USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com schneider-electric.com | 1 Installation Instructions © 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March 2018 Schneider Electric · 800 Federal Street, Andover, MA 01810 USA Z207552-0C nk Product Description SmartX sensors are a family of living space sensors for use with SmartX IP controllers that use the EcoStruxure Building Operation software user interface. These sensors use an RJ-45 sensor bus that provides communication and power from the SmartX IP controller. SmartX living space sensors are modular and are ordered in two parts: the sensor base and the cover. Four SmartX commu- nicating sensor base models are available that can be paired with any one of six covers. The SXWSCDXSELXX touchscreen cover displays current time, temperature, humidity percentage (if equipped), CO2 ppm (if equipped), as well as heating, cooling and Eco mode status. Temperature setpoint, override, temperature scale, fan speed, heating mode, and cooling mode are adjustable using the touchscreen. Setpoint, override, display timeout and display lockout parameters are configured using EcoStruxure Building Operation software. SmartX TM Living Space Sensor Touchscreen Covers SXWSCDXSELXX (Touchscreen Display) SXWSCDPSELXX (Touchscreen Display with Occupancy Sensor) The SXWSCDPSELXX includes the touchscreen display and occupancy sensor. The occupancy sensor uses a passive infra- red (PIR) motion detector to determine occupancy status. The system may be configured in EcoStruxure Building Operation software to override comfort settings to occupied status when occupancy is detected during scheduled unoccupied periods. Features Contemporary, sleek housing Full color, 61mm (2.4 In), 240 x 320 pixel, capacitive touchscreen display Displays sensor readings, time, network status Setpoint Override Display timeout Display lockout Mode adjustment Passive Infrared (PIR) motion/occupancy sensor (optional) Applicable Documentation Title Description SmartX Living Space Sensor Base Installation instructions for all base variants SmartX Living Space Sensor Blank Cover Installation instructions for blank cover without occupancy sensor SmartX Living Space Sensor Button and Occupancy Covers Installation instructions for 3-button covers with and without occupancy sensors and blank cover with occupancy sensor SmartX Living Space LCD Temperature Sensor LCD temperature sensor base and cover installation instructions SmartX Living Space Resistive Temperature Sensor Non-communicating temperature sensor installation instructions

SmartX Living Space Sensor Touchscreen Covers

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

USA: +1 888-444-1311Europe: +46 10 478 2000Asia: +65 6484 7877www.schneider-electric.com

schneider-electric.com | 1Installation Instructions

© 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March 2018 Schneider Electric · 800 Federal Street, Andover, MA 01810 USA Z207552-0C nk

Product DescriptionSmartX sensors are a family of living space sensors for use with SmartX IP controllers that use the EcoStruxure Building Operation software user interface. These sensors use an RJ-45 sensor bus that provides communication and power from the SmartX IP controller. SmartX living space sensors are modular and are ordered in two parts: the sensor base and the cover. Four SmartX commu-nicating sensor base models are available that can be paired with any one of six covers. The SXWSCDXSELXX touchscreen cover displays current time, temperature, humidity percentage (if equipped), CO2 ppm (if equipped), as well as heating, cooling and Eco mode status. Temperature setpoint, override, temperature scale, fan speed, heating mode, and cooling mode are adjustable using the touchscreen. Setpoint, override, display timeout and display lockout parameters are configured using EcoStruxure Building Operation software.

SmartXTM Living Space Sensor Touchscreen Covers SXWSCDXSELXX (Touchscreen Display) SXWSCDPSELXX (Touchscreen Display with Occupancy Sensor)

The SXWSCDPSELXX includes the touchscreen display and occupancy sensor. The occupancy sensor uses a passive infra-red (PIR) motion detector to determine occupancy status. The system may be configured in EcoStruxure Building Operation software to override comfort settings to occupied status when occupancy is detected during scheduled unoccupied periods.

