    Smart relays

    Zelio Logic

    06CatalogueNovember

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    2/72

    This international site allows you to access all theTelemecanique products in just 2 clicks viacomprehensive range data-sheets, with direct

    links to:1 Complete library: technical documents, catalogs,certificates, FAQs, brochures...

    1 Selection guides from the e-catalog.1

    Product discovery sites and their Flashanimations.

    You will also find illustrated overviews, news to

    which you can subscribe, a discussion forum, thelist of country contacts...To live automation solutions every day!

    123456525781 Interchangeable

    modular functions,

    to better meet therequirements for

    extensions

    1

    Software andaccessories common to

    multiple product families

    9731

    High functionality in a

    minimum of space1 Freedom in

    implementation

    35781

    Auto-adapts to itsenvironment, "plug &

    play"

    1 Application functions,control, communication

    and diagnostics

    embedded in theproducts

    1 User-friendly

    operation either directlyon the product orremotely

    331 Compliance with fieldbus, connection, and

    software standards1 Enablingdecentralised or remote

    surveillance via the webwith Transparent Readyproducts

    5255781 Cost effective

    optimum offers that

    make selection easy formost typical applications

    1 Products that areeasy to understand forusers, electricians and

    automation specialists

    1 User-friendly intuitiveprogramming

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    3/721

    Contents 0 Zelio Logic smart relays1

    Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 2 to 5

    Compact and modular smart relays1 Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 6 to 9

    1

    Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 10 to 12

    1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 13

    1 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 14 to 19

    1 Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 20 and 21

    1 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 22 to 27

    1

    Dimensions, mounting, schemes. . . . . . . . . . . . . . . . . . . . . . . . . . pages 28 to 31

    Communication1 Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 32

    Programming protocol1 Description, characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 33

    Modbus slave communication protocol1 Presentation, description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 34

    1 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 35

    1 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 36

    Ethernet server communication protocol1 Presentation, description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 37

    1 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 38

    1 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 39

    Communication1 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 40

    1 Dimensions, mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 41

    Analogue I/O extension modules1 Presentation, description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 42

    1 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 43

    1

    References, dimensions, schemes . . . . . . . . . . . . . . . . . . . . . . . pages 44 and 45

    Modem communication interface1 Presentation, description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 46 and 47

    1 Functions, setting-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 48 and 49

    1 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 50 and 51

    1

    References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 521 Dimensions, connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 53 to 55

    Analogue interfacesSelection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 56 and 57

    1 Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 58 and 59

    1

    Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 60 and 61

    1 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 62

    1 Dimensions, mounting, schemes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 63

    Powers supplies and transformers1 Presentation, description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 64

    1 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 65 to 68

    1 References, dimensions, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 69

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    4/722

    Selection guide 1 Zelio Logic smart relays 1Compact smart relays

    Product type Compact smart relays

    Supply voltage1111

    24 V1111

    100240 V

    Number of I/O 12 20 10 12 20

    Number of discrete inputs(of which analogue inputs)

    8 (0) 12 (0) 6 (0) 8 (0) 12 (0)

    Number of relay/transistor outputs 4/0 8/0 4/0 4/0 8/0

    With display, with clockProgramming language

    SR2 B2 2

    2 22 2

    2 2

    1BFBD or LADDER

    SR2 B2 2

    2 22 2

    2 2

    1FUFBD or LADDER

    With display, without clockProgramming language

    SR2 A2 22 22 22 2

    1FULADDER only

    Without display, with clockProgramming language

    SR2 E2 2

    2 22 2

    2 2

    1BFBD or LADDER

    SR2 E2 2

    2 22 2

    2 2

    1FUFBD or LADDER

    Without display, without clockProgramming language

    SR2 D2 22 22 22 2

    1FULADDER only

    Programming software (see page 26) Zelio Soft 2 SR2 SFT01 Zelio Soft 2 SR2 SFT01

    Connectionaccessories(see page 26)

