Soft Starters Page
Single-phase Soft Starters SAS 3 - 22kW 1.01
Two-phase Soft Starters DUOSTART 1,5 - 5,5kW 1.03
VS II …-17 … 45 7,5 - 22kW 1.05
VersiStart II … LDS 3 - 15kW 1.07
VS II …-50 ... 75 25 - 37kW 1.09
VersiStart i II 18 … 200 7,5 - 110kW 1.11
Three-phase Soft Starters MICROSTART 1,5 - 3kW 1.13
MINISTART 1,5 - 11kW 1.15
DAS-T 7,5 - 55kW 1.17
NEW: VersiStart i III … -23 … 220 7,5 - 110kW 1.19
NEW: VersiStart i III … -255 … 1600 132 - 500kW 1.21
Dimensioning Rules for Soft Starters 1.23
11/10
Features:
A single-phase controlled soft starter A all devices for pole-changing motors A dual-voltage, for 400V and 230V networks A terminal arrangement suitable for switchgear connection A for snap-mounting on 35mm standard rail A integrated bypass relay A no mains neutral conductor (N) required A special voltages up to 640V A also for single-phase applications A degree of protection IP 20 (SAS 3 ... SAS 11) degree of protection IP 00 (SAS 11PUST, 22PUST)
Function:
A soft start A 2 separately adjustable parameters starting torque, starting time A control contact for pole-changing motors
Upon Request:
A potential-free input control voltage 10 ... 30VDC
A SAS 3 up to SAS 11: standard up to 480V special voltages 500V up to 640V (all types in 100mm-housing)
A SAS 11PUST and SAS 22PUST: special voltages up to 690V
Technical Data SAS 3 5,5 7,5 11 11PUST 22PUST Mains / Motor voltage X1-X2 jumpered according to DIN EN 50160 (IEC 38)
160 ... 240V 10% 400V 15%
Mains / Motor voltage X1-X2 not jumpered according to DIN EN 50160 (IEC 38)
380 ... 480V 10%
Device nominal current 6,5A 12A 16A 25A 25A 45A Mains frequency 50/60HzMotor rating at 230V 1,5kW 3kW 4kW 5,5kW Motor rating at 400V 3kW 5,5kW 7,5kW 11kW 11kW 22kW min. motor current 10% of the device rated current Starting torque 0 ... 50% Starting time 0,5 ... 5s Reset time 200msmax. Switching cycle at 3x Ie and 5s tan 240/h 200/h 120/h 70/h 240/h 120/h max. Cross-sectional area 2,5mm² 16mm² I²t-Value Power semiconductor in A²s 265 610 800 1250 5000 10500 Ambient / Storage temperature 0°C ... 45°C / -25°C ... 75°C Weight / kg 0,3 0,3 0,5 0,5 2,7 3,0 Order number 20700.
4000320700.40005
20700.40007
20700.40011
20800.38011
20800.38022
Please observe supplementary sheet with dimensioning rules.
Soft StartersSAS 3 ... 11 SAS 11PUST, 22PUST
Soft Starters SAS 3 ... 11, SAS 11PUST, SAS 22PUST
Typical Applications:
packaging machinery sliding doors belt drives conveying machinery door drives of passenger and goods lifts limitation of starting current for transformers
1.01
control contactfor pole-changing
Motors
4T22T1 6T3 X3 X4
Controlfor
bypass
3L21L1 5L3
Trigger pulsegenerator
X1
Voltageselection
X2
Ramp-functiongenerator
M
t
Subject to change without notice.
Dimensions:
Connection Diagrams:
Soft Starters SAS 3 ... 11, SAS 11PUST, SAS 22PUST1.02
SAS 3/5,5 SAS 11PUST, 22PUST
100
SAS 7,5/11
73
120
12245
73
146175
Depth: 172mmfor M4
185
200
M~
SAS 3 ... 22PUST
Reverse circuit for pole-changing motors
X3
X3
L1 L1
K2
S21L1 3L2 5L3 X1 X2 X3 X4
SAS 3 ... 22PUST
PE
UbVbWb
4T22T1
K1
6T3
UaM3 ~ Wa
Va
K1
K2
L2L3NPEPEPEPE
K2 K31L1 3L2 5L3 X1 X2
K1 K3
K3
PE
UbVbWb 3
4T22T1
K1
6T3
12
Selectorswitch
L2L3NPE
K4
SAS 3 ... 22PUST
Standard circuit for pole-changing motors
~~PE 3M
4T2
3L2
2T1
1L1
6T3
X15L3 X2 X3 X4
K1
N
L1
L3L2
PE
Standard circuit
K1
~~PE 3M
SAS 3 ... 22PUST4T2
3L2
2T1
1L1
6T3
5L3 X2X1
Onswitch
N
L1
L3L2
PE
K1
Reverse circuit
Single-phase motor 230V AC
The terminal destinationfor SAS 11PUST and SAS 22PUST are likefollowing:
L1 - 1L1L2 - 3L2L3 - 5L3 U - 2T1 V - 4T2W - 6T3
By jumpering the contacts X1/X2 diveces SAS 3, SAS 5,5, SAS7,5 and SAS 11 can alsobe used for 220/240V networks.(no at SAS 11PUST and SAS 22PUST).
EMCThe limit values for emitted interference accordingto the applicable device standards do not rule outthe possibility that receivers and susceptible electronicdevices within a radius of 10m are subjectedto interference.If such interference, that is definitely attributable to theoperation of the soft starters "SAS", occurs, the emitted interference can be reduced by taking appropriatemeasures. Such measures are, e.g.:to connect reactors (3mH) or a suitable mains filter inseries before the soft starter, or to connect X-capacitors (0,15µ F) in parallel to the supply voltageterminals.
X4
K1
Ua
WaVa
K1 K2
K2
K3
K3
Reversingswitch
Selectorswitch
K4K5
K2 K3 S2
K5 0L R
S2
K4 K5
12
1L1
2T1
2T1
1L1
Single-phase application
Connection to single-phase networks
K1
X4
K2
K2
K1
0
K2
LS
R
Reversingswitch
Single-phase motor 230V AC
In the case of 400V single-phase networksremove jumper X1/X2
Start
3L2 5L3 X1 X2
4T2 6T3
SAS 3/5,5
X3 X4
M
L1N230V AC
X3
Start
SAS 7,5/11
3L2
4T2
5L3 X1 X2
6T3
N L1230V AC
L1230V AC
X4
M
11/10
Features:
A two-phase controlled soft starter A easy mounting, also for retrofitting into existing plants A integrated bypass relay A no mains neutral conductor (N) required A parameterization by means of three potentiometers A economically priced replacement for star/delta switches A for mounting on top hat rail A current reduction during acceleration A very compact design, overall width from 45mm on A degree of protection IP20
Function:
A soft start and soft stopp potential-free control input for soft start and soft stop A 3 separately adjustable parameters starting torque, acceleration time, deceleration time A control (start/stop) with contact or voltage 10-42VDC
Options: (upon request)
A DUOSTART ... M (beginning of acceleration until end of deceleration) A DUOSTART ... S control (start/stop) with voltage 10-42VDC A external 24V supply voltage (wide voltage range capability)
Technical Data DUOSTART 1,5 3 5,5 Mains / Motor voltage according to DIN EN 50160 (IEC 38) 400V 10% 50/60Hz
Device nominal current 3,5A 6,5A 12A Motor rating at 400V mains voltage 1,5kW 3kW 5,5kW min. motor current 40% of the device rated current Starting torque 0 ... 80% Acceleration time 0,5 ... 12s Deceleration time 0,5 ... 12s Reset time 200msmax. Switching cycle at 3x Ie and 5s tan 200/h 120/h 70/h max. Cross-sectional area solid stranded
2x 2,5mm² 2x 1,5mm²
2x 2,5mm² 2x 1,5mm²
2x 2,5mm² 2x 1,5mm²
I²t-Value Power semiconductor in A²s 72 265 610 Ambient / Storage temperature 0°C ... 45°C / -25°C ... 75°C Weight / kg 0,4 0,4 0,4 Special voltages 230V 230V
480V230V480V
Order number Option „M“ Option “S”
21500.40001 21501.40001 21502.40001
21500.40003 21501.40003 21502.40003
21500.40005 21501.40005 21502.40005
Please observe supplementary sheet with dimensioning rules.
