produce sanitary hot water; In summer, the underground water or ground is the cooling source, the heat pump can get heat from room by the compressor circuit, and the heat can be transferred into the cooling source through water, so the room becomes cool. The DHW function built-in can supply hot water every time, even if when cooling. In summer, DHW is heated from the waste heat that should be sent to ground, so the heat of DHW is free. DDR series heat pump delivers heat up to a fixed temperature level. This is called “fixed condensing”. DDR series heat pump can be docked to an external unit with its own heating controls, for example, room thermostat for floor heating system or thermostatic valve for radiator. 1. Characteristics ●The new renewable energy technology DISMY ground heat pumps use the earth's surface shallow geothermal energy as a source of hot and cold, for energy conversion of heating and cooling air-conditioning system, geothermal energy from the shallow surface area has much advantages, such as no resource constraints, limitless area, abundance, everywhere, almost unlimited. DISMY ground heat pump use earth’s surface shallow renewable resources, have opened up a new way to clean energy. ●Cost-effective and energy-saving The geo-temperature is stable all-year, it is higher than lapse rate in the winter, lower in the summer, so it is the ideal source for heat pump, comparing with the traditional central air-conditioning, the energy-saving is 60%-70%, energy-saving effect is very significant. ●Clean, green DISMY source heat pump run with electricity, running without pollution and waste, the groundwater will back to the ground after it get into the heat exchange unit, and it has no any adverse effects to other groundwater and soil , and it will not make the loss of groundwater. ●Multifunctional DISMY ground source heat pump can supply cooling, floor heating and domestic hot water, it is a multi-purpose. ●Stable, long-running The geo-temperature is relatively stable, it is an ideal operating conditions for the DISMY ground source heat pump, the unit runs with a stable condition, the life of the compressor is much higher than the traditional central air-conditioning.

  • - 21 -

    ●The super hot water function 1, When cooling in summer, the waste heat will be recovered to get free DHW, hot water temperature can reach 55-60 . ℃ 2, When no heating and cooling needed, it will become hot water heat pump and make DHW, hot water temperature can reach 55-60 . ℃ 3, When heating in winter, DHW is provided at the same time, hot water temperature can reach 55-60

    . ℃ ●Built-in Hydraulic module, easy installation(Optional) Hydraulic module (flow switch, expansion tank, water pumps) can be built-in.

  • - 22 -

    heating/cooling outlet

    DHW outlet

    heating/cooling inlet

    ground outlet

    ground inlet

    DHW inlet

  • - 23 -

    Performance parameter table (brine to water)

    Item Unit DDR-78GSP

    A2-FP

    DDR-112GS

    PA2-FP

    DDR-162GS

    PA2-FP

    DDR-192GS

    PB2-FP

    DDR-221GS

    PB2-FP

    Cooling capacity KW

    W25/W7 7.2 10.6 16.5 19.82 22.1

    Cooling power KW

    W25/W7 1.6 3.32 4.62 5.55 6.17

    Heating capacity KW B0/W35

    6.4 9.5 14.2 15.9 18.2

    Heating power KW B0/W35

    1.6 2.3 3.5 3.8 4.2

    Heating capacity KW B0/W50

    5.6 8.5 13.3 14.8 16.6

    Heating power KW B0/W50

    2.1 2.9 4.8 5.1 5.8

    Heating capacity KW B8/W35

    7.3 11.1 15.6 18.2 20.8

    Heating power KW B8/W35

    1.6 2.3 3.2 3.7 4.6

    Heating capacity KW B8/W50

    6.6 10.3 14.2 16.5 18.8

    Heating power KW B8/W50

    2.2 3.2 4.5 5.3 6.4

    Cooling source flow T/H 1.5 2.3 3.4 3.9 4.5 Cooling flow T/H 1.3 2 2.8 3.3 3.8 DHW water flow T/H 1.5 2.3 3.4 3.9 4.5

