Solar PV Power Generation System
Detailed Project Report
SOLAR PV POWER GENERATION SYSTEM
Detailed Project Report For 20.00 KWp Solar PV Grid Connected System
PROJECT
PROVIDING ON GRID TYPE 20.00KWp SOLAR PV POWER PLANT AT FACTORY
REF. NO. SM/RRD/SPV/OH 14000238
CLIENT
RR Donnelley Publishing India Private Limited
Plot No. C-10, SIPCOT Industrial Park
Irungattukottai
Sriperumpudur - 602 117
Tami Nadu, India
SUPPLIER
Swissmango Solar Energy Solutions Pvt Ltd Unit-7B, 7th Floor ‘A’ Block, Mena-Kampala Arcade
18 & 20, Sir Theyagaraya Road, T. Nagar, Chennai 600 017
DOCUMENT NO. SM/RRD/SPV/20140212A
REVISION NO 1.0
DATE February 12, 2014
PREPARED BY CHECKED BY APPROVED BY
N. Vijaya Balaji
Paramasivam V
K.Madhavan
Solar PV Power Generation System
Detailed Project Report
Confidential February 2014 2
Table of Contents
1. ABOUT SOLAR POWER SYSTEM Section 1
2. BILL OF MATERIALS Section 2
3. SOLAR PHOTVOLTAIC EQUIPMENT DETAILS Section 3
4. INSTALLATION & OTHER DRAWINGS Section 4
5. SOLAR PHOTOVOLTAIC MODULE DATA SHEET Section 5
6. CONTACT DETAILS Section 6
Solar PV Power Generation System
Detailed Project Report
Confidential February 2014 3
SECTION – 01
ABOUT SOLAR POWER
SYSTEM
Solar PV Power Generation System
Detailed Project Report
Confidential February 2014 4
SECTION – 01
ABOUT SOLAR POWER SYSTEM
1.1 SYSTEM OVERVIEW
A. About the system
The solar PV Power generation system (Powerpack) supplied by Swissmango Solar Energy Solutions Pvt Ltd is a high efficient, modular, extendable and cost effective power generation solution. The system is designed to International Standards to ensure that you have years of
trouble-free operations. As a result of proven technology, the system is highly efficient and maintenance free. With one-time investment, the Solar PowerPack provides the prudent way of managing the energy costs in an eco-friendly way. The savings made on energy costs will help the companies to directly benefit and contributing to their growth. The List of major components used in this system are listed below.
Solar PV Modules: The sun light (solar radiation) falling on the modules is converted in to DC energy by photovoltaic principle. The generated by solar modules can either be used to
supply the power to the connected load or to charge the battery bank.
PV Inverter(PCU): PCU is a common terminology used to the system consisting of Inverter and AC synchronization functionality. PCU does the function of controlling grid power by leading PF and prefer the solar energy to the load. The system also contains the Charge Controller as part of the same system or as an independent unit.
Module mounting structure(MMS): MMS is the structure to mount the solar PV modules with specified angle depending on the location when the system to be mounted. The tilting will vary depending on the longitude and latitude of the location.
B. Salient Features and Benefits of System
A clean, silent and eco-friendly source of power
Solar modules convert sunlight into electricity without pollution
Negligible maintenance as there are no moving parts and maximum reliability
Long life span of solar modules
Modular design and easily expandable
Simple installation: can be mounted on roof top or ground
Can be installed at point-of use to avoid transmission losses
Energy Independence
Protection against future escalation of energy costs
Available throughout the year
Solar PV Power Generation System
Detailed Project Report
Confidential February 2014 5
C. Applications
The system is ideal for industries and institutions where the energy usage is maximum during the sunlight hours. These include manufacturing companies, Software development Centres, Hospitals, Hotels, Schools, Colleges, Fuel Pump stations, R&D Centres, Transmission, Railways and Communication towers and many more applications.
1.2 SYSTEM WORKING PRINCIPLE
Solar photovoltaic(PV) system is like any other electrical power generation systems in terms of the output except for the source of the power is Solar radiation. The conversion of Solar radiation to the electrical power is based on the photovoltaic principles. However, the principles of operation of the connected load and interfacing with other electrical systems
remain the same. Though solar PV array produces power when exposed to sunlight, a number of other components are required to properly conduct, control, convert, distribute, and transform the energy produced by the array.
Solar power generating system supplied for this project shall be utilized for powering various office loads like Computer, Lighting loads, fans etc. for specified hours of sun shine operation.
This system is designed to generate the energy in an eco friendly manner with the source from solar radiation which is available in abundance. The system designed is for 20.00KWp Solar Power Generation Grid Connecting System. The system does not have any storage for standby power. The solar PV array will have 80 no’s of 250Wp crystalline solar modules. These modules will be connected in series / parallel combination t h r o u g h Optimizers to
Solar PV Power Generation System
Detailed Project Report
Confidential February 2014 6
the desired string configuration as per the design parameters of the PCU. The PCU is of 17KVA capacity with three phase AC Output. Grid power supply is provided to support the loads and to reduce the Grid power consumption when solar power is available.
