Solar PV | Solar Fuses68
www.rubiconsa.comSolar PV | Solar Fuses68
Bussman PV FusesOverview of String Protection
Depending on the desired capacity of the Photovoltaic (PV) system, there may be several PV strings connected in parallel to achieve higher currents and subsequently more power.
PV systems that have three or more strings connected in parallel need to have each string protected. Systems that have less than three strings will not generate enough fault current to damage the conductors, equipment or modules. Therefore they do not present a safety hazard, provided the conductor is sized correctly, based on local codes and installations requirements.
Where three or more strings are connected in parallel, a fuse link on each string will protect the conductors and
modules from over current faults and help minimise any safety hazards. It will also isolate the faulted string so that the rest of the PV system can continue to generate electricity.
It should be remembered that PV module output changes with the module temperature as well as the amount of sun it is exposed to. The exposure is dependent on irradiance level, incline as well as shading eff ect from trees/buildings or clouds. In operation, fuse links, as thermal devices, are infl uenced by ambient temperature. The current capability of the PV fuse links should be de-rated according to the Rated Current Dimensioning in the Cooper Bussmann High Speed Fuse Application Guide # 3160 at www.cooperbussmann.com.
1500V Fuses (DC)Eaton’s Bussmann™ series of 14x65mm (10x85mm with 10mm caps) package PV fuses are specifi cally designed for protecting and isolating photovoltaic strings. These fuse links are capable of interrupting low over-currents associated with faulted PV systems (reverse current, multi-array faults).
Cylindrical with 10mm fi xings
Product Code Rated Amps Rated Voltage Interrupting Rated
PV-2.25A14LF10F 2.25A 1500V DC 10kA
PV-2.5A14LF10F 2.5A 1500V DC 10kA
PV-3A14LF10F 3.0A 1500V DC 10kA
PV-3.5A14LF10F 3.5A 1500V DC 10kA
PV-4A14LF10F 4.0A 1500V DC 10kA
PV-15A14LF10F 15A 1500V DC 10kA
PV-20A14LF10F 20A 1500V DC 10kA
PV-25A14LF10F 25A 1300V DC 10kA
PV-32A14LF10F 32A 1300V DC 10kA
Holder for 1500V FusesProduct Code Number
Of PolesRated Voltage Rated Current
(Ul)Rated IsolationVoltage Ui
Rated Surge Volt. \ Uimp
Rated Breaking Capacity Icc
CHPV15V85 1 1000V AC /1500V DC
32A (IEC) / 30A 1500V 6 30kA
10X38 PV Fuses (DC)A range of UL 2579 fast-acting 600VDC Midget fuses specifi cally designed to protect solar power systems in extreme ambient temperature, high cycling and low level fault current conditions (reverse current, multi-array fault).
Product Code Rated Current Rated Voltage Breaking Capacity Dimensions Class
PV-2A10F 2A 600V DC 30kA 10x38mm GPV
PV-6A10F 6A 600V DC 30kA 10x38mm gPV
PV-8A10F 8A 600V DC 30kA 10x38mm GPV
PV-10A10F 10A 600V DC 30kA 10x38mm GPV
PV-12A10F 12A 600V DC 30kA 10x38mm GPV
PV-15A10F 15A 600V DC 30kA 10x38mm GPV
PV-20A10F 20A 600V DC 30kA 10x38mm GPV
PV-25A10F 25A 600V DC 30kA 10x38mm GPV
*30Amp available on special request only.
Holders For 10X38 FuseProduct Code Rated Current Rated Voltage No. Poles Fuse Blown Indication
*CHPV1IU 30A 1000V DC 1 With indication
CHPV2IU 30A 1000V DC 2 With indication
*CHPV1U 30A 1000V DC 1 Without indication
CHPV2U 30A 1000V DC 2 Without indication
JV-L Multi-pole connector Kit (10x38). For Use with Fuse Holders CHPV1U and CHPVIU
*Stocking items
PV-25A10F
CH
PV1U
- W
ithou
t Ind
icat
ion
PV-*
14LF
10F
1500V DC
CH
PV15
V85
Solar PV | Solar Fuses69
Solar PV | Solar Fuses70
NH1 Photovoltaic Fuses (DC)NH DIN blade fuse
A range of NH size fuse links specifi cally designed for protecting and isolating photovoltaic array combiners and DC disconnects. These fuse links are capable of interrupting low over currents associated with faulted PV systems (reverse current, multi-array fault).
