smoke control fans facilities I nuaire
testingfacilities• Nuaire has one of the foremost testing
facilities in the world.• Nuaire utilise ‘state of the art’ technology,
with separate testing facilities (ducted – type C, & D and open inlet – type A)
• Nuaire’s laboratories have the capability to carry out acoustic tests to BS848 part 2 and AMCA 300.
• Nuaire have a long standing relationship with BISRA (Building Services Research & Information Association), who choose to utilise Nuaire’s facilities for their own independent testing.
• Nuaire test all of their electrical products in-house for EMC (Electro magnetic compatibility).
• Nuaire’s team of technicians and test engineers have a wealth of knowledge gleaned from years of extensive acoustic andaerodynamic development and testing.
• Nuaire can advise you on the best solution possible for your requirement.
• Nuaire offer a ‘factory witness testing facility’for your and your client.
Part of Nuaire’s multi-million poundmanufacturing plant
Type ‘C’ and ‘D’ laboratory fortesting acoustic and aerodynamic
performance of duct mounted fans.
Type ‘A’ laboratory for testingacoustic and aerodynamic
performance of free inlet anddischarge eg. Roof mounted fans.
Control Office
Semi ReverberantPlenum Chamber
ConicalInlet
Door intoPlenum Chamber
InletCone
Silencer
Silencer
Control FanVariable Pitch
90 DegWith Turning Vanes
Delta PDifferentialPressure
▲ 4
StaticPressure
PS 3
StaticPressure
PS 4
FanUnder Test
Test Ducts
TransformationSection
Airflow
1m - 2m Diameter315 - 800mm Diameter
Ducted Fan Test Rig(Plan View)
smokecontrolShopping Centres & PublicBuildings: Safe EscapeThe main benefits of installing NuAire SmokeControl Systems are:• Safe escape for occupants• Safe entry for fire fighters• Reduced smoke damage• Reduced water damageNuAire fans provide a smoke ‘clear layer’ to allowbuilding occupants to safely escape from abuilding during a fire situation.
Commercial & Industrial Buildings:Safe Escape & Protecting GoodsIn addition these systems allow fire fightingservices to safely enter the building, to locate thefire and maintaining a clear layer helps prevent‘fire damage’ to stored goods or machinery.
Pressurisation of Escape RoutesBS5588 Part 4: specifies the use ofpressurisation for the means of escape.The systems ensure that stairs and corridors inmulit-storey buildings remain clear of smoke.
BS5588 Part 5: specifies the use ofpressurisation for fire fighting systems. Inaddition to providing safe means of escape,these are designed to offer safe access to firefighters.
Nuaire pressurisation run & stand by fans arespecially designed to meet the requirements ofthese standards.
Shopping Centres & Car Parks: Safe EscapeThrust Vent offers efficient daily ventilation forCO removal, smoke clearance and smokecontrol.
The system provides active cooling of thesmoke, creation of virtual smoke barriers, easyvisual location of the fire for emergency servicesand quick, efficient extinguishing of the fire.
For further details contact Nuaire on 029 2085 8200
Vent representing Leakage Path to Atmosphere
Fresh air fed in by MechanicalFan
Fire behind door
PressurisationRun & Standby Axial
ReservoirScreen
FreshAirflow
FreshAirflow
Safe Means of Escape
Pressurised Lobby
ClearLayer
PRODUCTS PRODUCTS PRODUCTS PRODUCTS
ClearLayer
High TemperatureFan/Cowl Combination
smoke control fans applications
smoke control fans I fan selection I 7.02
Thrust Vent smoke control system
Axus High TemperatureRoof Mounted Cowl/FanCombination
Axus High TemperatureLong Cased Axial
Purpose designed roof mountedsmoke extract unit.
Cowls - Low profile, high velocity, verticaldischargeOperating temperature - 300oC for 2 hour(optional 400oC for 2 hour)
• Low profile, weatherproof cowlTested in winds of 70mph and rainfall of 75mm/hrthe low profile cowl provides a weatherproof, aesthetic installation.
• Temperature/Time options300oC for 2 hours as standard(optional 400oC for 2 hours, contact Nuaire fordetails).
• Superb build qualityRobust heavy gauge aluminium alloy (sizes 560 & 710)or painted galvanised steel (sizes 1000 & 1250)construction for strength and durability.Tested to the highest standards
• Easy selectionThe cowl pressure drop is indicated on each fanperformance graph to provide quick, accurateinformation.
Purpose designed smoke extractunit.
Sizes - 16 Case diameters, from 315mm to 1600mmAirflow - Up to 85m3/s (306,000m3/hr) Static Pressure - Up to 1275 PaOperating temperature - 300oC for 2 hours (4000c fan 2 hours option)Matching attenuatorsInstallation ancillaries
• Wide rangeThe widest range of high temperature axials available.
• Superb build qualityWelded, heavy gauge galvanised steel constructionfor strength and durability.
• High performanceDeveloped to provide optimum performance for each case size.
• Tested to the highest standardsAir performance to BS848 (part1) 1997 and ISO5801(Part 1) 1997. Acoustic performance to AMCA300.High temperature operation to EN12101-3 2002
• Easy selectionThe performance curves illustrated in this catalogueare the standard 300oC range.
Performance figures for 400oC. For detailed selectionand technical data contact you local representative orNuaire’s technical department.
smoke control fans benefits
fan selection
smoke control fans I fan selection I 7.04
step 1Where is the fan to be located?
100
200
300
400
500
Fan
Sta
tic
Pres
sure
(Pa
34
5
12
11A
11B
step 2Which fan matches the required duty?Volume & flow rate?Pressure drop?
step 3What ancillaries do you need?Do I need attenuators, cowls, etc?
step 4Write your projectspecification?
fan selection I 7.03
axus contra-rotating I 7.05
axus run & standby I 7.07
high temperature axial withvertical cowl option I 7.09
high temperature squif I 7.29
smoke control fans axus contra-rotating I technical information
axuscontra-rotating
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com
Attenuators -Standard andLong options
available
Anti VibrationMounts
MountingBrackets
FlexibleConnectors
MatchingFlanges
Inlet Cones Damper Arc Cowl
Axus High Temperature Contra-Rotating Axial Flow Fans:• 13 Case diameters, 315 - 1250mm.
• Airflow - Up to 42m3/s.
• Static pressure - Up to 2500 Pa
• Operating temperature - 300oC for 2 hours/4OOoC for 2 hours.
• High performance - Developed to provide optimum performance for each case size.
• Tested to the highest standards-Air performance to BS848 (part 1) 1997 and IS05801 (Part 1) 1997.
Acoustic performance AMCA300.
High temperature operationEN 12101-3 2002
• General Features• 13 Case diameters, 315 - 1250mm
• Superb build quality - Welded, heavy gauge galvanised steel construction for strength and durability.
• High temperature performance -Units are suitable for smoke reservoir andnon smoke reservoir applcations. Units are dual purpose for day to day plus ‘one off’ emergency use.
• Flexible solution - Units can be installed at any angle.
• Matching Attenuators & ancillaries
• Advanced constructionAvoids the distortion associated with traditional methods of manufacturing and ensures consistency of performance.
• High performance - Developed to provide optimum performance for each case size.
• Available options: -AXUS units suitable for two speed operation (full and half speed).AXUS units available with access doors suitable for cleaning and observation.
• Ancillaries available - AV mounts, flexible connectors, mounting Brackets Matching Flanges, Inlet Cones, Guard, backdraught damper.
• Warranty
Axus Contra-Rotating have a 3 year warranty.
Note: An ambient option (550C) utilisingstandard motors are also available.
Code Descriptions
AXC 100 A - 4 1 3 A 7 T| | | | | | | | |1 2 3 4 5 6 7 8 9
1. Axus Contra-rotating axial2. Case diameter in cm3. Impeller specification reference4. Motor speed in poles5. Impeller blade angle reference6. Electrical supply in phase
3=400v, 50Hz three phase7. Impeller material
A = Aluminium8 Operating Temperature
7 = 3000C for 2 hours8 = 4000C for 2 hours
9 Other options (combinations possible)T = Two speed (full and half)Z = Access Door
Performance
smo
ke
con
tro
l fa
ns I
axu
s co
ntr
a-ro
tati
ng
tech
nica
l inf
orm
atio
n
Download specification from www.nuairegroup.com/specificationssmoke control fans I axus contra-rotating I 7.06
0 35000 72000 108000 144000 180000
m3/hr
4000
3500
3000
2500
2000
1500
1000
500
0
0 10 20 30 40 50
Fan
Sta
tic
Pre
ssu
re (
Pa)
Air Volume Flow Rate m3/s
3000C for 2 hours
4000C for 2 hours
Ambient (550C)
Code Frame A B C D E F G H J KAXC31 63-71 315 400 700 210 620 8 12 355 220 270AXC35 63-90 350 430 700 240 620 8 12 395 250 300AXC40 63-100 400 490 880 270 810 8 12 450 290 340AXC45 63-112 450 540 880 300 800 8 12 500 330 380AXC50 63-112 500 608 880 340 800 12 12 560 380 430AXC50 132 500 608 1200 340 1120 12 12 560 380 430AXC56 71-100 560 670 880 370 800 12 12 620 420 470AXC56 132 560 670 1200 370 1120 12 12 620 420 470AXC63 63-112 630 740 880 430 800 12 12 690 500 550AXC63 132-180 630 740 1200 430 1120 12 12 690 500 550AXC71 80-112 710 814 880 470 800 16 12 770 540 600AXC71 132 710 814 1400 470 1320 16 12 770 540 600AXC80 80-112 800 910 880 540 800 16 12 860 590 650AXC80 132-160 800 910 1400 540 1320 16 12 860 590 650AXC90 90-180 900 1016 1480 600 1400 16 15 970 670 750AXC100 90-180 1000 1128 1480 670 1370 16 15 1070 770 850AXC100 200 1000 1128 1700 670 1590 16 15 1070 770 850AXC112 100-160 1120 1240 1460 750 1350 20 15 1190 870 950AXC112 180-200 1120 1240 1730 750 1620 20 15 1190 870 950AXC112 225-250 1120 1240 2020 750 1910 20 15 1190 870 950AXC125 100-200 1250 1365 1730 830 1620 20 15 1320 920 1000AXC125 225-280 1250 1365 2020 830 1910 20 15 1320 920 1000For unit weights and pressure drops above 2500 pascals, please call our technical team on 029 2085 8200
F= No. of G dia holes equi-spacedon H p.c.d.
Unit shown supported on optional mounting brackets and A.V. mounts
AIRFLOW
E ctrsE ctrs
D
B F
lan
ge
A
C
K foot
J ctrs
Dimensions and Weights
smoke control fans axus run & standby I technical information
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com
axusrun&standby
Attenuators -Standard andLong options
available
Anti VibrationMounts
MountingBrackets
FlexibleConnectors
MatchingFlanges
Inlet Cones Damper Arc Cowl
Axus High Temperature Run & Standby Axial Fan• Airflow - Up to 73m3/s.
• Static pressure - Up to 1200 Pa.
• Operating temperature - 300oC for 2 hours/400oC for 2 hours.
• High performance - Developed to provide optimum performance for each case size.
• Tested to the highest standards, Airperformance to BS848 (partl) 1997 and IS05801 (Part 1) 1997.
• Acoustic performance AMCA300
• High temperature operationEN12101-3 2002
• General Features• 16 Case diameters, 315 - 1600mm
• High performance - Developed to provide optimum performance for each case size. Available options- AXUS units suitable for two speed operation (full and half speed).AXUS units available with access doors suitable for cleaning and observation.
• Matching Attenuators and ancillaries
• Superb build quality - Welded, heavy gauge galvanised steel construction for strength and durability.
• High temperature performance -Units are suitable for smoke reservoir andnon smoke reservoir applcations. Units are dual purpose for day to day plus ‘one off’ emergency use.
• Advanced constructionAvoids the distortion associated with traditional methods of manufacturing and ensures consistency of performance.
