Smoke Detector Reversing Relay ModuleD132A

en Installation manual

Page 2: Smoke Detector Reversing Relay Module
Page 3: Smoke Detector Reversing Relay Module

Smoke Detector Reversing Relay Module Notices | en 3

Bosch Securiity Systems, B.V. Installation manual 2019.08 | 05 | F.01U.069.463

1 NoticesThese instructions cover the installation of the D132A Smoke Detector Reversing RelayModule in a household fire system supervised by a fire alarm control panel (FACP) or acombination Burglary/Fire control panel.Before installing the module, become familiar with the Installation and Operation Guide for thecontrol panel you are using.Install, test and maintain the module according to these instructions, NFPA 72, local codes,and the authority having jurisdiction (AHJ). Failure to follow these instructions can result infailure of a detector to initiate an alarm event. Bosch Security Systems, Inc. is not responsiblefor improperly installed, tested or maintained devices.

!

Warning!Follow these instructions to avoid personal injury and damage to equipment.

NFPA 72 requires that you perform a complete system wide functional test following anymodifications, repair, upgrades or adjustments made to the system’s components, hardware,wiring, programming and software/firmware.

Page 4: Smoke Detector Reversing Relay Module

4 en | Description Smoke Detector Reversing Relay Module

2019.08 | 05 | F.01U.069.463 Installation manual Bosch Securiity Systems, B.V.

2 DescriptionThis module allows compatible control panels (see the table below) to sound all smokedetectors connected to point 1 or zone 1 when a single smoke detector on the loop goes intoalarm. To restore the smoke detectors to normal, reset the smoke detectors.The following table lists control panels compatible with the D132A:

Control panels Compatible relays See section:

Active:

B Series panels1 ** D275, PAM-4 Wiring to a B Series panel,page 8

D6412 and D4412 panels** Wiring to a D6412 or D4412panel, page 13

G Series (GV2 and higher)panels2

D275, PAM-4 Wiring to a G Series panel,page 14

Legacy:

G Series (prior to GV2)panels3

See control panel’s documentation on the Bosch website(http://www.boschsecurity.com)

D9412, D7412, D7212**panels

ICP-EZM2

D2812 panel**

D2412U and D2412UEpanels**

D2212, D2212B, andD2212BE panels**

DS7240 and DS7220 panels**

1 B Series panels = B6512**, B5512**, B4512**, and B3512**

2 G Series (GV2 and higher) panels = B9512G, B8512G, GV4 (D9412GV4, D7412GV4, andD7212GV4**), GV3 (D9412GV3, D7412GV3, and D7212GV3**), and GV2 (D9412GV2,D7412GV2, and D7212GV2**)

3 G Series (prior to GV2) panels = D9412G, D7412G, D7212G**

** indicates products which are not UL listed for commercial fire applications

Page 5: Smoke Detector Reversing Relay Module

Smoke Detector Reversing Relay Module Description | en 5

Bosch Securiity Systems, B.V. Installation manual 2019.08 | 05 | F.01U.069.463

Figure 2.1: D132A smoke detector reversing relay module

1 Mounting holes 6 Positive (+) power for module

2 Positive (+) to detector 7 Negative (-) power for module

3 Negative (-) to detector 8 Trigger to reverse detector powerPull to GND to activate

4 Powered loop from control panel orD125B

9 Positive (+) to trouble point

5 Powered loop from control panel orD125B

10 Negative (-) to trouble point

Page 6: Smoke Detector Reversing Relay Module

6 en | Installation Smoke Detector Reversing Relay Module

2019.08 | 05 | F.01U.069.463 Installation manual Bosch Securiity Systems, B.V.

3 Installation1. Align the module with an available three-hole module mounting location in the enclosure.2. Fasten the module to the enclosure with the three supplied screws.For mounting locations inside the enclosure, see the control panel’s Installation Instructions.

Page 7: Smoke Detector Reversing Relay Module

Smoke Detector Reversing Relay Module Wiring | en 7

Bosch Securiity Systems, B.V. Installation manual 2019.08 | 05 | F.01U.069.463

4 WiringUse the table below to ensure you are using the proper wire gauge for the number ofdetectors used and for the length of the detector circuit:

Number ofdetectors

Maximum detector circuit length

22 AWG(0.34 mm2)

20 AWG(0.5 mm2)

18 AWG(0.75 mm2)

16 AWG(1.5 mm2)

1 935 ft (285 m) 1490 ft (454 m) 2370 ft (722 m) 3770 ft (1149 m)

2 935 ft (285 m) 1490 ft (454 m) 2370 ft (722 m) 3770 ft (1149 m)

3 465 ft (142 m) 745 ft (227 m) 1185 ft (722 m) 1885 ft (575 m)

4 310 ft (95 m) 495 ft (150 m) 790 ft (241 m) 1255 ft (383 m)

5 230 ft (70 m) 370 ft (113 m) 590 ft (180 m) 940 ft (287 m)

6 185 ft (56 m) 295 ft (90 m) 470 ft (143 m) 750 ft (229 m)

7 155 ft (47 m) 245 ft (75 m) 395 ft (120 m) 625 ft (191 m)

8 130 ft (40 m) 210 ft (64 m) 335 ft (103 m) 535 ft (163 m)

Notice!To ensure system supervision, do not use looped wire under the terminals. Break the run toprovide supervision of the connections.

