Solution to Power Generation_ Transformer Oil Testing

Embed Size (px)

Citation preview

  • 8/12/2019 Solution to Power Generation_ Transformer Oil Testing

    1/16

  • 8/12/2019 Solution to Power Generation_ Transformer Oil Testing

    2/16

    7/13/2014 Solution to Power Generation: Transformer Oil Testing

    http://www.powervikas.com/2013/01/dga-faults-in-transformer-key-gases-insulating-oil -power-transformer-condition-monitoring-high-voltage-electrical- testing 2

    2. TYPES OF FAULTS IN THE TRANSFORMERFault conditions occur primarily from the thermal and electrical

    deterioration of oil and electrical insulation. Each combustible

    gas level will vary depending upon the fault process.

    2.1 ArcingLarge amounts of hydrogen and acetylene are produced, with

    minor quantities of methane and ethylene. Arcing occurs

    through high current and high temperature conditions. Carbon

    dioxide and carbon monoxide may also be formed if the fault

    involved cellulose. In some instances, the oil may become

    carbonized.

    2.2 CoronaCorona is a low -energy electrical fault. Low-energy electrical

    discharges produce hydrogen and methane, w ith small

    quantities of ethane and ethylene. Comparable amounts of

    carbon monoxide and dioxide may result from discharge incellulose.

    2.3 SparkingSparking occurs as an intermittent high voltage flashover

    without high current. Increased levels of methane and ethane

    are detected w ithout concurrent increases in acetylene,

    ethylene or hydrogen.

    2.4 OverheatingDecomposition products include ethylene and methane,together with smaller quantities of hydrogen and ethane. Traces

    of acetylene may be formed if the fault is severe

    or involves electrical contacts.

    2.5 Overheated CelluloseLarge quantities of carbon dioxide and carbon monoxide are

    evolved from overheated cellulose. Hydrocarbon gases, such as

    methane and ethylene, will be formed if the fault involved an

    oil-impregnated structure.

    2.6 Partial DischargeThe temperature plays a less important role in the chemical

    reaction occurring in the partial discharges since the vapor

    temperature in the discharge zone is not higher than 60-150C.

    Hydrocarbon cracking in the partial discharges occurs as a

    result of excitation of molecules and their subsequent

    dissoc iation by collision w ith high energy electrons, ions,

    atomic hydrogen and also free radicals.

    3. DISSOLVED GAS ANALYSIS (DGA)

    Methods for

    Calculating Short

    Circuit Current of

    Electrical System

    Generator Rotor

    Protection

    Transformer Oil

    Testing

    Boiler Efficiency

    Video Widget

    Power Plant

    Categories

    afbc-boiler

    back-emf

    boilers

    cfbc-boiler

    drum-level-control

    electrical-and-

    instrumentation

    heart

    home

    operation-and-maintenance

    Power Plant

    http://www.powervikas.com/search/label/Power%20stationhttp://www.powervikas.com/search/label/Power%20Planthttp://www.powervikas.com/search/label/operation-and-maintenancehttp://www.powervikas.com/search/label/homehttp://www.powervikas.com/search/label/hearthttp://www.powervikas.com/search/label/electrical-and-instrumentationhttp://www.powervikas.com/search/label/drum-level-controlhttp://www.powervikas.com/search/label/cfbc-boilerhttp://www.powervikas.com/search/label/boilershttp://www.powervikas.com/search/label/back-emfhttp://www.powervikas.com/search/label/afbc-boilerhttp://powervikas.blogspot.com/2012/12/power-plant-heart-of-every-industry.htmlhttp://www.powervikas.com/2013/01/boiler-efficiency-calculation-fuel-fired-system-ido-lpg-bagasse-rfo-combustion-properties-of-fuel-solid-fuels-liquid-fuels-viscosity-gaseous-fuels-combustion-of-carbon-combustion-air-requirement-combustion-testing-flue-gas-analysis-flue-gas-losses-thermal-efficiency.htmlhttp://www.powervikas.com/2013/01/dga-faults-in-transformer-key-gases-insulating-oil-power-transformer-condition-monitoring-high-voltage-electrical-testing-on-site-testing-insulating-oil-analysis-insulation-system-acetylene-hydrogen-ethylene-carbon-monoxide-winding-resistance-insulation-resistance-and-polarisation-index-winding-and-bushing-power-factor-low-voltage-excitation-current-test-transformer-turns-ratio-tap-changer-dynamic-resistance-measurement-Recovery-voltage-measurement-rvm-frequency-response-analysis-fra-interfacial-tension-dissolved-metal-analysis-liquid-power-factor-dielectric-breakdown-strength-moisture-neutralization-number-acidity.htmlhttp://www.powervikas.com/2013/01/generator-rotor-protection-rotor-earth-fault-rotor-overheating-protection-rotor-temperature-alarm-automatic-field-supression-and-use-of-neutral-circuit-breaker.htmlhttp://www.powervikas.com/2013/01/methods-for-calculating-short-circuit-current-of-electrical-system-short-circuit-analysis-overcurrent-protective-devices-ocpd-transformer-fault-current-generator-fault-current.html
  • 8/12/2019 Solution to Power Generation_ Transformer Oil Testing

    3/16

    7/13/2014 Solution to Power Generation: Transformer Oil Testing

    http://www.powervikas.com/2013/01/dga-faults-in-transformer-key-gases-insulating-oil -power-transformer-condition-monitoring-high-voltage-electrical- testing 3

    The DGA analysis is performed in three steps:

    Extraction of all the gases in the oil sample.

    Measurement of the quantity of each gas in the extracted gas.

    Calculation of the concentration of each gas in the oil sample.

    DGA is a pow erful diagnostic and it has capability to detect

    faults in the incipient stage before they develop into major

    faults and cause serious damage to transformer. The

    conventional Bucholtz Relay is universally used in transformer,

    to protect against severe damages. However, the limitations of

    this is that enough gas must be generated first to saturate the

    oil fully & then to come out and collect the relay.