Features• Contemporary, sleek housing• Full color, 61mm (2.4 In), 240 x 320 pixel, capacitive

touchscreen display• Displays sensor readings, time, network status • Setpoint• Override• Display timeout• Display lockout• Mode adjustment• Passive Infrared (PIR) motion/occupancy sensor (optional)

Applicable Documentation

Title DescriptionSmartX Living Space Sensor Base Installation instructions for all base variants

SmartX Living Space Sensor Blank Cover Installation instructions for blank cover without occupancy sensor

SmartX Living Space Sensor Button and Occupancy Covers Installation instructions for 3-button covers with and without occupancy sensors and blank cover with occupancy sensor

SmartX Living Space LCD Temperature Sensor LCD temperature sensor base and cover installation instructions

SmartX Living Space Resistive Temperature Sensor Non-communicating temperature sensor installation instructions

schneider-electric.com | 2Installation Instructions

USA: +1 888-444-1311Europe: +46 10 478 2000Asia: +65 6484 7877www.schneider-electric.com

© 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March 2018 Schneider Electric · 800 Federal Street, Andover, MA 01810 USA Z207552-0C nk

Available Products SmartX Sensor Bases

SmartX Covers for Use with Sensor Bases

Model Number Description Temp RH CO2 CoverSmartX System Bus

(Communicating)SXWSBTXXXSXX Sensor Base, Temperature X Not Included X

SXWSBTHXXSXX Sensor Base, Temperature, Humidity X X Not Included X

SXWSBTXCXSXX Sensor Base, Temperature, CO2 X X Not Included X

SXWSBTHCXSXX Sensor Base, Temp, Humidity, CO2 X X X Not Included X

Model Number Description61 mm (2.4”)

Color Touchscreen Override SetpointOccupancy Sensor

(PIR)SXWSCDXSELXX* Cover Plate, User Interface, Basic X X X

SXWSC3XSELXX Cover Plate, Pushbutton Override, Setpoint X X

SXWSCBXSELXX Cover Plate, Blank Cover

SXWSCDPSELXX* Cover Plate, User Interface, Basic, Occupancy X X X X

SXWSC3PSELXX Cover Plate, Pushbutton Overrode, Setpoint, Occupancy X X X

SXWSCBPSELXX Cover Plate, Blank Cover, Occupancy X

SpecificationsTouchscreen

Display 61 mm (2.4”), color, capacitive overlay

Pixel count 240 x 320

Backlight Yes

SetpointTemperature, Humidity or Fan Speed (setpoint type and allowable span set in EcoStruxure Building Operation software)

OverrideOverrides unoccupied mode (duration and comfort parameters configured in EcoStruxure Building Operation software)

Timeout Configurable through EcoStruxure Building Operation software

Lockout Configurable through EcoStruxure Building Operation software

LED halo Heating, cooling or Ecomode

Occupancy Version

Occupancy sensor Passive infrared

Lateral detection angle 140°Horizontal detection angle ±15°

Detection range 4-6 m (13-20 ft.) angle dependent (see detection pattern diagram, page 3)

Operating Environment

Operating temperature 0 to 50 °C (32 to 122 °F)Operating humidity range 0 to 95% RH, non-condensing

Housing material High impact ABS plasticFlammability rating UL 94 V-0

Mounting location Not suitable for wet locations. For indoor use only.

Input power Supplied by SmartX sensor base

Regulatory Information

Agency approvals

UL 916European conformance CE: EN61000-6-3 EN61000 Series - industrial immunity std. FCC Part 15 Class B, REACH, RoHS, Green Premium, RCM (Australia), ICES-003 (Canada), EAC (Russia)

*Covered by these installation instructions.

USA: +1 888-444-1311Europe: +46 10 478 2000Asia: +65 6484 7877www.schneider-electric.com

schneider-electric.com | 3Installation Instructions

© 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March 2018 Schneider Electric · 800 Federal Street, Andover, MA 01810 USA Z207552-0C nk

PrecautionsDimensions mm (in.) SmartX Base Cover

Installation

1. With sensor base fully installed, align top of cover to mounting tabs on top of sensor base. Swing cover down-ward until it latches at the bottom.

2. Install locking screw to secure cover in closed position.

Typical PIR Lens Detection Pattern A typical detection pattern for the PIR cover is illustrated below.

Top view

Side View

15º

140º

15º

6 m (20 ft.)6 m

(20 ft)5 m

(16 ft)4 m

(13 ft)4 m

(13 ft)5 m

(16 ft)6 m

(20 ft)

60º

25º

15º 15º

25º

Fresnel Lens Beam and Detection Field

Lateral movementForward movement

Top View

6 m (20 ft.) 6 m (20 ft.)