An external 12 VDC or 24 VDC power supply listed for fire signaling units and commercial orresidential burglary units can be used.The external power supply must be UL1481 or UL864 Listed, regulated, and power‑limited.Install the control panel and external power supply in the same room no more than 20 ft (6 m)apart. The interconnecting wires between the control panel and external power supply mustbe in conduit.The power source for both the auxiliary power supply and the control panel must be from thesame dedicated AC branch circuit.

Page 8: Smoke Detector Reversing Relay Module

8 en | Wiring Smoke Detector Reversing Relay Module

2019.08 | 05 | F.01U.069.463 Installation manual Bosch Securiity Systems, B.V.

4.1 Wiring to a B Series panel

4.1.1 Two-wire wiring for 12 VDC supplied by the control panel

Figure 4.1: Two-wire wiring of D132A modules to a B Series control panel for power supplied by the panel

1 Detector loop (2‑wire) 9 Connection from D125B switch powerto control panel’s A output relay (NC).Set the Output A jumper for AUX PWR.

2 EOL resistor 10 Connection for D125B Zone B to anon-board point on the control panel

3 D132A module 11 Connection for D125B Zone A to anon‑board point on the control panel

4 Connections for one D132A fire pointto D125B A loop

12 Connection from D125B Common(either 4 or 5) to the control panel’scommon for the on‑board pointsconnected

5 Connections for the other D132A firepoint to D125B B loop

13 Earth Ground

6 Connection for AUX PWR - from D132Amodules to B-series panel COM

14 B Series control panel

7 Connection for AUX PWR + fromD132A modules to B-series panel AUX

15 D125B module

8 Connection from reverse trigger onD132A modules to control panel B or CoutputPull to GND to activate

Page 9: Smoke Detector Reversing Relay Module

Smoke Detector Reversing Relay Module Wiring | en 9

Bosch Securiity Systems, B.V. Installation manual 2019.08 | 05 | F.01U.069.463

Notice!The illustration shows the D132A modules wired for both detector loops triggered by thesame output. For loops triggered by separate outputs, connect one D132A module reversetrigger to B output and the other D132A revese trigger to C output.

Page 10: Smoke Detector Reversing Relay Module

10 en | Wiring Smoke Detector Reversing Relay Module

2019.08 | 05 | F.01U.069.463 Installation manual Bosch Securiity Systems, B.V.

4.1.2 Four-wire wiring for 12 VDC supplied by the control panel

Figure 4.2: Four-wire wiring of D132A modules to a B Series control panel for 12 V power supplied by the panel

1 D132A module 9 D132A Trigger connection to panel’sOutput B or CPull to GND to activate

2 Resistor R4: for 4‑wire use, cut theresistor leads to remove the resistor

10 Positive (+) trouble point connectionto an on‑board point on the controlpanel

3 B Series control panel 11 Negative (-) trouble point connectionto an on‑board point on the controlpanel

4 End-of-line (EOL) supervisory relay 12 EOL resistors

5 Positive (+) power connection todetectors

13 Connections between an on‑boardpoint on the control panel , thedetectors (data lines), and the EOLSupervision Relay

6 Negative (-) power connection todetectors

14 First smoke detector on the detectorloop

7 Positive (+) fire point and AUX PWRconnection to panel’s AUX terminal

15 Last smoke detector on the detectorloop

8 Negative (-) fire point and AUX PWRconnection to panel’s COM terminal

Page 11: Smoke Detector Reversing Relay Module

Smoke Detector Reversing Relay Module Wiring | en 11

Bosch Securiity Systems, B.V. Installation manual 2019.08 | 05 | F.01U.069.463

4.1.3 Two-wire wiring for 12 VDC supplied by an external power supply

Figure 4.3: Two-wire wiring D132A modules to a B Series panel for 12 V power supplied by an external power supply

1 Detector loop (2‑wire) 9 Connection from D125B switch powerto control panel’s A output relay (NC).Set the Output A jumper for AUX PWR.

2 EOL resistor 10 Connection for D125B Zone B to anon-board point on the control panel

3 D132A module 11 Connection for D125B Zone A to anon‑board point on the control panel

4 Connections for one D132A fire pointto D125B A loop

12 Connection from D125B Common(either 4 or 5) to the control panel’scommon for the on‑board pointsconnected

5 Connections for the other D132A firepoint to D125B B loop

13 External power supply (12 VDC)

6 Connection for AUX PWR - from D132Amodules to B-series panel COM

14 Earth Ground

7 Connection for AUX PWR + fromD132A modules to B-series panel AUX

15 B Series control panel

8 Connection from reverse trigger onD132A modules to control panel B or Coutput. Pull to GND to activate

16 D125B module

Notice!The illustration shows the D132A modules wired for both detector loops triggered by thesame output. For loops triggered by separate outputs, connect one D132A module reversetrigger to B output and the other D132A reverse trigger to C output.