Soft StartersDUOSTART 1,5 ... 5,5
Soft Starters DUOSTART 1,5 ... 5,5
Typical Applications:
door and gate drives pumps, ventilators conveyorspackaging machinery transformer soft start
1.03
6T34T22T1
5L33L21L1
X4
X3
X2
X1
Supplyvoltage
Electronics
Triggerpulse
generatorRampcontrol
Controlfor
bypass
t an(t acc)
t aus(t dec)
M an (M acc)
Option
Startcontact
Operationalstatus
Subject to change without notice.
Dimensions:
Mounting dimensions W H D DUOSTART 1,5 ... 5,5 45mm 73mm 122mm
Connections Diagramms:
Soft Starters DUOSTART 1,5 ... 5,51.04
W
H
D
For pole-changing motors trimmer t aus to 0 (left stop)
Ua
X21L1 3L2 5L3 X1
DUOSTART 1,5 ... 5,54T22T1
PE
UbVbWb
M3 ~
K1
6T3
L2L3NPE
WaVa
K1 K2
K2
K1 K3
K3
K2 K3 S2 21
Selectorswitch
S - closed = soft start; S - open = soft stop
Standard circuit for pole-changing motors
~
DUOSTART 1,5 ... 5,5
M
L1
3PE
3L2
4T2
1L1
2T1
X25L3
6T3
X1
S
Standard circuit
L2L3NPE
L1
Ua
X21L1 3L2 5L3 X1
DUOSTART 1,5 ... 5,54T22T1
PE
UbVbWb
M3 ~
K1
6T3
L2L3NPE
K4
WaVa
K1 K2
K2
K1 K3
K3
K4Reversingswitch
K5
K2 K3 S2
K5 0L R
S2
K4 K5
21
Selectorswitch
The limit values for emitted interference accordingto the applicable device standards do not rule outthe possibility that receivers and susceptible electronicdevices within a radius of 10m are subjectedto interference.If such interference, that is definitely attributable to theoperation of the soft starters "DUOSTART", occurs,the emitted interference can be reduced by takingappropriate measures. Such measures are, e.g.:to connect reactors (3mH) or a suitable mains filter inseries before the soft starter, or to connect X-capacitors (0,15µ F) in parallel to the supply voltageterminals.
Reverse circuit for pole-changing motorsL1
EMC
S - closed = soft start; S - open = soft stop
~
DUOSTART 1,5 ... 5,5
M3PE
3L2
4T2
1L1
2T1
X25L3
6T3
X1
S
Reverse circuit
L2L3NPE
L1
K1
K2
K1 K2
K1
L
K2
0R
S1
Reversingswitch
Please observe supplementary sheet with dimensioning rules.
06/11
supplyvoltage
Triggerpulse
generator
6T32T1 4T2
Controlfor
bypass
5L31L1 3L2
Electronics
Rampcontrol
Start
U start
X8
X7RA2
t acc t dec
X3
X2
Boost
X6
X5RA1
X1
X4control supply U 24VDCat option "B"
+s
Features:
A two-phase controlled soft starter A controlled by microcontroller A optimized soft start A connection in the motor delta winding (cost saving via smaller rating) A current and torque reduction during acceleration A easy mounting, for snap-mounting on 35mm standard rail A integrated bypass relay A parameterization by means of three potentiometers A no additional control voltage required A no mains neutral conductor (N) required A economically priced substitute for star-delta starters A plug-in power terminals A control outputs with spring-loaded terminals A heat sink temperature monitoring A compact design, 45mm up to 32A and 52.5mm at 45A A degree of protection IP20
Function:
A soft acceleration and deceleration A potential-free control input for soft acceleration and deceleration A 3 separately adjustable parameters accel. time, start voltage, decel. time A boost-start selectable A potential-free relay output for operating state – unit bypassed – and failure
Options (upon request)
A special voltages 230V and 480V A wide voltage range 400-600V with external control supply voltage US 24VDC (B) A signaling contact (M)
beginning of acceleration until end of deceleration A motor PTC
Technical Data (standard) VS II 400-17 VS II 400-25 VS II 400-32 VS II 400-45 Mains / Motor voltage according to DIN EN 50160 (IEC 38) 400V 10% 50/60Hz
Rated device current 17A 25A 32A 45A Motor rating at 400V mains voltage 7,5kW 11kW 15kW 22kW max. Power dissipation - in operation - in standby
29,5W7,5W
29,5W7,5W
28,5W7,5W
27W7,5W
min. motor current 20% of the device rated current Acceleration time 0,5 … 10s Start voltage 40 … 80% Deceleration time 0,5 ... 10s Restart time 200msmax. Switching frequency at 3x Ie and 5s tan 50/h 35/h 25/h 10/h Cross-sectional area: Control terminals Power terminals
1,5mm²6mm²
1,5mm²16mm²
I²t - Power semiconductor in A²s 4900 4900 6050 6600 Tightening torque 1,2-1,5 Nm
11-13 Ibs in 1,5-1,7 Nm 13-15 Ibs in
Input resistance Control inputs 10kSwitching rating of relay output RA1/RA2 3A/250VAC; 3A/30VDC Overvoltage category / Pollution degree III (TT / TN systems) / 2 Installation class 3Surge strength 4kVAmbient / Storage temperature 0°C ... 45°C up to an altitude of 1000m / -25°C ... 70°C Weight / kg 1Special voltages (optional) 230V / 480V / wide voltage range 400-600V
with external control supply voltage US 24VDC 10%/150mA Order number 25700.40017 25700.40025 25700.40032 25700.40045
Soft StartersVS II …-17…45
Soft Starters VersiStart II …-17…45
Typical Applications:
door and gate drives pumps, ventilators, fans conveying systems packaging machines transport systems, assembly lines machine applications
1.05
Subject to change without notice.
Dimensions:
Mounting dimensions a b c d e VS II …- 17…32 125 158 53 45 173 VS II …- 45 125 158 53 52.5 178 All dimensions indicated in mm.
Connection Diagram:
Soft Starters VersiStart II …-17…451.06
On
Bypass
versi start II
12345678
0100%
0100%
0100%t
t
UStart
c
b
a
d
e
L1 L2 L3
T1 T2 T3
The limit values for emitted interference accordingto the applicable device standards do not rule out the possibility that receivers and susceptible electronic devices within a radius of 10m are subjectedto interference.If such interference, which is definitely attributable to theoperation of the soft starters "VersiStart II … ", occurs,the emitted interference can be reduced by takingappropriate measures.Such measures are, e.g.:To connect reactors (3mH) or a suitable mains filter inseries before the soft starter, or to connectX-capacitors (0.15µF) in parallel to thesupply voltage terminals.
S - closed = acceleration; S - open = deceleration
X3
~M
3L2
4T2
VersiStart II ...