    Serial link connecting cable SR2 CBL01 SR2 CBL01

    USB connecting cable SR2 USB01 SR2 USB01

    Bluetooth interface SR2 BTC01 SR2 BTC01

    Memory cartridge (see page 26) SR2 MEM02(1incompatible with SR2 COM01)

    SR2 MEM02(1incompatible with SR2 COM01)

    Discovery packs (see page 22) SR2 PACK2222

    FU

    Modem communication interface (see page 52) SR2 COM01 SR2 COM01 (for SR2B and SR2E)

    Alarm management software (see page 52) Zelio Logic Alarm SR2 SFT02 Zelio Logic Alarm SR2 SFT02

    Converters (thermocouple types J and K, Pt100 probesand voltage/current) (see page 62)

    Power supplies for d.c. control circuit(see page 69)

    References SR2 1 1 11 1 11 1 1

    1 1 1 1B SR2 1 1 11 1 11 1 1

    1 1 1 1FU

    Pages 22 and 23 22 and 23

    (1) FBD: Function Block Diagram.

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    5/723

    11

    3333

    12 V3333

    24 V

    12 20 10 12 20

    8 (4) 12 (6) 6 (0) 8 (4) 12 (2), 12 (6)

    4/0 8/0 4/0 4/0, 0/4 8/0, 0/8

    SR2 B2 2

    2 22 2

    2 2

    1JDFBD or LADDER

    SR2 B2 2 2

    2 2 22 2 2

    2 2 2

    BDFBD or LADDER

    SR2 A2 2 22 2 22 2 22 2 2

    BDLADDER only

    SR2 E2 2 2

    2 2 22 2 2

    2 2 2

    BDFBD or LADDER

    SR2 D2 2 22 2 22 2 22 2 2

    BDLADDER only

    Zelio Soft 2 SR2 SFT01 Zelio Soft 2 SR2 SFT01

    SR2 CBL01 SR2 CBL01

    SR2 USB01 SR2 USB01

    SR2 BTC01 SR2 BTC01

    SR2 MEM02(1incompatible with SR2 COM01)

    SR2 MEM02(1incompatible with SR2 COM01)

    SR2 PACK2222

    BD

    SR2 COM01 SR2 COM01 (for SR2 B and SR2 E)

    Zelio Logic Alarm SR2 SFT02 Zelio Logic Alarm SR2 SFT02

    RM2

    22

    2 2 2 2

    2 2 22 2 2

    2 2 2

    BD RM2

    22

    2 2 2 2

    2 2 22 2 2

    2 2 2

    BD

    ABL 7RM1202 ABL 7RM2401 1

    SR2 B 1 11 11 1

    1 1 1JD SR2 1 1 1 1 1 1 1 1 1 1 1 1

    1 1 1 1 BD

    22 22 and 23

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    6/724

    Selection guide 1 Zelio Logic smart relays 1Modular smart relays and I/O extension andcommunication modules

    Product types Modular smart relays

    Supply voltage1111

    24 V1111

    100...240 V

    Number of I/O 10 26 10 26

    Number of discrete inputs(of which analogue inputs)

    6 (0) 16 (0) 6 (0) 16 (0)

    Number of relay/transistor outputs 4/0 10/0 4/0 10/0

    With display, with clock Yes Yes

    Programming language FBD or LADDER FBD or LADDER

    Programming software (see page 26) Zelio Soft 2 SR2 SFT01 Zelio Soft 2 SR2 SFT01

    Connectionaccessories(see page 26)

    Serial link connecting cable SR2 CBL01 SR2 CBL01

    USB connecting cable SR2 USB01 SR2 USB01

    Bluetooth interface SR2 BTC01 SR2 BTC01

    Memory cartridge (see page 26) SR2 MEM02(1 incompatible with SR2 COM01)

    SR2 MEM02(1 incompatible with SR2 COM01)

    Discovery packs (see page 24) SR3 PACK1 BD

    Modem communication interface (see page 52) SR2 COM01 SR2 COM01

    Alarm management software (see page 52) Zelio Logic Alarm SR2 SFT02 Zelio Logic Alarm SR2 SFT02