    The DGA technique detects gas in parts per million (ppm)

    dissolved oil by the use of gas extraction unit and

    a gas chromatograph. It checks whether a transformer under

    service is being subjected to a normal aging and

    healthy or whether there are incipient defects such as hot

    spots, arcing, overheating or partial discharge. Such incipient

    faults otherwise remain undetected until they lead to an actual

    major failure.

    The most commonly measured gases are:

    O2 (Oxygen)

    N2 (Nitrogen)

    H2 (Hydrogen)

    CO (Carbon Monoxide)

    CO2 (Carbon Dioxide)

    CH4 (Methane)

    C2H2 (Ethane)

    C2H4 (Ethylene) and

    C2H2 (Acetylene)

    Other extracted gases are sometimes analyzed, such as C3H8,

    C3H6, and C3H4 to refine a diagnostic. However this approach

    is not w idely used. A high degree of success has been achieved

    in the area of determining a link betw een:

    Ratios of common fault gas concentration and specific fault

    types:

    The evolution of individual fault gases and the nature and

    severity of the transformer fault.

    4. INTERPRETATIONS OF DGA RESULTS ANDDIAGNOSTICS METHODS.There are many techniques of incipient fault diagnosis Review

    of the most commonly used gas-inoil diagnostic method is IEEE

    C57.104-1991. This method covers not only the determinations

    Pow er station

    products

    steam-turbine

    thermal-effiency

    Thermal-Pow er-Station

    transformer

    Blog Archive

    2013

    ( 26 )

    May

    ( 1 )

    March

    ( 2 )

    January

    ( 23 )

    Atmospheric Fluidised

    Bed Combustion

    Boilers

    Alignment

    Earthing Procedure in

    Power Plants

    Restricted Earth Fault

    Protection

    Transformer Oil Testing

    Methods for Calculating

    http://www.powervikas.com/2013/01/methods-for-calculating-short-circuit-current-of-electrical-system-short-circuit-analysis-overcurrent-protective-devices-ocpd-transformer-fault-current-generator-fault-current.htmlhttp://www.powervikas.com/2013/01/dga-faults-in-transformer-key-gases-insulating-oil-power-transformer-condition-monitoring-high-voltage-electrical-testing-on-site-testing-insulating-oil-analysis-insulation-system-acetylene-hydrogen-ethylene-carbon-monoxide-winding-resistance-insulation-resistance-and-polarisation-index-winding-and-bushing-power-factor-low-voltage-excitation-current-test-transformer-turns-ratio-tap-changer-dynamic-resistance-measurement-Recovery-voltage-measurement-rvm-frequency-response-analysis-fra-interfacial-tension-dissolved-metal-analysis-liquid-power-factor-dielectric-breakdown-strength-moisture-neutralization-number-acidity.htmlhttp://www.powervikas.com/2013/01/restricted-earth-fault-protection-of-transformer-ref-protection-schemetic-drawing-basic-operation.htmlhttp://www.powervikas.com/2013/01/earthing-procedure-in-power-plants-how-earthing-is-done-methods-of-earthing-earthing-to-water-main-pipe-earthing-plate-earthing.htmlhttp://www.powervikas.com/2013/01/motor-and-pump-alignment-problems-of-misalignment-method-of-alignment-face-and-rim-method-the-shaft-coupling-method--c-and-d-adapter-laser-method-moving-pump-driver-shims.htmlhttp://www.powervikas.com/2013/01/atmospheric-fluidised-bed-combustion-afbc-deming-cycle-pcda-cycle-mechanism-of-fluidised-bed-cobustion-time-temperature-turbulence-types-of-fludize-bed-combustion-boilers-bubbling-bed-general-arrangement-of-afbc-boiler-air-distributor-bed-and-bed-heat-transfer-surface-ash-handling-system-fuel-feeding-system-under-bed-feeding-over-bed-feeding-heat-transfer-surface-bed-temperature-bed-pressure-superficial-gas-velocity-bottom-ash-removal-fly-ash-removal.htmlhttp://www.powervikas.com/2013_01_01_archive.htmlhttp://void%280%29/http://www.powervikas.com/2013_03_01_archive.htmlhttp://void%280%29/http://www.powervikas.com/2013_05_01_archive.htmlhttp://void%280%29/http://www.powervikas.com/search?updated-min=2013-01-01T00:00:00%2B05:30&updated-max=2014-01-01T00:00:00%2B05:30&max-results=26http://void%280%29/http://www.powervikas.com/search/label/transformerhttp://www.powervikas.com/search/label/Thermal-Power-Stationhttp://www.powervikas.com/search/label/thermal-effiencyhttp://www.powervikas.com/search/label/steam-turbinehttp://www.powervikas.com/search/label/productshttp://www.powervikas.com/search/label/Power%20station
  • 8/12/2019 Solution to Power Generation_ Transformer Oil Testing

    4/16

    7/13/2014 Solution to Power Generation: Transformer Oil Testing

    http://www.powervikas.com/2013/01/dga-faults-in-transformer-key-gases-insulating-oil-power-transformer-condition-monitorin g-high-voltage-electrical-testing 4

    of the fault severity and its nature, but also offers some

    suggestions regarding the follow up actions to be taken.

    It is the only method that covers both the gases dissolved in oil

    and the gas present in the nitrogen cover of sealed type

    transformers. The method proceeds as follow s:

    Calculate the total of dissolved combustible gases (TDCG):

    TDCG = H2 + CO + CH4+ C2H6 + C2H4 +C2H2

    Classify the condition of the transformer according to the limits

    for each gas for the total of combustible gases.

    Evaluate the rate of increase of combustible gases in ppm/day.

    Determine what actions should be taken according to the level

    of combustible gases and their rates of increase. This method

    defines four possible transformer conditions:

    1) TDCG < 720 PPM : Operating satisfactorily

    2) TDCG = 721 to 1920 PPM: Faults may be present

    3) TDCG = 1921 to 4630 PPM: Faults are probably present

    4) TDCG > 4630 PPM: Continued operations could result in

    failure.