    DHW output L/H

    △ ℃35 162 253 349 405 462

    Compressor type scroll scroll scroll scroll scroll

    Compressor qty. pc 1 1 1 1 1

    Refrigerant R407C R407C R407C R407C R407C

    Refrigerant qty. kg 1.6 1.8 2.7 3.2 3.6

    DHW connector 1"F 1"F 1"F 1"F 1"F

    Source/load side

    connector 1-1/4"F 1-1/4"F 1-1/4"F 1-1/4"F 1-1/4"F

    Measure(L*W*H) mm 880*600*1130 880*600*1130 880*600*1130 880*600*1130 880*600*1130

    Weight kg 120 180 190 210 240

    Noise dBA 48 48 48 48 48

    Source temperature

    range for heating ℃ -5 to +25 -5 to +25 -5 to +25 -5 to +25 -5 to +25

    Max. heating

    temperature ℃ 55 55 55 55 55

    Soft starter Built-in Built-in NO NO NO

    Cooling start current

    A 19.5 41 41 49.5 55

    Heating start current

    A 24 45 45 54 60

  • - 24 -

    Cooling running current

    A 7.8 16.4 8.2 9.9 11

    Heating running current

    A 9.6 17.9 9 10.8 12

    Recommendatory breaker

    30(2P) 40(2P) 30(4P) 40(4P) 40(4P)

    Recommendatory power cable

    YCW2*4+1*

    2.5

    YCW2*10+1

    *6

    YCW3*6+1*

    4

    YCW3*6+1*

    4

    YCW3*6+1*

    4

    Power 230V/50HZ/1N 380V/50HZ/3N

    W25/W7 cooling: ground loop inlet temperature is 25 degree, cooling flow temperature is 7 degree. B0/W35 heating: Brine inlet temperature is 0 degree, heating flow temperature is 35 degree.

  • - 25 -

    Performance parameter table (brine to water)