Page 12: Smoke Detector Reversing Relay Module

12 en | Wiring Smoke Detector Reversing Relay Module

2019.08 | 05 | F.01U.069.463 Installation manual Bosch Securiity Systems, B.V.

4.1.4 Four-wire wiring for 12 VDC supplied by an exernal power supply

(+) COMN/O

(-)

10

Figure 4.4: Four-wire wiring D132A modules to a B Series panel for 12 V power supplied by an external power supply

1 External power supply (12 VDC) 9 Negative (-) fire point and AUX PWRconnection to panel’s COM terminal

2 D132A module 10 Connection from reverse trigger onD132A modules to control panel A or Brelay Pulls High in Alarm. Use a D130/PAM-4 to accomplish this.

3 Resistor R4: for 4‑wire use, cut theresistor leads to remove the resistor

11 Positive (+) trouble point connectionto an on‑board point on the controlpanel

4 B Series control panel 12 Negative (-) trouble point connectionto an on‑board point on the controlpanel

5 End-of-line (EOL) Supervision Relay 13 EOL resistors

6 Positive (+) power connection todetectors

14 Connections between an on‑boardpoint on the control panel, thedetectors (data lines), and the EOLSupervision Relay

7 Negative (-) power connection todetectors

15 First smoke detector on the detectorloop

Page 13: Smoke Detector Reversing Relay Module

Smoke Detector Reversing Relay Module Wiring | en 13

Bosch Securiity Systems, B.V. Installation manual 2019.08 | 05 | F.01U.069.463

8 Positive (+) fire point and AUX PWRconnection to panel’s AUX terminal

16 Last smoke detector on the detectorloop

4.2 Wiring to a D6412 or D4412 panel

4.2.1 Two-wire wiring for 12 VDC supplied by the control panel

Figure 4.5: Two-wire wiring D132A modules to a D6412 or D4412 control panel for 12 VDC supplied by the panel

1 Detector loop (2‑wire) 6 Trigger to reverse power

2 EOL resistor 7 Connections for trouble point

3 Smoke detectors (10 maximum) 8 End-of-line (EOL) resistor

4 Connections for fire point 9 D6412 or D4412 panel

5 Aux power connections (12 VDC) 10 D132A module

Page 14: Smoke Detector Reversing Relay Module

14 en | Wiring Smoke Detector Reversing Relay Module

2019.08 | 05 | F.01U.069.463 Installation manual Bosch Securiity Systems, B.V.

4.2.2 Two-wire wiring for 12 VDC supplied by an external power supply

Figure 4.6: Two-wire wiring a D132A module to a D6412 or D4412 control panel for 12 VDC supplied by an external power supply

1 Detector loop (2‑wire) 7 Connections for trouble point

2 EOL resistor 8 End-of-line (EOL) resistor

3 Smoke detectors (10 maximum) 9 D6412 or D4412 panel

4 Connections for fire point 10 D132A module

5 External power supply connections(12 VDC)

11 External power supply (12 VDC)

6 Trigger to reverse power

4.3 Wiring to a G Series panel

Notice!The D132A module has not been investigated by Underwriters Laboratories (UL) for use withG-series control panels in commercial fire applications.

Page 15: Smoke Detector Reversing Relay Module

Smoke Detector Reversing Relay Module Wiring | en 15

Bosch Securiity Systems, B.V. Installation manual 2019.08 | 05 | F.01U.069.463

4.3.1 Two-wire wiring for 12 VDC supplied by the control panel

5

1

11 1 1

Point Point Point Point

3

6

7

8

EARTH GROUND

COMMON

BATTERY NEGATIVE ONLY

BATTERY POSITIVE ONLY

RELAY A

RELAY B

RELAY C

+ AUX POWER

CLASS 2 TRANSFORMER16.5 VAC 40 VA 60 HzModel D1640Internally Fused - Do not shortRequires Unswitched OutletDo not share with other equipment

GROUND FAULT DETECT

EnabledDisabled

PHONELED

RED

ON whencommunicatingOFF when idle

Commercial

D9412GV2 Control Panel is UL Listed For Central StHousehold Fire Alarm, and Central Stand Encrypted Line Security when communicatin

System is intended to be checked by a Qualified T The types of initiating circuits the control p The types of signaling the control p

F01U003643-01

1211 13

Point 1 Point 2

1514 16

Point 3 Point 4

LEDs Off When Normal

Charging Status

Low Battery - 12.1 VDC

YEL

RED

10.2 VDC - Battery Load Shed

This equipment should be instand NFPA 72 (National Fire Warning Systems and under the limits of the Local Protection Association, Battermarch Park, Quincyproper installation, operation, testing, maintenabe provided with this equipment.