    These conditions are also determined accordingly to individual

    gas levels. If any one of the gases exceeds a

    given level (Refer Table-1) the transformer is classified

    accordingly

    4.1 Gas Content in Oil Due to Fault

    Short Circuit Current

    of E...

    Variable Frequency

    Drives

    Generator and

    Transformer

    Protection

    Generator Over Heaing

    Protection

    Generator Inter turn

    fault protection

    Differential Protection

    for Gnerators

    Generator Rotor

    Protection

    Boiler Efficiency

    Products

    Drum Level Control

    CFBC Boiler

    Water Chemistry

    Electrical Sw itches

    Coal Analysis in Power

    Plants

    Parallel Operation of

    Transformer

    Erection &

    Commissioning of

    Transformer

    Electric Motors

    Thermal Power Station

    http://www.powervikas.com/2013/01/methods-for-calculating-short-circuit-current-of-electrical-system-short-circuit-analysis-overcurrent-protective-devices-ocpd-transformer-fault-current-generator-fault-current.htmlhttp://void%280%29/http://www.powervikas.com/2013/01/thermal-power-station-power-plant-steam-turbine-electrical-generator-Rankine-cycle-coal-fossil-fueled-plants-combined-heat-and-power-CH-and-P-plants-co-generation-plants-energy-efficiency-of-thermal-power-station-laws-of-thermodynamics-cooling-towers-electricity-cost-boiler-and-steam-cycle-furnace-esp-feed-water-heating-and-deaeration-conductivity-water-deaerator.htmlhttp://www.powervikas.com/2012/12/synchronous-motors-asynchronous-motors-squirrel-cage-induction-motors-slip-ring-motors-commutator-motors-single-phase-induction-motors-three-phase-induction-motors-variable-speed-motors.htmlhttp://www.powervikas.com/2013/01/what-is-the-parallel-operation-of-transformer-importance-of-phase-sequece-phase-rotation-fault-mva-calculation-transformer-installation-and-commissioning-daily-check-list-of-transformer-overhauling-of-transformer-site-preperation-for-transformer-installation-transformer-oil-oil-filling-under-vacuum-buchhloz-relay-earthing-terminals-cable-boxes-silicagel-breater-magbetic-oil-level-indicator-radiators-marchalling-box-oil-temperature-indicator-oti-winding-temperature-indicator-wti-bushings-explosion-vent-dielectric-strength-test-of-oil-lifting-lugs-jacking-pads-rollersconservator-tap-changer.htmlhttp://www.powervikas.com/2013/01/Same-phase-sequence-parallel-operation-of-transformers-same-voltage-ratio-Same-percentage-impedance-Same-polarity-Why-parallel-operation-of-transformers-is-required.htmlhttp://www.powervikas.com/2013/01/coal-properties-what-is-coal-analysis-in-power-plants-grade-of-coal-calorific-value-range-physical-properties-chemical-properties-analysis-of-coal-measurement-of-moisture-volatile-matter-carbon-and-ash-proximate-analysis-fixed-carbon-sulphur-content-ultimate-analysis.htmlhttp://www.powervikas.com/2013/01/mcb-mccb-elcbair-circuit-breaker-vacuum-circuit-breaker-rcd-residual-current-device-rccb-residual-current-circuit-breaker-elcb-earth-leakage-circuit-breaker-rcbo-residual-circuit-breaker-with-over-load-mcb-selection-difference-between-elcb-and-rccb-fuse-and-mcb-characteristics-why-fuses-can-sometimes-blow-for-no-obvious-reason.htmlhttp://www.powervikas.com/2013/01/Why-chemical-treatment-of-boiler-is-required-boiler-scale-boiler-efficiency-boiler-leakage-and-scalling-treatment-what-cause-the-high-alkalinities-cause-caustic-embrittlement-What-happens-to-all-the-mud-and-clay-build-up-Why-should-we-care-for-steam-purity-Why-feedwater-pump-fail-due-to-excessive-corrosion-What-tests-should-be-performed-on-condensate-system-Why-are-condensate-pipes-leaking-or-excessively-corroding-What-is-boiler-carryover-Why-it-is-required-to-feed-a-polymer-or-phosphate-to-boiler-What-is-boiler-blowdown-How-much-blowdown-is-required-for-boiler-What-is-a-Deaerator-How-to-improve-poor-boiler-steam-fuel-ratio-and-increase-boiler-efficiency-How-to-reduce-soot-formation-and-deposition-how-to-reduce-blow-down-rate-corrosion-problem-in-the-pressure-parts-on-F.W.-circuit-What-are-the-symptoms-of-caustic-attack-What-are-symptoms-of-Oxygen-pitting-causes-of-Oxygen-pitting-What-are-the-causes-of-acid-attack-What-are-the-symptoms-of-Stress-corrosion-cracking-What-are-causes-of-water-side-corrosion-fatigue-What-are-the-symptoms-of-Super-heater-Fireside-Ash-Corrosion-What-are-the-symptoms-of-erosion-What-are-the-causes-of-erosion-What-are-the-causes-of-mechanical-fatigue-Explain-the-common-metallurgical-problems-occur-in-the-boiler-.htmlhttp://www.powervikas.com/2013/01/boilers-cfbc-boiler-circulating-fluidised-bed-combustion-.htmlhttp://www.powervikas.com/2013/01/boiler-drum-level-control-single-element-control-feedback-control-two-element-control-cascade-control-three-element-control-cascade-feedforward-control-low-load-operation-of-boiler-and-drum-level-control.htmlhttp://www.powervikas.com/2013/01/products.htmlhttp://www.powervikas.com/2013/01/boiler-efficiency-calculation-fuel-fired-system-ido-lpg-bagasse-rfo-combustion-properties-of-fuel-solid-fuels-liquid-fuels-viscosity-gaseous-fuels-combustion-of-carbon-combustion-air-requirement-combustion-testing-flue-gas-analysis-flue-gas-losses-thermal-efficiency.htmlhttp://www.powervikas.com/2013/01/generator-rotor-protection-rotor-earth-fault-rotor-overheating-protection-rotor-temperature-alarm-automatic-field-supression-and-use-of-neutral-circuit-breaker.htmlhttp://www.powervikas.com/2013/01/differential-protection-of-generator-limitation-of-this-method-modified-differential-protection-biased-circulating-current-protection-percentage-differential-relay-protection-advantage-of-this-method.htmlhttp://www.powervikas.com/2013/01/generator-protection-stator-inter-turn-fault-protection.htmlhttp://www.powervikas.com/2013/01/generator-protection-over-heating-high-temperature.htmlhttp://www.powervikas.com/2013/01/generator-differential-protection-87-generator-transformer-differential-protection-generator-stator-earth-fault-64-generator-stator-inter-turn-fault-generator-rotor-earth-fault-protection-generator-field-failure-protection-generator-backup-protection-generator-negative-phase-sequence-protection-generator-under-power-anti-protection-generator-overload-protection-generator-over-voltage-protection-generator-field-failure-protection-lockout-relay.htmlhttp://www.powervikas.com/2013/01/electrical-and-instrumentataion-variable-frequency-drive-vfds-vfd-operation-benifits-ofvfd-energy-saving-low-motor-starting-current-reduction-of-mechanical-and-thermal-stress-on-motors-and-belts-during-starts-high-power-factor-simple-installation-lower-kva-mechanical-power-control-low-inrush-motor-starting-soft-starters-harmonics-definition-what-causes-harmonics-are-harmonics-harmful.htmlhttp://www.powervikas.com/2013/01/methods-for-calculating-short-circuit-current-of-electrical-system-short-circuit-analysis-overcurrent-protective-devices-ocpd-transformer-fault-current-generator-fault-current.htmlhttp://2.bp.blogspot.com/-FqhrDBYMtPw/UQa-A2Isz4I/AAAAAAAAAUk/7j78KW3Ch-4/s1600/dga4.JPG
  • 8/12/2019 Solution to Power Generation_ Transformer Oil Testing