• Ancillaries available - AV mounts, Flexible connectors, Mounting Brackets, Matching Flanges, Inlet Cones, Guard, Backdraft Damper and attenuators.
• Warranty
Axus Run & Standby have a 3 year warranty.
Note: An ambient option (550C) utilisingstandard motors are also available.
Code Descriptions
AXT 100 A - 4 1 3 A 7 T| | | | | | | | |1 2 3 4 5 6 7 8 9
1. Axus Run & Standby axial2. Case diameter in cm3. Impeller specification reference4. Motor speed in poles5. Impeller blade angle reference6. Electrical supply in phase
3=400v, 50Hz three phase7. Impeller material
A = Aluminium8 Operating Temperature
7 = 3000C for 2 hours8 = 4000C for 2 hours
9 Other options (combinations possible)T = Two speed (full and half)Z = Access Door
smo
ke
con
tro
l fa
ns I
axu
s ru
n &
sta
nd
by
tech
nica
l inf
orm
atio
n
Download specification from www.nuairegroup.com/specificationssmoke control fans I axus run & standby I 7.08
Performance
Air Volume Flow Rate (m3/s)
Fan
Sta
tic
Pre
ssu
re (
Pa)
100
300
200
400
700
600
500
800
900
1000
1100
1200
1300
10 3020 40 50 60 70 800
0m3/hr
36000 10800072000 144000 216000 252000180000 288000
300oC for 2 hours
400oC for 2 hours
Ambient (55oC)
Code Frame A B C D E F G H J KAXT31 63-71 315 400 700 210 620 8 12 355 220 270AXT35 63-90 350 430 700 240 620 8 12 395 250 300AXT40 63-100 400 490 880 270 810 8 12 450 290 340AXT45 63-112 450 540 880 300 800 8 12 500 330 380AXT50 63-112 500 608 880 340 800 12 12 560 380 430AXT50 132 500 608 1200 340 1120 12 12 560 380 430AXT56 71-100 560 670 880 370 800 12 12 620 420 470AXT56 132 560 670 1200 370 1120 12 12 620 420 470AXT63 63-112 630 740 880 430 800 12 12 690 500 550AXT63 132-180 630 740 1200 430 1120 12 12 690 500 550AXT71 80-112 710 814 880 470 800 16 12 770 540 600AXT71 132 710 814 1400 470 1320 16 12 770 540 600AXT80 80-112 800 910 880 540 800 16 12 860 590 650AXT80 132-160 800 910 1400 540 1320 16 12 860 590 650AXT90 90-180 900 1016 1480 600 1400 16 15 970 670 750AXT100 90-180 1000 1128 1480 670 1370 16 15 1070 770 850AXT100 200 1000 1128 1700 670 1590 16 15 1070 770 850AXT112 100-160 1120 1240 1460 750 1350 20 15 1190 870 950AXT112 180-200 1120 1240 1730 750 1620 20 15 1190 870 950AXT112 225-250 1120 1240 2020 750 1910 20 15 1190 870 950AXT125 100-200 1250 1365 1730 830 1620 20 15 1320 920 1000AXT125 225-2880 1250 1365 2020 830 1910 20 15 1320 920 1000For unit weights and pressure drops above 2500 pascals, please call our technical team on 029 2085 82001800 & 2000 are available with standard motors (ambient 550c)Unit sizes 1400 - 1600mm call Nuaire for details.
F= No. of G dia holes equi-spacedon H p.c.d.
Unit shown supported on optional mounting brackets and A.V. mounts
AIRFLOW
E ctrsE ctrs
D
B F
lan
ge
A
C
K foot
J ctrs
Dimensions and Weights
smoke control fans axial I technical information
axialfans
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com
AXUSCircular Axial
AXUSRun & Standby
AXUSContra-Rotating
Arc Cowl
• Tried & tested Nuaire’s high temperature fans have beentested in accordance with the latest legislation and testing procedures. High temperature fans have been tested to EN12101-3 (2002) 3000C for 2 hours or 4000C for 2 hours.
• High temperature performanceUnits are suitable for smoke reservoir andnon smoke reservoir applcations. Units are dual purpose for day to day plus ‘one off’ emergency use.
• Wide range The widest range of hgh temperature axials available. A fan to match every application ensures maximum efficiency and saving costly energy.
• Heavy gauge galvanised steel constructionEnsuring strength, durability, protection from damage during installation and corrosion resistant for a long life.
• Manufactured by using advanced production methodsensures high quality, free from defect fans, to give superior performance consistently at lower costs.
• Tested to the highest standards Air performance to BS848 (part 1)1997 and ISO5801(part1)1997 with acoustic performance to AMCA300. All carried outat our own test facilities to ensure the most accurate performance figures and noise data is provided, constantly monitored to give you up to date information you can rely on.
• Fan optionsAs well contra-rotating & run /standby series, other options available are 4000cfor 2 hours & two speed.
high temperature
Code Descriptions
AX 100 A - 4 1 3 A 7 T| | | | | | | | |1 2 3 4 5 6 7 8 9
1. Axus long cased axial2. Case diameter in cm3. Impeller specification reference4. Motor speed in poles5. Impeller blade angle reference6. Electrical supply in phase
3=400/415v, 50Hz three phase7. Impeller material
A = Aluminium8 Operating Temperature
7 = 3000C for 2 hours8 = 4000C for 2 hours
9 Other options (combinations possible)T = Two speed (full and half)T6 = Two speed (full & two thirds) (4/6 pole only)
• Comprehensive ancillaries including a range of attenuators, and mounting ancillaries all pre-selected for the individual fan to ensure a perfect match and eliminate any on-site fitting problems.
• Warranty
High Temperature Axial fans have a 3 yearwarranty.
smo
ke
con
tro
l fa
ns I
axia
l fa
ns
tech
nica
l inf
orm
atio
n
Download specification from www.nuairegroup.com/specificationssmoke control fans I axial fans I 7.10
Below is an indication of the overall duty range, a selection of which is covered in this brochure. Please contact Nuaire Technical on (029) 2085 8200 for any duty outside the range indicated.
Axus Long Cased Axial
Air Volume Flow Rate (m3/s)
Fan
Sta
tic
Pre
ssu
re (
Pa)
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
10 20 30 40 50 60 70 80 900
2POLE
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
4 POLE 6 POLE
8 POLE
Air Volume Flow Rate (m3/s)
Fan
Sta
tic
Pre
ssu
re (
Pa)
100
200
300
400
500
600
700
800
900
1000
1100
10 20 30 40 50 600
2 POLE
6 POLE
4 POLE
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
8 POLE
AXUS - Axial flow fans for smoke control (3000C for 2 Hour)
AXUS - Axial flow fans for smoke control (4000C for 2 Hour)
smoke control fans axial I technical information
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com
Mounting Brackets (pair) Code: CMB31
Matching Flange (single) Code: CMF31
Flexible Connector (single) Code: CFC31
Anti-Vibration Mounts (for fan only)Codes: See table
Attenuator (standard, long & podded options)Code: CA31S, CA31L, CA31SP, CA31LP
GuardCode: CGD31
Inlet Cone Code: CIC31
Backdraught Damper Code: CBD31
Axus Long Cased Axial - 315mm ø (3000c for 2 hours)
0 0.2 0.4 0.6 0.8
20
40
60
120
100
80
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
1 23
4
5
6
78
0 0.4 0.6 0.80.2 1.0 1.2 1.4
100
50
150
200
250
300
400
350V
Type DAir Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
910
11
14
13
1516
12
General Electrical/Motor Noise/SoundIn-duct sound power levels dB re 1pW
Motor 3 Phase (400v) Inlet BreakoutCurve Unit Blade Speed Unit A.V. frame Motor flc sc Octave band mid frequency Hz dBANo Code Angle0 RPM kg Set size kW amps amps 125 250 500 1k 2k 4k 8k @ 3m315 Ø - 4pole/1440 rpm
1 AX31M-413A7 20 1415 21 NAV38 80 0.55 1.5 7.2 85 72 65 61 58 50 42 422 AX31X-413A7 25 1415 21 NAV38 80 0.55 1.5 7.2 77 72 63 61 58 48 42 403 AX31X-423A7 30 1415 21 NAV38 80 0.55 1.5 7.2 79 72 64 61 58 49 43 404 AX31X-443A7 35 1415 21 NAV38 80 0.55 1.5 7.2 77 70 63 62 58 48 41 395 AX31X-463A7 40 1415 21 NAV38 80 0.55 1.5 7.2 82 71 64 63 59 50 44 416 AX31F-443A7 40 1415 21 NAV38 80 0.55 1.5 7.2 70 75 63 65 61 53 46 417 AX31F-453A7 45 1415 21 NAV38 80 0.55 1.5 7.2 71 72 64 65 61 55 48 408 AX31B-453A7 45 1415 21 NAV38 80 0.55 1.5 7.2 71 71 63 61 59 55 50 39315 Ø - 2pole/2800rpm9 AX31M-213A7 20 2875 23 NAV38 80 0.75 1.65 11.2 81 97 80 78 74 70 63 5710 AX31B-213A7 25 2875 23 NAV38 80 0.75 1.65 11.2 72 78 75 75 72 69 63 511 AX31X-223A7 30 2875 23 NAV38 80 0.75 1.65 11.2 85 86 80 77 73 68 64 5412 AX31F-223A7 30 2875 23 NAV38 80 0.75 1.65 11.2 79 78 80 76 73 70 65 5213 AX31X-243A7 35 2875 23 NAV38 80 0.75 1.65 11.2 82 89 79 79 75 71 64 5414 AX31F-233A7 35 2875 23 NAV38 80 0.75 1.65 11.2 79 77 78 77 74 71 65 5215 AX31F-243A7 40 2875 23 NAV38 80 0.75 1.65 11.2 82 79 79 79 74 69 65 5316 AX31B-243A7 40 2875 23 NAV38 80 0.75 1.65 11.2 76 80 78 78 73 68 64 50All start currents are for DOL starting unless otherwise indicated
315mm Ø - 4 Pole/1440 RPM 315mm Ø - 2 Pole/2800 RPM
Notes relating to the tableThe electrical and sound information inthe table is nominal. Breakout dBA @3m is spherical, free field..
Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200
smo
ke
con
tro
l fa
ns I
axia
l fa
ns
tech
nica
l inf
orm
atio
n
smoke control fans I axial fans I 7.12
Axus Long Cased Axial - 350mm ø (3000c for 2 hours)
0 0.20 0.40 0.60 0.80 1.00 1.20
20
80
60
40
140
125
100
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
12
3
45
67
0 0.50 1.00 1.50 2.00 2.5
150
100
50
200
250
300
450
400
500
350
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
8 9 10 11 1213
14
General Electrical/Motor Noise/SoundIn-duct sound power levels dB re 1pW
Motor 3 Phase (400v) Inlet BreakoutCurve Unit Blade Speed Unit A.V. frame Motor flc sc Octave band mid frequency Hz dBANo Code Angle0 RPM kg Set size kW amps amps 125 250 500 1k 2k 4k 8k @ 3m350 Ø - 4pole/1440 rpm
1 AX35M-413A7 20 1415 22 NAV38 80 0.55 1.5 7.2 81 69 66 64 61 56 50 442 AX35F-413A7 25 1415 22 NAV38 80 0.55 1.5 7.2 75 72 66 65 63 57 49 413 AX35D-413A7 25 1415 22 NAV38 80 0.55 1.5 7.2 69 67 66 62 62 55 48 424 AX35X-423A7 30 1415 22 NAV38 80 0.55 1.5 7.2 89 77 66 63 59 50 43 485 AX35F-433A7 35 1415 22 NAV38 80 0.55 1.5 7.2 69 78 64 64 62 56 49 446 AX35F-443A7 40 1415 22 NAV38 80 0.55 1.5 7.2 73 75 64 63 59 55 50 427 AX35F-453A7 45 1415 22 NAV38 80 0.55 1.5 7.2 74 78 65 65 61 57 53 45350 Ø - 2pole/2800rpm8 AX35M-213A7 20 2875 23 NAV38 80 1.1 2.3 17.9 81 88 79 81 76 72 67 559 AX35X-213A7 25 2875 26 NAV38 80 1.1 2.3 17.9 84 89 81 80 76 74 66 5710 AX35X-223A7 30 2875 26 NAV38 80 1.1 2.3 17.9 85 96 81 81 77 74 66 6011 AX35X-243A7 35 2875 26 NAV38 80 1.1 2.3 17.9 87 88 83 84 79 75 68 5812 AX35M-273A7 40 2875 23 NAV38 80 1.1 2.3 17.9 86 101 82 82 79 74 69 6513 AX35F-243A7 40 2875 22 NAV38 90 1.5 3.1 25.7 90 85 86 84 81 76 71 6014 AX35F-253A7 45 2875 22 NAV38 90 1.5 3.1 25.7 90 85 86 84 81 76 71 60All start currents are for DOL starting unless otherwise indicated
350mm Ø - 4 Pole/1440 RPM 350mm Ø - 2 Pole/2800 RPM
Notes relating to the tableThe electrical and sound information inthe table is nominal. Breakout dBA @3m is spherical, free field.