    Converters (thermocouple types J and K, Pt100 probesand voltage/current) (see page 62)

    Power supplies for d.c. control circuit(see page 69)

    References (see page 24) SR3 B1 1

    1 11 1

    1 1

    1B SR3 B 2 22 22 22 2 1FU

    Associated I/O extension andcommunication module types

    Discrete I/O extension modules Discrete I/O extension modules

    Number of I/O 6 10 14 6 10 14

    Type and number of discrete inputs(or analogue inputs)

    4 (0) 6 (0) 8 (0) 4 (0) 6 (0) 8 (0)

    Type and number of relay outputs(or analogue outputs)

    2 (0) 4 (0) 6 (0) 2 (0) 4 (0) 6 (0)

    References SR3 XT1 1 11 1 11 1 11 1 1

    B SR3 XT1 1 11 1 11 1 11 1 1

    FU

    Pages 25 25

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    7/725

    11

    3333

    12 V3333

    24 V

    26 10 26

    16 (6) 6 (4) 16 (6)

    10/0 4/0, 0/4 10/0, 0/10

    Yes Yes

    FBD or LADDER FBD or LADDER

    Zelio Soft 2 SR2 SFT01 Zelio Soft 2 SR2 SFT01

    SR2 CBL01 SR2 CBL01

    SR2 USB01 SR2 USB01

    SR2 BTC01 SR2 BTC01

    SR2 MEM02(12incompatible with SR2 COM01)

    SR2 MEM02(12incompatible with SR2 COM01)

    SR3 PACK1

    BD

    SR2 COM01 SR2 COM01

    Zelio Logic Alarm SR2 SFT02 Zelio Logic Alarm SR2 SFT02

    RM 2 4 2 2 2 2 4 2 2 2 2 4 2 2 2

    2 4 2 2 2 BD RM2 4 2 2 2 2 4 2 2 2 2 4 2 2 2

    2 4 2 2 2 BD

    ABL 7RM1202 ABL 7RM2402 2

    2 22 2

    2 2

    SR3 B261JD SR3 B1 1 1

    1 1 11 1 1

    1 1 1

    BD

    Discrete I/O extension modules Network communication modules I/O extension modules

    Modbus slave Ethernet server Analogue Discrete

    6 10 14 2 Number of words:3 4 (inputs)3 4 (outputs)3 4 (clock)3

    1 (status)

    2 Number of words:3 4 (inputs)3 4 (outputs)3 4 (clock)3

    1 (status)

    4 6 10 14

    4 (0) 6 (0) 8 (0) 0 (2) 4 (0) 6 (0) 8 (0)

    2 (0) 4 (0) 6 (0) 0 (2) 2 (0) 4 (0) 6 (0)

    SR3 XT1 1 11 1 11 1 11 1 1

    JD SR3 MBU01BD SR3 NET01BD SR3 XT43BD SR3 XT1 1 11 1 11 1 11 1 1

    BD

    25 40 44 25

    andor or

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    8/726

    Presentation 1 Zelio Logic smart relays 1Compact and modular smart relays

    PresentationZelio Logic smart relays are designed for use in small automated systems. They areused in both the industrial and commercial sectors.

    2

    22

    2

    For industry:

    2

    automation of small finishing, production, assembly or packaging machines.2 decentralised automation of ancillary equipment of large and medium-sizedmachines (textile, plastics, materials processing sectors etc.),2 automation systems for agricultural machinery (irrigation, pumping, greenhousesetc.).

    2

    22

    2 For the commercial/building sectors:

    2 automation of barriers, roller shutters, access control,2 automation of lighting systems,2

    automation of compressors and air conditioning systems.

    Their compact size and ease of setting-up make them a competitive alternative tosolutions based on cabled logic or specific cards.

    2

    22

    2 ProgrammingSimple programming, ensured by the universal nature of the languages, meets all therequirements of automation specialists and also the needs of the electric ian.Programming can be performed:2 independently, using the buttons on the Zelio Logic smart relay (ladder language),2 on a PC using Zelio Soft 2 software.When using a PC, programming can be performed either in LADDER language or infunction block diagram (FBD) language, see pages 8 to 12.