    5/16

    7/13/2014 Solution to Power Generation: Transformer Oil Testing

    http://www.powervikas.com/2013/01/dga-faults-in-transformer-key-gases-insulating-oil -power-transformer-condition-monitoring-high-voltage-electrical- testing 5

    Continuous Monitoring of Key Fault Gases(H2 AND CO)

    Key Gas method becomes applicable to transformer w ith

    developed faults w here absolute values of key gases are

    considered. The key gases are acetylene, hydrogen, ethylene

    and carbon monoxide.

    Follow ing table illustrates the nature of faults, when key gas is

    abnormally high.

    KEY GAS NATURE OF FAULT

    Acetylene C2H2 =Electrical arc in oil

    Hydrogen H2 = Corona , partial discharge

    Ethylene C2H4 = Thermal degradation of oil

    Carbon Monoxide = Thermal ageing of oil

    Various Types of Faults Depending on theGas Composition

    2012

    ( 5 )

    Powered by Blogger.

    Home

    Products

    Techical

    Contact Us

    Join us Free

    Feedback

    Advertise w ith Us

    http://powervikash.somee.com/advertise_with_us.aspxhttp://powervikas.somee.com/feed_back.aspxhttp://powervikas.somee.com/join_us.aspxhttp://www.powervikas.com/p/contact-us.htmlhttp://www.powervikas.com/p/blog-page.htmlhttp://www.powervikas.com/p/products.htmlhttp://www.powervikas.com/http://www.blogger.com/http://www.powervikas.com/search?updated-min=2012-01-01T00:00:00%2B05:30&updated-max=2013-01-01T00:00:00%2B05:30&max-results=5http://2.bp.blogspot.com/-qNsWUduVDYk/UQa-FKGeb0I/AAAAAAAAAUs/xAzLxXnGKDM/s1600/dga3.JPGhttp://4.bp.blogspot.com/-jAQ31QgGIuw/UQa-IIkj9RI/AAAAAAAAAU8/h_P9aROv1fk/s1600/dga5.JPG
  • 8/12/2019 Solution to Power Generation_ Transformer Oil Testing

    6/16

    7/13/2014 Solution to Power Generation: Transformer Oil Testing

    http://www.powervikas.com/2013/01/dga-faults-in-transformer-key-gases-insulating-oil -power-transformer-condition-monitoring-high-voltage-electrical- testing 6

    ELECTRICAL TESTS

    Preventive maintenance testing of in-service transformers has

    the primary objective of monitoring conditions in the insulation

    and evaluating the useful life still available in the transformer

    tested.

    Winding ResistanceThe w inding resistance is measured in the field to identify

    shorted turns (although this is better identified in the ratio test),

    poor joints, high resistance connections or contacts and open

    circuits. The resistance is measured on all taps of a tapped

    winding to ensure that the OLTC dose not open circuit during

    the tap changing operation.

    Insulation Resistance and PolarisationIndexThe perfect dielectric can be represented, at pow er frequencies,

    as a lumped prefect capacitance. The application of a direct

    electric field to this capac itance w ill results in a charging

    current flow ing for a short time giving the capac itor sufficient

    charge to support a voltage of V= Q/C. The time taken for the

    capacitance to achieve this equilibrium will be determined by

    the supply source resistance.

    In practical dielectrics the charging current does not cease after

    this short period but decreases gradually to a minimum value.

    The taken for this minimum value to be reached depends upon

    the dielectric and can range from seconds to days. The

    insulation resistance is defined from Ohms Law as the ratio of

    http://1.bp.blogspot.com/-Q4X_9qoa2v8/UQa-Gr8g8QI/AAAAAAAAAU0/KRAUHUnSJk4/s1600/dga6.JPG
  • 8/12/2019 Solution to Power Generation_ Transformer Oil Testing

    7/16

    7/13/2014 Solution to Power Generation: Transformer Oil Testing

    http://www.powervikas.com/2013/01/dga-faults-in-transformer-key-gases-insulating-oil -power-transformer-condition-monitoring-high-voltage-electrical- testing 7

    the applied voltage to this residual current.