Mounting Brackets (pair) Code: CMB35
Matching Flange (single) Code: CMF35
Flexible Connector (single) Code: CFC35
Anti-Vibration Mounts (for fan only)Codes: See table
Attenuator (standard, long & podded options)Code: CA35S, CA35L, CA35SP, CA35LP
GuardCode: CGD35
Inlet Cone Code: CIC35
Backdraught Damper Code: CBD35
Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200
Download specification from www.nuairegroup.com/specifications
smoke control fans axial I technical information
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com
Mounting Brackets (pair) Code: CMB40
Matching Flange (single) Code: CMF40
Flexible Connector (single)Code: CFC40
Anti-Vibration Mounts (for fan only)Codes: See table
Attenuator (standard, long & podded options)Code: CA40S, CA40L, CA40SP, CA40LP
GuardCode: CGD40
Inlet Cone Code: CIC40
Backdraught Damper Code: CBD40
Axus Long Cased Axial - 400mm ø (3000c for 2 hours)
0 0.4 0.80.6 1.00.2 1.2 1.4 1.6
20
60
40
200
80
100
120
140
160
180 VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
1
2
34
5
6
0 1.0 2.01.5 2.50.5 3.0
100
700
200
300
400
500
600
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
7 8
9
10
1112
13
Roof cowlresistance
General Electrical/Motor Noise/SoundIn-duct sound power levels dB re 1pW
Motor 3 Phase (400v) Inlet BreakoutCurve Unit Blade Speed Unit A.V. frame Motor flc sc Octave band mid frequency Hz dBANo Code Angle0 RPM kg Set size kW amps amps 125 250 500 1k 2k 4k 8k @ 3m400 Ø - 4pole/1440 rpm
1 AX40D-413A7 25 1415 26 NAV38 80 0.55 1.5 7.2 71 81 69 66 65 59 51 492 AX40I-413A7 25 1415 30 NAV38 80 0.55 1.5 7.2 72 77 73 69 67 63 54 453 AX40I-423A7 30 1415 30 NAV38 80 0.55 1.5 7.2 69 76 70 66 64 60 53 444 AX40I-433A7 35 1415 30 NAV38 80 0.55 1.5 7.2 72 79 70 67 63 58 53 455 AX40I-443A7 40 1415 30 NAV38 80 0.55 1.5 7.2 76 77 70 68 64 60 55 456 AX40I-453A7 45 1415 30 NAV38 80 0.55 1.5 7.2 76 77 71 69 64 60 55 46400 Ø - 2pole/2800rpm7 AX40C-213A7 25 2875 31 NAV38 80 0.75 1.65 11.2 81 90 83 80 75 71 69 598 AX40M-213A7 20 2875 31 NAV38 80 0.75 1.65 11.2 81 89 83 84 79 75 72 579 AX40F-213A7 25 2875 38 NAV39 90 1.5 3.1 25.7 78 82 86 83 81 78 74 5810 AX40I-223A7 30 2875 39 NAV39 90 1.8 3.6 31.3 82 81 89 84 80 78 75 6111 AX40I-233A7 35 2875 39 NAV39 90 2.2 4.4 39.6 85 83 90 84 80 75 70 6212 AX40I-243A7 40 2875 41 NAV39 100 3 5.8 53 88 86 92 85 81 76 72 6313 AX40I-253A7 45 2875 44 NAV39 100 3 5.8 53 92 87 90 90 85 80 76 63All start currents are for DOL starting unless otherwise indicated
400mm Ø - 4 Pole/1440 RPM 400mm Ø - 2 Pole/2800 RPM
Notes relating to the tableThe electrical and sound information inthe table is nominal. Breakout dBA @3m is spherical, free field.
Roof CowlCode: ARC56
Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200
smo
ke
con
tro
l fa
ns I
axia
l fa
ns
tech
nica
l inf
orm
atio
n
smoke control fans I axial fans I 7.14
Axus Long Cased Axial - 450mm ø (3000c for 2 hours)
0 0.5 1.00.75 1.25 1.50.25 1.75 2.0 2.25 2.5
50
100
150
200
250
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
1
24
56
7
89
3
0 1.0 2.01.5 2.5 3.00.5 3.5 4.0 4.5
100
300
200
1000
400
500
600
700
800
900 VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
1011
1214
15 16 1713
Roof cowlresistance
General Electrical/Motor Noise/SoundIn-duct sound power levels dB re 1pW
Motor 3 Phase (400v) Inlet BreakoutCurve Unit Blade Speed Unit A.V. frame Motor flc sc Octave band mid frequency Hz dBANo Code Angle0 RPM kg Set size kW amps amps 125 250 500 1k 2k 4k 8k @ 3m450 Ø - 4pole/1400 rpm1 AX45S-413A7 20 1415 34 NAV38 80 0.55 1.5 7.2 82 81 80 75 71 66 58 522 AX45P-413A7 20 1415 32 NAV38 80 0.55 1.5 7.2 79 79 78 74 71 66 58 503 AX45S-433A7 30 1415 34 NAV38 80 0.55 1.5 7.2 83 82 78 75 70 64 57 514 AX45S-453A7 35 1415 34 NAV38 80 0.55 1.5 7.2 83 81 80 78 72 68 61 535 AX45S-473A7 40 1415 34 NAV38 80 0.55 1.5 7.2 85 86 80 78 71 65 59 546 AX45S-483A7 45 1415 37 NAV39 80 0.75 2 9.8 83 84 80 77 69 65 59 557 AX45AA-453A7 37.5 1415 36 NAV39 80 0.55 1.5 7.2 82 79 75 73 68 61 55 498 AX45P-473A7 40 1415 36 NAV39 80 0.75 2 9.8 79 82 73 72 67 62 57 499 AX45P-483A7 45 1415 36 NAV39 80 0.75 2 9.8 80 81 73 71 66 60 55 49450 Ø - 2pole/2800rpm10 AX45P-213A7 20 2875 42 NAV39 90 1.8 3.6 31 85 86 91 91 87 83 81 6411 AX45AA-213A7 32.5 2875 54 NAV41 100 3 5.8 53 90 87 91 89 85 81 79 6412 AX45S-253A7 35 2910 55 NAV41 112 4 7.8 66 91 91 95 94 90 86 82 6813 AX45P-243A7 32.5 2910 53 NAV41 112 4 7.8 66 88 86 91 90 87 82 79 6514 AX45P-253A7 35 2910 53 NAV41 112 4 7.8 66 89 87 91 91 85 81 78 6515 AX45AA-253A7 37.5 2910 56 NAV41 112 4 7.8 66 92 89 92 90 85 80 74 6616 AX45F-243A7 45 2910 51 NAV41 112 4 7.8 66 85 82 93 89 85 81 78 6517 AX45F-253A7 45 2910 51 NAV41 112 4 7.8 66 87 84 92 90 86 82 79 66All start currents are for DOL starting unless otherwise indicated
450mm Ø - 4 Pole/1440 RPM 450mm Ø - 2 Pole/2800 RPM
Notes relating to the tableThe electrical and sound information inthe table is nominal. Breakout dBA @3m is spherical, free field.
Start currents (sc.) are DOL for allmotor sizes.
Mounting Brackets (pair) Code: CMB45
Matching Flange (single) Code: CMF45
Flexible Connector (single) Code: CFC45
Anti-Vibration Mounts (for fan only)Codes: See table
Attenuator (standard, long & podded options)Code: CA45S, CA45L, CA45SP, CA45LP
GuardCode: CGD45
Inlet Cone Code: CIC45
Backdraught Damper Code: CBD45
Roof CowlCode: ARC56
Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200
smoke control fans axial I technical information
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com
Mounting Brackets (pair) Code: CMB50
Matching Flange (single) Code: CMF50
Flexible Connector (single) Code: CFC50
Anti-Vibration Mounts (for fan only)Codes: See table
Attenuator (standard, long & podded options)Code: CA50S, CA50L, CA50SP, CA50LP
GuardCode: CGD50
Inlet Cone Code: CIC50
Backdraught Damper Code: CBD50
Axus Long Cased Axial - 500mm ø (3000c for 2 hours)
0 2.01.5 2.5 3.00.5 1.0
50
100
150
200
250
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
1
23
45 6
7
0 4.03.0 5.0 6.01.0 2.0
400
600
800
1000
1200
200
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
89
1011
12 13 14 Roof cowlresistance
General Electrical/Motor Noise/SoundIn-duct sound power levels dB re 1pW
Motor 3 Phase (400v) Inlet BreakoutCurve Unit Blade Speed Unit A.V. frame Motor flc sc Octave band mid frequency Hz dBANo Code Angle0 RPM kg Set size kW amps amps 125 250 500 1k 2k 4k 8k @ 3m500 Ø - 4pole/1440 rpm
1 AX50P-413A7 20 1415 33 NAV38 80 0.55 1.5 7.2 79 80 81 77 73 68 60 532 AX50S-433A7 30 1415 35 NAV38 80 0.55 1.5 7.2 80 82 79 77 73 68 62 523 AX50S-443A7 32.5 1415 40 NAV39 80 0.75 2 9.8 81 87 79 78 73 68 61 534 AX50S-453A7 35 1415 40 NAV39 80 0.75 2 9.8 81 84 80 78 73 68 61 535 AX50S-473A7 40 1430 44 NAV39 90 1.1 2.5 14.3 85 84 78 77 70 65 60 536 AX50P-473A7 40 1430 42 NAV39 90 1.1 2.5 14.3 79 80 77 74 70 64 60 527 AX50P-483A7 45 1430 42 NAV39 90 1.1 2.5 14.3 79 80 77 74 69 63 59 52500 Ø - 2pole/2800rpm8 AX50P-213A7 20 2875 53 NAV41 100 3 5.8 53 87 87 93 95 92 87 85 679 AX50P-223A7 25 2910 58 NAV41 112 4 7.8 66 86 90 96 95 92 86 81 6810 AX50S-243A7 32.5 2930 77 NAV43 132 7.5 14 118 93 94 96 94 89 85 81 6911 AX50S-253A7 35 2930 77 NAV43 132 7.5 14 118 93 91 99 95 91 87 85 7112 AX50S-273A7 40 2935 88 NAV43 132 9 16.6 146 95 93 97 97 92 88 86 7113 AX50P-263A7 40 2930 75 NAV43 132 7.5 14 118 91 90 98 94 92 85 82 7014 AX50P-283A7 45 2935 85 NAV43 132 9 16.6 146 93 91 99 95 91 86 85 71All start currents are for DOL starting unless otherwise indicated
500mm Ø - 4 Pole/1440 RPM 500mm Ø - 2 Pole/2800 RPM
Notes relating to the tableThe electrical and sound information inthe table is nominal. Breakout dBA @3m is spherical, free field.
Start currents (sc.) are DOL for allmotor sizes.