140 O

19.75(.8)

85(3.3)

115(4.5)

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH• Follow safe electrical work practices. See NFPA 70E in the

USA, CSA Z462 in Canada, or applicable local codes.• Read and understand the instructions before installing the

product. Follow the instructions during installation.• Installation, wiring, testing or service must be performed only by

qualified persons in accordance with all applicable codes and regulations.

• Do not use the product for life or safety applications.• Do not install the product in hazardous or classified locations.• Do not exceed the product’s ratings or maximum limits.• Turn off ALL power supplying equipment before working on or

inside the equipment.• Use a properly rated voltage sensing device to confirm that all

power is off.• Do not depend on the product for voltage indication.• Remove all wire scraps and tools, replace all doors, covers and

protective devices before powering the equipment.Failure to follow these instructions will result in death or serious injury.

A qualified person is one who has skills and knowledge related to the construction and operation of this electrical equipment and installations, and has received safety training to recognize and avoid the hazards involved. NEC Article 100If this product is used in a manner not specified by the manufacturer, the protection provided by the product may be impaired. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

DANGER

USA: +1 888-444-1311Europe: +46 10 478 2000Asia: +65 6484 7877www.schneider-electric.com

schneider-electric.com | 4Installation Instructions

© 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March 2018 Schneider Electric · 800 Federal Street, Andover, MA 01810 USA Z207552-0C nk

PIR Installation Considerations Install the SmartX room unit with occupancy sensor as close to a door as possible (but not blocked by the door) or in an area with high occupant movement.

The unit should be installed 1.35 m (4.5 ft.) above the floor surface to ensure the maximum detection range is achieved. Ensure that occupants will cross the lens beam in a perpendic-ular path within the prescribed detection zone.

Recommended Installation Example Room 1 shows one SmartX room unit with occupancy sensor installed beside a door in the middle of the room. Occupant traffic is high in several areas of the room. Occupant movement typically flows lateral to the PIR, maximizing detection and with-in the PIR detection range of 6 m (20 ft.) at 140°, and 5 m (16 ft.) between 15° to 30° laterally.

Room 2 shows one SmartX room unit with occupancy sensor installed adjacent to the door. Occupant traffic is high and en-sures the occupant will almost always cross the PIR detection path laterally and within the detection range.

Room 1

Room 2

Room 1

Room 2

Non-recommended Installation Example Room 1 shows one SmartX room unit with occupancy sensor installed near the entrance, and a second installed beside the reception area. The unit installed at the entrance behind the door may be blocked. For the unit installed beside the reception area, occupant traffic could fall outside the detection zone.

Room 2 shows one SmartX room unit with occupancy sen-sor installed in a low traffic area near the door, and a second installed on the wall directly opposite the door. The unit installed near the door could be blocked by the opened door, restrict-ing PIR detection. The unit installed opposite the door could fall outside the specified detection zone and most occupant movement may not fall within lateral crossing patterns for PIR detection.

Features SmartX Touchscreen Covers connect to a SmartX Sensor Base and provide an attractive user interface. The Cover/Base unit communicates sensor readings back to the SmartX IP controller via the Sensor Bus. The display provides local sensor status and allows the user to adjust comfort settings within the param-eters set in EcoStruxure Building Operation software. The dis-play and touchscreen can be configured through EcoStruxure Building Operation software to be active at specific times. For example, to minimize unintended usage, the touchscreen func-tionality may be disabled in public areas during business hours and fully functional during closed hours, allowing employee-only use. Display duration may also be configured in EcoStruxure Building Operation software ranging from always on to only on for a few seconds after a touch.

USA: +1 888-444-1311Europe: +46 10 478 2000Asia: +65 6484 7877www.schneider-electric.com

schneider-electric.com | 5Installation Instructions

© 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March 2018 Schneider Electric · 800 Federal Street, Andover, MA 01810 USA Z207552-0C nk

Touchscreen Operation Default View

Ecomode Example

9:00 AM

.523°C

Heating Example

Cooling Example

Regular State Example

9:00 AM

.523°C9:00 AM

.523°C9:00 AM

.523°C9:00 AM

.523°C20°24°

Touch anywhere on the screen to begin. Two optional default/home screens are configurable in EcoStruxure Building Operation software.