    In practical applications the charging current can consist of

    volume and surface currents. Therefore the insulation resistance

    measurement of plant w ill be affected by the condition of the

    insulation itself and the cleanliness of the insulation surfaces.

    This effect can be allowed for in some plant types by the use of

    guarding electrodes.

    The time dependency of the insulation resistance can result

    from electronic and ionic conductivity, dipole orientation

    (dielectric absorption), and space charge polarisation. As the

    charging current time constants are affected by the presence of

    impurities, the time taken for the leakage current to settle dow n

    can be used as an insulation condition indicator. The ratio of

    the insulation resistance value take ten minutes after

    application of the measurement voltage to that taken one

    minute after voltage application is known as the Polarisation

    Index. Generally insulation in good (dry) condition has a PI

    greater than 1.2.

    Winding and Bushing Power FactorOne of the major tests performed in the field is the

    measurement of the w inding and bushing capac itance and

    pow er factor.

    Capacitance measurements of each of the w indings to ground

    and betw een w indings is performed to provide an indication of

    the condition of the w inding insulation and some indication of

    the structural integrity o f the w indings. Similar measurements

    are performed on the bushings to provide an indication of the

    condition of the insulation in the condenser bushing and of the

    pow er factor test points.

    As described above, the perfect dielectric can be represented

    as a lumped perfect capacitance. The charging current flow ing

    in the capac itance w hen an AC filed is applied should lead the

    applied voltage by 90. In practical insulating systems losses

    (caused by conduction and polarisation currents) cause the

    current to lead the voltage by less than 90. The complement of

    the angel betw een the voltage and current vec tors is called the

    dielectric loss of the angle or DLA. The tangent of this angle,

    tan , provides an indication of the losses in the insulation and

    is know n as the POWER FACTOR or DIELECTRIC DISSIPATION

    FACTOR (DDF).

    The power factor of the w indings and the bushings is usually

    measured in the field as a condition assessment tool. The

  • 8/12/2019 Solution to Power Generation_ Transformer Oil Testing

    8/16

    7/13/2014 Solution to Power Generation: Transformer Oil Testing

    http://www.powervikas.com/2013/01/dga-faults-in-transformer-key-gases-insulating-oil -power-transformer-condition-monitoring-high-voltage-electrical- testing 8

    pow er factor can give an indication of the moisture content of

    the paper and oil in the transformer and the bushings. Major

    deterioration of the insulation w ill also be detected.

    Low Voltage Excitation Current TestThe low voltage excitation test is performed to identify shorted

    turns or severe core damage. This method is a natural extension

    of the pow er factor test and makes use of the same equipment.

    The test results of a three-phase core form transformer w ill give

    a pattern of tw o similar currents and one lower current. This is

    usually the H2 phase of the transformer as the magnetic

    reluctance of this phase is low er than the other tw o phases

    resulting in a low er excitation current value.

    Transformer Turns RatioThe ratio of the transformer is normally measured at

    commissioning or after major refurbishment. The test is also

    performed to identify incipient faults or after a transformer fault

    trip to identify shorted turns. A turns ratio measurement can

    show that a fault exists but does not determine the exact

    locat ion of the fault.

    Tap Changer Dynamic ResistanceMeasurementThe dynamic resistance measurement detects carbonized spots

    and weak contacts in the mechanism of a tap changer. The

    advantage of this diagnostics is that not only end positions of

    the tap changer contacts can be checked but the complete

    stroke of contact movement while changing between taps. This

    also allow s one to diagnose the diverter switch in the tap

    changer mechanism.

    New Condition Monitoring ToolsMoisture, in conjunction w ith the other factors, acts on the

    paper insulation reducing the papers strength and volume. This

    reduces the papers, and the transformers, ability to perform its

    function. Therefore two new s tests have been introduced to

    determine the moisture content in the cellulose accurately and

    movement of the w inding structure respectively.

    Recovery Voltage Measurement (RVM)One of the critical measures of transformer condition is the

    moisture content of the paper insulation. It is well know n that

    an increase in the paper moisture content w ill result in a

    corresponding increase in the transformer ageing rate.

    One method of determining the moisture content of paper is to

    use equilibrium diagrams that relate oil/water content, sample

    temperature and paper moisture content. How ever, as

  • 8/12/2019 Solution to Power Generation_ Transformer Oil Testing

    9/16

    7/13/2014 Solution to Power Generation: Transformer Oil Testing

    http://www.powervikas.com/2013/01/dga-faults-in-transformer-key-gases-insulating-oil -power-transformer-condition-monitoring-high-voltage-electrical- testing 9

    transformers in the field are rarely in equilibrium, this method

    has varying degrees of accuracy.

    A second method of determining the paper moisture content is

    to drain oil and take an a paper sample from the insulation. This

    method is more accurate, but costly and exposes the

    transformer to the atmosphere and the possibility of moisture

    ingress. RVM provides an indication of the paper moisture

    content without the drawbacks of the above two methods.

    RVM is non-intrusive and has proven to be accurate w hen

    compared to know n paper moisture contents in oil test cells.

    Moisture and the decay products from insulation degradation

    are polar in nature. When an electric field is applied to a

    dielectric containing polar contaminants, the polar products

    become aligned w ith the electric field. If the levels of these

    contaminants increase, the time required for the dipoles to align

    with the applied field is reduced. This is equivalent to a

    reduction in the system time constant. The RVM determines the

    equivalent paper moisture content by measuring the time

    constant of the insulation system. Instrumentation software

    calculates the equivalent paper moisture content from the

    system time constant and temperature.

    Frequency Response Analysis (FRA)The conventional techniques of ratio, resistance, DDF and even

    HV testing are often unable to detec t w inding deformation,

    except in the most serious of cases. Any changes in the spatial

    position of the w inding structrue will result in relative changes

    to the internal inductive and capac itive network of the winding

    structure w hich produce changes in the frequency response of

    the transformer.