3PE
1L1
2T1
5L3
6T3
X2
S
Standard circuit
L2
L3
N
PE
L1
EMC
X1
Star
t
X7X6X5 X8
X4
Ext. control voltage10 ... 24VDC
Fault Devicebypassed
Boos
t
RA1 RA2
F
11/10
Features:
A two-phase controlled soft starter A controlled by microcontroller A easy mounting, also for retrofitting into existing plants A integrated bypass relay A no additional control voltage required A no mains neutral conductor (N) required A parameterization by means of three potentiometers A economically priced substitute for star-delta starters A current reduction during acceleration A circuit-board version for mounting onto DIN rail A plug-in control terminals A degree of protection IP00
Function:
A soft acceleration and deceleration A potential-free control input for
soft acceleration and deceleration A 3 separately adjustable parameters:
starting torque, accel. time, decel. time A two wire or three wire control via contact or voltage 10-42VDC A boost-start selectable
Options: (upon request)
A Special voltages 230V and 480V
Technical Data VS II 3 LDS VS II 5,5 LDS VS II 7,5 LDS VS II 11 LDS VS II 15 LDS Mains / Motor voltage according to DIN EN 50160 (IEC 38) 400V 10% 50/60Hz
Rated device current 6,5A 12A 15A 25A 32A Motor rating at 400V mains voltage 3kW 5,5kW 7,5kW 11kW 15kW min. motor current 20% of the device rated current Starting torque 0 ... 80% Acceleration time 0,5 ... 10s Deceleration time 0,5 ... 10s Restart time 200msmax. Switching frequency at 3x Ie and 5s tan 120/h 65/h 100/h 65/h 35/h Cross-sectional area FASTON 6.3 1,5mm² 2,5mm² litz 2,5mm² I²t – Power semiconductor in A²s 265 610 4900 4900 6050 Techn. parameter of relay output RA1 3A/250VAC; 3A/30VDC Techn. parameter of open-collector LO1 24VDC / 200mA Ambient / Storage temperature 0°C ... 40°C / -25°C ... 75°C Weight / kg 0,27 0,4 Special voltages (optional) 230V / 480V Order number 25723.40003 25723.40005 25723.40007 25723.40011 25723.40015 Please observe supplementary sheet with dimensioning rules.
Soft StartersVS II 3 ... 15LDS
Soft Starters VersiStart II 3 ... 15LDS
Typical Applications:
door and gate drives pumps, ventilators conveying systems packaging machines
1.07
Supplyvoltage
Triggerpulse
generator
6T32T1 4T2
Controlfor bypass
5L31L1 3L2
Electronics
Rampcontrol
Start
M an(M acc)
X2Option
X1
RA1
X6
t an(t acc)
t aus(t dec)
X5
X7
Boost
X3 X8LO1
X4Stop
Subject to change without notice.
Dimensions:
Mounting dimensions a b c d e f g h VS II 3 ... 5.5LDS 102,5 108,5 98,5 92,5 82,5 5,0 55,0 40 VS II 7.5 ... 15LDS 102,5 139,0 129,0 92,5 82,5 5,0 55,0 40 All dimensions indicated in mm.Connection Diagrams:
Soft Starters VersiStart II 3 ... 15LDS1.08
X1 d a
cb
35m
m
hg
f
3L2
6T34T2
5L32T1
1L1
e
for pole-changing motors turn trimmer t aus to 0 (left stop)
The limit values for emitted interference according to theapplicable device standards do not rule out the possibilitythat receivers and susceptible devices within a radius of 10m are subjected to interference.If such interference, which is definitely attributable to theoperation of the soft starters "VersiStart II...LDS", occurs,the emitted interference can be reduced by takingappropriate measures.Such measures are, e.g.:To connect reactors (3mH) or a suitable mains filter inseries before the soft starter, or to connect X-capacitors(0.15µ F) in parallel to the supply voltage terminals.
Ua
X61L1 3L2 5L3 X5
4T2VersiStart II 3 ... 15LDS
2T1
PE
UbVbWb
M3 ~
K1
6T3
L2L3NPE
WaVa
K1 K2
K2
K1 K3
K3
K2 K3 S2 21
Selectorswitch
S - closed = acceleration; S - open = deceleration
Standard circuit for pole-changing motors
X6
~M
3L2
4T2VersiStart II 3 ... 15LDS
L1
3PE
1L1
2T1
5L3
6T3
X5
S
Standard circuit
L2L3NPE
L1
Ua
X61L1 3L2 5L3 X5
4T2VersiStart II 3 ... 15LDS
2T1
UbVbWb
M3 ~
K1
6T3
L2L3NPE
K4
WaVa
K1 K2
K2
K1 K3
K3
K4Reversingswitch
K5
K2 K3 S2
K5 0L R
S2
K4 K5
21
Selectorswitch
Reversing circuit for pole-changing motorsL1
EMC
S - closed = acceleration; S - open = deceleration
X6
~M
3L2
4T2VersiStart II 3 ... 15LDS
3
1L1
2T1
5L3
6T3
X5
S
Reversing circuit
L2L3NPE
L1
K1
K2
K1 K2
K1
L
K2
0R
S1
Reversingswitch
PE
PE
Please observe supplementary sheet with dimensioning rules.
11/10
Features:
A two-phase controlled soft starter A controlled by microcontroller A optimized soft start A heatsink temperature detection A connection in the motor delta winding (cost saving via
smaller rating) A current and torque reduction during acceleration A easy mounting, also for retrofitting into existing plants A integrated bypass relay A parameterization by means of four potentiometers A no additional control voltage required A no mains neutral conductor (N) required A economically priced substitute for star-delta starters A control outputs with spring-loaded terminals A compact design, 103mm width A degree of protection IP20
Function:
A soft acceleration and deceleration A potential-free control input for
soft acceleration and deceleration A 4 separately adjustable parameters
accel. time, start voltage, decel. time, max. start current
A boost-start selectable A Motor PTC A current controlled start-up with external transformer (transformer is included in delivery) A potential-free control output for operating state – unit bypassed – and failure
Options: (upon request)
A special voltages 230V and 480V A wide voltage range 200-400V or 400-600V with external control
supply voltage US 24VDC (option B)
Technical Data (standard) VS II 400-50 VS II 400-65 VS II 400-75 Mains / Motor voltage according to DIN EN 50160 (IEC 38) 400V 10% 50/60Hz
Rated device current 50A 65A 75A Motor rating at 400V mains voltage 25kW 30kW 37kW max. Power dissipation - in operation - in standby
30W10W
min. motor current 20% of the device rated current Acceleration time 0,5 … 10s Start voltage 40 … 80% Deceleration time 0,5 ... 10s max. Start current 200% - 500% of the device rated current Restart time 200msmax. Switching frequency at 3x Ie and 10s tan 35/h 25/h 30/h I²t - Power semiconductor in A²s 6600 11200 25300 Cross-sectional area: Control terminals Power terminals
0,2 - 2,5mm²/24 – 12 AWG solid 1 - 35mm², 18 – 2 AWG / stranded 1 – 25mm², 18 – 3 AWG
Tightening torque (power terminals) 25mm² = 2,5 Nm 35mm² = 4,5 Nm 25mm² = 22 Ibs in 35mm² = 40 Ibs in
Input resistance Control inputs 10kSwitching rating of relay output RA1/RA2/RA3 3A/250VAC; 3A/30VDC Overvoltage category / Pollution degree III (TT / TN systems) / 2 Installation class 3Surge strength 4kVAmbient / Storage temperature 0°C... 45°C up to an altitude of 1000m / -25°C ... 70°C Weight / kg 1,5 1,5 2,2 Special voltages (optional) 230V / 480V /wide voltage range 200-400V or 400-600V
with external control supply voltage US 24VDC 10%/150mA Order number 25700.40050 25700.40065 25700.40075
Soft StartersVS II …-50…75
Soft Starters VersiStart II …-50…75
Typical Applications:
door and gate drives packaging machines pumps, ventilators, fans transport systems, assembly lines conveying systems machine applications
1.09
6T32T1 4T2
5L31L1 3L2
X12
X11RA2
X3
X2
X10
X9RA1
X14 X13RA3
I T
U USupplyvoltage
Triggerpulse
generator
Controlfor
bypass
Electronics
Ramp control
t acc t dec
U start
Start
Boost
X1 X4 X7 X8 X5 X6
I
Subject to change without notice.
