Upload
hamed
View
217
Download
0
Embed Size (px)
Citation preview
8/16/2019 Solar t 60 Mpu Technical Presentation
1/36
5.2 MW Solar Mobile Power Unit
NeutralGroundingResistor
Lube oil cooler
Leveling jacks &pads
Access stairs &platforms
ExhaustSilencer
Ventilation airintake
Gas & LiquidFuel Connections
Air inlet &silencer
13.8 to 480 vac Aux.Power Transformer
Ventilationair exhaust
Power Control Room & Trailer-13.8 KV switchgear-CO2 fire system-480 VAC MCCC for turbineaccessories
-120VDC battery systems
-Allen Bradley TT4000Monitor/control
8/16/2019 Solar t 60 Mpu Technical Presentation
2/36
Solar 5.2 MW Mobile Power Unit
Solar T60 MPU
8/16/2019 Solar t 60 Mpu Technical Presentation
3/36
Mobile Turbine Design Goals
Standard Solar Taurus 60 Power Gen. Package
Rapid Setup & Commissioning
Ease of transport…Land, Sea, & Air
Totally self contained, Needs only…
o Gas and/or Liquid Fuel
o 13.8kV load connectiono Black Start Requires 480VAC
8/16/2019 Solar t 60 Mpu Technical Presentation
4/36
Mobile Turbine Design Goals
Standard Solar Taurus 60 Power Gen. Package
PartsService
Overhauls
Upgrades
Retrofits
8/16/2019 Solar t 60 Mpu Technical Presentation
5/36
Solar T60 – Engine
Simple Cycle Single shaft axial flow engine
Close Coupled to separate Gear Box
Twelve-stage axial flow compressor
Variable geometry control on inlet guide
vanes and first three rows of stators
Annular combustor with 12 fuel injectors
Three-stage turbine assembly
Standard Solar Taurus 60 Power Gen.
Package
8/16/2019 Solar t 60 Mpu Technical Presentation
6/36
Solar T60 – Gear Box
Coupled directly to the
turbine engine
Speed Reduciton from
13,800RPM to 1800 RPM
8/16/2019 Solar t 60 Mpu Technical Presentation
7/36
Solar T60 – Generator & Voltage Regulation
Ideal or Alstom
Sleeve Bearings with pressure fed sumps
Six-lead WYE connection Form wound stator windings
Permanent magnet pilot exciter
12,470 – 13,800 Volt, 3 phase, 60 Hz.
11kV, 3 phase, 50 Hz.
Insulation class F with
Voltage Regulator Characteristics
Solid state, Single-phase sensing
0.5% steady state voltage regulation
Reactive load sharing to within 5% nameplate rating
Crosscurrent compensation capability
8/16/2019 Solar t 60 Mpu Technical Presentation
8/36
Solar T60 – Dual Fuel System
Designed to operate on Natural Gas or Distillate Liquid Fuels
NATURAL GASo maximum flow demand rate of 1200 scfm
o 250 psig minimum and 300 psig maximum
Distillate Liquid Fuels
o maximum flow demand rate of 8.0 gpm.
o 20ft. Suction minimum to 25 psig maximum
8/16/2019 Solar t 60 Mpu Technical Presentation
9/36
Solar T60 – Starter, Lube system
Direct drive AC motor with VFD motor controller
Lube system provides oil to the Taurus 60 gas turbine
engine, gear box and generator.
o Engine driven lube oil pump
o Pre/Post Lube AC Motor Driven Pump
o Pre/Post Lube DC Motor Drive Pump
o Lube Oil Sump (integral part of turbine skid) with
space heater, level controls, and thermostaticcontrol valve.
o Horizontal core lube oil cooler mtd. on Power
Control Room
8/16/2019 Solar t 60 Mpu Technical Presentation
10/36
Solar T60 – Auxiliary Systems
On Crank and On Line Water Wash
WEATHERPROOF ACOUSTIC ENCLOSURE
o
Ventilation Silencers and Fans,o Lights
o Fire Detection and Gas Monitoring System
o High Temperature Detection and Alarm
o CO2 Fire Suppression System.
High Efficiency Combustion Air Barrier Filter and
Silencer
Trailer mounted exhaust silencer
8/16/2019 Solar t 60 Mpu Technical Presentation
11/36
Solar T60 – Allen Bradley PLC5 Control System
Flexibility to change logic or add features
Relay backup in event of PLC failure
Operational summary
Alarms, shutdowns,
Temperatures, pressures, vibration,
Engine performance,
Generator kW, voltage, p.f., hz., amps, current.