    FRA measures the frequency response of the transformer

    windings up to 10 MHz. This method involves injecting a low

    voltage signal of varying frequency into each end of the

    winding and measuring the response at the other end of the

    winding.

    The transformer under test is always disconnected from

    adjacent equipment. This is done to eliminate the effect of

    connect ing equipment although it is reported that short lengths

    of busbar are not usually a problem. Winding movement is more

    likely to occur in older, aged transformers that have reduced

    winding c lamping pressure. This is particularly true when the

    transformer is placed under a high mechanical load such as

    experienced during fault conditions.

    The advantage of obtaining a baseline signature of the

    transformer is that future tests w ill be able to determine the

    extent of any w inding distortion that occurs after the

    measurement has been taken. This test is particularly valuable

  • 8/12/2019 Solution to Power Generation_ Transformer Oil Testing

    10/16

    7/13/2014 Solution to Power Generation: Transformer Oil Testing

    http://www.powervikas.com/2013/01/dga-faults-in-transformer-key-gases-insulating-oil -power-transformer-condition-monitoring-high-voltage-electrical- testin 10

    as a baseline reference for a new transformer prior to placing in

    service as w ell as for older transformer after re-refurbishment.

    A spectrum analyzer is used to excite, monitor and record the

    response from the transformer. A softw are program downloads

    the recorded data to a PC for analysis. Results for each phase

    are then plotted against frequency. Each w inding is tested

    separately. To ensure repeatable measurements, all other

    windings in the transformer are left floating. The test tap

    position selected to ensure that the maximum amount of

    w inding is included in each measurement.

    INSULATING OIL ANALYSISA regular program of oil testing is recommended to monitor for

    changes in oil quality. Specialized tests are also performed that

    identify specific compounds in the oil and helps determine

    whether fault conditions exist inside the unit. The recommended

    battery of tests include the follow ing:

    Liquid pow er factor at 25o and 100o C

    Dielectric breakdown strength

    Moisture

    Neutralization number(Acidity)

    Interfacial tension

    Color/Visual Examination

    Sludge/Sediment

    Inhibitor

    Dissolved gas analysis

    Dissolved metal analysis

    Furanic compounds

    Liquid Power FactorThe IEC standard method for this test is IEC 247. This involves

    measuring the pow er loss through a thin film of the liquid being

    testing.

    Water, contamination, and the decay products of oil oxidation

    tend to increase the pow er factor of the oil. New oil has very

    low pow er factor values much less than 0.1% at 25o C and

    1.0% at 90o C. As the oil ages and moisture accumulates, or ifthe unit is contaminated, the liquid pow er factor tends to

    increase. This increase in liquid pow er factor is a direct

    indication that materials harmful to the paper and to the

    continued operation of the transformer are building up.

    Many transformer ow ners make the mistake of having this test

    run at only one temperature. While the 90o C test is more

    sensitive, both temperatures need to be used. The relationship

    between the 25o and 90o values can help in making a

  • 8/12/2019 Solution to Power Generation_ Transformer Oil Testing

    11/16

    7/13/2014 Solution to Power Generation: Transformer Oil Testing

    http://www.powervikas.com/2013/01/dga-faults-in-transformer-key-gases-insulating-oil -power-transformer-condition-monitoring-high-voltage-electrical- testin 1

    diagnosis as to w hether the problem is moisture, oxidation, or

    contamination.

    Dielectric Breakdown StrengthThe dielectric breakdow n voltage is a measure of the ability of

    oil to w ithstand electric stress. Dry and clean oil exhibit an

    inherently high breakdown voltage. Free w ater and solid

    particles, the latter particularly in combination with high levels

    of dissolved w ater, tend to migrate to regions of high electric

    stress and reduce the breakdow n voltage dramatically. The

    measurement of breakdow n voltage, therefore, serves primarily

    to indicate the presence of contaminants such as water or

    conducting particles. A low breakdow n voltage value can

    indicate that one or more of these are present. How ever, a high

    breakdown voltage does not necessarily indicate the absence

    of all contaminants. This test is performed in accordance w ith

    IEC 156.

    MoistureThe purpose for which the dielectric tests were invented monitoring moisture content can be done directly. IEC 733 is

    well established and can measure moisture down to low parts

    per million levels.

    While acceptable values have been established by voltage class

    for moisture (less than or equal to 30 ppm for voltages up to

    145 kV, 20 ppm for voltages above 145 kV as used by TNBT),

    these are somewhat misleading. A truer picture of moisture in

    the transformer must take the sampling temperature into

    account so that % saturation of the oil by moisture and %

    moisture by dry w eight of the solid insulation can be

    calculated. A transformer at 20o C that has 20 ppm moisture in

    the oil is considerably wetter than a similar unit, w ith a similar

    20 ppm moisture, but that is operating at 40o C. A new

    transformer should be less than 0.5% moisture by dry w eight.

    Anything over 3.0% (or 30% saturation) is considered extremely

    wet. Most owners dehydrate transformers w hen the moisture

    level exceeds 1.5 to 2.0% moisture by dry w eight.

    Neutralization Number (Acidity)This value, measured by IEC standard method IEC 1125Areported as mg KOH/g sample, reports the relative amount of a

    number of oil oxidation products, primarily acids, alcohols and

    soaps. As the oil continues to oxidize, acid number increases

    gradually, generally over a period of years. Running the acid

    number regularly provides guidance as to how far oxidation of

    the oil has proceeded. Th acceptable limit is test is usually used

    as a general guide for determining w hen an oil should be

    replaced or reclaimed.

  • 8/12/2019 Solution to Power Generation_ Transformer Oil Testing

    12/16

    7/13/2014 Solution to Power Generation: Transformer Oil Testing

    http://www.powervikas.com/2013/01/dga-faults-in-transformer-key-gases-insulating-oil -power-transformer-condition-monitoring-high-voltage-electrical- testin 12

    Acceptable values for acid number are 0.20 and low er.