Roof CowlCode: ARC71
Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200
smo
ke
con
tro
l fa
ns I
axia
l fa
ns
tech
nica
l inf
orm
atio
n
smoke control fans I axial fans I 7.16
Axus Long Cased Axial - 560mm ø (3000c for 2 hours)
0 1.0 2.0 3.0 4.0 5.0
50
100
150
200
250
300
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
1
2 3 4
5
6 78
0 2 3 4 5 61
200
200
400
600
300
600
700
800
900
1000
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
9 10 1112
Roof cowlresistance
General Electrical/Motor Noise/SoundIn-duct sound power levels dB re 1pW
Motor 3 Phase (400v) Inlet BreakoutCurve Unit Blade Speed Unit A.V. frame Motor flc sc Octave band mid frequency Hz dBANo Code Angle0 RPM kg Set size kW amps amps 125 250 500 1k 2k 4k 8k @ 3m560 Ø - 4pole/1440 rpm1 AX56S-413A7 20 1415 41 NAV39 80 0.75 2 9.8 74 72 80 79 77 74 73 552 AX56S-423A7 25 1415 41 NAV39 80 0.75 2 9.8 75 73 81 80 78 75 74 553 AX56S-433A7 30 1430 43 NAV39 90 1.1 2.5 14.3 78 76 82 81 78 75 73 564 AX56S-453A7 35 1435 47 NAV40 90 1.5 3.4 19.7 80 79 83 80 76 72 68 565 AX56S-473A7 40 1435 47 NAV40 90 1.5 3.4 19.7 85 84 84 80 76 72 67 556 AX56S-483A7 45 1435 49 NAV40 90 1.8 4 24.4 83 87 83 81 77 74 68 557 AX56AA-473A7 45 1435 49 NAV40 90 1.8 4 24.4 83 82 82 79 74 70 66 538 AX56X-483A7 50 1435 44 NAV40 90 1.5 3.4 19.7 87 79 80 77 71 66 63 52560 Ø - 2pole/2800rpm9 AX56D-213A7 25 2875 42 NAV39 90 1.8 3.6 31.3 83 79 88 91 89 87 86 6610 AX56F-213A7 25 2875 49 NAV40 100 3 5.8 53 86 82 89 89 90 88 87 6511 AX56S-223A7 25 2930 94 NAV44 132 7.5 14 118 90 89 97 96 94 91 89 7012 AX56S-233A7 30 2935 102 NAV44 132 9 16.6 146 97 93 99 97 92 89 84 70All start currents are for DOL starting unless otherwise indicated
560mm Ø - 4 Pole/1440 RPM 560mm Ø - 2 Pole/2800 RPM
Notes relating to the tableThe electrical and sound information inthe table is nominal. Breakout dBA @3m is spherical, free field.
Start currents (sc.) are DOL for allmotor sizes.
Mounting Brackets (pair) Code: CMB56
Matching Flange (single) Code: CMF56
Flexible Connector (single) Code: CFC56
Anti-Vibration Mounts (for fan only)Codes: See table
Attenuator (standard, long & podded options)Code: CA56S, CA56L, CA56SP, CA56LP
GuardCode: CGD56
Inlet Cone Code: CIC56
Backdraught Damper Code: CBD56 Roof Cowl
Code: ARC71
Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200
Download specification from www.nuairegroup.com/specifications
smoke control fans axial I technical information
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com
Mounting Brackets (pair) Code: CMB63
Matching Flange (single) Code: CMF63
Flexible Connector (single) Code: CFC63
Anti-Vibration Mounts (for fan only)Codes: See table
Attenuator (standard, long & podded options)Code: CA63S, CA63L, CA63SP, CA63LP
GuardCode: CGD63
Inlet Cone Code: CIC63
Backdraught Damper Code: CBD63
Axus Long Cased Axial - 630mm ø (3000c for 2 hours)
0 2.0 3.0 4.0 5.0 6.0 7.01.0
100
50
150
200
250
300
350
400
450
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa) 1
2 3 4 5 6
7
Roof cowlresistance
0 3 4 5 6 7 8 921
200
400
600
800
1000
1200
1400
1600
1800
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
8
910
11
12
Roof cowlresistance
General Electrical/Motor Noise/SoundIn-duct sound power levels dB re 1pW
Motor 3 Phase (400v) Inlet BreakoutCurve Unit Blade Speed Unit A.V. frame Motor flc sc Octave band mid frequency Hz dBANo Code Angle0 RPM kg Set size kW amps amps 125 250 500 1k 2k 4k 8k @ 3m630 Ø - 4pole/1440 rpm1 AX63S-413A7 20 1430 50 NAV40 90 1.1 2.5 14.3 85 85 83 81 78 76 68 562 AX63S-423A7 25 1430 50 NAV40 90 1.1 2.5 14.3 82 82 83 80 77 75 67 553 AX63AD-423A7 30 1435 56 NAV41 100 1.8 4 24.4 85 87 86 80 76 72 64 574 AX63AD-443A7 35 1435 59 NAV41 100 2.2 4.7 30.1 85 90 85 81 78 76 68 585 AX63AD-473A7 45 1435 61 NAV41 100 3 6.4 41 87 87 84 81 77 73 67 586 AX63AD-483A7 50 1455 65 NAV41 112 4 8.2 *57 86 87 86 82 78 74 68 597 AX63AA-483A7 50 1455 63 NAV41 112 4 8.2 *57 83 87 85 82 77 71 67 58630 Ø - 2pole/2800rpm8 AX63P-213A7 20 2915 81 NAV43 132 5.5 10.3 100 86 89 97 99 98 92 90 729 AX63P-223A7 25 2935 88 NAV43 132 9 16.6 146 94 93 102 101 98 93 90 7410 AX63AD-213A7 25 2935 123 NAV46 160 11 19.9 183 92 92 100 99 96 92 93 7311 AX63AD-223A7 30 2940 141 NAV46 160 15 27 265 95 94 105 98 95 91 91 7512 AX63AD-243A7 35 2938 156 NAV47 180 22 39.9 319 97 97 107 100 95 92 91 77All start currents are for DOL starting unless otherwise indicated
630mm Ø - 4 Pole/1440 RPM 630mm Ø - 2 Pole/2800 RPM
Notes relating to the tableThe electrical and sound information inthe table is nominal. Breakout dBA @3m is spherical, free field.
Start currents (sc.) are DOL for allmotor sizes.
Roof CowlCode: ARC71
Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200
smo
ke
con
tro
l fa
ns I
axia
l fa
ns
tech
nica
l inf
orm
atio
n
smoke control fans I axial fans I 7.18
Axus Long Cased Axial - 710mm ø (3000c for 2 hours)
0 2.0 3.0 4.0 5.0 6.01.0 1.5 2.5 3.5 4.5 5.50.5
20
40
160
180
120
140
80
60
100
200
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
1 2 3 4 5 67
0 2 3 4 5 6 7 8 9 101
100
50
200
150
300
250
400
350
450
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
8
910
11 12 1314
15Roof cowlresistance
General Electrical/Motor Noise/SoundIn-duct sound power levels dB re 1pW
Motor 3 Phase (400v) Inlet BreakoutCurve Unit Blade Speed Unit A.V. frame Motor flc sc Octave band mid frequency Hz dBANo Code Angle0 RPM kg Set size kW amps amps 125 250 500 1k 2k 4k 8k @ 3m710 Ø - 6pole/960 rpm1 AX71O-613A7 20 920 43 NAV39 90 0.55 1.75 8.1 78 79 76 76 72 66 57 492 AX71P-623A7 25 920 45 NAV39 90 0.55 1.75 8.1 82 76 74 74 72 67 58 493 AX71AA-623A7 30 920 47 NAV40 90 0.55 1.75 8.1 83 78 74 74 73 65 56 494 AX71AD-643A7 35 920 57 NAV41 90 1.1 3.0 13.3 79 79 77 73 70 64 58 505 AX71AD-663A7 40 920 61 NAV41 100 1.5 4 19.2 81 79 77 73 70 65 60 506 AX71AD-673A7 45 920 61 NAV41 100 1.5 4 19.2 79 78 78 73 70 65 61 517 AX71AD-683A7 30 960 66 NAV42 112 2.2 5.2 31.7 79 81 79 75 72 67 61 52710 Ø - 4pole/1400 rpm8 AX71O-413A7 20 1415 44 NAV39 80 0.75 2 9.8 83 82 84 85 81 78 72 579 AX71O-423A7 25 1430 45 NAV39 90 1.1 2.5 14.3 81 81 80 80 79 77 70 5610 AX71P-423A7 25 1435 48 NAV40 100 1.8 4 24.4 100 95 90 86 81 79 72 6111 AX71AD-423A7 30 1435 63 NAV41 100 3 6.4 41 83 92 88 86 83 81 72 6012 AX71AA-463A7 40 1455 64 NAV41 112 4 8.2 57 83 95 89 86 83 81 73 6313 AX71AD-463A7 40 1455 97 NAV44 132 5.5 10.8 81 86 91 86 83 80 75 69 6014 AX71AD-473A7 45 1455 97 NAV44 132 5.5 10.8 81 85 96 87 85 80 75 70 6215 AX71AD-483A7 50 1455 124 NAV46 132 7.5 14.5 107 86 94 90 87 84 80 76 64All start currents are for DOL starting unless otherwise indicated
710mm Ø - 6 Pole/960 RPM 710mm Ø - 4 Pole/1400 RPM
Notes relating to the tableThe electrical and sound information inthe table is nominal. Breakout dBA @3m is spherical, free field.
Start currents (sc.) are DOL for allmotor sizes.
Mounting Brackets (pair) Code: CMB71
Matching Flange (single) Code: CMF71
Flexible Connector (single) Code: CFC71
Anti-Vibration Mounts (for fan only)Codes: See table
Attenuator (standard, long & podded options)Code: CA71S, CA71L, CA71SP, CA71LP
GuardCode: CGD71
Inlet Cone Code: CIC71
Backdraught Damper Code: CBD71
Roof CowlCode: ARC100
Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200
Download specification from www.nuairegroup.com/specifications
smoke control fans axial I technical information
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com
Mounting Brackets (pair) Code: CMB80
Matching Flange (single) Code: CMF80
Flexible Connector (single) Code: CFC80
Anti-Vibration Mounts (for fan only)Codes: See table
Attenuator (standard, long & podded options)Code: CA80S, CA80L, CA80SP, CA80LP
GuardCode: CGD80
Inlet Cone Code: CIC80
Backdraught Damper Code: CBD80
Axus Long Cased Axial - 800mm ø (3000c for 2 hours)
qv - Air volume flow (m3/s)
0 2 3 4 5 6 7 81
50
100
150
200
250
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
p sF -
Sta
tic
Pre
ssu
re (
Pa)
12 3 4 5 6 7
0 2 4 6 8
50
100
150
200
250
300
350
400
450
500
10 12 14
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
10 11 1213
14
15
8
9
Roof cowlresistance
General Electrical/Motor Noise/SoundIn-duct sound power levels dB re 1pW
Motor 3 Phase (400v) Inlet BreakoutCurve Unit Blade Speed Unit A.V. frame Motor flc sc Octave band mid frequency Hz dBANo Code Angle0 RPM kg Set size kW amps amps 125 250 500 1k 2k 4k 8k @ 3m800 Ø - 6pole/960 rpm1 AX80O-623A7 25 920 57 NAV41 90 0.55 1.75 8.1 80 76 76 77 75 71 60 502 AX80P-623A7 25 920 59 NAV41 90 0.55 1.75 8.1 82 75 77 76 75 71 60 503 AX80AG-623A7 30 920 87 NAV43 100 1.5 4 19.2 82 85 83 79 78 72 63 564 AX80AG-643A7 35 960 100 NAV44 112 2.2 5.2 31.7 80 86 81 79 78 74 66 555 AX80AG-663A7 40 960 100 NAV44 112 2.2 5.2 31.7 81 84 81 78 76 72 64 556 AX80AG-673A7 45 945 125 NAV46 132 3 7 39.2 84 86 83 79 76 71 66 587 AX80AG-683A7 50 945 135 NAV46 132 4 9.3 52 83 88 84 81 78 74 68 57800 Ø - 4pole/1440 rpm8 AX80O-413A7 20 1430 57 NAV41 90 1.1 2.5 14.3 83 84 86 91 88 82 76 629 AX80P-423A7 25 1435 63 NAV41 100 2.2 4.7 30.1 80 86 87 87 85 84 78 6110 AX80AA-423A7 30 1435 69 NAV42 100 3 6.4 41 82 88 88 86 83 82 74 6111 AX80AG-443A7 35 1455 134 NAV46 132 7.5 14.5 107 87 89 92 90 87 85 79 6412 AX80AG-463A7 40 1455 149 NAV46 160 11 21.2 163 89 94 94 89 86 84 78 6413 AX80AG-473A7 45 1455 149 NAV46 160 11 21.2 163 91 93 93 89 85 82 77 6614 AX80AG-483A7 50 1456 159 NAV47 160 15 28.8 202 93 93 96 91 89 85 82 6815 AX80AD-483A7 50 1455 145 NAV46 160 11 21.2 163 88 96 92 89 87 84 81 65All start currents are for DOL starting unless otherwise indicated
800mm Ø - 6 Pole/960 RPM 800mm Ø - 4 Pole/1440 RPM
Notes relating to the tableThe electrical and sound information inthe table is nominal. Breakout dBA @3m is spherical, free field.