Dimensions:
Mounting dimensions a b c d e VS II …- 50…65 103 230 125 86 220 VS II …- 75 103 230 140 80 220All dimensions indicated in mm.
Connenction Diagramm:
Soft Starters VersiStart II …-50…751.10
1L1 3L2 5L3
2T1 4T2 6T3
d
e
a
b
c
X3
~M
3L2
4T2VersiStart II ...
3PE
1L1
2T1
5L3
6T3
X2
Standard circuit
L2L3NPE
L1
X1
Star
t
X11X10X9 X12
X4
ext. control voltage10 ... 24VDC
FaultDevicebypassed
Boos
t
RA1 RA2
F
X13 X14RA3
Motorruns
X5 X6
X7 X8
currenttransformer
The limit values for emitted interference accordingto the applicable device standards do not rule out the possibility that receivers and susceptible electronic devices within a radius of 10m are subjectedto interference.If such interference, which is definitely attributable to theoperation of the soft starters "VersiStart II … ", occurs,the emitted interference can be reduced by takingappropriate measures.Such measures are, e.g.:To connect reactors (3mH) or a suitable mains filter inseries before the soft starter, or to connectX-capacitors (0.15µF) in parallel to thesupply voltage terminals.
EMCMotorthermistor
03/11
Control
Control voltage
Triggerstage
Monitoring
2/T1 6/T34/T2
1/L1 5/L33/L2
Voltagesupply
A1 A3
Controlinputs
2 Relayoutputs
Thermistor
A2
0102
13142324
B4 B5
Controlfor
bypass
Features:
A two-phase controlled soft starter A controlled by microcontroller A integrated bypass relay A current and torque reduction during acceleration A integrated motor overload protection A motor PTC connection A voltage range 200 - 440V or 200 - 575V A degree of protection: IP20 (up to 100A), IP00 (from 140A up)
Function:
A 2 relay outputs A acceleration time monitoring A Adjustable parameters: - rated motor current - current ramp - current limit - soft stop – ramp time - motor protection class - output relay function - phase rotation protection
Accessories:
A ext. operating panel and interface (29000.25901) A USB module (29000.25910) A DeviceNet module (29000.25903) A Modbus module (29000.25904) A Profibus module (29000.25905) A Finger protection (29000.25907)
Technical Data VS i II 440 - 18C1 34C1 42C1 48C1 60C1 75C1 85C1 100C1 140C1 170C1 200C1 18C2 34C2 42C2 48C2 60C2 75C2 85C2 100C2 140C2 170C2 200C2Mains voltage according toDIN EN 50160 (IEC 38) 200-440V 45-66Hz
VS i II 575- 18C1 34C1 42C1 48C1 60C1 75C1 85C1 100C1 140C1 170C1 200C1 18C2 34C2 42C2 48C2 60C2 75C2 85C2 100C2 140C2 170C2 200C2Mains voltage according toDIN EN 50160 (IEC 38) 200-575V 45-66Hz Rated device current in A 18A 34A 42A 48A 60A 75A 85A 100A 140A 170A 200A Motor rating at 400V in kW 7,5 15 18,5 22 30 37 45 55 75 90 110 Current ramp 2s, 5s, 15s with 150%, 200% and 250% In Current limit 250%, 275%, 300%, 325%, 350%, 375%, 400%, 425%, 450% In Motor protection class adjustable Deceleration time 2s – 20s Switching frequency 4x Ie and 6s AC 53b 10/h AC 53b 6/h Techn. parameter of relay outputs 6A/30VDC; 2A/400VAC Ambient temperature -10°C…+40°C (+60°C Derating) Control voltage C1: 110-240VAC -15%/+10% 380-440VAC -15%/+10%; C2: 24VDC/24 VAC 20%Weight / kg 2,4 4,3 6,8 Order number: 440V/C1 25900.44… 018 034 042 048 060 075 085 100 140 170 200440V/C2 25901.44… 018 034 042 048 060 075 085 100 140 170 200 575V/C1* 25900.57… 018 034 042 048 060 075 085 100 140 170 200 575V/C2* 25901.57… 018 034 042 048 060 075 085 100 140 170 200 * units with 575V are not available ex stock, upon request
Soft Starters VS i II 18 … 200
Soft Starters VersiStart i II 18 … 200 1.11
Typical Applications:
pumps, ventilators compressors mills, crushers, presses conveying systems drives with high-inertia starting
Subject to change without notice.
A3 A1 A2 01 02
A3 A1 A2 01 02
110 - 240VAC24VAC/24VDC
STAR
T
STOP
START/STOP
A3 A1 A2 01 02
A3 A1 A2 01 02
380 - 440VAC
STAR
T
STOP
START/STOP
Two - wire
Three - wire
Dimensions:
Connection Diagram:
B (mm) H (mm) T (mm) VS i II…-18 98 203 165 VS i II…-34 98 203 165 VS i II…-42 98 203 165 VS i II…-48 98 203 165 VS i II…-60 98 203 165 VS i II…-75 145 215 193 VS i II…-85 145 215 193 VS i II…-100 145 215 193 VS i II…-140 202 240 214 VS i II…-170 202 240 214 VS i II…-200 202 240 214
Soft Starters VersiStart i II 18 … 200
B
TH
3
2
1L1 L2 L3
1/L1 3/L2 5/L3 A3 A1(+)
A2(-)
01 02 B4 B5
Thermistor
Controlvoltage
1 - C12 - C13 - C2
380 - 440VAC110 - 240VAC24VAC/24VDC
Maincontactor
Progr.output
2/T1 4/T2 6/T3
13 14 23 24
M3 ~
1.12
11/10
Features:
A three-phase controlled soft starter A easy mounting, also for retrofitting into existing plants A terminal arrangement suitable for switchgear connection A for snap-mounting on 35mm standard rail A integrated bypass relay A no mains neutral conductor (N) required A functional peak current reduction A degree of protection IP 20
Function:
A soft acceleration and deceleration A 4 separately adjustable parameters
starting torque, acceleration time, soft stop torque, deceleration time
A soft start and soft stop via control contact possible
Upon Request:
A potential-free input -control voltage 10 ... 30VDC
Option: (upon request)
A „SST“ - pluggable
Technical Data MICROSTART 1,5 3
Mains / Motor voltage according to DIN EN 50160 (IEC 38) 400V 15% 50/60Hz
Device nominal current 4A 6.5A Motor rating 1,5kW 3kW min. motor current 10% of the device rated current Adjustment range of starting torque 0 ... 80% Adjustment range of acceleration time 1 ... 15s Adjustment range of soft stop torque 20 ... 80% Adjustment range of deceleration time 0 ... 15s Reset time 200msmax. Switching cycle at 3x Ie and 10s tan 120/h 60/h max. Cross-sectional area 2,5mm² I²t-Value Power semiconductor in A²s 40 450 Ambient / Storage temperature 0°C ... 45°C / -25°C ... 75°C Weight / kg 0,75 0,75 Order number Option „SST“
21300.38001 21304.38001
21300.38003 21304.38003
Please observe supplementary sheet with dimensioning rules.
Soft StartersMICROSTART 1,5 / 3
Soft Starters MICROSTART 1,5 / 3
Typical Applications:
pumps, ventilators belt drives, driving pulleys / coil winders conveying machinery compressors
1.13
Control forbypass
Triggerpulse
generator
U V W
L3L1 L2
Supplyvoltage
Rampcontrol
Startcontact
M an(M acc)
M aus(M dec)
t an(t acc)
t aus(t dec)
Electronics
Subject to change without notice.
Dimensions:
Connection Diagram:
Soft Starters MICROSTART 1,5 / 31.14
166
106
55
23
118
55
128
Option "SST"MICROSTART 1,5/3
168All dimensions in mm!