1. Default screen with a combination of:• Time• Temperature and/or temperature setpoint• Ecomode icon• Up/down temperature indication

2. Same as above, adding potential for humidity and CO2.

9:00 AM

.569°F

9:00 AM

.569°F9:00 AM

.569°F74°9:00 AM

.569°F65°9:00 AM

.569°F

Note: During firmware updates, the display may appear to be off. Please allow five minutes for this process to complete before disconnecting the sensor. This may also occur when the sensor is first connected to a controller.

USA: +1 888-444-1311Europe: +46 10 478 2000Asia: +65 6484 7877www.schneider-electric.com

schneider-electric.com | 6Installation Instructions

© 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March 2018 Schneider Electric · 800 Federal Street, Andover, MA 01810 USA Z207552-0C nk

Touchscreen Operation (cont.) Adjusting the Temperature (when allowed)

Press the “+” button to increase temperature.

Touch anywhere on the screen.

Turn off LED to conserve power.

Temperature displayedSetpoint displayed

Press the Enter button to confirm.Note: Waiting 6 seconds without activity cancels the operation. The user is returned to the home screen with no changes made.

Press the “+” button again, once for each full degree F, or once for each half degree C.

Screen returns to default after 6 seconds of inactivity or if the Enter button is pressed.

Temperature is achieved. The backlight and LED are off. The arrow and setpoint are removed.

While the unit is waiting for the MPX to change mode color, the setpoint will show user feedback. The screen returns to white each time the user takes action and the unit waits for the MPX to return to the correct mode.

The home screen illuminates red. The up arrow indicates temperature direction and the setpoint is displayed. Allow a 3-second minimum delay before updating the color. The screen will illuminate blue to indicate a decrease in temperature.

9:00 AM

.061°F 9:00 AM

.060°F

9:00 AM

.061°F

9:00 AM

.077°F

9:00 AM

.077°F9:00 AM

.075°F77°

9:00 AM

.075°F77°

USA: +1 888-444-1311Europe: +46 10 478 2000Asia: +65 6484 7877www.schneider-electric.com

schneider-electric.com | 7Installation Instructions

© 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March 2018 Schneider Electric · 800 Federal Street, Andover, MA 01810 USA Z207552-0C nk

Touchscreen Operation (cont.) Scenarios for Changing Temperature When Restricted

Press the back arrow to return to the default screen.

Press the “+” button toincrease temperature. Repeat Repeat

At this point, the allowable override set in EcoStruxure Building Operation software has been met.

9:00 AM

The ‘+’ button goes into a visibly disabled state.

Press the Enter button to confirm the change and return to the default screen.

The Lock icon indicates no further changes are allowed.

Return to the home screen.

To main menu

Settings buttons are grayed out, indicating that the setpoint cannot be changed.

Touch the Menu button to return to the main menu.

Temperature displayed

9:00 AM

.078°F 9:00 AM

.078°F

9:00 AM

.075°F

9:00 AM

.076°F

9:00 AM

.077°F

9:00 AM

.078°F

9:00 AM

.078°F

°FA

Viewing the Main Menu

When user is not allowed to adjust the temperature:

When user is allowed to change the temperature within ±3°:

9:00 AM

.060°F

Press the left arrow to return to the default screen.

Touch anywhere on the screen.

Press the Menu button.

Toggle between Heating and Cooling modes.

Toggles between fan speeds

Occupied/Unoccupied: doubles as override

Toggle between °C and °F.

Access the submenu (when applicable).

Temperature displayed

°FA

°FA

°FA

9:00 AM

.061°F

USA: +1 888-444-1311Europe: +46 10 478 2000Asia: +65 6484 7877www.schneider-electric.com

schneider-electric.com | 8Installation Instructions

© 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March 2018 Schneider Electric · 800 Federal Street, Andover, MA 01810 USA Z207552-0C nk

Touchscreen Operation (cont.) Main Menu Settings

Viewing the Submenu

Press the Menu button

Press the Menu button.

Press the Menu button.

Press the Menu button.

Press the Fan icon (if allowed)

Press the Degree icon (if allowed).

Press the Occupancy icon (if configured as an override).