Start currents (sc.) are DOL for allmotor sizes.
Roof CowlCode: ARC100
Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200
smo
ke
con
tro
l fa
ns I
axia
l fa
ns
tech
nica
l inf
orm
atio
n
smoke control fans I axial fans I 7.20
Axus Long Cased Axial - 900mm ø (300 0c for 2 hours)
0 2 3 4 5 6 7 81
50
100
150
200
250
300
9 10 11 12
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
1
23
4 5
Roof cowlresistance
0 4 6 8 10 12 14 162
200
300
400
500
600
100
18
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
6
78 9 10
11Roof cowlresistance
General Electrical/Motor Noise/SoundIn-duct sound power levels dB re 1pW
Motor 3 Phase (400v) Inlet BreakoutCurve Unit Blade Speed Unit A.V. frame Motor flc sc Octave band mid frequency Hz dBANo Code Angle0 RPM kg Set size kW amps amps 125 250 500 1k 2k 4k 8k @ 3m900 Ø - 6pole/960 rpm1 AX90AA-623A7 30 920 102 NAV44 100 1.5 4 19.2 85 82 80 79 79 74 61 542 AX90AG-643A7 35 945 144 NAV46 132 4 9.3 52 83 90 85 83 82 78 69 603 AX90AG-663A7 40 945 144 NAV46 132 4 9.3 52 84 88 84 81 80 75 68 584 AX90AG-673A7 45 950 149 NAV46 132 5.5 12.7 72 88 90 87 83 79 75 69 625 AX90AG-683A7 50 970 174 NAV47 160 7.5 16.1 76 87 92 88 85 82 78 72 61900 Ø - 4pole/1440 rpm6 AX90AA-423A7 30 1455 120 NAV45 132 5.5 10.8 81 85 92 92 90 86 85 78 717 AX90AG-423A7 30 1455 163 NAV47 160 11 21.2 163 90 94 96 92 89 89 81 698 AX90AG-443A7 35 1456 173 NAV47 160 15 28.8 202 90 93 96 93 90 89 82 699 AX90AG-463A7 40 1456 187 NAV47 180 18.5 35.2 268 92 97 97 93 90 88 82 6910 AX90AG-473A7 45 1456 203 NAV47 180 22 41.7 329 94 96 97 93 89 85 81 7011 AX90AG-483A7 50 1450 256 NAV48 200 30 56.3 372 97 97 99 95 92 88 85 71All start currents are for DOL starting unless otherwise indicated
900mm Ø - 6 Pole/960 RPM 900mm Ø - 4 Pole/1440 RPM
Notes relating to the tableThe electrical and sound information inthe table is nominal. Breakout dBA @3m is spherical, free field.
Start currents (sc.) are DOL for allmotor sizes.
Mounting Brackets (pair) Code: CMB90
Matching Flange (single) Code: CMF90
Flexible Connector (single) Code: CFC90
Anti-Vibration Mounts (for fan only)Codes: See table
Attenuator (standard, long & podded options)Code: CA90S, CA90L, CA90SP, CA90LP
GuardCode: CGD90
Inlet Cone Code: CIC90
Backdraught Damper Code: CBD90
Roof CowlCode: ARC125
Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200
Download specification from www.nuairegroup.com/specifications
smoke control fans axial I technical information
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com
Mounting Brackets (pair) Code: CMB100
Matching Flange (single) Code: CMF100
Flexible Connector (single)Code: CFC100
Anti-Vibration Mounts (for fan only)Codes: See table
Attenuator (standard, long & podded options)Code: CA100S, CA100L, CA100SP, CA100LP
GuardCode: CGD100
Inlet Cone Code: CIC100
Backdraught Damper Code: CBD100
Axus Long Cased Axial - 1000mm ø (300 0c for 2 hours)
0 4 106 8 122 14 16
50
350
100
150
200
250
300V
Type DAir Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
1 2 3
45 6
Roof cowlresistance
0 105 252015
200
100
300
400
500
600
900
700
800V
Type DAir Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
78
9 10 11
12 13
Roof cowlresistance
General Electrical/Motor Noise/SoundIn-duct sound power levels dB re 1pW
Motor 3 Phase (400v) Inlet BreakoutCurve Unit Blade Speed Unit A.V. frame Motor flc sc Octave band mid frequency Hz dBANo Code Angle0 RPM kg Set size kW amps amps 125 250 500 1k 2k 4k 8k @ 3m1000 Ø - 6pole/960 rpm1 AX100AD-613A7 25 960 115 NAV45 112 2.2 5.2 31.7 83 89 94 93 85 81 67 642 AX100AD-623A7 30 945 127 NAV46 132 3 7 39.2 93 88 95 95 89 83 73 663 AX100CX-623A7 30 950 161 NAV47 132 5.5 12.7 72 100 94 89 82 77 74 67 634 AX100CX-643A7 35 970 190 NAV47 160 7.5 16.1 76 94 89 85 80 76 77 71 605 AX100CX-663A7 40 970 214 NAV47 160 11 23.3 107 95 90 87 82 78 79 74 616 AX100CX-673A7 45 970 214 NAV47 160 11 23.3 107 100 91 86 83 79 78 75 621000 Ø - 4pole/1440 rpm7 AX100AD-413A7 25 1455 103 NAV44 132 5.5 10.8 81 84 97 94 100 96 91 86 718 AX100AD-423A7 25 1455 129 NAV46 160 11 21.2 163 96 98 103 103 98 92 87 749 AX100CX-413A7 30 1455 179 NAV47 160 11 21.2 163 97 96 97 93 89 88 81 6910 AX100CX-423A7 35 1456 187 NAV47 160 15 28.8 202 102 98 97 94 90 88 83 7011 AX100CX-443A7 35 1456 221 NAV47 180 22 41.7 329 100 100 98 95 91 90 87 7112 AX100CX-463A7 40 1460 319 NAV49 200 30 56 372 101 101 100 97 93 92 89 7313 AX100CX-473A7 45 1468 359 NAV49 225 37 69 433 103 101 100 98 95 95 93 73All start currents are for DOL starting unless otherwise indicated
1000mm Ø - 6 Pole/960 RPM 1000mm Ø - 4 Pole/1440 RPM
Notes relating to the tableThe electrical and sound information inthe table is nominal. Breakout dBA @3m is spherical, free field.
Start currents (sc.) are DOL for allmotor sizes.
Roof CowlCode: ARC125
Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200
smo
ke
con
tro
l fa
ns I
axia
l fa
ns
tech
nica
l inf
orm
atio
n
smoke control fans I axial fans I 7.22
Axus Long Cased Axial - 1120mm ø (300 0c for 2 hours)
0 5 10 15 20 25
50
500
100
150
200
250
300
350
400
450 VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
12 3
4 5 6
Roof cowlresistance
0 10 15 20 25 305
800
1000
1200
600
400
200
35
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
78 9 10 11 12
Roof cowlresistance
General Electrical/Motor Noise/SoundIn-duct sound power levels dB re 1pW
Motor 3 Phase (400v) Inlet BreakoutCurve Unit Blade Speed Unit A.V. frame Motor flc sc Octave band mid frequency Hz dBANo Code Angle0 RPM kg Set size kW amps amps 125 250 500 1k 2k 4k 8k @ 3m1120 Ø - 6pole/960 rpm1 AX112CW-613A7 25 945 196 NAV47 132 3 7 43 91 95 94 95 88 83 74 692 AX112CX-613A7 25 950 212 NAV47 132 5.5 12.7 72 94 93 88 85 81 80 82 673 AX112CX-623A7 30 970 228 NAV47 160 7.5 16.1 76 98 94 89 86 83 80 79 684 AX112CX-643A7 35 970 252 NAV48 160 11 23.3 107 99 96 91 87 85 83 79 695 AX112CX-663A7 40 970 252 NAV48 160 11 23.3 107 101 98 94 89 87 86 83 726 AX112CX-673A7 45 970 293 NAV48 180 15 30.1 205 104 100 95 91 89 88 86 731120 Ø - 4pole/1440 rpm7 AX112CW-413A7 25 1455 222 NAV47 160 11 21.2 163 95 101 105 104 98 92 85 778 AX112CX-413A7 25 1455 233 NAV47 160 15 28.8 202 98 99 99 94 92 88 93 759 AX112CX-423A7 30 1455 270 NAV48 180 22 41.7 329 102 100 100 95 94 89 90 7610 AX112CX-443A7 35 1460 323 NAV49 200 30 56.3 372 103 102 102 96 95 92 90 7711 AX112CX-463A7 40 1470 369 NAV49 225 37 69 433 105 104 105 98 98 95 94 8012 AX112CX-473A7 45 1480 531 NAV51 250 55 101 707 108 106 106 100 100 97 97 81All start currents are for DOL starting unless otherwise indicated
1120mm Ø - 6 Pole/960 RPM 1120mm Ø - 4 Pole/1440 RPM
Notes relating to the tableThe electrical and sound information inthe table is nominal. Breakout dBA @3m is spherical, free field.
Start currents (sc.) are DOL for allmotor sizes.