D94

PHONE LINE SEIZED

TIP RINGTELCO CORD MODEL D161

Refer to the D9412GV2/D7412GV2 Approved For System Wiring Diagram, Issue A

POWER SUPPLYThe Power Supply provides a maximum o

Operation and Installation Guide

(P/N: F01U003641) for Power Requirement

CAUTION: Refer to the

All external connections except T

limited. Requirements for battery st

WARNING!Multi-Battery installation requiresModel D122/D122L Dual BatteryHarness. Improper installation canbe a fire hazard.

Incorrect wiring willdamage this equipment.

Suitable for dry indooruse only.

Devices powered by theAUX power output mustbe supervised.

Minimum system requirementULUL Listed and Classified keypUL Listed Local Bell

CAUTION: Avoid damage to Panel.Do not connect 24 V to terminals.

Maximum charging current 1.4 A

PROGRAMMABLEALARM OUTPUTS

Terminals

SWITCHED AUX

and6 7

Terminal

8

(+)

(-)

5

6

7

8

9

10

4

1

2

3

CC

D0

x-

0xxxx

-0

00

©R

AD

ION

ICS

INC

.

D1

25

B

19

92

1

SWITCH

POWER

10

EARTH

GND

2

ZONE

B

4 5

PANEL

COMMON

3

ZONE

A

6

B-

LOOP

7

A-

LOOP

8

B+

LOOP

9

A+

LOOP

R21

R9

R10

R14 R11

R12

R22

RV2

RV3RV4

R8

RV1

TB1/J1

R3

C1

R7

C3

C2

R1

3

R4

R5

R6

U1

PTC2 PTC1

R1R2

D125B

(+)

(-)

3

1

2

1211

13

DE

TE

CT

OR

+

DE

TE

CT

OR

-

FIR

E P

T

+

FIR

E P

T

-

AU

X P

WR

+

AU

X P

WR

-

RE

VE

RS

E

TR

IGG

ER

TR

BL

PT

+

TR

BL

PT

-

R4

D132A

DE

TE

CT

OR

+

DE

TE

CT

OR

-

FIR

E P

T

+

FIR

E P

T

-

AU

X P

WR

+

AU

X P

WR

-

RE

VE

RS

E

TR

IGG

ER

TR

BL

PT

+

TR

BL

PT

-

R4

D132A

15

14

(-)

(+)COMN/O

Figure 4.7: Two-wire wiring of D132A modules to a G Series control panel for power supplied by the panel

1 Detector loop (2‑wire) 9 Connection from D125B switch powerto control panel’s C relay (switchedAux).

2 EOL resistor 10 Connection for D125B Zone B to anon-board point on the control panel

3 D132A module 11 Connection for D125B Zone A to anon‑board point on the control panel

4 Connections for one D132A fire pointto D125B A loop

12 Connection from D125B Common(either 4 or 5) to the control panel’scommon for the on‑board pointsconnected

5 Connections for the other D132A firepoint to D125B B loop

13 Earth Ground

6 Connection for AUX PWR + fromD132A modules to B-series panel AUX

14 D125B module

7 Connection for AUX PWR - from D132Amodules to B-series panel COM

15 G Series control panel

8 Connection from reverse trigger onD132A modules to control panel A or BrelayPulls High in AlarmUse a D130/PAM-4 to accomplish this.

Page 16: Smoke Detector Reversing Relay Module

16 en | Wiring Smoke Detector Reversing Relay Module

2019.08 | 05 | F.01U.069.463 Installation manual Bosch Securiity Systems, B.V.

Notice!The illustration shows the D132A modules wired for both detector loops triggered by thesame output. For loops triggered by separate outputs, connect one D132A module reversetrigger to the A relay and the other D132A revese trigger to the B relay.

4.3.2 Four-wire wiring for 12 VDC supplied by the control panel

5

1

ZONEX IN

ZONEX POWER

ZONEX

1 1 21 1 1 1 1 2 2

5

6 7

Point Point Point Point Point Point Point Point

3

6

7

8

EARTH GROUND

COMMON

BATTERY NEGATIVE ONLY

BATTERY POSITIVE ONLY

RELAY A

RELAY B

RELAY C

+ AUX POWER

CLASS 2 TRANSFORMER16.5 VAC 40 VA 60 HzModel D1640Internally Fused - Do not shortRequires Unswitched OutletDo not share with other equipment

GROUND FAULT DETECT

EnabledDisabled

PHONELED

RED

ON whencommunicatingOFF when idle

Commercial Protected-Premises Control Panel

D9412GV2 Control Panel is UL Listed For Central Station, Local, Auxiliary, Proprietary, and Household Fire Alarm, and Central Station, Local, Police Station Connect, Household Burglar Alarmand Encrypted Line Security when communicating via a network.

