Thermal Dispersion
& Paddle Type Flow Switch
visit our website
1
OPERATING PRINCIPLEThermal dispersion flow switches measure the
velocity of a liquid inside a pipe or channel.
The switch’s probe contains two key components
– a heating sensor and temperature sensor. The
heating sensor is positioned closest to the flowing
liquid and provides a consistent heat. The
temperature sensor measures the temperature
emitted from the heating sensor.
When liquid is flowing, there is a temperature
difference between the two sensors. The
temperature difference has an inverse relationship
with the flow velocity (fast flowing liquids will result
in greater heat differences and vice versa).
Since the device contains no moving parts, has no
wear and tear and maintains a long lifespan.
High sensitivity and accuracy.
Suitable for corrosive and hazardous
conditions.
Able to be calibrated for liquids with different
densities and impurities.
Suitable for complex locations with easy
installation.
Customized probe lengths available.
Three different output signals options.
FEATURES APPLICATIONPetrochemicals, Hydroelectric plants, Shipyard,
HVAC Systems, Steel Industry Food and Beverage,
Pharmaceutical,Optics and Semiconductor Industry,
Cooling pipes flow control
Any pipes carrying liquid where flow measurement
is needed.
PRODUCT INTRODUCTION
2
PRODUCT SPECIFICATIONS
Water: 1~150 cm/s
Oil: 3~300 cm/s
SUS304 / 316L
Approx.10 Sec
G1/2, G1/4, NPT1/2
19 ~ 30Vdc
50mA (max.)
-20 ~ 80BC
Open Collector : NPN / PNPRelay : 1A/30Vdc, 0.3A/125Vac (NO or NC)
(<400mA)
100 bar (max.)
-20 ~ 80BC
Water: 1~150 cm/s
Oil: 3~300 cm/s
Operating temp.
Ambient temp.
Model
Alarm output
Operating pressure
Housing
Protection level
Warm-up time
Connection thread
Operating voltage
Measuring range
Power consumption
Accessory
Drawings
IP67
Water: 1~150 cm/s
Oil: 3~300 cm/s
G1/2, NPT1/2
-20 ~ 80BC
100 bar (max.)
-20 ~ 80BC
SUS304 / 316L
3-wire NPN/PNPPower-brownGrounding-blue Output-black
Approx.15 Sec Approx.15 Sec
Flow velocity below set point- Red LED on, Open
Flow velocity equals set point- Yellow LED on, Close
Flow velocity above set point- 4 Green LED to indicate flow speed, Close
Led indication
Wiring
Gasket, 2m Cable
SP200-Compact model
9-99-9-9 SP201-Extension model
9-99-9-9
f7.4
1/2"PF L=31
HEX38
72.559.5
M12
SP202-High Temp. model
9-99-9-9
40.5
L(Max.200)
HEX38
M12
G 1/2"
f7.4
f16
40.5
31
HEX38
f7.4
M12
G 1/2"
SUS304/ 316/ 316L
-20 ~ 120BC
100 bar (max.)
-20 ~ 80BC
G1/2, G1/4, NPT1/2
3
PRODUCT SPECIFICATIONS
Operating temp.
Ambient temp.
Model
Alarm output
Operating pressure
Housing
Protection level
Warm-up time
Connection thread
Operating voltage
Measuring range
Accessory
Drawings
Flow below set point- Red LED on, Open
Flow velocity equals set point- Yellow LED on, Close
Flow velocity above set point- 4 Green LED to indicate
flow speed, Close
velocity
Led indication
Power consumption
G1/2, NPT1/2
Approx.15 Sec
100 bar (max.)
IP65
PC
19 ~ 30Vdc
50mA (max.)
3-wire NPN/PNPPower-brownGrounding-blue Output-black
Gasket, 2m Cable
Water: 1~150 cm/s
Oil: 3~300 cm/s
-20 ~ 80BC
-20 ~ 80BC
SP220-9-99-9-9 Economy model
Open Collector : NPN / PNP(<400mA)
Relay : 1A/30Vdc, 0.3A/125Vac (NO or NC)
f7.4
30 19.8
L=31
106
40M12
1/2"PF
Footnote Sensitivity and Alarm setting not available.
