    GEO TECHNICAL INVESTIGATION REPORT FOR THE PROPOSED

    HOSPITAL BUILDING AT POTHIREDDYPALLY (V), SANGAREDDY,

    MEDAK DT., TELANGANA STATE

    1. INTRODUCTION

    Dr Anand Naik is proposing to construct a Hospital Building at Tirumala Enclave in

    Pothireddypally (V), Sangareddy (M), Medak Dt in Telangana State.

    Fig. 1 gives the site plan.

    The aim of this Report is to determine the depth of foundations and the safe bearing

    capacity, based on Field and Laboratory Investigations

    2. SCOPE OF WORK

    The geo technical Investigation job was awarded to M/s Geo Explorations,

    Hyderabad. The scope of the work is as follows :

    i) To drill four (4 ) Bore holes at specified locations as shown in Fig.1.

    ii) Collection of Samples from the Bore holes at significant depths

    iii) Conduct SPT as per IS : 2131 in the Bore holes

    iv) To conduct Laboratory Testing for relevant engineering properties

    v) To prepare a Technical report incorporating Field and Lab test results,

    recommending the foundations and SBC.

    All sub soil investigations are carried out in accordance with the following BIS (IS

    Codes).

    IS : 1892 .. Code of investigations for Subsurface Investigations

    IS : 2131 Method for Standard Penetration Test for soils

    Other applicable IS (BIS) Codes are listed in Appendix

    .

  • 7/26/2019 Soil Test for Hospital Building

    2/8

    3. FIELD INVESTIGATIONS

    a) BORE HOLES :

    The bore holes were planned so as to yield complete information in the effective and

    critical zones under the foundations.

    The following relevant data was recorded during drilling operations.

    Nature of strata Details of samples

    Rate of drilling Colour of water

    The bore holes were drilled to a depth of 6.0 m each below the existing GL.

    b) SPT :

    In addition, Standard Penetration Tests were conducted in the Bore holes, as per

    with IS : 2131. In this test, a standard weight is dropped through a specified height

    for a penetration of 300 m The number of blows is designated as N. According to the

    Code, if N exceeds 50, refusal is said to be reached, and further drilling is

    discontinued

    4. LABORATORY TESTING

    The soil samples were tested at the Geotechnical Engineering laboratory at

    Hyderabad. The following tests were performed on soil samples:

    a) Densityb) Natural Moisture contentc)Specific gravityd)Particle size analysis ( Sieve & Hydrometer )e)Atterberg Limitsf)Shear tests

    All the relevant tests were conducted as per IS : 2720.

    A brief description of various Tests is given below :

  • 7/26/2019 Soil Test for Hospital Building

    3/8

    a) Specific gravity :

    In this test as per IS : 2720-3, small quantity of the sample is tested using Specific

    gravity bottle . Weights are obtained with and without water, and Specific Gravity

    (G) is calculated. Low G indicates the presence of chalky components.

    b) Bulk Density :

    The test is conducted as per IS : 2720- 29. The weight and volume of the sample

    give the bulk density.

    c) Moisture content :

    The test is conducted as per Is : 2720 -4. Weights of the wet sample and dry smple (

    after oven- drying ) are determined to evaluate the moisture content.

    d) Grain size analysis :

    The test is conducted as per Is : 2720 -4. In this test, Sieves are used to separate

    different sizes of coarse grained particles into gravel, sand and fines.

    Hydrometer is used the differentiate silt and clay size particles.

    e) Shear Test :

    Direct shear test is conducted as per IS : 2720-13. A block of sample is tested in

    shear to determine the friction and cohesion parameters of the soil.

    5. RESULTS

    Fig. 2 gives the Summary of Bore Logs. The strata details, depth wise, are

    given.

    Table 1 gives the soil properties.

  • 7/26/2019 Soil Test for Hospital Building

    4/8

    6. FOUNDATIONS

    Following is the generalized profile of sub soil.:

    Depth below GL Strata N value

    0 -1.5 m Silt

    1.5 3 m Silty gravel 13 - 24

    3 6 m SDR >50 Refusal

    No water is seen in the BH ,

    The soft disintegrated rock is weathered and fissured, and is relatively soft.