System is intended to be checked by a Qualified Technician at least every 3 years. The types of initiating circuits the control panel has been approved for are A, M, W, SS. The types of signaling the control panel has been approved for are DAC, OT, NC

Reset PinDisable all except Battery

Charging and Programming

PERIPHERAL DEVICE CONNECTIONS

RED POWER +

YELLOW DATA BUS A

GREEN DATA BUS B

BLACK COMMON

ZONEX OUT 1

ZONEX IN 1

N.F.P.A.Style 4.0SignalingLineCircuits

F01U003643-01

1211 13

Point 1 Point 2

1514 16

Point 3 Point 4

1817 19

Point 5 Point 6

2120 22

Point 7 Point 8

LEDs Off When Normal

Charging Status

Low Battery - 12.1 VDC

YEL

RED

10.2 VDC - Battery Load Shed

This equipment should be installed in accordance with the NFPA 70 (National Electrical Code)and NFPA 72 (National Fire Alarm Code) for Local, Central Station, Proprietary and Household FireWarning Systems and under the limits of the Local Authority Having Jurisdiction (National Fire Protection Association, Battermarch Park, Quincy, MA 02269). Printed information describing proper installation, operation, testing, maintenance, evacuation planning and repair service is tobe provided with this equipment.

D9412GV2

26

25

ZONEX POWER + 24

ZONEX COMMON 23

PHONE LINE SEIZED

TIP RINGTELCO CORD MODEL D161

SDI Connector

ZONEX OUT 2

ZONEX IN 2

Refer to the D9412GV2/D7412GV2 Approved Applications Compliance Guide (P/N: F01U003639) For System Wiring Diagram, Issue A and for Compatible Smoke Detectors

POWER SUPPLY REQUIREMENTSThe Power Supply provides a maximum of 1.4 Amps for the Control Panel and all Accessory Devices. For System Loading, refer to the D9412GV2/D7412GV2 Operation and Installation Guide (P/N: F01U003641).

(P/N: F01U003641) for Power Requirements relating to Terminals 6 and 7 .

CAUTION: Refer to the D9412GV2/D7412GV2 Operation and Installation Guide

All external connections except Terminal 5 (battery positive) are inherently power

limited. Requirements for battery standby time might reduce allowable output.

WARNING!Multi-Battery installation requiresModel D122/D122L Dual BatteryHarness. Improper installation canbe a fire hazard.

Battery: Replace every 3 to5 years with one or two Model D126 or D1218 12V Lead Acid Batteries.

VOLTAGE RANGESOpen 3.7 - 5.0 VDC Short 0.0 - 1.3 VDCNormal 2.0 - 3.0 VDC

Op

era

tio

n M

on

ito

rP

uls

es W

hen

No

rmal

Flickers

Wh

en

Rin

gin

g

GRN

D5200/D5360 PROG CONN

Point 8S3 Option

Closed = 1KW EOLNormal Operation

Open =AB-12 ULBell Box 220 KW

Incorrect wiring willdamage this equipment.

Suitable for dry indooruse only.

Devices powered by theAUX power output mustbe supervised.

Minimum system requirements for Classification in accordance with ANSI/SIA CP-01-2000:UL Listed and Classified control unit Model D9412GV2, D7412GV2, or D7212GV2;UL Listed and Classified keypad Model D1256, D1257, D1260, D1255, D1255R, or D1255RW;UL Listed Local Bell

CAUTION: Avoid damage to Panel.Do not connect 24 V to terminals.

Maximum charging current 1.4 A

PROGRAMMABLEALARM OUTPUTS

Terminals

SWITCHED AUX

and6 7

Terminal

8

5

6

7

8

9

10

4

3

1

12

11

13

DE

TE

CT

OR

+

DE

TE

CT

OR

-

FIR

E P

T

+

FIR

E P

T

-

AU

X P

WR

+

AU

X P

WR

-

RE

VE

RS

E

TR

IGG

ER

TR

BL

PT

+

TR

BL

PT

-

R4

D132A

+12 VDC+24 VDC

Common (-)

(+)

(-)

(+) (+)

(-) (-)

2

14 15(+) COMN/O

(-)

Figure 4.8: Four-wire wiring of D132A modules to a G Series control panel for 12 V power supplied by the panel

1 D132A module 9 Connection from reverse trigger onD132A modules to control panel A or Brelay Pulls High in Alarm. Use a D130/PAM-4 to accomplish this.