Mounting Brackets (pair) Code: CMB112
Matching Flange (single) Code: CMF112
Flexible Connector (single) Code: CFC112
Anti-Vibration Mounts (for fan only)Codes: See table
Attenuator (standard, long & podded options)Code: CA112S, CA112L, CA112SP, CA112LP
GuardCode: CGD112
Inlet Cone Code: CIC112
Backdraught Damper Code: CBD112
Roof CowlCode: ARC125
Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200
Download specification from www.nuairegroup.com/specifications
smoke control fans axial I technical information
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com
Mounting Brackets (pair) Code: CMB125
Matching Flange (single) Code: CMF125
Flexible Connector (single)Code: CFC125
Anti-Vibration Mounts (for fan only)Codes: See table
Attenuator (standard, long & podded options)Code: CA125S, CA125L, CA125SP, CA125LP
GuardCode: CGD125
Inlet Cone Code: CIC125
Backdraught Damper Code: CBD125
Axus Long Cased Axial - 1250mm ø (300 0c for 2 hours)
0 10 15 20 255
100
200
300
400
500
30
600
35
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
12 3 4
5
6
Roof cowlresistance
0 10 15 20 25 30 35 405
800
1000
1200
1400
600
400
200
45 50
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
qv - Air volume flow (m3/s)
p sF -
Sta
tic
Pre
ssu
re (
Pa)
7
8 910 11 12
Roof cowlresistance
General Electrical/Motor Noise/SoundIn-duct sound power levels dB re 1pW
Motor 3 Phase (400v) Inlet BreakoutCurve Unit Blade Speed Unit A.V. frame Motor flc sc Octave band mid frequency Hz dBANo Code Angle0 RPM kg Set size kW amps amps 125 250 500 1k 2k 4k 8k @ 3m1250 Ø - 6pole/960 rpm1 AX125CW-613A7 25 945 245 NAV48 132 4 9.3 52 95 99 100 99 94 87 80 732 AX125CX-613A7 25 970 257 NAV48 160 7.5 16.1 76 95 96 91 88 84 83 85 703 AX125CX-623A7 30 970 281 NAV48 160 11 23.3 107 99 97 92 89 86 83 82 714 AX125CX-643A7 35 970 311 NAV48 180 15 30.1 205 100 99 94 90 88 86 82 725 AX125CX-663A7 40 970 347 NAV49 200 18.5 37 237 102 101 97 92 90 89 86 756 AX125CX-673A7 45 970 377 NAV49 200 22 43.6 262 105 103 98 94 92 91 89 761250 Ø - 4pole/1440 rpm7 AX125CW-413A7 25 1460 245 NAV48 160 15 28.8 202 99 105 109 108 102 96 89 818 AX125CX-413A7 25 1460 289 NAV48 180 22 41.7 329 99 102 100 97 93 91 94 789 AX125CX-423A7 30 1460 353 NAV49 200 30 56 372 103 103 101 98 95 92 91 7910 AX125CX-443A7 35 1470 423 NAV50 225 45 83 525 104 105 103 99 96 95 91 8011 AX125CX-463A7 40 1480 619 NAV53 250 55 101 707 106 107 106 101 99 98 95 8312 AX125CX-473A7 45 1480 724 NAV54 280 75 137 986 109 109 107 103 101 100 98 84All start currents are for DOL starting unless otherwise indicated
1250mm Ø - 6 Pole/960 RPM 1250mm Ø - 4 Pole/1440 RPM
Notes relating to the tableThe electrical and sound information inthe table is nominal. Breakout dBA @3m is spherical, free field.
Start currents (sc.) are DOL for allmotor sizes.
Roof CowlCode: ARC125
Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200
smo
ke
con
tro
l fa
ns I
axia
l fa
ns
tech
nica
l inf
orm
atio
n
smoke control fans I axial fans I 7.24
Dimensions and WeightsF= No. of G dia holes equi-spacedon H p.c.d.
Unit shown supported on optional mounting brackets and A.V. mounts
OptionalAV mounts
AIRFLOW
E ctrs
D
B F
lan
ge
A
C
K foot
J ctrs
Max.Weight
Code Frame A B C D E F G H J K kgAX31 80 315 400 350 210 270 8 12 355 220 270 23AX35 90 350 430 350 240 270 8 12 395 250 300 26AX40 90-100 400 490 440 270 370 8 12 450 290 340 44AX45 90-112 450 540 440 300 360 8 12 500 330 380 65
132 450 540 600 300 520 8 12 500 330 380AX50 90-112 500 608 440 340 360 12 12 560 380 430 88
132 500 608 600 340 520 12 12 560 380 430AX56 90-100 560 670 440 370 360 12 12 620 420 470 104
132 560 670 600 370 520 12 12 620 420 470AX63 90-112 630 740 440 430 360 12 12 690 500 550 209
132-180 630 740 600 430 520 12 12 690 500 550AX71 90-112 710 814 440 470 360 16 12 770 540 600 124
132 710 814 700 470 620 16 12 770 540 600AX80 90-112 800 910 440 540 360 16 12 860 590 650 142
132-160 800 910 700 540 620 16 12 860 590 650AX90 112-180 900 1016 740 600 660 16 15 970 670 750 203AX100 112-180 1000 1128 740 670 630 16 15 1070 770 850 324
200 1000 1128 850 740 16 15 1070 770 850AX112 132-160 1120 1240 730 750 620 20 15 1190 870 950 551
180-200 1120 1240 865 750 755 20 15 1190 870 950225-250 1120 1240 1010 750 900 20 15 1190 870 950
AX125 132-200 1250 1365 865 830 755 20 15 1320 920 1000 729225-280 1250 1365 1010 830 900 20 15 1320 920 1000
Please call Nuaire on (029) 2085 8200 if you require further details
Download specification from www.nuairegroup.com/specifications
smoke control fans axial I ancillaries
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com
ancillariesAttenuatorsAttenuators shall be rigidly constructed from galvanised steel, internally linedwith sound absorbing material not less than 100mm thick retained bygalvanised steel perforated sheet.Attenuator ‘end faces’ shall be drilled and tapped to match the flange details ofthe associated fan. Attenuator ‘sound absorbing material’ shall be chemicallyinert, non combustible, non-hygroscopic and vermin resistant.Attenuator shall be tested in accordance with BS4718 : 1971 ASTME 477.All attenuators shall be suitable for internal and external use at any installedangle.Standard - Typical code: CA100S.Long - Typical code: CA100L
Dimensions (mm) Weight (kg)Unit Code A B C C D E F Standard LongCode Standard Long No Pod No PodCA31 315 515 315 630 8 M8 355 8 15CA35 355 555 355 710 8 M8 395 11 21CA40 400 600 400 800 8 M10 450 16 30CA45 450 650 450 900 8 M10 500 20 38CA50 500 700 500 1000 12 M10 560 23 42CA56 560 760 560 1120 12 M10 620 25 47CA63 630 830 630 1260 12 M10 690 30 56CA71 710 910 710 1420 16 M10 770 34 63CA80 800 1000 800 1600 16 M10 860 73 133CA90 900 1100 900 1800 16 M12 970 92 166CA100 1000 1200 1000 2000 16 M12 1070 111 203CA112 1120 1320 1120 2240 20 M12 1190 143 261CA125 1250 1450 1250 2500 20 M12 1320 188 343For Further attenuation please refer to Axial Section
Bdia
Adia
CLength
'E' No. of holes tapped 'F' equi-spaced on 'G' P.C.D.
Airflow
Mounting BracketsManufactured from heavy gauge galvanised steel mounting brackets are supplied inpairs. See table 1 for dimensions and weights. Typical code: CMB100 (100 = fan diameter in cm) F base
fixing centres
E
C/L fan
Flexible Connector Circular without flanges. Flexible connectors are suitable for operation at 400oCfor 2 hours and are resistant to chemicals, ozone, oil and grease. The connectoris airtight, waterproof and tested to BS476 Part 7. Flexible connector is suitablefor 400oC and 2 hours Temperature/Time. Clamping bands included.
Typical code: CFCH100 (100 = fan diameter in cm)B
To matchfan diameter
Inlet Cone (single)Manufactured in heavy gauge galvanised steel with a single bolted flange. See table 1 for dimensions and weights.Low loss inlet cone 0.38
Typical code: CIC100 (100 = fan diameter in cm)
C
D
smo
ke
con
tro
l fa
ns I
axia
l fa
ns
tech
nica
l inf
orm
atio
n
smoke control fans I axial fans I 7.26
Vertical Discharge Cowl
FLOW
A sq
C
A sq
B
D sqInside Skirt
Dimensions (mm)
Code A B C D Max WeightARC56 845 570 535 786 93.0kgARC71 1100 770 760 1045 146.0kgARC100 1295 1000 880 1234 364.0kgARC125 1795 1300 1160 1738 615.0kgFor further assistance, please contact Nuaire Technical on (029) 2085 8200Fans and Cowls are supplied seperately
Curb Dimensions (3000/4000 units)Code Dimensions (mm)
A B C DARC56 600 75 675 746ARC71 800 100 875 1016ARC100 1000 100 1100 1198ARC125 1500 100 1600 1700
PrefabricatedCurb
BuildersUpstand
C & C inside trimmer angles
A x A
D x D maximum
Flashing can be extended over curbor to underside of timber
A x A minimum dim. Inside roof opening
B
D x D maximum
150 min
150 min
CONCRETEROOF
DECKINGROOF
Trimmer
Purlin
Wood capping(optional 15mmoverhang)
Note:Wooden capping to be hardwood or treated softwood.
Download specification from www.nuairegroup.com/specifications
Wiring
smoke control fans axial I technical information
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com
2 Speed 3 phase Dual Wound Motors
(D.O.L. starting both speeds)
400V 3 phase 50Hz supply
1U
1V
1W
2U
2V
2W
1U
1V
1W
2U
2V
2W
L1
L2
L3
L1
L2
L3
High speedLow speedNOTE: If a two speed starter is used it must have TWO contactorsIndividual wiring diagrams are included with each unit.
2 Speed 3 phasePAP/PAM Wound Motors
(D.O.L. starting both speeds)
1U
1V
1W
2U
2V
2W400V 3 phase 50Hz supply
Link (if no control
is used )
High speedLow speed
NOTE: If a two speed starter is used it must have THREE contactorsIndividual wiring diagrams are included with each unit.
L1
L2
L3
1U
1V
1W
2U
2V
2W
L1
L2
L3
Single Speed3 Phase (Below 4kW)
L1 L2 L3
400V 3 phase 50Hz supply
Fanunit
3 phase for Star/Delta Starting(4kW and above)
U1
V1
W1
W2
U2
V2
400V 3 phase 50Hz supply
STAR
L1 - U1L2 - V1L3 - W1Link W2, U2, V2
DELTA
L1 - U1 - W2L2 - V1 - U2 L3 - W1 - V2
Note: individual wiring instructions are included with all units
Note:For D.O.L. (Direct On Line) operation or Inverter type Speed Controlwire in DELTA
3 Phase inputMatched NuAire Inverter Speed Control
L1 L2 L3
L1 L/L2 N/L3 PE/ W V U
400V 3 phase 50Hz supply
3 Phase onlyINVERTER SPEED CONTRO L
Connectionsto motor
3 Phase input
Motor3 phase
Notes:Motors should be fitted with PTC Termistors. Refer toInverter installation sheet fot instructions on connection and programming.Total length of motor leads should not exceed 50 metres.If a screened motor cable is used, maximum length should be 25 metres. Consult out Technical Department if you wish to use longer leads. Inverters are configured to suit specific fans and control applications as described on the Customer Order free of charge.
Matched NuAire Inverter Speed Control
smo
ke
con
tro
l fa
ns I
axia
l fa
ns
tech
nica
l inf
orm
atio
n
smoke control fans I axial fans I 7.28
Axial Fans
Consultants Specification
System specification - Smoke extractThe ventilation fan Unit shall be configured and arranged as detailedon the drawings and in accordance with the schedule of equipmentand shall be of the High Temperature AXUS axial flow fan asmanufactured by Nuaire. The units shall be manufactured heavygauge Aluzinc corrosion resistant steel to BS EN10142 1991. Thecase shall be fitted with an external terminal box to IP55
The fan impeller and motor shall be direct drive with EFF2 highefficiency motors to BS5000 as standard and shall be foot mountedTENV type with IP55 enclosures and class H insulation inaccordance with BS4999 part 20 (EFF1 motors are optional). Theyshall have sealed for life ball bearings. Motors shall be pre-wired toan external electrical terminal box through weatherproof flexibleconduit to IP55.
The units shall be suitable for operation in ambient temperatures upto 60°C and a one off operation of 300°C for 2 hours to classF300/120 minutes or 400°C for 2 hours to class F400/120 minutes.
The unit shall be certified to EN12101-3. The unit has beenindependently tested for high temperature operation by BSRIA andcertified by BSI. The unit is suitable for operating in smoke reservoirand non smoke reservoir applications.
A two speed version of the unit to be provided where specified andcontrolled in accordance with the specification and manufacturersrecommendations.
The unit shall be supplied with all necessary ancillaries asrecommended by the manufacturer and in accordance with theequipment schedule.
The contractor shall allow for all necessary ductwork transformationsto and from the fan unit and any associated components inaccordance with the manufacturers recommendations, DW 144 andgeneral good practice.
The impeller blades shall be of special aero-foil section givingexcellent performance and low noise characteristic manufacturedfrom cast aluminium alloy. All units shall be suitable for internal andexternal operation and can be installed any angle.
The units will be provided complete with matching flanges, flexibleconnections, anti vibration mounts and all other necessarycomponents to complete the installation and shall be in accordancewith the manufacturer’s specification.