EMCThe limit values for emitted interference accordingto the applicable device standards do not rule outthe possibility that receivers and susceptible electronicdevices within a radius of 10m are subjectedto interference.If such interference, that is definitely attributable to theoperation of the soft starters "MICROSTART", occurs,the emitted interference can be reduced by takingappropriate measures. Such measures are, e.g.:to connect reactors (3mH) or a suitable mains filter inseries before the soft starter, or to connect X-capacitors (0,15µ F) in parallel to the supply voltageterminals.
For pole-changing motors trimmer t aus to 0 (left stop)
Ua
U V 1 3V W
PE
UbVbWb
M3 ~
K1
MICROSTART 1,5 / 3L2L1
L2L3NPE
L3 PE
WaVa
K2
K2 K1
K3K2
K1 K3
K3
S2 21
Selectorswitch
S - closed = soft start; S - open = soft stop
Standard circuit for pole-changing motors
~
MICROSTART 1,5 / 3
M
L2
L1
3PE
U V
L1 L3 PE
W 1 3
Standard circuit
L2L3NPE
L1
Ua
U V W 1 3
PE
UbVbWb
M3 ~
K1
MICROSTART 1,5 / 3L2L1
L2L3NPE
K4
L3 PE
WaVa
K2
K2 K1
K3K2
K1 K3
K3
K4Reversingswitch
K5
S2
K5 0L R
S2
K4 K5
21
Selectorswitch
Reverse circuit for pole-changing motorsL1
S
S - closed = soft start; S - open = soft stop
~
MICROSTART 1,5 / 3
M
L2
3PE
U V
L1 L3 PE
W 1 3
Reverse circuit
L2L3NPE
L1
K1
K2
K1 K2
K1
L
K2
0R
S1
Reversingswitch
S
11/10
Features:
A three-phase controlled soft starterA easy mounting, also for retrofitting into existing plants A terminal arrangement suitable for switchgear connection A for snap-mounting on 35mm standard rail A integrated bypass relay A extensive monitoring functions A robust metal housing A no mains neutral conductor (N) required A special voltages up to 600V A functional peak current reduction A degree of protection IP 20
Function:
A soft acceleration and deceleration A 4 separately adjustable parameters starting torque, acceleration time, soft stop torque, deceleration time A potential-free input for soft start or soft stop -control voltage 10 ... 30VDC A potential-free output for fault indication A potential-free output for operational status * -loadable with 250V/8A each A temperature monitoring A phase-failure monitoring during ramp-up
*- with standard devices closed, when power semiconductors are bridged - with option “S” closed from start of acceleration to end of deceleration
Technical Data MINISTART 1,5 3 5,5 7,5 11 Mains / Motor voltage according to DIN EN 50160 (IEC 38) 400V 15% 50/60Hz
Device nominal current 4A 6,5A 12A 16A 25A Motor rating 1,5kW 3kW 5,5kW 7,5kW 11kW min. motor current 10% of the device rated current Starting torque 0 ... 80% Acceleration time 1 ... 20s Soft stop torque 20 ... 80% Deceleration time 0 ... 20s Reset time 200msmax. Switching cycle at 3x Ie and 10s tan 120/h 60/h 20/h max. Cross-sectional area Control terminals Power terminals
1,5mm²4,0mm²
I²t-Value Power semiconductor in A²s 40 450 550 9100 9100 Ambient / Storage temperature 0°C .... 45°C / -25°C ... 75°C Weight / kg 1,2 1,2 1,35 1,5 1,5 Order number 21200.38001 21200.38003 21200.38005 21200.38007 21200.38011 Please observe supplementary sheet with dimensioning rules.
Soft StartersMINISTART 1,5 ... 11
Soft Starters MINISTART 1,5 ... 11
Typical Applications:
pumps, ventilators cranestravelling and rotary operating mechanisms conveying machinery washing machines, linen dryers
1.15
U WV
L1 L3L2enclosure
internal temperature
supplyvoltage
phase-failure
recognition
triggerpulse
generator
controlfor
bridging
monitoring
pulseinhibitor
electronicssupply
(braking time)t aus
(t dec)t an
(t acc)
M aus(M dec)
(braking current)
M an(M acc)
rampcontrol
Fault
Startcontact
Operationalstatus
Subject to change without notice.
Dimensions:
W H D Mounting dimensions 166mm 106mm 117mm
Connection Diagram:
Soft Starters MINISTART 1,5 ... 111.16
HW D
For pole-changing motors trimmer t aus to 0 (left stop)
Ua
10 11U V 95 6 7 8W
PE
UbVbWb
M3 ~
K1
MINISTART 1,5 ... 11L2L1
L2L3NPE
L3 PE
12
WaVa
K2
K2 K1
K3K2
K1 K3
K3
S2 21
Selectorswitch
Standard circuit for pole-changing motors
10 11
~
MINISTART 1,5 ... 11
M
L2
L1
3PE
U V
L1
W 5 6 7 8 9
L3 PE
Standard circuit
L2L3NPE
L1
12
Ua
10 11U V 95 6 7 8W
PE
UbVbWb
M3 ~
K1
MINISTART 1,5 ... 11L2L1
L2L3NPE
K4
L3 PE
12
WaVa
K2
K2 K1
K3K2
K1 K3
K3
K4Reversingswitch
K5
S2
K5 0L R
S2
K4 K5
21
Selectorswitch
Reverse circuit for pole-changing motors
The limit values for emitted interference accordingto the applicable device standards do not rule outthe possibility that receivers and susceptible electronicdevices within a radius of 10m are subjectedto interference.If such interference, that is definitely attributable to theoperation of the soft starters "MINISTART", occurs,the emitted interference can be reduced by takingappropriate measures. Such measures are, e.g.:to connect reactors (3mH) or a suitable mains filter inseries before the soft starter, or to connect X-capacitors (0,15µ F) in parallel to the supply voltageterminals.
L1
EMC
10 11
~
MINISTART 1,5 ... 11
M
L2
3PE
U V
L1
W 5 6 7 8 9
L3 PE
Reverse circuit
L2L3NPE
L1
K1
K2
K1
12
K2
K1
L
K2
0R
S1
Reversingswitch
S
- +10 ... 30VDC15mA
control via contactcontrol via controlvoltage
11/10
Features:
A three-phase controlled soft starter A easy mounting, also for retrofitting into existing systems A terminal arrangement suitable for switchgear connection A integrated bypass contactor A no mains neutral conductor (N) required A functional peak current reduction A monitoring of heat sink temperature A monitoring of motor temperature via motor thermistor A potential-free control inputs and outputs A special voltages up to 690V A robust metal enclosure A degree of protection IP 20
Function:
A soft acceleration and deceleration A acceleration/deceleration via control contact or control voltage 10 ... 42VDC (selectable) A 4 separately adjustable parameters starting torque, acceleration time, soft stop torque, deceleration time A potential-free output for operational status* 250VAC/8A A fault signalling contact (250VAC/8A) A input for motor thermistor A for special voltages higher than 500V an external electronic supply (230VAC) is necessary.
* closed when power semiconductors are bridged, or closed from start of acceleration to end of deceleration
Technical Data DAS-T 7,5 11 15 22 30 37 55 Mains / Motor voltage (Standard) according to DIN EN 50160 (IEC 38) 400V 15% 50/60Hz (up to 690V upon request)
Device rated current 17A 25A 32A 48A 63A 75A 105A Motor rating 7,5kW 11kW 15kW 22kW 30kW 37kW 55kW min. motor current 10% of the device rated current Starting torque 0 ... 80% Acceleration time 0,5 ... 25s Soft stop torque 20 ... 80% Deceleration time 0 ... 15s Reset time 200msmax. Switching cycle at 3x Ie and 10s tan 120/h 100/h 80/h 60/h 40/h 40/h 20/h
1,5mm²Cross-sectional area Control terminals of connecting cable Power terminals 16mm² 35mm² I²t-Value Power semiconductor in A²s 3600 3600 8000 10500 18000 51200 125000 Ambient / Storage temperature 0°C ... 45°C / -25°C ... 75°C Weight / kg 3,8 3,8 4 4 7,8 8 8,2 Order number 20900.