    Item Unit DDR-256GS

    PB2-FP

    DDR-322

    GSPB2-F

    P

    DDR-383

    GSPB2-R

    P

    DDR-442

    GSPB2-R

    P

    DDR-540

    GSPB2-R

    P

    DDR-680GS

    PB2-RP

    Cooling capacity KW

    W25/W7 27.76 33 39.64 44.1 55.52 63.8

    Cooling power KW

    W25/W7 7.3 9.24 11.1 12.3 14.6 17.12

    Heating capacity KW B0/W35

    20.8 28.4 31.5 34.4 41.2 59.4

    Heating power KW B0/W35

    4.8 6.8 7.5 8.3 9.8 14.3

    Heating capacity KW B0/W50

    20.2 27.5 29.6 33.5 40.4 58.2

    Heating power KW B0/W50

    6.8 9.3 10.5 11.6 13.4 20.3

    Heating capacity KW B8/W35

    23.2 31.2 35.1 39.2 45 62.4

    Heating power KW B8/W35

    4.3 6.2 7.5 9.3 10 14.6

    Heating capacity KW B8/W50

    21.2 28.2 32.7 36.2 43.2 57.4

    Heating power KW B8/W50

    6.8 9.2 10.6 11.7 13.6 20.2

    Cooling source flow T/H 5.2 6.5 7.8 8.8 10.5 13.8

    Cooling flow T/H 4.4 5.5 6.6 7.4 8.9 11.7

    DHW water flow T/H 5.2 6.5 3.9 4.4 5.25 6.9

    DHW output L/H

    △ ℃35 521 692 402 445 531 705

    Compressor type scroll scroll scroll scroll scroll Scroll

    Compressor qty. pc 1 2 2 2 2 2

    Refrigerant R407C R407C R407C R407C R407C R407C

    Refrigerant qty. kg 4 2.7*2 3.2*2 3.6*2 4.5*2 5.4*2

    DHW connector 1"F 1"F 1"F 1-1/4"F 1-1/4"F 1-1/4"F

    Source/load side

    connector 1-1/4"F 1-1/4"F 1-1/4"F 2"F 2"F 2"F

    Measure(L*W*H) mm 880*600*1130 1100*800*

    1350

    1100*800*

    1350

    1200*800*

    1420

    1200*800*

    1420 1200*800*1420

    Weight kg 280 300 290 340 400 410

    Noise dBA 48 50 50 50 50 50

    Source temperature

    range for heating ℃ -5 to +25 -5 to +25 -5 to +25 -5 to +25 -5 to +25 -5 to +25

    Max. heating

    temperature ℃ 55 55 55 55 55 55

    Soft starter NO NO NO NO NO NO

    Cooling start current

    A 64 82 99 110 128 147

  • - 26 -

    Heating start current

    A 69.5 90 108 120 139 160

    Cooling running current

    A 12.8 16.4 19.8 22 25.6 29.4

    Heating running current

    A 13.9 18 21.6 24 27.8 32

    Recommendatory breaker

    63(4P) 63(4P) 63(4P) 63(4P) 63(4P) 63(4P)

    Recommendatory power cable

    YCW3*10+1*6

    Power 380V/50HZ/3N

    W25/W7 cooling: ground loop inlet temperature is 25 degree, cooling flow temperature is 7 degree. B0/W35 heating: Brine inlet temperature is 0 degree, heating flow temperature is 35 degree.

  • - 27 -

    (5) ground source heat pump with built-in tank for heating/DHW (brine to water)

  • - 28 -

  • - 29 -

    Performance parameter table (brine to water)

    Item Unit DDR-78G

    SPA2-A

    DDR-112

    GSPA2-A

    DDR-162GS

    PB2-A

    DDR-192GS

    PB2-A

    DDR-221

    GSPB2-A

    DDR-256GS

    PB2-A

    DDR-322GS

    PB2-A

    Heating capacity

    KW B0/W35

    6.4 9.5 14.2 15.9 18.2 20.8 28.4

    Heating power

    KW B0/W35

    1.6 2.3 3.5 3.8 4.2 4.8 6.8

    Heating capacity

    KW B0/W50

    5.6 8.5 13.3 14.8 16.6 20.2 27.5

    Heating power

    KW B0/W50

    2.1 2.9 4.8 5.1 5.8 6.8 9.3

    Heating capacity

    KW B8/W35

    7.3 11.1 15.6 18.2 20.8 23.2 31.2

    Heating power

    KW B8/W35

    1.6 2.3 3.2 3.7 4.6 4.3 6.2

    Heating capacity

    KW B8/W50

    6.6 10.3 14.2 16.5 18.8 21.2 28.2

    Heating power

    KW B8/W50

    2.2 3.2 4.5 5.3 6.4 6.8 9.2

    Auxiliary heater KW 3/6 3/6 3/6 3/6 3/6 3/6 3/6

    Tank L 200 200 200 200 200 200 200

    Brine flow T/H 1 1.5 2.1 2.5 2.8 3.3 4.3 Heating flow T/H 1.3 1.9 2.7 3.1 3.6 4 5.4 Compressor SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL

    Compressor

    qty. Pc 1 1 1 1 1 1 1

    Refrigerant R407C R407C R407C R407C R407C R407C R407C

    Refrigerant qty. kg 1.6 1.8 2.7 3.5 4.0 6.0 7.5

    DHW

    connector 1"F 1"F 1"F 1"F 1"F 1-1/4"F 1-1/4"F

    Brine/heating

    Connector 1"F 1"F 1"F 1"F 1"F 1-1/4"F 1-1/4"F

    Measure(L*W*

    H) mm

    760*940*1400

    Weight kg 165 180 200 230 245 260 270

    Noise dBA 48 48 48 48 48 48 48

    Brine inlet

    range ℃ -5 to +25 -5 to +25 -5 to +25 -5 to +25 -5 to +25 -5 to +25 -5 to +25

    Max. eating

    temperature ℃ 55 55 55 55 55 55 55

    Power 230V/1N/50HZ 380V/3N/50Hz

    B0/W35 heating: Brine inlet temperature is 0 degree, heating flow temperature is 35 degree.

  • - 30 -

    (6) water source heat pump for heating(water to water) (7) water source heat pump for heating/DHW(water to water)

    Water source heat pump technology implements transferring the low-temperature from groundwater

    that absorption of solar energy and geothermal energy, to high-temperature by importing a little of

    electricity. Water source heat pump can supply cooling, heating and domestic hot water.