Wiring
4
PRODUCT SPECIFICATION SEE PAGE ABOVE FOR CORRECTIONS (YELLOW)
SP210modelStainless Steel
Water: 1~150 cm/s
Oil: 3~300 cm/s
SUS304
G1/2, NPT1/2
60mA (max.)
-20 ~ 80BC
Relay: 5A/250Vac
100 bar (max.)
-20 ~ 80BC
IP67
19 ~ 30Vdc
SP170-(½) Explosion Proof model
31
f38
f70
Sight Window
46
PG
32
f7.4G1/2"
78
Operating temp.
Ambient temp.
Model
Alarm output
Operating pressure
HousingHousing
Protection level
Warm-up time
Connection thread
Operating voltage
Wiring
Measuring range
Accessory
Drawings
Approx.15 Sec
5-wire Relay OutputPower- redGrounding- blackCOM- whiteNC- yellowNO- blue
Flow below set point- Red LED on, Open
Flow velocity equals set point- Yellow LED on, Close
Flow velocity above set point- 4 Green LED to indicate
flow speed, Close
velocity
Led indication
Power consumption
Gasket, 2m Cable
SUS304
G1/2, NPT1/2
60mA (max.)
IP67
19 ~ 30Vdc
Approx.15 Sec
Water: 1~150 cm/s
Oil: 3~300 cm/s
-20 ~ 80BC
Relay: 3A/250Vac
100 bar (max.)
-20 ~ 80BC
NC C NOF G
Cert. Number GYJ071446
31
f38
f70
46
32
f7.4G1/2"
78
SUS304 / 316 / 316L
SUS304 / 316 / 316L Wetted material
Fig. 1
4. Screw tightly to avoid. Can be installed from various angles. For best sensitivity and response speed, please install using in the demonstrated in Fig. 4
5. Installing a filter upstream can decrease liquid impurities which can reduce wear and tear on the switch.
a
a
da³4xd
5
INSTALLATION
Fig. 3
Fig. 2
Fig. 4
1. Use the water-proof gasket provided 2. The distance "a" should be 4 times larger
than the switches’ screw diameter. (Fig. 1)3. The pipe is bubble free for proper
functioning. (Fig. 2)4. For not-completely-filled pipes, install from
the bottom. The liquid level needs to be higher than the probe height. (Fig. 3)
INSTALLATION
13
4
2
CWIRING AND CONNECTIONS
ALARMSENSITIVITY
)3
1
4NPN
Fig. 7, NPN output type wiring
Brown
Black
Blue
)
)
Relay
Fig. 9, Relay output type wiring
Blue
Black
Red
WIRING
White
Yellow
COM
NC
NO
)3
1
4PNP
Fig. 8, PNP output type wiring
Blue
Black
Brown
)
)
)1
2
3
NO
Blue
Green
Brown
)
)4 Black)
3-wire
Fig. (NO)10, Relay output type wiring
6
)1
2
3
NC
Blue
Green
Brown
)
)4 Black)
Fig. (NC)11, Relay output type wiring
Fig. 5Wire terminal diagram
(NPN, PNP and 1A relay output type)Fig. 6
5-wire
4-wire
7
HOW TO ORDER
0: SUS304
6: SUS316
L: SUS316L
N: NPN (current limit: 400mA)
P: PNP (current limit: 400mA)
A: Relay 1A/30Vdc (NO)
B: Relay 1A/30Vdc (NC)
C: Relay 5A/250Vac (SPDT) (for SP210/ SP211/ SP212)
0
1 f
(for )
2 ( )
: Compact model
: Stainless Steel model 70X78
SPDT 5A/250Vac
: Economy model Plastic Housing
Cable Wire Length(unit: m)
※ Length tolerance: 65mm
※ Dimensions are subject to change
※ Customized lengths available on request * Max.200mm
Model Description
SP29 9- 9 - 99 - 9- 9 - ( 9999 )
Material
Output
Size Specification
A: 3/8" (10A)B: 1/2" (15A)C: 3/4" (20A)D: 1" (25A)2: 1/4"S: Other