4000720900.40011
20900.40015
20900.40022
20900.40030
20900.40037
20900.40055
Please observe supplementary sheet with dimensioning rules.
Soft StartersDAS-T 7,5 ... 55
Soft Starters DAS-T 7,5 ... 55
Typical Applications:
pumpsventilatorsconveying machinery dryers, washing machines compressors cranes, trolleys
1.17
Triggerpulse
generator
U V
Controlfor
bypass
W
L1 L2
Supplyvoltage
L3
Startcontact
Rampcontrol
M an(M acc)
M aus(M dec)
Operationalstatus
t an(acc) t aus(dec)
Motorthermistor
Faultindication
Controlelectronics
external electronicsupply 230VAC
option
Subject to change without notice.
Dimensions:
W [mm]
W’[mm]
H[mm]
H’[mm]
D[mm]
DAS-T 7,5 235 218 245 170 140 DAS-T 11 235 218 245 170 140 DAS-T 15 235 218 245 170 140 DAS-T 22 235 218 245 170 140 DAS-T 30 335 318 245 170 170 DAS-T 37 335 318 245 170 170 DAS-T 55 335 318 245 170 170
Connection Diagramms:
Soft Starters DAS-T 7,5 ... 551.18
H' H
W'
W
for M4
D
M~
Reversing circuit for pole-switching motors
Fault
11
Opera-tionalstatus
Opera-tionalstatus
for pole-changing motors turn trimmer t aus to 0 (left stop)
K2
S2L1 L2 L3PE 6 7
PE
UbVbWb
K1
T1 T2 T3DAS-T 7,5 ... 55
4PE
UaM3 ~ Wa
Va
K1
K2
5 1211Fault
Opera-tionalstatus9
L2L3NPE
L1
K2 K3102 L1 L2 L3PE
K1 K3
K3
PE
UbVbWb 3
K1
T1 T2 T3DAS-T 7,5 ... 55
4 5PE
1
Selectorswitch
L3NPE
L2L1
K4
9 10
Standard circuit for pole-changing motors
K1
S - closed = acceleration; S - open = deceleration
Opera-tionalstatus
PE T1 T2 T3 4
~M
3PE
L2DAS-T 7,5 ... 55
L1PE L39
5
Fault11 12
10 .. 42VDC
10S
+
6 7
Standard circuit
L2L3NPE
L1
K2
K2 K1
4 5PE T1 T2 T3
~M
3PE
L2L1 L3DAS-T 7,5 ... 55
9 10PE
L
Reversingswitch
0R
S1
L2L3NPE
L1
K1
Reversing circuit
The limit values for emitted interference according to the applicable device standardsdo not rule out the possibility that receiversand susceptible electronic devices within aradius of 10m are subjected to interference.If such interference, that is definitelyattributable to the operation of the soft starters"DAS", occurs, the emitted interference can bereduced by taking appropriate measures.Such measures are, e.g.:To connect reactors (3mH) or a suitable mainsfilter in series before the soft starter, or to connect X-capacitors (0.15µ F) in parallel to thesupply voltage terminals.
26 7
K1
Ua
WaVa
K1 K2
K2
12Fault
K3
K3
Reversingswitch
Selectorswitch
K4K5
K2 K3 S2
K5 0L R
S2
K4 K5
1
K111 12
K2
6 7
S
K2
EMC
K1
0L
K2
Reversingswitch
RS1
12
12
12
12
11/10
Control voltage
Triggerstage
Monitoring
2/T1 6/T34/T2
1/L1 5/L33/L2
Controlwith
oper. unit
Voltagesupply
A4 A6 24VDC output
Remotecontrolinputs
Analogoutput
3 Relayoutputs
MotorPTC
A5
Control forbypass
Features:
A three-phase controlled digital-soft starter (7,5-800kW) A integrated Bypass up to 110kW (up to 500kW by end year 2011) A current and torque reduction during acceleration A Comprehensive and customizable motor protection A DC Braking - Contactorless A Display graphical LCD - Real time graphs of motor operating performance A Inside Delta (6-wire) connection A degree of protection: IP20 (up to 100A), IP00 (from 140A up) A motor PTC connection
Function:
A Emergency run A Forward or reverse jog direction. A Remote control inputs
(3x fixed, 1x programmable) A Relay outputs
(3x programmable) A 24VDC output A Analog output A divers Soft Start/Stop control types A units with 690V upon request
Accessories:
A Control Software A DeviceNet module (29000.25903) A Modbus module (29000.25904) A Profibus module (29000.25905) A USB module (29000.25910) A Finger protection (from 145A up, 29000.25909)
Technical Data VS i III 525 - 23C1 43C1 53C1 76C1 105C1 145C1 170C1 220C1 23C2 43C2 53C2 76C2 105C2 145C2 170C2 220C2 Mains voltage according toDIN EN 50160 (IEC 38) 200-525V 45-66Hz
VS i III 690- 23C1 43C1 53C1 76C1 105C1 145C1 170C1 220C1 23C2 43C2 53C2 76C2 105C2 145C2 170C2 220C2 Mains voltage according toDIN EN 50160 (IEC 38) 380-690V 45-66Hz
Rated device current in A 23A 43A 53A 76A 105A 145A 170A 220A Motor rating at 400V in kW -7,5 -15 -22 -30 -55 -60 -75 -110 I²t-Value Power semiconductor in kA²s 1,15 8 15 15 125 125 320 320 Acceleration Constant current, Current ramp, “Adaptive Acceleration Control”, Torque Control Deceleration Timed voltage ramp soft Stopp, Brake Switching frequency 3x Ie and 10s AC53b 3.0 - 10:350 10/h AC53b 3.0 – 10:590 10/h Techn. parameter of relay outputs 10A/250VAC resistive; 5A/250VAC AC15 Ambient temperature -10°C…+40°C (+60°C Derating) Control voltage C1: 110VAC; 220VAC; -15%/+10%; C2: 24VDC/24VAC 20% Weight / kg 3,2 3,5 4,8 16 Order number: 525V/C1 2S000.50..* 023 043 053 076 105 145 170 220525V/C2 2S001.50..* 023 043 053 076 105 145 170 220
Soft Starters VersiStart i III ...-23 … 220
Typical Applications:
pumps, ventilators compressors mills, crushers, presses, conveying systems drives with high-inertia starting machines with gear units, belt or chain drives
Soft StartersVS i III ...-23 … 220
1.19
Subject to change without notice.