    Unacceptable values are over 0.20. These are the values used

    by TNBT. How ever, there are countries that use values that are

    even as low as 0.05. The are reasons why. First of all, if one

    examines paper from a 0.05 acid number transformer, it is

    readily apparent that even at this low acid number value that

    decay products are depositing in and damaging the paper

    fibers. Once the damage starts, the life of the insulation is

    compromised. Second, between 0.05 and 0.10, visible sludge

    will start to form in operating transformers.

    The short answer is that the questionable range of 0.05 to 0.10

    is where the oil starts to lose its effectiveness w ith respect to

    one or more of the functions that it is supposed to fulfill.

    Studies have been performed that indicate that the paper w ill

    lose 75-80% of its strength (and therefore be at the end of its

    effective life) before the acid number reaches 0.40 mg KOH/ g

    sample a value that some still consider to be below the value

    where the oil needs to be serviced.

    Interfacial TensionThe test method for interfacial tension (IFT), IEC 6295, measures

    the strength in mN/m of an interface that w ill form betw een

    service aged oil and distilled w ater. Because decay products of

    oil oxidation are both oil and w ater soluble, their presence w ill

    tend to weaken the interface and depress the interfacial tension

    value. Brand new oil is frequently 40-50 mN/m. An acceptable

    value for in-service oil is greater than 25 mN/m or greater;

    unacceptable results are below 28 mN/m.

    Color/VisualField examination of insulating liquids (IEC 296) includes

    examination for presence of cloudiness or sediment and general

    appearance as w ell as a color examination. As oil ages, it will

    darken gradually. Very dark oils or oils that change drastically

    over a short period of time may indicate problems. Any

    cloudiness or sediment indicates the presence of free w ater or

    particles that may be detrimental to continued operation of the

    equipment. Taken alone, without consideration of past history

    or other test parameters, color is not very important fordiagnosing transformer problems. If the oil has an acrid or

    unusual odour, consideration should be given to carrying out

    further tests.

    Sludge/SedimentThe test in IEC 296 distinguishes betw een sediment and sludge.

    Sediment is insoluble material present in the oil. Sediment may

    consist of insoluble oxidation or degradation products of solid

    or liquid materials, solid products such as carbon or metallic

  • 8/12/2019 Solution to Power Generation_ Transformer Oil Testing

    13/16

    7/13/2014 Solution to Power Generation: Transformer Oil Testing

    http://www.powervikas.com/2013/01/dga-faults-in-transformer-key-gases-insulating-oil -power-transformer-condition-monitoring-high-voltage-electrical- testin 13

    oxides and fibres or other foreign matter.

    Sludge is polymerized oxidation products of solid and liquid

    insulating material. Sludge is soluble in oil up to a certain limit.

    At sludge levels above this, the sludge comes out of the

    solution contributing an additional component to the sediment.

    The presence of sludge and sediment may change the electrical

    properties of the oil and hinder heat exchange, thus

    encouraging deterioration of the insulating materials.

    Inhibitor ContentInhibited oil deteriorates more slow ly than uninhibited oil so

    long as active oxidation inhibitor is present. However, once the

    oxidation inhibitors are consumed, the oil may oxidise at a

    greater rate. The determination of residual oxidation inhibitor in

    in-service transformer oil is carried as per IEC 666.

    Dissolved Metals AnalysisDissolved metals analysis (in particular, for three metals: iron,

    copper, and aluminum) can be of use in further identifying the

    location of transformer faults discovered by dissolved gas

    analysis. For example, dissolved metals analysis indicating the

    presences of conductor metals may indicate a fault is occurring

    in the w inding or at a connection w hile the presence of iron

    indicates involvement of the core steel.

    Furanic CompoundsWhen paper breaks dow n, the cellulose chains are broken and

    glucose molecules (which serve as the building blocks of the

    cellulose) are chemically changed. Each of the glucose monomermolecules that are removed from the polymer chain becomes

    one of a series of related compounds called furans or furanic

    compounds. Because these furanic compounds are partially

    soluble in oil, they are present in both the oil and the paper.

    Measuring the concentration in the oil can tell us quite a bit

    about the condition of the paper.

    The standard method typically tests for five compounds that

    are normally only present in the oil as a result of the paper

    breaking dow n. Those five compounds, and their probable

    causes, are:5-hydroxymethyl-2-furaldehyde (5H2F), typically formed by

    oxidation of paper.

    2-furyl alcohol (2FOL), typically formed in connection with a

    high moisture content.

    2-furaldehyde (2FAL), very common, formed by all overheating

    and aging conditions.

    2-acetyl furan (2ACF), very rare, may be related to electrical

    stress.

    5-methyl-2furaldehyde (5M2F), typically formed as a result of

  • 8/12/2019 Solution to Power Generation_ Transformer Oil Testing

    14/16

    7/13/2014 Solution to Power Generation: Transformer Oil Testing

    http://www.powervikas.com/2013/01/dga-faults-in-transformer-key-gases-insulating-oil -power-transformer-condition-monitoring-high-voltage-electrical- testin 14

    overheating.

    These are typically present in very low concentrations,

    microg/kg or parts per billion, requiring detailed extraction

    methods and analysis using a very sophisticated instrument: a

    high performance liquid chromatograph. Typically, we find that

    total furan concentrations relate w ell to the following

    conditions:

    i) 25 parts per billion (ppb) is a new transformer with only

    background presence of furans.

    ii) Up to 100 ppb is an in service transformer that has aged

    normally (Acceptable level).

    iii) 100 to 1000 ppb is a unit that may have accelerated ageing

    (Questionable level).

    iv) Over 1000 ppb has significantly aged and should be

    investigated (Unacceptable level).

    Very high levels, 1000 ppb and above starts to enter the

    danger zone. Transformers with total furans 1000 ppb and

    above have a much higher failure rate because they are starting

    to reach their end of life or because small areas of the paper

    have been destroyed by localized overheating.