Q: PTT: BSPR: PFU: NPTV: GASS: Other
Connection
Length L (Unit: mm)
2: 2m 5: 5m
0:
1:
2:
Except SP220
Standard
Probe Extension model
120BC High Temperature model
( )
model
Probe Type
S: Other
*Standard connection: 1/2"PF, 1/2"NPT, 1/2"PT
8
※ Length tolerance: 65mm
※ Dimensions are subject to change
※ Customized lengths available on request * Max.200mm
1: SUS304
2: SUS316L
C: SPDT 3A/250Vac
70 ---Explosion Proof Type
SP170- 9 - 99 - 9 - 9999
Size Specification
D: 1" (25A)S: Other
B: 1/2" (15A) Q: PTT: BSPR: PFV: GASU: NPTS: Other
Length L (Unit: mm)
Output
Material
Model Description
( )
HOW TO ORDER
SECTIONAL DRAWINGS
1. O-Ring
2. Paddle
3. Axis
4. Reed switch
5. Spring
6. Magnet
7. Housing
8. Screw
9. Center rod
MODEL: SF1800Standard model
1"1-1/4"
1-1/2"
2"
2-1/2"
3"
2
3 8
49
5
6
1
7
Optional part*
1/2"NPT
Flow Switch can detect liquid movement in pipes. When the liquid is static or nonexistent, the spring is fully extended pulling the magnet downward and opening the switch.As flow occurs and the paddle is thrusted forward 20BC~30 C (or more) the paddle will push the magnet upward and actuate the switch (closing the circuit) The length of paddle can be adjusted to the pipe's diameter.
B
Switch on in case of liquid flowing in pipes
spring
magnet
reed switch
axis
paddleMODEL: SF1710Explosion proof model
*1/2"NPT
80
80
Switch off in case of no moving liquid in pipes
spring
magnet
reed switch
axis
paddle
NEPSI
PADDLE TYPE FLOW SWITCH
9
22
13
22
140
1"PT
HEX38
80
22
13
22
140
25
70
1"PT
HEX38
25
PRINCIPLE
1. The paddle length is dependent on the lowest paddle point to actuate the switch. Cut the pad-dle at appropriate pipe size mark or wherever desired. The minimum is 1".
2. The paddle must be at a right angle to the direc-tion of flow
3. The FLOW mark on the screw must beparallel to the pipe.
4. Before installing the unit to a tee pipe, apply thread seal tape to the screw and then tighten.
1. The pressure and temperature ranges as shown in the catalog, must not be exceeded and also take the abrupt pressure and temperature into consid-erations.
2. Large sudden changes in liquid temperature and density (specific gravity) changes will influence the flow switch accuracy
3. Although highly rigid and durable, shock and vibra-tion should be minimized.
4. Excessive fluid debris might inhibit paddle opera-tion. Occasionally remove switch and clean off any debris.
5. Sealing electrical connections and the connection will reduce moisture damage.
1 Not recommended for 1" or smaller NPT plastic pipes.
CAUTIONINSTALLATION
FLOW CONTROL RANGE TABLE
Flow Volume
GallonMin.
1"
Act. De-Act. Act. De-Act. Act. De-Act. Act. De-Act. Act. De-Act.
1-1/2" 2" 2-1/2" 3"
1"
1-1/4"
1-1/2"
2"
2-1/2"
3"
Paddle Length
(32Max)
ModelSpec.
Housing material
Operation temp.