2 Resistor R4: for 4‑wire use, cut theresistor leads to remove the resistor

10 Positive (+) trouble point connectionto an on‑board point on the controlpanel

3 G Series control panel 11 Negative (-) trouble point connectionto an on‑board point on the controlpanel

Page 17: Smoke Detector Reversing Relay Module

Smoke Detector Reversing Relay Module Wiring | en 17

Bosch Securiity Systems, B.V. Installation manual 2019.08 | 05 | F.01U.069.463

4 End-of-line (EOL) supervisory relay 12 EOL resistors

5 Positive (+) power connection todetectors

13 Connections between an on‑boardpoint on the control panel , thedetectors (data lines), and the EOLSupervision Relay

6 Negative (-) power connection todetectors

14 First smoke detector on the detectorloop

7 Positive (+) fire point and AUX PWRconnection to panel’s AUX powerterminal

15 Last smoke detector on the detectorloop

8 Negative (-) fire point and AUX PWRconnection to panel’s COMMONterminal

Page 18: Smoke Detector Reversing Relay Module

18 en | Wiring Smoke Detector Reversing Relay Module

2019.08 | 05 | F.01U.069.463 Installation manual Bosch Securiity Systems, B.V.

4.3.3 Two-wire wiring for 12 VDC supplied by an external power supply

POS

+NEG

-

5

1

11 1 1

Point Point Point Point

3

6

7

8

EARTH GROUND

COMMON

BATTERY NEGATIVE ONLY

BATTERY POSITIVE ONLY

RELAY A

RELAY B

RELAY C

+ AUX POWER

CLASS 2 TRANSFORMER16.5 VAC 40 VA 60 HzModel D1640Internally Fused - Do not shortRequires Unswitched OutletDo not share with other equipment

GROUND FAULT DETECT

EnabledDisabled

PHONELED

RED

ON whencommunicatingOFF when idle

D9412GV2 Control Panel is UL Listed For Central Household Fire Alarm, and Central St

The types of initiating circuits the control p The types of signaling the control p

F01U003643-01

1211 13

Point 1 Point 2

1514 16

Point 3 Point 4

LEDs Off When Normal

Charging Status

Low Battery - 12.1 VDC

YEL

RED

10.2 VDC - Battery Load Shed

This equipment should be instand NFPA 72 (National Fire Warning Systems and under the limitProtection Association, Battermarch Park, Quincproper instbe provided with this equipment.

PHONE LINE SEIZED

TIP RINGTELCO CORD MODEL D161

Refer to the D9412GV2/D7412GV2 Approved For System Wiring Diagram, Issue A

POWER SUPPLY

Operation and Installation Guide

(P/N: F01U003641) for Power Requirement

CAUTION: Refer to the

All external connections except T

limited. Requirements for battery st

WARNING!Multi-Battery installation requiresModel D122/D122L Dual BatteryHarness. Improper installation canbe a fire hazard.

Incorrect wiring willdamage this equipment.

Suitable for dry indooruse only.

Devices powered by theAUX power output mustbe supervised.

Minimum system requirementULUL Listed and Classified keypUL Listed Local Bell

CAUTION: Avoid damage to Panel.Do not connect 24 V to terminals.

Maximum charging current 1.4 A

PROGRAMMABLEALARM OUTPUTS

Terminals

SWITCHED AUX

and6 7

Terminal

8

(+)

(-)

5

6

7

8

9

10

4

1

2

3

CC

D0

x-

0xxxx

-0

00

©R

AD

ION

ICS

INC

.

D1

25

B

19

92

1

SWITCH

POWER

10

EARTH

GND

2

ZONE

B

4 5

PANEL

COMMON

3

ZONE

A

6

B-

LOOP

7

A-

LOOP

8

B+

LOOP

9

A+

LOOP

R21

R9

R10

R14 R11

R12

R22

RV2

RV3RV4

R8

RV1

TB1/J1

R3

C1

R7

C3

C2

R1

3

R4

R5

R6

U1

PTC2 PTC1

R1R2

D125B

(+)

(-)

3

1

2

1211

16

DE

TE

CT

OR

+

DE

TE

CT

OR

-

FIR

E P

T

+

FIR

E P

T

-

AU

X P

WR

+

AU

X P

WR

-

RE

VE

RS

E

TR

IGG

ER

TR

BL

PT

+

TR

BL

PT

-

R4

D132A

DE

TE

CT

OR

+

DE

TE

CT

OR

-

FIR

E P

T

+

FIR

E P

T

-

AU

X P

WR

+

AU

X P

WR

-

RE

VE

RS

E

TR

IGG

ER

TR

BL

PT

+

TR

BL

PT

-

R4

D132A

13

15

14

(+)

COMN/O

(-)

Figure 4.9: Two-wire wiring D132A modules to a G Series panel for 12 V power supplied by an external power supply

1 Detector loop (2‑wire) 9 Connection from D125B switch powerto control panel’s C relay (switchedAux)

2 EOL resistor 10 Connection for D125B Zone B to anon‑board point on the control panel

3 D132A module 11 Connection for D125B Zone A to anon‑board point on the control panel

4 Connections for one D132A fire pointto D125B A loop

12 Connection from D125B Common(either 4 or 5) to the control panel’scommon for the on board pointsconnected

5 Connections for the other D132A firepoint to D125B B loop

13 External power supply (12 VDC)

6 Positive (+) connection from externalpower supply to AUX PWR + terminalson D132A modules

14 Earth Ground

7 Negative (-) connection from externalpower supply to AUX PWR - terminalson D132A modules

15 G Series control panel

Page 19: Smoke Detector Reversing Relay Module

Smoke Detector Reversing Relay Module Wiring | en 19

Bosch Securiity Systems, B.V. Installation manual 2019.08 | 05 | F.01U.069.463

8 Connection from reverse trigger onD132A modules to control panel A or BrelayPulls High in AlarmUse a D130/PAM-4 to accomplish this.