The power generated from solar array is fed into the PCU through Optimizer and being inverted by the PCU (Vac). This voltage is being combined with standard grid supply to the phases (R/Y/B) and will lead the power factor of the inverter supply by comparing the grid power factor. So the solar generated power will always be preferred by the leading power factor and rest of the power will be used from the grid as required by the load. If the load demand is lesser than the solar power generated, the balance power may be exported to grid and customer may get feed-in benefit as per the policies of the local electricity board. This system is working in the principal of power factor comparison and the system will feed the power either to load or grid through grid power supply. That means loads will be indirectly connected with the solar system. So, if the grid supply is not available at any moment the solar system will shut OFF immediately. We can only use sunlight directly to the load whenever the grid power is available. The system will shuts OFF at the time of low intensity or no sun light and restarts automatically when the sunlight is available. The proposed system does not required any dedicated loads or separate wiring to work on. At the time of power failure if the customer turns ON the DG supply again the solar system will run and pushes the energy back to the DG. To avoid this reverse current situation, the DG rating should be atleast be 4 to 5 times higher rating than the proposed solar power plant rating.
System Details:
1. Solar PV Modules: PV PowerTech, ECO 250Wp – Polycrystalline
Quantity: 80 Nos. (80 x 250 = 2000kWp).
- Solar PV Module exposed to the sunlight converts it into DC energy.
2. Optimizer: Solar Edge Power Optimizer (OP MV 600W) – 600W
Quantity - 40 Nos.
- The power optimizer is a DC/DC converter connected to Solar PV modules to increase the energy output from PV systems by constantly tracking the maximum power point
(MPPT) for one or more modules individually
3. PCU / Inverter: Solar Edge SE17K-ER-01 Grid connected system,
3 Phase – AC Output - 1 No
- The inverter responsible for DC to AC inversion
4. The output of the inverter is connected to the AC Panel through a proper AC Protection.
5. Inter connecting cables are used to interconnect solar PV components like Solar Modules, Junction Boxes, & Inverter.
Solar PV Power Generation System
Detailed Project Report
Confidential February 2014 7
SECTION – 02
BILL OF MATERIALS
Solar PV Power Generation System
Detailed Project Report
Confidential February 2014 8
SECTION – 2 BILL OF MATERIALS
Srl. No
Description
Quantity
1.
Polycrystalline Solar PV Modules – 250Wp
PV Powertech Eco 250Wp
80 Nos.
2.
Power Optimizers – 600W
Solar Edge Power Optimizer – OP MV 600W
40 Nos.
3.
Solar PV Inverter – 17KVA – 3 Phase
Solar Edge SE17K-ER-01
1 No.
4.
Data Logging for monitoring Available as part of the PCU
5.
DC Cable 6 Sq.mm (Module to Optimizer and
Optimizer to PCU)
100 Mtrs
6.
AC Cable - 6 Sq.mm /10 Sq.mm Inverter to
ADCB
100 Mtrs
8. Earthing Kit 1 Set
9. Module Mounting Structure 1 Set
10. Installation Kit (Cable tie, Nuts, bolts, lugs, etc) 1 Set
Solar PV Power Generation System
Detailed Project Report
Confidential February 2014 9
SECTION – 03
SOLAR PHOTOVOLTAIC
EQUIPMENT DETAILS
Solar PV Power Generation System
Detailed Project Report
Confidential February 2014 10
SECTION – 03
SOLAR PHOTOVOLTAIC EQUIPMENT DETAILS
3.1 SOLAR POWER GENERATING SYSTEM DETAILS
The solar PV Power generation system (Powerpack) supplied by Swissmango Solar Energy Solutions Pvt Ltd is a high efficient, modular, extendable and cost effective power generation solution. The system is designed to International Standards to ensure that you have years of trouble-free operations.
Technical data of the solar power pack supplied is given below.
ü System Type Solar PV Grid Connect System
ü System Solar Array Capacity - Nominal 20kWp @ standard test condition
ü System Output AC voltage - Nominal 400Vac (line to line), 50 Hz (230V - Line to Neutral)
ü Inverter Output Rating - Nominal 17000VA
3.2 SOLAR PV MODULE
The PV Powertech solar photovoltaic module provides superior value and performance. They may be used in single-module and multiple module systems to meet the current or voltage requirements of a wide range of applications with its nominal power; it’s well-suited to utility grid systems and traditional applications.
The high efficiency Solar PV Modules are:
Made from imported Poly-Crystalline solar cells to exacting International Standards
Modules comply with the International standards IEC 61215, IEC 61730 and IEC 61701 product certification
Standard 10 year manufacturing warranty
10 years/25 years limited power guarantee for 90% & 80% power respectively
Cells are encapsulated with premium EVA from USA, with good light transmission resistance to degradation over a long period of time
Back sheet is from Japan with extra white surface for light reflection and high strength
Junction box has six bypass diodes for extra protection and standard MC4 compatible connectors for easy installation. IP65 compliant for all weather usage
Structural integrity offered by a robust double wall screw‐less, snap‐fit aluminum frame that is anodized for safety against corrosion
Solar PV Power Generation System
Detailed Project Report
Confidential February 2014 11
Technical data of solar PV module is given below.