    Interpretation of Test ResultsTypically, the justification for running transformer oil tests is to

    provide the maintenance program w ith information to allow the

    efficient and safe continued use of the equipment. In this

    context, transformer oil tests listed in the table above (except

    for DGA, furans, metals, and PCBs) are run on a regular basis

    usually annually or every six months. Trends of the oil quality

    are monitored so that w hen the oxidation inhibitor nears

    depletion and/or when one or more of the other test

    parameters enter the questionable range, the oil can be

    serviced to restore it to new oil quality before any lasting

    damage to the insulation system is done.

    Oil servicing includes reclamation by processing the oil through

    filtering (to remove solid materials), through heat and vacuum to

    remove moisture and dissolved gases, and through a chemical

    adsorbent such as fullers earth to remove acids, sludges, and

    decay products. Oil can generally be reclaimed, however far the

    oxidation process has proceeded, and it can generally be

    reclaimed any number of times to like new oil quality. Oil that

    has aged in a transformer, how ever, has caused degradation

    products to build up inside the transformer, particular on and

    inside the structure of the solid insulation. Removing and

    replacing the oil regardless as to whether the replacement oil

    is new or reclaimed has little effect w ith regard to cleaning up

  • 8/12/2019 Solution to Power Generation_ Transformer Oil Testing

    15/16

    7/13/2014 Solution to Power Generation: Transformer Oil Testing

    http://www.powervikas.com/2013/01/dga-faults-in-transformer-key-gases-insulating-oil -power-transformer-condition-monitoring-high-voltage-electrical- testin 15

    the inside of the transformer. Reclamation of the transformer oil

    in the transformer, frequently referred to as hot oil cleaning,

    cycles the oil from the transformer through a processing rig

    where the oil is cleaned up. Because the oil passing over the

    internal structures of the transformer has been heated, it

    redissolves the acids and sludges, even those that are inside

    the solid insulation. Depending on how far oxidat ion of the oil

    has been allow ed to proceed, a reclaiming project may require

    a volume of oil passing through the transformer that is

    anywhere from 4 to 20 times the liquid volume capacity of the

    transformer. If done properly, reclaiming can frequently be done

    without deenergizing the transformer. Energized reclaiming

    saves on equipment dow ntime, and the loading and vibration

    of the energized equipment actually makes the cleaning of the

    internal structures proceed more effectively. Limiting factors on

    whether reclamation can proceed on an energized basis include

    the moisture content, voltage class of the equipment, volume

    and access to the oil, and presence of incipient fault conditions.

    Faults identified and diagnosed by DGA, furans, and/or metals

    analysis must be corrected to ensure that the unit can continue

    to operate safely. These faults typically require an outage to

    repair as they are related to electrical or mechanical problems

    with the internal components. Since it is not always practical to

    immediately schedule an outage (and if the fault is not

    immediately destructive of the equipment), the monitoring

    interval betw een DGA tests or furan analyses may be decreased

    normal intervals for DGA may be 3 months to one year

    sometimes to daily retests w here problems are particularly

    severe. Except for highly critical units, furans and metals are run

    only w hen they w ill be useful to help diagnose fault conditions.

    The key issue behind testing is to use the information to

    improve operations. Too frequently, limited funds are spent on

    testing units w here no remedial act ion will ever be taken. It

    would be much more cost effective to reallocate those funds to

    more critical units perhaps shortening testing intervals where

    testing results are a determinant in the continuing maintenance

    of that equipment.

    Conclusion:An attempt has been made in this paper to review modernchemical and electrical diagnostic methods for proper

    transformer maintenance. DGA is the most w idely used method

    for investigating incipient faults. So, w ith this case study we

    can analyze the higher concentration of C2H4 indicates thermal

    Fault, maximum fall in condition 3 in which fault probably

    present and then monitor the rate of rise of individual gases,

    indicates higher concentration of key gases. But there is no fault

    and transformer presently in service condition.

  • 8/12/2019 Solution to Power Generation_ Transformer Oil Testing

    16/16

    7/13/2014 Solution to Power Generation: Transformer Oil Testing

    Newer Post Older Post

    New comments are not allow ed.

    Home

    The transformer just like human beings needs a physical check-

    up, for a clean bill of health. No single test procedure is

    adequate to supply all the necessary information needed to

    properly evaluate a transformer, resulting in the various test

    performed by the condition monitoring unit.

    The frequency of the tests w ill be determined by many factors

    such as the age, loading and history of operation. These tests

    may fulfill three distinct but general functions:

    i) Prove the integrity of a piece of equipment at the time of

    acceptance.

    ii) Verify the continued integrity of the unit at periodic intervals

    of time.

    iii) Determine the nature of the extent of the damage w hen a

    unit has failed.

    Recommend this on Google

    0 comments:

    Copyright 2013 Solution to Pow er Generation and Customized byCyberOceanZ

    Terms Privacy Policy Sitemap Contact Us.

    From Twitter Recent Posts Custom content Get in Touch

    - Template by SoraTemplates

    http://www.soratemplates.com/http://www.cyberoceanz.com/http://www.powervikas.com/http://www.blogger.com/share-post.g?blogID=3471583257878549326&postID=8115254755881664195&target=facebookhttp://www.blogger.com/share-post.g?blogID=3471583257878549326&postID=8115254755881664195&target=twitterhttp://www.blogger.com/share-post.g?blogID=3471583257878549326&postID=8115254755881664195&target=bloghttp://www.blogger.com/share-post.g?blogID=3471583257878549326&postID=8115254755881664195&target=emailhttp://www.powervikas.com/http://www.powervikas.com/2013/01/methods-for-calculating-short-circuit-current-of-electrical-system-short-circuit-analysis-overcurrent-protective-devices-ocpd-transformer-fault-current-generator-fault-current.htmlhttp://www.powervikas.com/2013/01/restricted-earth-fault-protection-of-transformer-ref-protection-schemetic-drawing-basic-operation.html