    DISMY Water source heat pump extracts energy from the heat source medium at a low temperature

    level. This extracted energy is then transferred to the heating water at a higher level, enriched with the

    energy transferred by the compressor. Subject to the heat source temperature, the heating water can

    be heated up to a flow temperature of 55 .℃

    A three-way valve built-in(optional) have been integrated for diverting the flow either to the heating

    circuit or the DHW circuit. DHW is heated by pumping the heating water, which has been heated by

    the heat pump, through a heat exchanger into the DHW cylinder, where it transfers its energy to the

    DHW. DM2066 DHW thermostat can be used to start DHW function instant or by timing.

    DDR series heat pump delivers heat up to a fixed temperature level. This is called “fixed condensing”.

    DDR series heat pump can be docked to an external unit with its own heating controls, for example,

    room thermostat for floor heating system or thermostatic valve for radiator.

  • - 31 -

    Top pipe connection:

    Single heating(DDR-U) Heating/DHW(DDR-UV) Back pipe connection:

    Single heating(DDR-U) Heating/DHW(DDR-UV)

  • - 32 -

    Performance parameter table---- Top pipe connection (water to water) Item Unit

    DDR-78WSPA2-U(UV)

    DDR-112WSPA2-U(UV)

    DDR-162WSPB2-U(UV)

    DDR-192WSPB2-U(UV)

    DDR-221WSPB2-U(UV)

    Heating capacity KW W10/W35 8.2 12.1 17.2 17.2 20.8

    Heating power KW W10/W35 1.6 2.3 3.5 3.5 4.1

    Heating capacity KW W10/W50 6.8 10.2 14.8 14.8 17.7

    Heating power KW W10/W50 2.2 3.28 4.6 4.6 5.3

    water flow T/H 1.1 1.7 2.4 2.9 3.4 Heating flow T/H 1.4 2.1 3 3.6 4.2 Evaporator pressure drop

    Pa 10 10 10 10 10

    Condenser pressure drop

    Pa 10 10 10 10 10

    Compressor SCROLL SCROLL SCROLL SCROLL SCROLL Compressor qty. Pc 1 1 1 1 1 Refrigerant R407C R407C R407C R407C R407C Refrigerant qty. kg 1.6 1.8 2.7 3.2 3.6 DHW connector 1"F 1"F 1"F 1"F 1"F Connector 1-1/4"F 1-1/4"F 1-1/4"F 1-1/4"F 1-1/4"F Recommendatory heating pipe

    DN32 DN32 DN32 DN32 DN40

    Measure(L*W*H) mm 600*600*1300 Weight kg 120 180 185 210 225 Noise dBA 48 48 48 48 48 water inlet range ℃ 7 to +25 7 to +25 7 to +25 7 to +25 7 to +25 water inlet range ℃ -5 to +25 -5 to +25 -5 to +25 -5 to +25 -5 to +25 Max. heating temperature

    ℃ 55 55 55 55 55

    Soft starter Built-in Built-in No No No Recom. breaker 30(2P) 40(2P) 30(4P) 40(4P) 40(4P) Recom. power cable

    YCW2*4+1*2.5

    YCW2*10+1*6

    YCW3*6+1*4

    YCW3*6+1*4

    YCW3*6+1*4

    Power 230V/1N/50Hz 380V/3N/50Hz W10/W35 heating: ground water inlet temperature is 10 degree, heating flow temperature is 35 degree.