16 D125B module

Notice!The illustration shows the D132A modules wired for both detector loops triggered by thesame output. For loops triggered by separate outputs, connect one D132A module reversetrigger to the A relay and the other D132A revese trigger to the B relay.

4.3.4 Four-wire wiring for 12 VDC supplied by an exernal power supply

5

1

ZONEX IN

ZONEX POWER

ZONEX

1 1 21 1 1 1 1 2 2

5

6 7

Point Point Point Point Point Point Point Point

3

6

7

8

EARTH GROUND

COMMON

BATTERY NEGATIVE ONLY

BATTERY POSITIVE ONLY

RELAY A

RELAY B

RELAY C

+ AUX POWER

CLASS 2 TRANSFORMER16.5 VAC 40 VA 60 HzModel D1640Internally Fused - Do not shortRequires Unswitched OutletDo not share with other equipment

GROUND FAULT DETECT

EnabledDisabled

PHONELED

RED

ON whencommunicatingOFF when idle

Commercial Protected-Premises Control Panel

D9412GV2 Control Panel is UL Listed For Central Station, Local, Auxiliary, Proprietary, and Household Fire Alarm, and Central Station, Local, Police Station Connect, Household Burglar Alarmand Encrypted Line Security when communicating via a network.

System is intended to be checked by a Qualified Technician at least every 3 years. The types of initiating circuits the control panel has been approved for are A, M, W, SS. The types of signaling the control panel has been approved for are DAC, OT, NC

Reset PinDisable all except Battery

Charging and Programming

PERIPHERAL DEVICE CONNECTIONS

RED POWER +

YELLOW DATA BUS A

GREEN DATA BUS B

BLACK COMMON

ZONEX OUT 1

ZONEX IN 1

N.F.P.A.Style 4.0SignalingLineCircuits

F01U003643-01

1211 13

Point 1 Point 2

1514 16

Point 3 Point 4

1817 19

Point 5 Point 6

2120 22

Point 7 Point 8

LEDs Off When Normal

Charging Status

Low Battery - 12.1 VDC

YEL

RED

10.2 VDC - Battery Load Shed

This equipment should be installed in accordance with the NFPA 70 (National Electrical Code)and NFPA 72 (National Fire Alarm Code) for Local, Central Station, Proprietary and Household FireWarning Systems and under the limits of the Local Authority Having Jurisdiction (National Fire Protection Association, Battermarch Park, Quincy, MA 02269). Printed information describing proper installation, operation, testing, maintenance, evacuation planning and repair service is tobe provided with this equipment.

D9412GV2

26

25

ZONEX POWER + 24

ZONEX COMMON 23

PHONE LINE SEIZED

TIP RINGTELCO CORD MODEL D161

SDI Connector

ZONEX OUT 2

ZONEX IN 2

Refer to the D9412GV2/D7412GV2 Approved Applications Compliance Guide (P/N: F01U003639) For System Wiring Diagram, Issue A and for Compatible Smoke Detectors

POWER SUPPLY REQUIREMENTSThe Power Supply provides a maximum of 1.4 Amps for the Control Panel and all Accessory Devices. For System Loading, refer to the D9412GV2/D7412GV2 Operation and Installation Guide (P/N: F01U003641).

(P/N: F01U003641) for Power Requirements relating to Terminals 6 and 7 .

CAUTION: Refer to the D9412GV2/D7412GV2 Operation and Installation Guide

All external connections except Terminal 5 (battery positive) are inherently power

limited. Requirements for battery standby time might reduce allowable output.

WARNING!Multi-Battery installation requiresModel D122/D122L Dual BatteryHarness. Improper installation canbe a fire hazard.

Battery: Replace every 3 to5 years with one or two Model D126 or D1218 12V Lead Acid Batteries.

VOLTAGE RANGESOpen 3.7 - 5.0 VDC Short 0.0 - 1.3 VDCNormal 2.0 - 3.0 VDC

Op

era

tio

n M

on

ito

rP

uls

es

Wh

en

No

rma

lF

lic

ke

rs W

he

n R

ing

ing

GRN

D5200/D5360 PROG CONN

Point 8S3 Option

Closed = 1KW EOLNormal Operation

Open =AB-12 ULBell Box 220 KW

Incorrect wiring willdamage this equipment.

Suitable for dry indooruse only.

Devices powered by theAUX power output mustbe supervised.