The unit and ancillaries shall be supplied with a 3 yearsmanufacturer’s warranty
The unit shall be of the High Temperature AXUS type asmanufactured by Nuaire Ltd.
Download specification from www.nuairegroup.com/specifications
smoke control fans squif I features
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com
SplitterAttenuator
AV Mounts FlexibleConnectors
Feet(As Standard)
Fan Guard
• Quiet operation One of the quietest solutions for motor unit ‘out of airstream’ applications.
• High temperature operation400 degrees for 2 hours on standard
motors, reducing cost and lead times.
• Easy maintenance ‘Out of air stream’ allows for quick and easy access ensures lower maintenance costs.
• Ideal for high resistances High pressure development suitable for ducted systems.
• Flexible solution Can be mounted internally, externally, vertically or horizontally.
• Fan to suit all applications2-speed motors available for day to day use and smoke extract.
• Safety tested Fans are tested to comply with EN12101-3 2002.
• High temperature application Capable of running continuously at 900C,ideal for kitchen canopy applications with a one off 4000C for 2 hours.
• WarrantyHigh temperature Squif has a 3 year warranty.
Note: Suitable for Non-Smoke Reservoirapplications.
squifhigh temperature
smo
ke
con
tro
l fa
ns I
squ
ifte
chni
cal i
nfor
mat
ion
smoke control fans I squif I 7.30
Air Volume Flow Rate (m3/s)
Fan
Sta
tic
Pre
ssu
re (
Pa)
0 10
1600
1200
800
400
2 3 4 5 6 7
12
3
4
5
6
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
Air Volume Flow Rate (m3/s)
Fan
Sta
tic
Pre
ssu
re (
Pa)
0 1 2 3 4 5 60
800
600
400
2007
8
9
10
VType D
Air Density 1.2 kg/m3
ISO 5801 1997AMCA 300
Performance Casing
Code Descriptions
SQF 4 1 - 3| | | |1 2 3 4
1. Squif range2. Pole (4 or 6)3. Curve No.4. Phase (1 or 3)
Download specification from www.nuairegroup.com/specifications
WeightUNIT SIZE A B C D E F G H M (kg)SQF 41-3 634 500 500 532 532 26.5 273 227 193 52SQF 41-1 634 500 500 532 532 26.5 273 227 193 52SQF 42-3 692 700 600 730 630 32 382 318 215 60SQF 42-1 692 700 600 730 630 32 382 318 215 60SQF 43-3 750 750 650 780 680 32 412 338 231 70SQF 43-1 750 750 650 780 680 32 412 338 231 70SQF 44 820 800 700 830 730 32 440 360 290 100SQF 61 820 800 700 830 730 32 440 360 290 100SQF 61 820 800 700 830 730 32 440 360 290 100SQF 45 901 900 800 930 830 32 490 410 290 150SQF 62 901 900 800 930 830 32 490 410 290 150SQF 62 901 900 800 930 830 32 490 410 290 150SQF 46 994 1000 900 1030 930 32 546 454 387 255SQF 63 994 1000 900 1030 930 32 546 454 387 255SQF 64 1114 1100 1000 1130 1030 32 600 500 387 315
Electrical and Sound - Extract units
Motor Sound Power Levels (dB re 10 -12 W)Power flc sc sc Data Octave band mid frequency (Hz) dBA
Curve Code Phase RPM (kW) (amps) (amps) ★/▲ Type 125 250 500 1k 2k 4k 8k @ 3m
1 SQF 41-3 3 1450 0.37 1.1 5.2 - I 90 79 70 70 70 69 62 50SQF 41-1 1 1410 0.37 2.8 11.2 O 91 74 68 74 75 70 64
2 SQF 42-3 3 1450 0.75 2 9.0 - I 92 82 77 74 76 75 67 53SQF 42-1 1 1370 0.75 5.4 21 O 93 78 74 78 80 77 69
3 SQF 43-3 3 1450 1.1 2.5 12 - I 95 83 79 77 78 78 71 56SQF 43-1 1 1420 1.1 7 35 O 96 79 77 82 83 79 73
4 SQF 44 3 1450 2.2 4.8 12 - I 93 89 82 77 80 80 71 58O 87 86 87 81 82 82 68
5 SQF 45 3 1450 4 8.3 45 15 I 99 87 85 85 84 83 81 62O 100 83 82 89 89 84 83
6 SQF 46 3 1450 7.5 15.2 108 36 I 103 92 86 86 85 86 83 63O 92 90 91 89 87 87 81
7 SQF 61 3 960 0.75 2.1 8.82 - I 89 84 75 70 73 73 64 47O 83 81 80 74 75 75 61
8 SQF 62 3 960 1.1 3 13.2 - 96 83 78 76 75 74 72 56O 97 78 76 80 79 75 74
9 SQF 63 3 960 2.2 5.9 28.9 - I 100 87 79 76 76 77 73 59O 101 82 77 80 80 78 75
10 SQF 64 3 960 4 9.4 63 20.4 I 103 91 82 79 77 77 74 62O 104 86 80 83 82 78 76
The electrical and sound information in the table is nominal. Breakout dBA@3m is spherical, free field. Start currents (sc) are DOL. * Motor electrical supply, 1=1 phase (230V, 50Hz) 3=3phase (400V, 50Hz) I = induct inlet O = induct outlet
Performance
smoke control fans squif I technical information
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com
Quick Selection GuideFan unit Standard Long Flexible Fan AV
silencers silencers Connectors Guards MountsSQF41-3 SQFS1S SQFS1L SQFF1 SQFGD1 NAV2SQF41-1 SQFS1S SQFS1L SQFF1 SQFGD1 NAV2SQF42-3 SQFS2S SQFS2L SQFF2 SQFGD2 NAV2SQF42-1 SQFS2S SQFS2L SQFF2 SQFGD2 NAV2SQF43-3 SQFS3S SQFS3L SQFF3 SQFGD3 NAV2SQF43-1 SQFS3S SQFS3L SQFF3 SQFGD3 NAV2SQF44 SQFS4S SQFS4L SQFF4 SQFGD4 NAV5SQF45 SQFS4S SQFS4L SQFF5 SQFGD5 NAV5SQF46 SQFS5S SQFS5L SQFF6 SQFGD6 NAV3SQF61 SQFS5S SQFS5L SQFF4 SQFGD4 NAV3SQF62 SQFS6S SQFS6L SQFF5 SQFGD5 NAV4SQF63 SQFS7S SQFS7L SQFF6 SQFGD6 NAV4SQF64 SQFS8S SQFS8L SQFF7 SQFGD7 NAV6
Dimensions and Weights
FLOW
FLOW
View A
View B
A
Binside
Dctrs
Ectrs
H
G
Cinside
FLOW
FLOW
B inside
D ctrs
C in
side
16 flange holes11mm dia (2 planes equi-spaced)
E ctrs
A
F
HG
M
View A
View B
smo
ke
con
tro
l fa
ns I
squ
ifte
chni
cal i
nfor
mat
ion
smoke control fans I squif I 7.32
Silencers
C
B
Ectrs
F ctrs
A
16 flange holes11mm dia (2 planes equi-spaced)
Squif Long SilencersMatchingAttenuatorAirflow Dynamic Attenuation Dimensions & WeightsUnit Code m3/s 125 250 500 1k 2k 4k 8k A B C E F G Weight Kg ZSQF 41-3 SQFS1L 0-1.1 -8 -12 -32 -42 -33 -32 -18 1200 560 560 532 532 11 38 36.8SQF 41-1 SQFS1L 0-1.1 -8 -12 -32 -42 -33 -32 -18 1200 560 560 532 532 11 38 36.8SQF 42-3 SQFS2L 0-1.6 -8 -12 -32 -42 -33 -32 -18 1200 760 660 630 730 11 43 30.5SQF 42-1 SQFS2L 0-1.6 -8 -12 -32 -42 -33 -32 -18 1200 760 660 630 730 11 43 30.5SQF 43-3 SQFS3L 0-2.2 -8 -12 -32 -42 -33 -32 -18 1200 810 710 680 780 11 46 30.5SQF 43-1 SQFS3L 0-2.2 -8 -12 -32 -42 -33 -32 -18 1200 810 710 680 780 11 46 30.5SQF 44 SQFS4L 0-3.1 -8 -12 -32 -42 -33 -32 -18 1200 860 760 730 830 11 60 10.9SQF 61 SQFS4L 0-1.9 -8 -12 -32 -42 -33 -32 -18 1200 860 760 730 830 11 60 10.9SQF 45 SQFS5L 0-4.3 -8 -12 -32 -42 -33 -32 -18 1200 980 880 830 930 12.5 91 5.47SQF 62 SQFS5L 0-2.7 -8 -12 -32 -42 -33 -32 -18 1200 980 880 830 930 12.5 91 5.47SQF 46 SQFS6L 0-6.5 -8 -12 -32 -42 -33 -32 -18 1200 1080 980 930 1030 12.5 98 5.47SQF 63 SQFS7L 0-4.2 -8 -12 -32 -42 -33 -32 -18 1200 1080 980 930 1030 12.5 116 1.54SQF 64 SQFS8L 0-6 -8 -12 -32 -42 -33 -32 -18 1200 1180 1080 1030 1130 12.5 122 1.54Squif Short SilencersSQF 41-3 SQFS1S 0-1.1 -4 -8 -18 -24 -19 -16 -11 900 560 560 532 532 11 15 36.8SQF 41-1 SQFS1S 0-1.1 -4 -8 -18 -24 -19 -16 -11 900 560 560 532 532 11 15 36.8SQF 42-3 SQFS2S 0-1.6 -4 -8 -18 -24 -19 -16 -11 900 760 660 630 730 11 29 30.5SQF 42-1 SQFS2S 0-1.6 -4 -8 -18 -24 -19 -16 -11 900 760 660 630 730 11 29 30.5SQF 43-3 SQFS3S 0-2.2 -4 -8 -18 -24 -19 -16 -11 900 810 710 680 780 11 32 30.5SQF 43-1 SQFS3S 0-2.2 -4 -8 -18 -24 -19 -16 -11 900 810 710 680 780 11 32 30.5SQF 44 SQFS4S 0-3.1 -4 -8 -18 -24 -19 -16 -11 900 860 760 730 830 11 42 10.9SQF 61 SQFS4S 0-1.9 -4 -8 -18 -24 -19 -16 -11 900 860 760 730 830 11 42 10.9SQF 45 SQFS5S 0-4.3 -4 -8 -18 -24 -19 -16 -11 900 980 880 830 930 12.5 61 5.47SQF 62 SQFS5S 0-2.7 -4 -8 -18 -24 -19 -16 -11 900 980 880 830 930 12.5 61 5.47SQF 46 SQFS6S 0-6.5 -4 -8 -18 -24 -19 -16 -11 900 1080 980 930 1030 12.5 68 5.47SQF 63 SQFS7S 0-4.2 -4 -8 -18 -24 -19 -16 -11 900 1080 980 930 1030 12.5 81 1.54SQF 64 SQFS8S 0-6 -4 -8 -18 -24 -19 -16 -11 900 1180 1080 1030 1130 12.5 86 1.54Note: Air Pressure Drop of Attenuator (Pa) = Z x Q2 where Z = Factor listed in table above Q = Air Volume Flow Rate (m3/s)
Manufactured from galvanised steelwire or polyester coated mild steel.Resistance to airflow is negligible.
Guard for Square Fans
Code Squif Fan A B C
SQFGD 1 SQF41-3 532 532 11SQF41-1
SQFGD 2 SQF42-3 730 630 13SQF42-1
SQFGD 3 SQF43-3 780 680 13SQF43-3
SQFGD 4 SQF44 830 730 13SQF61
SQFGD 5 SQF45 930 830 13SQF62
SQFGD 6 SQF46 1030 930 13SQF63
SQFGD 7 SQF64 1130 1030 13
A sq
4 holesB dia
Flexible duct material is flame proof.Heat resistance is 400°C with excellentresistance to chemicals, ozone, oil andgrease. The connector is air-tight,waterproof and tested to BS476 Part 7.