  • - 33 -

    Performance parameter table---- Back pipe connection (water to water)

    Item Unit DDR-78WSPA

    2-UB(UV)

    DDR-112WSP

    A2-UB(UV)

    DDR-162WSP

    B2-UB(UV)

    DDR-192WSP

    B2-UB(UV)

    DDR-221WSP

    B2-UB(UV)

    Heating capacity KW W10/W35 8.2 12.1 17.2 17.2 20.8

    Heating power KW W10/W35 1.6 2.3 3.5 3.5 4.1

    Heating capacity KW W10/W50 6.8 10.2 14.8 14.8 17.7

    Heating power KW W10/W50 2.2 3.28 4.6 4.6 5.3

    water flow T/H 1.1 1.7 2.4 2.9 3.4 Heating flow T/H 1.4 2.1 3 3.6 4.2 Evaporator pressure drop

    KPa 10 10 10 10 10

    Condenser pressure drop

    KPa 10 10 10 10 10

    Compressor SCROLL SCROLL SCROLL SCROLL SCROLL Compressor qty. Pc 1 1 1 1 1 Refrigerant R407C R407C R407C R407C R407C Refrigerant qty. kg 1.6 1.8 2.7 3.2 3.6

    DHW connector 1"F 1"F 1"F 1"F 1"F

    Connector 1-1/4"F 1-1/4"F 1-1/4"F 1-1/4"F 1-1/4"F

    Recommendatory heating pipe

    DN32 DN32 DN32 DN32 DN40

    Measure(L*W*H) mm 500*679*900 500*679*900 500*679*900 500*679*900 500*679*900 Weight kg 120 180 185 210 225 Noise dBA 48 48 48 48 48 water inlet range ℃ 7 to +25 7 to +25 7 to +25 7 to +25 7 to +25 Max. heating temperature

    ℃ 55 55 55 55 55

    Soft starter Built-in Built-in No No No Recom. breaker 30(2P) 40(2P) 30(4P) 40(4P) 40(4P) Recom. power cable

    YCW2*4+1*2.5

    YCW2*10+1*6

    YCW3*6+1*4

    YCW3*6+1*4

    YCW3*6+1*4

    Power 230V/1N/50Hz 380V/3N/50Hz W10/W35 heating: ground water inlet temperature is 10 degree, heating flow temperature is 35 degree.

  • - 34 -

    (7) water source heat pump for heating/cooling (water to water)

    Water source heat pump technology implements transferring the low-temperature from groundwater

    that absorption of solar energy and geothermal energy, to high-temperature by importing a little of

    electricity. Water source heat pump can supply cooling, heating and domestic hot water.

    DISMY Water source heat pump extracts energy from the heat source medium at a low temperature

    level. This extracted energy is then transferred to the heating water at a higher level, enriched with the

    energy transferred by the compressor. Subject to the heat source temperature, the heating water can

    be heated up to a flow temperature of 55 .℃

    A three-way valve built-in(optional) have been integrated for diverting the flow either to the heating

    circuit or the DHW circuit. DHW is heated by pumping the heating water, which has been heated by

    the heat pump, through a heat exchanger into the DHW cylinder, where it transfers its energy to the

    DHW. DM2066 DHW thermostat can be used to start DHW function instant or by timing.

    DDR series heat pump delivers heat up to a fixed temperature level. This is called “fixed condensing”.

    DDR series heat pump can be docked to an external unit with its own heating controls, for example,

    room thermostat for floor heating system or thermostatic valve for radiator.

  • - 35 -

    Top pipe connection:

    Back pipe connection:

  • - 36 -

    Performance parameter table---- Top pipe connection (water to water)

    Item Unit DDR-78WSPA

    2

    DDR-112WSP

    A2

    DDR-162WSP

    B2

    DDR-192WSP

    B2

    DDR-221WSP

    B2

    Cooling capacity KW W25/W7

    7.8 11.2 16.2 19.2 22.1

    Cooling power KW W25/W7

    1.4 2.43 2.88 3.4 4.25

    Heating capacity KW W10/W35 8.2 12.1 17.2 17.2 20.8

    Heating power KW W10/W35 1.6 2.3 3.5 3.5 4.1

    Heating capacity KW W10/W50 6.8 10.2 14.8 14.8 17.7

    Heating power KW W10/W50 2.2 3.28 4.6 4.6 5.3

    water flow(cooling) T/H 1.6 2.3 3.3 3.9 4.5 cooling flow T/H 1.3 1.9 2.8 3.3 3.8 Evaporator pressure drop