Press the Heating & Cooling icon (if allowed).

A

Fan States

Degree States

Occupancy States

Heating & Cooling Modes

OFF Level 1 Level 2 Level 3 Automatic

Touch anywhere on the screen

Setting the Fan Speed

Setting the Degree Type

Changing the Occupancy Mode or Override

Changing the Unit View

Touch anywhere on the screen.

Touch anywhere on the screen.

Touch anywhere on the screen

A

70°

Cooling Mode button

Unoccupied button

Heating Cooling AutomaticA A

OFF Low High Automatic

OFF ON Automatic

A

A

Unoccupied Occupied

The system goes into its preconfigured override state.

A

9:00 AM

.074°F

9:00 AM

.075°F A°F

9:00 AM

.074°F

9:00 AM

.523°C

9:00 AM

.075°F A°F

9:00 AM

.074°F

9:00 AM

.061°F

9:00 AM

.060°F A°F

A

9:00 AM

.060°F

9:00 AM

.060°F

9:00 AM

.060°F A°F

A°F

A°C

°F

A°F

°F °C

A°F

The chosen fan speed is displayed.

The chosen degree state is displayed (°C).

The chosen occupancy state is displayed.

The chosen heating/cooling state is displayed. The system returns

to the default.

Press the right arrow button.

Press the right arrow button.

Press the Information button. Parent Model:

S/N:IP:Parent Device ID:

MP-CMPXWDE1122330

192.168.256.25640

Press the Menu button.

Touch anywhere on the screen. CO2 PPM:

Humidity %:Tempurature °F:Montion Sensor:

8764574

Off

Device Model:S/N:Device ID:Comm. Status:

RU-CSWXFRD1100011

35Yes

Press the right arrow button to return to the beginning of the cycle.

Default screen

9:00 AM

.075°F

9:00 AM

.074°F A°F

USA: +1 888-444-1311Europe: +46 10 478 2000Asia: +65 6484 7877www.schneider-electric.com

schneider-electric.com | 9Installation Instructions

© 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March 2018 Schneider Electric · 800 Federal Street, Andover, MA 01810 USA Z207552-0C nk

A

Lock persists for 3 seconds and then returns to the Fan Speed icon.

°FA

Press the Occupancy button.

Press the Degree button.

Press the Fan Speed button.

A

Press the Heat/Cool button.

A

If the submenu is set to Restricted, the button to access the submenu will be hidden from view.

A

A

A°F °F °F°F

A°F

°FLock persists for 3 seconds and then returns to the Occupancy icon.

Lock persists for 3 seconds and then returns to the Degree icon.

Lock persists for 3 seconds and then returns to the Heat/Cool icon.

A°F

°F

Touchscreen Operation (cont.) On/Off States and Restrictions

If the main menu, submenu and temperature controls are all turned off in EcoStruxure Building Operation software, then the touch aspect is turned off.

User not allowed to change fan speed:

User not allowed to change Degree setting:

User not allowed to change the Occupancy mode or there is no override:

User not allowed to change the Heating/Cooling mode:

User not allowed to access a submenu:

USA: +1 888-444-1311Europe: +46 10 478 2000Asia: +65 6484 7877www.schneider-electric.com

schneider-electric.com | 10Installation Instructions

© 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March 2018 Schneider Electric · 800 Federal Street, Andover, MA 01810 USA Z207552-0C nk

China RoHS Compliance Information Environment-Friendly Use Period (EFUP) Table

本表格依据SJ/T11364的规定编制。

O: 表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572规定的限量要求以下。

X: 表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T 26572规定的限量要求。

(企业可在此处,根据实际情况对上表中打 的技术原因进行进一步说明。)

This table is made according to SJ/T 11364.O: indicates that the concentration of hazardous substance in all of the homogeneous materials for this part is below the limit as stipulated in GB/T 26572.X: indicates that concentration of hazardous substance in at least one of the homogeneous materials used for this part

X O O O O O

is above the limit as stipulated in GB/T 26572

Z000057-0B

部件名称

Part Name有害物质 - Hazardous Substances

铅 (Pb) 汞 (Hg) 镉 (Cd) 六价铬 (Cr (VI)) 多溴联苯 (PBB) 多溴二苯醚 (PBDE)电子件

Electronic