Product Code Rated Current Rated Voltage Breaking Capacity Dimensions Class
PV-32ANH1 32A 1000V DC 30kA NH1 GPV Fuse Links
PV-40ANH1 40A 1000V DC 30kA NH1 GPV Fuse Links
PV-50ANH1 50A 1000V DC 30kA NH1 GPV Fuse Links
PV-63ANH1 63A 1000V DC 30kA NH1 GPV Fuse Links
PV-80ANH1 80A 1000V DC 30kA NH1 GPV Fuse Links
PV-100ANH1 100A 1000V DC 30kA NH1 GPV Fuse Links
PV-125ANH1 125A 1000V DC 30kA NH1 GPV Fuse Links
PV-160ANH1 160A 1000V DC 30kA NH1 GPV Fuse Links
Holders for NH1 Photovoltaic FusesProduct Code Rated Current Rated Voltage No. Poles Description
SD1-D 250A 1000V DC 1 DIN-Rail and screw mounting
TD1-D 250A 1000V DC 2 DIN-Rail and screw mounting
XL Photovoltaic Fuses (DC)
A range of XL package fuse links specifi cally designed for protecting and isolating photovoltaic array combiners and disconnects. These fuse links are capable of interrupting low over currents associated with faulted PV systems (reverse current, multi-array fault).
Product Code Product Code Rated Current Rated Voltage Body Size
Bladed Bolted
PV-63A-01XL PV-63A-01XL-B 63A 1000V DC 01
PV-80A-01XL PV-80A-01XL-B 80A 1000V DC 01
PV-100A-01XL PV-100A-01XL-B 100A 1000V DC 01
PV-125A-01XL PV-125A-01XL-B 125A 1000V DC 01
PV-160A-01XL PV-160A-01XL-B 160A 1000V DC 01
PV-200A-1XL PV-200A-1XL-B 200A 1000V DC 1XL
PV-200A-2XL PV-200A-2XL-B 200A 1000V DC 2XL
PV-250A-2XL PV-250A-2XL-B 250A 1000V DC 2XL
PV-315A-2XL PV-315A-2XL-B 315A 1000V DC 2XL
PV-350A-3L PV-350A-3L-B 350A 1000V DC 3L
PV-400A-3L PV-400A-3L-B 400A 1000V DC 3L
PV-500A-3L PV-500A-3L-B 500A 1000V DC 3L
PV-630A-3L PV-630A-3L-B 630A 1000V DC 3L
Holders for XL Photovoltaic FusesProduct Code Description
SD1XL-S Suitable for 01 & 1XL fuse
SB2XL-S Suitable for 2XL fuse
SB3L-S Blocks Size 3L fuse
SD1X
L-S
SB2X
L-S
& S
B3L
-S
PV-***-*
SD1-
D /
TD1-
DSD
1-D
/ TD
1-D
PV-*
AN
H1
Solar PV | Solar Fuses69
www.rubiconsa.comSolar PV | Solar Fuses70
AC Fuses NH DIN HRC Fuse Links(120kA / 500V)Product Code Description Size Quantity
24700-10A Std. protection fuse with indicator 00 1
24700-16A Std. protection fuse with indicator 00 1
24700-25A Std. protection fuse with indicator 00 1
24700-32A Std. protection fuse with indicator 00 1
24700-40A Std. protection fuse with indicator 00 1
24700-63A Std. protection fuse with indicator 00 1
24700-80A Std. protection fuse with indicator 00 1
24700-100A Std. protection fuse with indicator 00 1
Battery Protection For AC/DC Systems: Multibloc 00.St8 (For NH Fuses) (Holders)
Product Code Rated Voltage Rated Current No. Poles Size Cable Termination Components
F229292 690V AC / 220V DC 160A 1 00 2 M8 screws
G229293 690V AC / 220V DC 160A 2 00 4 M8 screws
Battery Protection For AC/DC Systems: Multibloc 00.St9 (For NH Fuses) (Holders)
Product Code Rated Voltage Rated Current No. Poles Size Cable Termination Components
P1023007 690V AC / 440V DC 160A 3 00 6 M8 screws
MC Inline FuseMolded inline fuses utilise genuine MC4 connectors from MultiContact to ensure the lowest losses and highest quality connection, while maintaining the full system safety. Fully overmolded, non-replaceable fuses are disposable to ensure user safety.
Product Code Description
MCfuse-1-xx* 1000V DC inline fuse, MC4
MCfuse1500-1-xx* 1500V DC inline fuse, MC4
*Insert current rating: 4A, 6A, 10A, 12A, 15A, 20A | To order with pigtails, please contact a branch near you.
Solar Diode ConnectorAnti-aging Material: PPO / PC material,strong anti-aging, anti-UV, life ≥25 years; hardware connectors: High-quality tinned copper, Low resistance, plug long life; waterproof rating IP67.
Rated voltage: TUV 1000V DC / UL 600V DCSuitable cable cross sections: NOTerminal size: Φ4.0mmPollution degree: 2
Protection class: Class 11Contact resistance: ≤ 5mΩIP rating: IP67(IEC 60529)Flame Class: UL94V - 0
Ordering InformationProduct Code Description Rated Current Test Temp. Test Voltage
CB-D4A Solar Diode connector MC4 style
3 ~ 8A -40 to +85oC DC 8kV 1min
P102
3007
G22
9293
F229
292
NH DIN HRC Fuse Links (120kA / 500V)
CB
-D4A