Remote Video Display (TT4000) interface and monitoring.
Interface and monitoring in power control trailer via
Local operator interface and monitoring.
Sequencing of
Starting,
Running & shutdownPackage monitoring and protection
Solar Turbotronic Controller
8/16/2019 Solar t 60 Mpu Technical Presentation
12/36
Solar T60 Performance (ISO Conditions)
Table 1. Dual Fuel Performance Data ISO*, XQ5200 Mobile Power Unit
300% for 10 sec.300% for 10 sec.300% for 10 sec.300% for 10 sec.Short Circuit
0.5%0.5%0.5%0.5%Voltage Steady State
60 Hz.60 Hz.60 Hz.60 Hz.Gen. Frequency
12.47 or 13.8 KV12.47 or 13.8 KV12.47 or 13.8 KV12.47 or 13.8 KVGen. Voltage
50 PPMvd 50 PPMvd 50 PPMvd 50 PPMvd CO
96 PPMvd 96 PPMvd 48 PPMvd 25 PPMvd
48 PPMvd 25 PPMvd (1.1 lb.)/MW-hr)
Emissions, NOX
61. mmkJ/hr57.9 mmBTU/hr 61.8 mmkJ/hr 58.6 mmBTU/hr Fuel Flow (LHV)
12,002 kJ/kWe-hr 11,376 Btu/kWe-hr 11,900 kJ/kWe-hr 11,263 Btu/kWe-hr Heat Rate
5,089 kWe5,089 kWe5,200 kWe5,200 kWe Power Output
Metric English Metric English
Diesel #2 Diesel #2 Natural Gas
Natural Gas
8/16/2019 Solar t 60 Mpu Technical Presentation
13/36
Solar T60 Performance
“TaurusTM
60, 7300 Industrial Gas Turbine
• ISO Condit ions (5,200MWe) 15o C (59o F) Sea Level,
0 Inlet/Exhaust Losses Varies with Air Temperature
and Altitude• Taurus 60 at 152 M (500 ft .)
5367 kWe @ 4.4o C (40o F)4345 kWe @ 32o C (90o F)
• Taurus 60 at 457M (1500 ft.)
5165 kWe @ 4.4o C (40o F) 4182 kWe @ 32o C (90o F)
8/16/2019 Solar t 60 Mpu Technical Presentation
14/36
Mobile Turbine Design Goals
Standard Solar Taurus 60 Power Gen. Package
Ease of transport…Land, Sea, & Air
Totally self contained, Needs only…..
o Gas and/or Liquid Fuel
o 13.8kV load connection
o Black Start Requires 480VAC
8/16/2019 Solar t 60 Mpu Technical Presentation
15/36
Ease of transport…Land, Sea, & Air
8/16/2019 Solar t 60 Mpu Technical Presentation
16/36
Ease of transport…Land, Sea, & Air
• Turbine Generator Trailer & 2-
Axle Booster Unit
18.9M (62 ft.)
Weight: 57MT (125,000 lbs.)
• Power Control Room Trailer
14M (46 ft.)
Weight: 25MT (55,000 lbs.)• Shipped Loose
Step deck or 12.2M (40 ft.) High
Cube
8.2MT (18,000 lbs.)
• Designed for All U.S. States and
Canadian Provinces
8/16/2019 Solar t 60 Mpu Technical Presentation
17/36
Markham Ontario, 98 MW
Rapid Setup and Commissioning…8 wks.
8/16/2019 Solar t 60 Mpu Technical Presentation
18/36
Rapid Setup and Commissioning…. 4 wks
Nassau, Bahamas, 20 MW Liquid Fuel
8/16/2019 Solar t 60 Mpu Technical Presentation
19/36
Prudhoe Bay, Alaska USA; 15MW Natural Gas Fuel
Rapid Setup and Commissioning…. 2 wks
8/16/2019 Solar t 60 Mpu Technical Presentation
20/36
Self Contained Power Plant
NeutralGroundingResistor
Lube oil cooler
Leveling jacks &pads
Access stairs &platforms
ExhaustSilencer
Ventilation airintake
Gas & LiquidFuel Connections
Air inlet &silencer
13.8 to 480 vac Aux.Power Transformer
Ventilationair exhaust
Power Control Room & Trailer-13.8 KV switchgear-CO2 fire system-480 VAC MCCC for turbineaccessories
-120VDC battery systems-Allen Bradley TT4000Monitor/control
8/16/2019 Solar t 60 Mpu Technical Presentation
21/36
Heavy Turbine & Power Control room easily set in place
Ease of Placement
8/16/2019 Solar t 60 Mpu Technical Presentation
22/36
No Large Cranes Required
5,000 lbs. ….. Heaviest item lifted
8/16/2019 Solar t 60 Mpu Technical Presentation
23/36
Easy Siting Requirements
Level compacted surface 2,500 lbs. per square ft.