Solar Module Type Poly crystalline silicon cell module
Single Module rated power - Nominal 250Wp @ standard test conditions
Single Module open circuit voltage - Nominal 37.00Vdc
Single Module short circuit current - Nominal 8.55A
Single module current @ max (Imp) 8.08A
Single module voltage @ max (Vmp) 30.95Vdc
No. of modules in series / string* 20 Nos.
No. of such strings in parallel / Array** 4 Nos.
Total no. of solar modules / system 80 Nos.
Total solar Array voltage - Nominal 619 Vdc
Total solar Array capacity - Nominal 2000 Wp @ standard test conditions
*String: - A number of modules or panels interconnected electrically in series to produce the required
operating voltage.
**Array: - Number of modules or panel strings connected in parallel at one common place.
3.3 SOLAR MODULE MOUNTING STRUCTURE
To use the fixed module mounting structure made of mild steel with hot dipped galvanization/ pre-galvanized structure for mounting the solar PV modules on the canopy of the main entrance.
Solar PV Power Generation System
Detailed Project Report
Confidential February 2014 12
3.4 INVERTER
Inverter is designed for years of trouble-free use. The Inverter is a Grid connected sine wave to serve the loads. It is rated for 17000VA at 400Vac, 50Hz and designed to operate with DC input only. Inverter
required grid supply mandatorily to synchronize the source. Without grid the system, the inverter
will go OFF.
Solar Edge Inverters (Three Phase) with Optimizers
a. Inverters specifically designed to work with power optimizers b. Superior efficiency (>97%) c. Excellent reliability with standard 12 year warranty against manufacturing defects d. Small, lightweight and easy to install e. Built-in module-level monitoring receiver f. IP65 / NEMA 3R – Outdoor and indoor installation
Technical details of inverter is given below
ü Inverter Model & Capacity Solar Edge – SE5K - SE17K – 17KW
ü Output Voltage 400 Vac ü Frequency 50/60 Hz nominal
ü Rated Output VA 17000 VA ü Rated DC Watts 20000 W ü Operating Temperature -20° C to +60° C
Solar PV Power Generation System
Detailed Project Report
Confidential February 2014 13
SECTION – 04
INSTALLATION & OTHER
DRAWINGS
Solar PV Power Generation System
Detailed Project Report
Swissmango Solar Energy Solutions Pvt Ltd Title: Line Diagram for 20.00 Kwp Grid Connected SPV System Client : RR Donnelley Publishing India Private Limited
Solar PV Power Generation System
Detailed Project Report
SECTION – 05
SOLAR PHOTOVOLTAIC MODULE DATA SHEET
Solar PV Power Generation System
Detailed Project Report
The PV Module proposed for the project is ECO 250.
Electrical Characteristics:
Model Name ECO 225 ECO 230 ECO 235 ECO 240 ECO 245 ECO 250 Cell Configurations (Nos.) 10 x 6 (60)
Pmax (W) (Tolerance: +3% , -0) 225 230 235 240 245 250
Voc (V) (Tolerance ±3%) 36.2 36.38 36.50 36.65 36.85 37.00
Isc (A) (Tolerance ±3%) 8.11 8.21 8.30 8.40 8.48 8.55
Vmax (V) (Tolerance ±3%) 29.6 29.8 30.05 30.25 30.6 30.95
Imax (A) (Tolerance ±3%) 7.61 7.73 7.85 7.94 8.01 8.08
Module Efficiency (%) 13.9 14.2 14.5 14.8 15.1 15.4
Maximum System Voltage (DC) 1000
Series Fuse Rating (A) 15
Nominal Operating Cell Temp. (°C) 44.6
Temp. Coefficient of Pmax (%/°C) -0.45
Temp. Coefficient of Voc (%/°C) -0.36
Temp. Coefficient of Isc (%/°C) 0.043
Electrical values measured at STC: 25°C, 1.5AM, 1000 W/m²
Solar PV Power Generation System
Detailed Project Report
Mechanical Characteristics Dimensions & Mounting Holes ECO 230 - IV & PMAX GRAPH
Solar PV Power Generation System
Detailed Project Report
SECTION – 06
CONTACT DETAILS
Solar PV Power Generation System
Detailed Project Report
CONTACT DETAILS:
RR Donnelley Publishing India Private Limited
Plot No. C-10, SIPCOT Industrial Park
Irungattukottai
Sriperumpudur - 602 117
Tamil Nadu, India
Beneficiary Primary Conact:
K.Madhavan, Manager-Manufacturing & Maintenance Manufacturing Department
Telephone: +91 44 2715 1202
Mobile: +91 98407 57487
E-mail: [email protected]
===============================================================================
Supplier Primary Contact: N.Vijaya Balaji Telephone: +91 44 4218 7544 Mobile: +91 98418 6852