A
65
64
5857565455+5341-40+A6A5A4
E
5/L3
3/L2
1/L1 1/T1
4/T2
6/T3
13142122243334
L1B
L2B
L3B
DC
B
A
E
Dimensions:
Connection Diagram:
ModelA
mmB
mmC
mmD
mmE
mmWeight
kgVS i III -23 VS i III -43 VS i III -53
192 3.2
VS i III -76 3.5
VS i III -105
156.5 124 294.5 278
2234.8
VS i III -145 VS i III -170 VS i III - 220
282 250 438 380 250 16
Soft Starters VersiStart i III 23 … 2201.20
11/10
Control voltage
Triggerstage
Monitoring
2/T1 6/T34/T2
Controlwith
oper. unit
Voltagesupply
A4 A6 24VDC output
Remotecontrolinputs
Analogoutput
3 Relayoutputs
MotorPTC
A51/L1 5/L33/L2L1B L2B L3B
Features:
A three-phase controlled digital-soft starter (7,5-800kW) A integrated Bypass up to 110kW (up to 500kW by end year 2011) A current and torque reduction during acceleration A Comprehensive and customizable motor protection A DC Braking - Contactorless A Display graphical LCD - Real time graphs of motor operating performance A Inside Delta (6-wire) connection A degree of protection: IP20 (up to 100A), IP00 (from 140A up) A motor PTC connection
Function:
A Emergency run A Forward or reverse jog direction. A Remote control inputs
(3x fixed, 1x programmable) A Relay outputs
(3x programmable) A 24VDC output A Analog output A divers Soft Start/Stop control types A units with 690V upon request
Accessories:
A Control Software A DeviceNet module (29000.25903) A Modbus module (29000.25904) A Profibus module (29000.25905) A USB module (29000.25910) A Finger protection (29000.25909)
Upon request:
A units up to 500kW
N = without bypass (integrated Bypass by end year 2011)
Technical Data VS i III 525 - 255N C1 380N C1 430N C1 650N C1 790N C1 930N C1 255N C2 380N C2 430N C2 650N C2 790N C2 930N C2 Mains voltage according toDIN EN 50160 (IEC 38) 200-525V 45-66Hz
VS i III 690- 255N C1 380N C1 430N C1 650N C1 790N C1 930N C1 255N C2 380N C2 430N C2 650N C2 790N C2 930N C2 Mains voltage according toDIN EN 50160 (IEC 38) 380-690V 45-66Hz
Rated device current in A 255A 380A 430A 650A 790A 930A Motor rating at 400V in kW -132 -185 -220 -315 -400 -500 I²t-Value Power semiconductor in kA²s 320 320 320 1200 2530 4500Acceleration Constant current, Current ramp, “Adaptive Acceleration Control”, Torque ControlDeceleration Timed voltage ramp soft Stopp, Brake Switching frequency 3x Ie and 10s AC53b 3.0 – 10:590 10/h Techn. parameter of relay outputs 10A/250VAC resistive; 5A/250VAC AC15 Ambient temperature -10°C…+40°C (+60°C Derating) Control voltage C1: 110VAC; 220VAC -15%/+10%; C2: 24VDC/24 VAC 20% Weight / kg 25 50,5 53,5 Order number: 525V/C1 2S010.50..*1 255 380 430 650 790 930525V/C2 2S011.50..*1 255 380 430 650 790 930
Soft Starters VersiStart i III ...-255 … 1600
Typical Applications:
pumps, ventilators compressors mills, crushers, presses, conveying systems drives with high-inertia starting machines with gear units, belt or chain drives
Soft StartersVS i III ...-255 … 1600
1.21
Subject to change without notice.
DC
B
A
E
A
65
64
5857565455+5341-40+A6A5A4
E
5/L3
3/L2
1/L1 1/T1
4/T2
6/T3
13142122243334
L1B
L2B
L3B
Dimensions:
Connection Diagram:
ModelA
mmB
mmC
mmD
mmE
mmWeight
kgVS i III -255N 390 320 417 400 281 25
VS i III -380N VS i III -430N
50.5
VS i III -650N VS i III -790N VS i III -930N
430 320 545 522 299 53.5
Soft Starters VersiStart i III 255 … 16001.22
Dimensioning Rules for Soft Starters
04/11
All data sheets and commissioning instructions are available on our homepage at: www.peter-electronic.com.
Configuration instructions
The two following diagrams for an 11kW-drive operated at nominal load show the waveforms of electrical and mechanical quantities of the drive during the ramp-up phase, both with and without soft starter:
Ramp-up of a three-phase asynchronous motor directly connected to the mains (at nominal load)
Ramp-up of a three-phase asynchronous motor with soft starter (at nominal load)
Both groups of curves show the complete acceleration and deceleration phase.
In this connection, especially the waveform of the current during ramp-up with a soft starter is of interest. Depending on the adjusted starting voltage (boost), this current increases more or less steeply until nominal speed is reached. For the following load diagrams (thermal load), the mean value of that current is to be used which is formed by the current flowing at the starting point and the current flowing when nominal speed is reached (see example).
The following diagrams show how the maximum starting frequency (in starts per hour) depends on the ramp-up time and the mean starting current flowing during ramp-up. The curves represent the thermal ratio of the heat generated in the power semiconductors and the possible dissipation of heat by the integrated heat sinks, i.e., a high starting frequency in combination with a large mean starting current causes intense heating by the power semiconductors. If, in addition, a long ramp-up time is required for the starting operation, the number of starts possible within a certain unit of time reduces accordingly.
1.23
Motor current
Motor voltage
Torque
Speed
Speed
Motor current
Motor voltage
Torque
Dimensioning Rules for Soft Starters
The following example is to explain how to select a soft starter:
Assumption: Motor shaft power: 15kW Nominal/rated motor current: 29.5A max. Ramp-up time: 6s Mean starting current to be expected: 90A (no high-inertia starting) max. Starting frequency: 40 starts/h
In compliance with the power rating of the motor, a VersiStart II 400-32 soft starter is selected (acc. to the data sheet it is suitable for 15kW motors, Ie = 32A). However, when checking the number of starts per hour possible with this device under these conditions, it turns out that this device is not suitable:
VersiStart II 400-32
2xIe
2xIe
3xIe
3xIe
4xIe
4xIe
5xIe
5xIe
6xIe
6xIe
1
10
100
1000
1 10
Anlaufzeit/Ramp-up time (s)
Star
ts/h
25 Starts/h
Ramp-up time 6s
When dividing the starting current of 90A to be expected by the nominal current of 32A of the soft starter VersiStart II 400-32, this gives approx. 3 x Ie (90A/32A) of the soft starter. Consequently, a maximum starting frequency of 60 starts per hour is permissible for this device, i.e., in this case VersiStart II 400-32 would be overloaded.
This is only possible by reducing the ramp-up time. As demonstrated by the two below diagrams, the ramp-up time maximally possible for the application of a VersiStart II 400-32 would be approx. 3,7s.
VersiStart II 400-32
2xIe
2xIe
3xIe
3xIe
4xIe
4xIe
5xIe
5xIe
6xIe
6xIe
1
10
100
1000
1 10
Anlaufzeit/Ramp-up time (s)
Star
ts/h40 Starts/h
max. Ramp_up time approx. 3,7s
1.24
Dimensioning Rules for Soft Starters
04/11
If it is due to technological reasons not possible to go below the specified ramp-up time of 6s, a device that complies with the requested parameters has to be used.
When looking at the characteristic curves, it becomes clear that, for this case of application, a DAS-T 15 is suitable. With a threefold nominal current of the soft starter, i.e., 3 x Ie (90A/32A), and a ramp-up time of 6s, this device has a starting frequency of approx. 130 starts/h.
Since only 40 starts/h are required, this device is optimally designed to withstand the most unfavorable thermal loading.