    Pa 10 10 10 10 10

    Condenser pressure drop

    Pa 10 10 10 10 10

    Compressor SCROLL SCROLL SCROLL SCROLL SCROLL Compressor qty. Pc 1 1 1 1 1 Refrigerant R407C R407C R407C R407C R407C Refrigerant qty. kg 1.6 1.8 2.7 3.2 3.6

    Connector 1-1/4"F 1-1/4"F 1-1/4"F 1-1/4"F 1-1/4"F

    Recommendatory heating pipe

    DN32 DN32 DN32 DN32 DN40

    Measure(L*W*H) mm 600*600*1300 Weight kg 120 180 185 210 225 Noise dBA 48 48 48 48 48 water inlet range ℃ 7 to +25 7 to +25 7 to +25 7 to +25 7 to +25 Max. heating temperature

    ℃ 55 55 55 55 55

    Soft starter Built-in Built-in No No No Recom. breaker 30(2P) 40(2P) 30(4P) 40(4P) 40(4P) Recom. power cable

    YCW2*4+1*2.5

    YCW2*10+1*6

    YCW3*6+1*4

    YCW3*6+1*4

    YCW3*6+1*4

    Power 230V/1N/50Hz 380V/3N/50Hz W25/W7 cooling: ground water inlet temperature is 25 degree, cooling flow temperature is 7 degree. W10/W35 heating: ground water inlet temperature is 10 degree, heating flow temperature is 35 degree.

  • - 37 -

    Performance parameter table---- Back pipe connection (water to water)

    Item Unit DDR-78WSPA

    2-B

    DDR-112WSP

    A2-B

    DDR-162WSP

    B2-B

    DDR-192WSP

    B2-B

    DDR-221WSP

    B2-B

    Cooling capacity KW W25/W7

    7.8 11.2 16.2 19.2 22.1

    Cooling power KW W25/W7

    1.4 2.43 2.88 3.4 4.25

    Heating capacity KW W10/W35 8.2 12.1 17.2 17.2 20.8

    Heating power KW W10/W35 1.6 2.3 3.5 3.5 4.1

    Heating capacity KW W10/W50 6.8 10.2 14.8 14.8 17.7

    Heating power KW W10/W50 2.2 3.28 4.6 4.6 5.3

    water flow(cooling) T/H 1.6 2.3 3.3 3.9 4.5 cooling flow T/H 1.3 1.9 2.8 3.3 3.8 Evaporator pressure drop

    Pa 10 10 10 10 10

    Condenser pressure drop

    Pa 10 10 10 10 10

    Compressor SCROLL SCROLL SCROLL SCROLL SCROLL Compressor qty. Pc 1 1 1 1 1 Refrigerant R407C R407C R407C R407C R407C Refrigerant qty. kg 1.6 1.8 2.7 3.2 3.6

    Connector 1-1/4"F 1-1/4"F 1-1/4"F 1-1/4"F 1-1/4"F

    Recommendatory heating pipe

    DN32 DN32 DN32 DN32 DN40

    Measure(L*W*H) mm 500*679*900 500*679*900 500*679*900 500*679*900 500*679*900 Weight kg 120 180 185 210 225 Noise dBA 48 48 48 48 48 Brine inlet range ℃ 7 to +25 7 to +25 7 to +25 7 to +25 7 to +25 Max. heating temperature

    ℃ 55 55 55 55 55

    Soft starter Built-in Built-in No No No Recom. breaker 30(2P) 40(2P) 30(4P) 40(4P) 40(4P) Recom. power cable

    YCW2*4+1*2.5

    YCW2*10+1*6

    YCW3*6+1*4

    YCW3*6+1*4

    YCW3*6+1*4

    Power 230V/1N/50Hz 380V/3N/50Hz W25/W7 cooling: ground water inlet temperature is 25 degree, cooling flow temperature is 7 degree. W10/W35 heating: ground water inlet temperature is 10 degree, heating flow temperature is 35 degree.

  • - 38 -

    screw compressor ground source heat pump for commercial application

  • - 39 -

  • - 40 -

  • - 41 -