    Significant portions of the rock show discoloration and weathering effects. The rock

    has dull sound under hammer, and shows significant loss of strength as compared

    with fresh rock. The degree of weath ering may be termed moderate.

    Open foundations are recommended.

    Appendix gives the calculations for SBC.

    7. RECOMMENDATIONS :

    Based on Field Investigations and Laboratory Tests, following recommendations are

    given for the proposed Hospital Building at Tirumala Enclave in Pothireddypally (V),

    Sangareddy (M), Medak Dt in Telangana State.

    The recommendations are based on (4) Bore holes of depth 6 m each.

    a) Following is the generalized profile of the site :

  • 7/26/2019 Soil Test for Hospital Building

    5/8

    Depth below GL Strata N value

    0 -1.5 m Silt

    1.5 3 m Silty gravel 13 - 24

    3 6 m SDR >50 Refusal

    No water is seen in the BH ,

    b) Open foundations ( Footings) are recommended.

    c) It is understood that there will be a Cellar for the Building. Accordingly, SBC for

    Open foundations is recommended as follows :

    Depth of foundation

    below cellar level

    Resting in Strata Recommended SBC

    1 m SDR 40 t / sq m

    d) The actual size of the foundations will be based on the loads from the

    superstructure.

    For GEO EXPLORATIONS

    Pramod Nair

    Consulting Geologist

  • 7/26/2019 Soil Test for Hospital Building

    6/8

    TABLE 1 :

    SUMMARY OF SOIL PROPERTIES

    HOSPITAL BUILDING AT POTHIREDDYPALLY (V)SANGAREDDY, MEDAK DT., TELANGANA STATE

    BH No.Depth

    , mSoil Moistur

    econtent

    %

    Specific

    Gravity

    Grain size,percentage

    KN/

    Cum

    ShearParameters

    Gr

    >4.75mm

    Sa

    4.75to

    0.075mm

    Si

    .075to

    .002mm

    Cl

  • 7/26/2019 Soil Test for Hospital Building

    7/8

    Appendix :

    Calculation of SBC

    HOSPITAL BUILDING AT POTHIREDDYPALLY (V)SANGAREDDY, MEDAK DT., TELANGANA STATE

    FOUNDATIONS RESTING IN SDR ( Based on N Value)

    a) Shear Criterio n :

    Assumed value of N = 50

    Assumed width of foundation =2 m

    Assumed depth of foundation = 1 m inside SDR

    Correction factors Rq = Rr = 0.5

    With a F.S. of 3 ,

    Allowable q = 1 / 18 [ 2 N 2 B Rr + 6 ( 100 + N 2 ) D Rq ] = 711 kN / sq m

    b) Set t lement Cr i ter ion :

    For permissible settlement of 40 mm,

    Allowable Bearing Pressure = 12.25 N ( B + 0.3) / B

    = 704 kN / sq m

    Adopt 400 kN / sq m .

    c) As p er IS : 8009 ( Fig . 2 ) Code of Pract ice for ca lcula t ion of s e t t lements o f

    founda t ions :

    For N = 50, B = 2 m ,

    Settlement = 0.0048 m per unit pressure of 1 kg / sq cm

  • 7/26/2019 Soil Test for Hospital Building

    8/8

    For a pressure of 40 t/ sq m,

    Settlement = 0.004 x 4.8 x1000 = 19.2 mm OK

    d) As p er IS : 12070 ( Code of Pract ice for Design & Con struct io n of Shal low

    Founda t ions on Rocks ) :

    Weathered and disintegrated rock is treated under Classification No. V of

    Table 3 of the Code

    For this very poor rock , net allowable bearing pressure is recommended as

    45 t / sq m , for settlement less than 12 mm.

    Keeping the above considerations in view, Recommended Safe Bearing

    Capacity is 40 t per sq m