DAS-T 15
2xIe
3xIe
3xIe
4xIe
4xIe
5xIe
5xIe
6xIe
6xIe
1,00
10,00
100,00
1000,00
1 10 100
Anlaufzeit/Ramp-up time (s)
Star
ts/h
Ramp-up time 6s
130 Starts/h
1.25
Dimensioning Rules for Soft Starters
Load diagrams:
SAS3, SAS11 PUST, DAS-T 7,5, MINISTART 1,5 ... 5,5, MICROSTART 1,5
1,00
10,00
100,00
1000,00
1 10 100
Anlaufzeit/Ramp-up time (s)
Star
ts/h 2xIe
3xIe4xIe5xIe6xIe
SAS 5,5, DAS-T 11, MINISTART 1,5 ... 5,5B, DUOSTART 1,5
1,00
10,00
100,00
1000,00
1 10 100
Anlaufzeit/Ramp-up time (s)
Star
ts/h 2xIe
3xIe4xIe5xIe6xIe
SAS 7,5, SAS 22PUST, DAS-T 22, MICROSTART 3, DUOSTART 3, MINISTART 7,5
1,00
10,00
100,00
1000,00
1 10 100
Anlaufzeit/Ramp-up time (s)
Star
ts/h
2xIe3xIe4xIe5xIe6xIe
1.26
Dimensioning Rules for Soft Starters
04/11
SAS 11, DAS-T 30, DAS-T 37, DUOSTART 5,5
1,00
10,00
100,00
1000,00
1 10 100
Anlaufzeit/Ramp-up time (s)
Star
ts/h
2xIe3xIe4xIe5xIe6xIe
MINISTART 11, DAS-T 55
1,00
10,00
100,00
1000,00
1 10
Anlaufzeit/Ramp-up time (s)
Star
ts/h
2xIe3xIe4xIe5xIe6xIe
DAS-T 15
1,00
10,00
100,00
1000,00
1 10 100
Anlaufzeit/Ramp-up time (s)
Star
ts/h
2xIe3xIe4xIe5xIe6xIe
1.27
Dimensioning Rules for Soft Starters
VersiStart II 3 LDS
2xIe
2xIe
3xIe
3xIe
4xIe
5xIe
6xIe
4xIe
5xIe
6xIe
1
10
100
1000
1 10
Anlaufzeit/Ramp-up time (s)
Star
ts/h
VersiStart II 5,5 / 11 LDS
2xIe
2xIe
3xIe
3xIe
4xIe
4xIe
5xIe
5xIe
6xIe
6xIe
1
10
100
1000
1 10
Anlaufzeit/Ramp-up time (s)
Star
ts/h
VersiStart II 7,5 LDS
2xIe
2xIe
3xIe
3xIe
4xIe
4xIe
5xIe
5xIe
6xIe
6xIe
1
10
100
1000
1 10
Anlaufzeit/Ramp-up time (s)
Star
ts/h
1.28
Dimensioning Rules for Soft Starters
04/11
VersiStart II 15 LDS
2xIe
2xIe
3xIe
3xIe
4xIe
4xIe
5xIe
5xIe
6xIe
6xIe
1
10
100
1000
1 10
Anlaufzeit/Ramp-up time (s)
Star
ts/h
VersiStart II 400-17
2xIe
2xIe
3xIe
3xIe
4xIe
4xIe
5xIe
5xIe
6xIe
6xIe
1
10
100
1000
1 10
Anlaufzeit/Ramp-up time (s)
Star
ts/h
VersiStart II 400-25
2xIe
2xIe
3xIe
3xIe
4xIe
4xIe
5xIe
5xIe
6xIe
6xIe
1
10
100
1000
1 10
Anlaufzeit/Ramp-up time (s)
Star
ts/h
1.29
Dimensioning Rules for Soft Starters
VersiStart II 400-32
2xIe
2xIe
3xIe
3xIe
4xIe
4xIe
5xIe
5xIe
6xIe
6xIe
1
10
100
1000
1 10
Anlaufzeit/Ramp-up time (s)
Star
ts/h
VersiStart II 400-45
2xIe
2xIe
3xIe
3xIe
4xIe
4xIe
5xIe
5xIe
6xIe
6xIe1
10
100
1000
1 10
Anlaufzeit/Ramp-up time (s)
Star
ts/h
VersiStart II 400-50
2xIe
2xIe
3xIe
3xIe
4xIe
4xIe
5xIe
5xIe
6xIe
6xIe1
10
100
1000
1 10
Anlaufzeit/Ramp-up time (s)
Star
ts/h
1.30
Dimensioning Rules for Soft Starters
04/11
VersiStart II 400-65
2xIe
2xIe
3xIe
3xIe
4xIe
4xIe
5xIe
5xIe
6xIe
6xIe1
10
100
1000
1 10
Anlaufzeit/Ramp-up time (s)
Star
ts/h
VersiStart II 400-75
2xIe
2xIe
3xIe
3xIe
4xIe
4xIe
5xIe
5xIe
6xIe
6xIe1
10
100
1000
1 10
Anlaufzeit/Ramp-up time (s)
Star
ts/h
1.31
Dimensioning Rules for Soft Starters
Dimensioning of pre-fuses:
Pre-fuses F can be dimensioned according to the following instructions.
Basically, two types of fuse protection are available for the user. 1. Fusing according to allocation type „1“, DIN EN 60947-4-2.
After a short circuit the soft starter is allowed to be inoperative and repair work is possible. 2. Fusing according to allocation type „2“, DIN EN 60947-4-2.
After a short circuit the device must be suitable for further use. However, there is the danger that the contacts of the by-passrelays (-contactors) weld. Therefore, if possible, these contacts are to be checked prior to reconnecting the device to the supply. If this check cannot be carried out by the user, the device has to be returned to the producer in order to have it checked.
The following dimensioning information refers to the below operating conditions: - Use of standard asynchronous motors - Standard ramp-up and/or deceleration times
Fusing according to allocation type „1“:As pre-fuses, we recommend to use line protection fuses (utilization category gL) or automatic circuit-breakers with type K trippingcharacteristic. In the case of automatic circuit-breakers the tripping characteristic of the type series is to be taken into account. With 2x Inthe tripping time should be at least 20s (I1).The fuse values are to be determined by taking the conductor cross-sectional area of the wiring into account. The wiring cross-sectionalarea is to be determined in dependence on the rated motor current, the maximally occurring starting current (normally up to the 5-fold rated device current) and the starting frequency. Table 1 shows the values for numerous applications, i.e., with a 3-fold nominal/ratedcurrent as mean starting current and a maximum ramp-up time of 10s. In the case of parameter values exceeding these values, it may be necessary to adapt the fuse value accordingly. Note! Wiring cross-sectional area according to DIN VDE 0100-430, DIN EN 57100-430.
Fusing according to allocation type „2“:The power semiconductors are to be protected by fuses of the utilization category gR (semiconductor fuses, high-speed fuses). However, since these fuses do not ensure line protection, it is necessary to use additionally line protection fuses (utiliz. category gL). To protect the semiconductors it is necessary to select gR-fuses featuring cutoff-I²t-values which are approx. 10-15% below the I²t-value of the power semiconductor (see technical data). In this connection, the current-value of the selected fuse should not be smaller than the starting current to be expected. PETER electronic does not prescribe the use of semiconductor protection fuses. However, for some UL- or CSA-listed devices there are exceptions which are indicated in the relevant commissioning instructions.
NotesOn the basis of the I²t-value of the power semiconductors, the ramp-up time and possibly the max. starting current, the fuse supplier is able to select a suitable type. Due to the great variety of producers, sizes and types, PETER electronic does not recommend anyparticular fuses.
If the value of the fuse or the cutoff-I²t-value is selected too small, it may happen that the semiconductor fuse reacts during the starting phase or during deceleration.
In the case of special devices having increased ramp-up or deceleration times, the recommended fuse value may have to be adapted.
Table 1 Nominal/rateddevice current(techn. data)
Device type Fuse value
in the case ofallocation type 1
Starting frequency Starts / h
3,5A / 4A DUOSTART, MICROSTART, MINISTART 10A 90
6,5A DUOSTART, MICROSTART, MINISTART VS II 10A 40
60
12A DUOSTART, MINISTART VS II 20A 60
3015A DAS-T, VS II 25A 40 17A VS II 25A 60
25A MINISTART, DAS-T, VS II VS II 35/40A 30
40
32A VS II VS II 50A 20
3045A VSII 63A 10 48A DAS-T 63A 20 50A VS II 100A 35 63A DAS-T 80A 40 65A VS II 125A 25
75A DAS-TVS II
100A125A
4020
88A DAS-T 100A 20 105A DAS-T 125A 20
1.32