8/16/2019 Solar t 60 Mpu Technical Presentation
24/36
Easy Siting Requirements
• Low Profile
7.3M (24 ft.) Stack Height
• Sound Attenuation Package 85 dba @ 1 meter
CSA/NRTL
8/16/2019 Solar t 60 Mpu Technical Presentation
25/36
Oil Cooler Lines Factory Polished
Rapid Installation
8/16/2019 Solar t 60 Mpu Technical Presentation
26/36
Color Coded Quick Connectors
Rapid Installation
8/16/2019 Solar t 60 Mpu Technical Presentation
27/36
13.8KV Quick Connect Load Cable
Rapid Installation
8/16/2019 Solar t 60 Mpu Technical Presentation
28/36
CO2 Fire System
Rapid Installation
8/16/2019 Solar t 60 Mpu Technical Presentation
29/36
Stairs & Platforms contribute to an easy installation
Ease of Use
8/16/2019 Solar t 60 Mpu Technical Presentation
30/36
Set Up & Operational in 3 - 5 Days
Experienced Field Set Up Crew
8/16/2019 Solar t 60 Mpu Technical Presentation
31/36
Solar T60 MPU Product Features
Power Control Room
400 or 480400 or 480 Volt Motor Volt Motor
ControlControlCenterCenter
MetalMetal--CladClad15Kv15Kv
SwitchgearSwitchgear
Turbine &Turbine &
SwitchgearSwitchgearBatteryBatterySystemsSystems
BeckwithBeckwithProgrammableProgrammable
ProtectiveProtectiveRelay ModuleRelay Module
GeneratorGenerator Voltage: Voltage:
11,000 or11,000 or13,800 Class F13,800 Class F
Insulation/Insulation/Class FClass F
TemperatureTemperatureRiseRiseStepStep--down transformer & down transformer &
Neutral GroundingNeutral GroundingResistorResistor
BaslerBasler OverOverCurrent RelaysCurrent Relays
8/16/2019 Solar t 60 Mpu Technical Presentation
32/36
Remote Dial-up (Modem)
Historical Data
Solar T60 MPU Product Features
Turbotronic Controller, AllenBradley PLC5(Turbine andGenerator) Auto Synch
Voltage Adjust
kW Control
KVAR/Power FactorControl
TT4000Remote Control andMonitoring:
8/16/2019 Solar t 60 Mpu Technical Presentation
33/36
Solar T60 MPU Installation Requirements
• Minimum Soil Loading
• (2,500 lb./ft2) 12.2MT/M2
Flat and Level Surface
• Gas Supply
(240-300 psig) 1725- 2068 KPAG Gas Supply
Distillate Liquid Fuelso maximum flow demand rate of 8.0 gpm.
o 20ft. Suction minimum to 25 psig maximum
• 15kV load connections to PCR
Turbine AC and DC auxiliary loads powered Internally
• Grounding to Grid
• 480VAC, 400A Black Start
8/16/2019 Solar t 60 Mpu Technical Presentation
34/36
Solar T60 MPU Installation Requirements (cont’)
• Small Drain Tank, 70 L (20
gal.)
• Crane with Lifting Capability
of 2.5MT (5,500 lbs.)
• Installation and
Commissioning
3 Man Crew to Install Standard Hand Tools
5-7 Days to Commission
• Input Signal From Utility Tie
Breaker Island Mode Operation
8/16/2019 Solar t 60 Mpu Technical Presentation
35/36
Solar T60 MPU Operations and Service
• Rental Rate Covers all
Maintenance, inspections andFailure Repair.
• Routine Daily Maintenance by
End User or PetersonOperators (if provided)
• Typical Overhaul Interval
is 30,000 Hours
• Overhaul by Exchange of
Entire Turbine
• Limited Field Maintenance, 2
Inspections/Year
Maintenance and Operation
8/16/2019 Solar t 60 Mpu Technical Presentation
36/36
Solar T60 MPU
Thank you
hank you