Wetted material
Operation pressure
Pressure drop allowance
Set point tolerance
Repeatability tolerance
Contact capacity
Aluminum Alloy, Ex d IIC T6~T4
-30BC~100BC
SUS304
Max. 355 PSIG
3 PSIG
K25%
K5%
60W 220Vac/200Vdc, SPDT
Aluminum Alloy, IP 65
-30BC~150BC
SUS304
Max. 355 PSIG
3 PSIG
K25%
K5%
60W 220Vac/200Vdc, SPDT
SF1710 SF1800
10
※1 Gallon=3.7854 Litter
4.7 3.9 10.9 8.3 19.9
31.3 7.7 6.1
5.7 4.5
16.5
13.4
8.4
16.1
12.3
9.5
6.3
25.2
15.1
13.9
22.8
18.5
12.8
10
29.7
20.4
17.1
21.9
15.4
12.8
08-SPSF-B0-EP, 01/29/2013
Distributor:
[SF] Paddle Flow Switch
[FC/FD] Mini Float/Magnetic Float Level Switch
[SD] Optical Level Switch
[FA/FB] Cable Float Level Switch
[FF] Side Mounting Float Switch
[SB] RF-Capacitance / Admittance Level Switch
[SE] Rotary Paddle Level Switch
[SC] Vibrating Probe Level Switch
[SC] Tuning Fork Level Switch
[LR] Loop Power Indicator
[SA] Capacitance Level Switch
[SP] Thermal Dispersion Flow Switch
[EC] Pressure Level Transmitter
[ED] Speed Monitor
[PB/PM] Microprocessor Based Bargraphic Display Scaling Meter
[BRD/AE] Valve and Controller for Dust Collector System
[EB] RF-Capacitance Level Transmitter
[FG] Magnetic Float Level Transmitter
[EG] Magnetostrictive Level Transmitter
[EA] Ultrasonic Level Transmitter
[EF] By-Pass Level Transmitter
[MEF] Mini By-Pass Level Transmitter
[BAS/BAH/BVP] Air Hammer
[BVK/BVR/BVT] Pneumatic Vibrator
[JFR] FMCW Radar Level Transmitter
[EE] Electromechanical Level Measuring System
[SRT/SRS] Conveyer Belt Misalignment Switch &
Safety Cable Pull Switch
TEL: 886 2 2269 6789 FAX: 886 2 2268 6682Email: [email protected] http://www.fine-tek.com
Taichung Branch TEL: 886 4 2337 0825 FAX: 886 4 2337 0836Tainan Branch TEL: 886 6 289 0635 FAX: 886 6 289 4073Kaohsiung Branch TEL: 886 7 333 6968 FAX: 886 7 536 8758
Fine automation (ShangHai) Co., Ltd.No.451 DuHui Rd, MinHang District, Shanghai, China 201109TEL: 86 21 6490 7260 FAX: 86 21 6490 7276Email: [email protected]
FineTek Pte Ltd.No. 60 Kaki Bukit Place, #07-06 Eunos Techpark 2 Lobby B, Singapore 415979TEL: 65 6452 6340 FAX: 65 6734 1878Email: [email protected]
FineTeK GmbHFrankfurter Str. 62, OG D-65428 Ruesselsehim, GermanyTEL: 49 6142 17608 0 FAX: 49 6142 17608 20E-Mail: [email protected]
Aplus Finetek Sensor inc.355 S. Lemon Ave, Suite D, Walnut, CA 91789Tel : 1 909 598 2488 Fax : 1 909 598 3188Email: [email protected]
FineTek Co., Ltd.No.16, Tzuchiang St., Tucheng Industrial Park, New Taipei City 236, Taiwan.
[FA/FB]
[PB]
[EG]
[SF]
[EF]
[JFR] [FC/FD]
[EC]
[FF]
[SA]
[EB]
[EA]
[FG]
[SP]
[SC]
[SB]
[FC/FD] [SD]
[LR]
[EB]
[SE]
[PB/PM]
[EB]
[EE] [EA]
[BAS/BAH/BVP]
[BVK/BVR/BVT]
[EB]
[SA]
[SB]
[SC]
[SC]
[SC] [JFR] [SE]
[SB]