Double Flanged Flexible Connectors
Code Squif Fan A B C F E
SQFF 1 SQF41-3 150 560 560 532 532
SQF41-1
SQFF 2 SQF42-3 150 760 660 730 630
SQF42-1
SQFF 3 SQF43-3 150 810 710 780 680
SQF43-1
SQFF 4 SQF44 150 860 760 830 730
SQF61
SQFF 5 SQF45 150 980 880 930 830
SQF62
SQFF 6 SQF46 150 1080 980 1030 930
SQF63
SQFF 7 SQF64 150 1180 1080 1130 1030
Fctrs
C
A B
Ectrs
16 flange holes11mm dia (2 planes equi-spaced)
Download specification from www.nuairegroup.com/specifications
smoke control fans technical information
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com
WiringSingle phase single speed.
Fan Unit
L N230V 1 phase 50 Hz supply
X L N
3 phase units up to 3KW
U1 V1 W1
L1 L2 L3 E
W2 U2 V2
3 phase units 4KW and above
W2
L1
U2
L2
V2
L3 E
U1 V1 W1
Two speed motors DOL starting on both speeds
1U 1V 1W
2U 2V 2W E
400V 3 phase 50Hz supply
Motor Terminal Box
Note: HIGH SPEED -Supply 2U 2V 2W
Link 1U 1V 1WLOW SPEED
Supply 1U 1V 1W
Three phase motors are connected directlyto the Motor Terminal Box.
observe the motor plate and connection details.3 phase two speed tap/pam wound motors require a threecontactor control.3 phase Dual wound motors require a two contactor control.
3 phase units with matched frequency inverter
L1 L2 L3
L1 L/L2 N/L3 PE/ W V U
400V 3 phase 50Hz supply
3 Phase onlyINVERTER SPEED CONTROL
Connect as figure 7 or 8.
Connectionsto motor
3 Phase input
Ecosmart3 phase
Notes:Total length of motor leadsshould not exceed 50 mtrs.If a screened motor cable isused,maximum lengthshould be 25 mtrs.Consult our TechnicalDepartment if you wish touse longer leads.Inverters are configured tosuit specific fans andcontrol applications asdescribed on the CustomerOrder.
smo
ke
con
tro
l fa
ns I
squ
ifte
chni
cal i
nfor
mat
ion
smoke control fans I squif I 7.34
Squif
Consultants Specification
System specificationThe SMOKE EXTRACT fan Unit shall be configured and arranged asdetailed on the drawings and in accordance with the schedule ofequipment and shall be of the SQUIF type as manufactured byNuaire. The units shall be manufactured heavy gauge Aluzinccorrosion resistant steel. The general construction is to class Aleakage.
The fan impeller and motor shall be selected to provide the mostenergy efficient solution conforming to part L regulations and shallbe direct drive with EFF2 high efficiency motors to BS5000 asstandard.
The fan impeller shall be a high efficiency backward curvedcentrifugal design, manufactured in galvanised steel and the motorshall be positioned outside the ventilation airflow path. It shallprovide excellent in duct and breakout noise levels.
The unit shall be capable of continuous operation at 90°C and a oneoff operation at up to 400°C for a period of 2 hrs certified toEN12101-3. The unit has been independently tested for hightemperature operation by BSRIA and certified by BSI. This shall beachieved using a standard non temperature rated motor. The unit issuitable for non smoke reservoir applications.
A two speed version of the unit to be provided where specified andcontrolled in accordance with the specification and manufacturersrecommendations.
The unit shall be supplied with all necessary ancillaries asrecommended by the manufacturer and in accordance with theequipment schedule.
The contractor shall allow for all necessary ductwork transformationsto and from the fan unit and any associated components inaccordance with the manufacturers recommendations, DW 144 andgeneral good practice.
The unit and ancillaries shall be supplied with a 3 yearsmanufacturer’s warranty
The unit shall be of the SQUIF type as manufactured by Nuaire Ltd.
Download specification from www.nuairegroup.com/specifications
smokecontrol car park ventilation
C
B
A
smoke control car park ventilation
axusimpulse fanscar park ventilation
Directional outletdiffuser
Inlet/Outlet silencerwith integrated bell
mouth
Unique mountingbracket
Safety inlet guard
As from April 2005 it is mandatory for allemergency smoke ventilation equipment for usein the EU to be independently tested in anaccredited test facility and certified by theappropriate notified body (BSI)** to ensure itssuitability for the purpose.All such equipment must be independently tested to BSEN12101-3:2002 Smoke and heat control systems.Specification for powered smoke and heat exhaust ventilators.
Nuaire’s Axus range of high temperature fans and ancillarieshave been tested at BSRIA* in accordance with the abovestandard, ensuring your system meets these stringentrequirements.
Nuaire, through their partners Airvent Systems, can offer acomplete smoke ventilation solution for car parks & buildingsin general from initial conceptual discussions right throughthe design, installation, commissioning and handover stages.
Nuaire’s comprehensive high temperature range includes -• Up to 1600mm diameter• 3000C for 2 hours• 4000C for 2 hours
The Impulse system • Energy efficient – By monitoring the air quality and
operating the system at optimum level the overall motor power and running costs can be reduced by up to 40%
• Space saving by up to 40% – Low depth unit eliminates the need for ducting, maximising car park space availability
• Full design & installation service – An experienced technical team offer design, supply, installation & commissioning to suit your project requirements
• Quiet systems – Unit has inlet and outlet silencersensuring low noise levels are maintained
• Cost savings – Less ductwork can typically reduce costs by up to 30%
• Safety tested – All equipment is tested to EN12101-3, 3000C for 2 hours
• Fully reversible option – Flexible directional flowresponds to any fire location
• Quick and easy installation - Unique mountingbracket allows for 2 stage, ‘quick’ installation
• Warranty – AXUS Impulse range has a 3 year warranty
*BSRIA – the Building Services Research and Information Association operate the only UKAS Accredited facility in the UK to test to EN 12101-3. (www.bsria.co.uk )**BSI – the British Standards Institution, is the UK notified body under the Construction Products directive, under which compliance with this standard requires typetesting and approval and monitoring of the factory production control systems. (www.bsi.co.uk)
The car park impulse system is used to control and remove contaminants on a day to day basis, whilst ensuring that smoke isremoved quickly and efficiently in the event of a fire. The systems utilises a number of strategically positioned impulse fans, mountedon the ceiling, that push the fumes and smoke towards a designated point of exhaust. This in effect compartmentalises the smokestream ensuring quick and effective clearance whilst keeping the rest of the car park smoke free. This removes the need forcomplicated ductwork systems and optimises space.
Technical details and performance dataFan Reference: SVT-1 (A-E) SVT- 2 (A-E)
Airflow m3/s: Half/Full Speed 0.5/1.1 0.9/1.8
Thrust Newtons: Half/Full Speed* 5/24N 12/50N
Motor Power kw: Half/Full Speed* 0.23/1.1 0.23/1.1
Protection Class: IP55 IP55
Insulation: H H
Electrical Supply 400/3/50 400/3/50
Motor FLC amps: Half/Full Speed 0.83/2.7A 0.83/2.7A
Motor SC amps: DOL Half/Full Speed 2.9/14.5 2.9/14.5
Temperature Classification: EN12101-3 3000deg. C for 2 hours 3000deg. C for 2 hours
Speed RPM: Half/Full Speed 1370/2775 1370/2775
Sound dBA @ 1m: Half/Full Speed 50/65 52/67
Material Finish: Galvanised Galvanised
Dimensions AxBxC (mm) See opposite 2610x320x600 2610X400X600
* These are based on an airflow deflector angle of 50
How the system works
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com
The system runs at low speed ensuring that Carbon Monoxide levelsand other contaminants are kept within acceptable limits. Strategicallyplaced detectors monitor the air and control the units which can directlyeffect the condition.
Smoke detectors throughout the car park identify the units which canmost effectively contain the smoke layer and increases the fan speed tomaximum, the main exhaust unit is also switched to maximum.
A fire starts in one of the vehicles and smoke starts to spreadthroughout the car park, the smoke detection system identifies thesituation and the fire alarm system will be activated.
The smoke layer is contained and directed towards the main extractunit, where the smoke can be safely exhausted to atmosphere. Thismaximises the space within the car park, keeping large areas clear ofsmoke, enabling the area to be quickly and safely evacuated.
Car Park Impulse Fan Key:Low speed/day to day
High speed/smoke mode
Main exhaust/extract unit, low speed/day to day
Main exhaust/extract unit, high speed/smoke mode
Fan CodeDescriptionsSVT - 1 (A-E)
| | |1 2 3
1 AXUS Impulse range2 Case size3 Impeller blade angle
1 3
2 4
tech
nica
l spe
cific
atio
nIca
r p
ark
im
pu
lse
ven
tial
tio
n s
yste
m
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com/specifications
Car park impulse system specification
The car park ventilation system shall control and remove pollutants,such as Carbon Monoxide, on a day to day basis, whilst ensuringthat smoke is removed quickly and efficiently in the case of fire.
The car park Impulse Ventilation System shall consist of a number ofstrategically positioned acoustically treated Impulse fans distributedthroughout the car park, the positions shall be in accordance withthe specialists design & layout drawings.
Carbon Monoxide & smoke detectors shall be strategically placed inaccordance with the specialists design and shall control theoperation of the impulse fans in individual areas appropriately. Bycontrolling the fans in this way the impulse fans will containpollutants and smoke within a defined & predetermined corridor andchannel its flow to the extract point where it can be evacuatedsafely to atmosphere by the main exhaust fan unit. The controlsystem ensures that only the fans that can directly effect theventilation requirement are in operation.
The Nuaire SVT impulse unit comprises a high temperature axial fan with specially designed inlet and outlet attenuators which, alongwith the fan unit, are encased in a Galvanised steel acousticenclosure.
The Nuaire SVT unit comprising fan/motor assembly, and inlet &outlet silencers shall be certified for high temperature operation at3000C for 2 hours, the range shall have been type tested toEN12101-3.The Axus Main exhaust unit and ancillaries shall havebeen type tested and certified for high temperature operation at3000C for 2 hours to EN12101-3.
The units shall be either 2 speed or inverter driven providing, low speed for day to day environmental extract and one offoperation for emergency extract. They shall also be suitable forreversible operation.
Fully reversible options (i.e similar duty in both airflow directions) areavailable, please contact Nuaire for details.
The unit shall have a unique mounting bracket, which shall enablethe bracket to be positioned as a “first fix” component with the unitbeing fitted as a “second fix” component, avoiding possiblemechanical damage.
The Nuaire SVT unit shall have inlet guards for safety purposes andalso to prevent debris being sucked through the fan. It also has aspecially designed airflow deflector to direct the jet stream from thefan at the required angle sufficient to overcome the naturalbuoyancy effect of the smoke.
The car park impulse units shall be the SVT type and the main Exhaust unit shall be the high temperature AXUS type all as manufactured by Nuaire.
Complete solution for car parkventilation
Airvent Systems have over twenty years experience in the smokeventilation industry and their project managers were instrumental inestablishing the first Car Park impulse system in the UK, designing,installing and commissioning the system
Airvent systems utilise the latest computer aided design,computational fluid dynamic technology and extensive testing, tomaster the physics and behaviour of fires within buildings. Byunderstanding the movement of the fire and smoke and combiningthat with the knowledge and expertise of fire engineering, ventilationand containment principles, Airvent are capable of designingbespoke smoke ventilation systems to protect any building and itsoccupants whilst providing safe, healthy, clean and welcoming carparks.
Airvent offer;
• Conceptual design• UK’s largest sales engineer network• Dedicated technical in-house support team• Regulatory compliance/co-ordination• Onsite liaison• Installation• Commissioning• Maintenance• Whole life support facility
Contact us to discuss your requirements or for a focused and highlyrelevant CPD seminar at a location to suit your teamtel:029 (20) 858 200.
Systems Designed for Life
Aug
ust
2006
Issu
e 1