Minimum system requirements for Classification in accordance with ANSI/SIA CP-01-2000:UL Listed and Classified control unit Model D9412GV2, D7412GV2, or D7212GV2;UL Listed and Classified keypad Model D1256, D1257, D1260, D1255, D1255R, or D1255RW;UL Listed Local Bell

CAUTION: Avoid damage to Panel.Do not connect 24 V to terminals.

Maximum charging current 1.4 A

PROGRAMMABLEALARM OUTPUTS

Terminals

SWITCHED AUX

and6 7

Terminal

8

56

7

8

9

10

4

12

11

14

DE

TE

CT

OR

+

DE

TE

CT

OR

-

FIR

E P

T

+

FIR

E P

T

-

AU

X P

WR

+

AU

X P

WR

-

RE

VE

RS

E

TR

IGG

ER

TR

BL

PT

+

TR

BL

PT

-

R4

D132A

+12 VDC+24 VDC

Common (-)

(+)

(-)

(+) (+)

(-) (-)

2

POS

+NEG

-

13

13

15 16

(+)

COMN/O

(-)

Figure 4.10: Four-wire wiring of D132A modules to a G Series control panel for 12 V power supplied by an external power supply

Page 20: Smoke Detector Reversing Relay Module

20 en | Wiring Smoke Detector Reversing Relay Module

2019.08 | 05 | F.01U.069.463 Installation manual Bosch Securiity Systems, B.V.

1 External power supply (12 VDC) 9 Negative (-) connection from externalpower supply to D132A’s Fire Point -and AUX PWR - terminals and tocontrol panel’s COM terminal

2 D132A module 10 Connection from reverse trigger onD132A modules to control panel A or Brelay Pulls High in Alarm. Use a D130/PAM-4 to accomplish this..

3 Resistor R4: for 4‑wire use, cut theresistor leads to remove the resistor

11 Positive (+) trouble point connectionto an on‑board point on the controlpanel

4 G Series control panel 12 Negative (-) trouble point connectionto an on‑board point on the controlpanel

5 End-of-line (EOL) Supervision Relay 13 EOL resistors

6 Positive (+) power connection todetectors

14 Connections between an on‑boardpoint on the control panel, thedetectors (data lines), and the EOLSupervision Relay

7 Negative (-) power connection todetectors

15 First smoke detector on the detectorloop

8 Positive (+) connection from externalpower source to D132A’s Fire Point +and AUX PWR + terminals

16 Last smoke detector on the detectorloop

Page 21: Smoke Detector Reversing Relay Module

Smoke Detector Reversing Relay Module Programming | en 21

Bosch Securiity Systems, B.V. Installation manual 2019.08 | 05 | F.01U.069.463

5 ProgrammingProgram a B Series control panel output to provide GND to the module’s reverse triggerduring Fire Alarm (Steady output will produce a steady tone; pulsed output will produce apulsed tone from the devices). Fire points should be programmed as described in the controlpanel’s Program Entry Guide.On a G Series control panel, A Relay (D130/PAM-4) will need to be connected to the on-boardA or B output and will be used to activate the module's reverse trigger.

Page 22: Smoke Detector Reversing Relay Module

22 en | Specifications Smoke Detector Reversing Relay Module

2019.08 | 05 | F.01U.069.463 Installation manual Bosch Securiity Systems, B.V.

6 SpecificationsElectrical

Current draw

– Alarm 70 mA maximum

– Standby 10 mA maximum

Voltage 10.2 VDC to 13.9 VDC

Environmental

Relative Humidity 5% to 93% at +86°F (+30°C)

Temperature (operating) +32°F to +120°F (0°C to +49°C)

Mechanical

Dimensions (HxW) 3 in. x 3 in. (7.6 cm x 7.6 cm)

Page 23: Smoke Detector Reversing Relay Module

Smoke Detector Reversing Relay Module Compatible detectors | en 23

Bosch Securiity Systems, B.V. Installation manual 2019.08 | 05 | F.01U.069.463

7 Compatible detectors

7.1 Compatible 2-wire detectorsUnderwriters Laboratories (UL) has found the following 2‑wire detectors to be compatiblewith the D132A:

Manufacturer CTN Series Base Reversing* Maximum number ofdetectors per loop

Bosch D263THS D263 N/A ● 8

* D132A does not operate at 24 V; use only on 12 V powered loops.

7.2 Compatible 4 wire detectorsUnderwriters Laboratories (UL) has found the following 4‑wire detectors to be compatiblewith the D132A:

Manufacturer CTN Series Base Reversing*

Bosch D273THCS D273 N/A ●

D273THS ●

D273THES ●

* D132A does not operate at 24 V; use only on 12 V powered loops.

Page 24: Smoke Detector Reversing Relay Module

24 | Compatible detectors Smoke Detector Reversing Relay Module

2019.08 | 05 | F.01U.069.463 Installation manual Bosch Securiity Systems, B.V.