    Backlighting of the LCD display (1) is obtained by activating one of the 6 programmingbuttons on the Zelio Logic smart relay or by programming with Zelio Soft 2 software(example: flashing in the event of a malfunction).

    The autonomous operating time of the clock, assured by a l ithium battery, is 10years.

    Data backup (preset values and current values) is provided by an EEPROM Flashmemory (10 years).

    Compact smart relays

    Compact smart relays meet requirements for simple automation systems.The number of inputs/outputs can be:1 12 or 20 I/O, supplied with 4 24 V or 5 12 V,1 10, 12 or 20 I/O, supplied with 4 100240 V or 5 24 V.

    Modular smart relays and extensions

    The number of inputs/outputs for modular smart relays can be:1 26 I/O, supplied with 5 12 V,1 10 or 26 I/O, supplied with 4 24 V, 4 100240 V or 5 24 V

    To improve performance and flexibility, Zelio Logic modular smart relays can be fitted

    with communication modules and I/O extension modules to obtain a maximum of40 I/O:1

    Modbus or Ethernet communication modules, supplied with5

    24 V via theZelio Logic smart relay at the same voltage.1 analogue I/O extension modules with 4 I/O, supplied with 5 24 V via theZelio Logic smart relay at the same voltage,1 discrete I/O extension modules with 6, 10 or 14 I/O, supplied via the Zelio Logicsmart relay at the same voltage.

    (1) LCD: Liquid Crystal Display.

    109446

    Zelio Logic compact smart relay

    109458

    1 2

    1 Zelio Logic modular smart relay(10 or 26 I/O)

    2 I/O extension module: discrete (6, 10 or 14I/O) or analogue (4 I/O)

    000003-2

    6

    1 2

    1 Zelio Logic modular smart relay(10 or 26 I/O)

    2 Modbus or Ethernet communicationmodules

    3 I/O extension module: discrete (6, 10 or 14I/O) or analogue (4 I/O)

    3

    Functions :pages 10 to 12

    Characteristics:pages 14 to 19

    Curves :pages 20 and 21

    References:pages 22 to 27

    Dimensions, schemes:pages 28 to 31

    Combination of modular smart relays with I/O

    extension and communication modules

    1

    11

    1

    The order shown above must be observed when usinga Modbus slave or Ethernet server communicationmodule and a discrete or analogue I/O extension module.An I/O extension module cannot be fitted before theModbus slave communication module.

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    9/727

    Presentation(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays

    (1) Public Switched Telephone Network.(2) Global System Mobile.

    CommunicationCabled and wireless programming tools

    1

    These programming tools allow the Zelio Logic smart relay to be connected to aPC running Zelio Soft 2 software:2

    Link by cables:- Cable SR2 CBL01 to 9-pin serial portor- Cable SR2 USB01 to USB port

    2 Wireless link:- Bluetooth interface SR2 BTC01

    1 Memory cartridgeThe Zelio Logic smart relay can be fitted with a backup memory cartridge whichenables the application program to be copied into another Zelio Logic smart relay.However, loading and updating of the firmware (software embedded in the product)is only possible with memory cartridge SR2 MEM02.

    The memory cartridge also enables a backup copy of the program to be saved priorto replacing the product.

    When used with a smart relay without display or buttons, the copy of the programcontained in the cartridge is automatically transferred into the Zelio Logic smart relayon power-up.

    Modbus slave and Ethernet server communication modulesModbus and Ethernet communication modules allow connection to automationsystem equipment such as display units or programmable controllers (see pages 32to 41).

    Modem communication interface

    The Modem communication interface products in the Zelio Logic range include:1 a Modem communication interface SR2 COM01 connected between a Zelio Logicsmart relay and a Modem,1 analogue (PSTN) Modems (1) SR2 MOD01 or GSM Modem (2) SR2 MOD02,1

    Zelio Logic Alarm software SR2 SFT02.

    They are designed for monitoring or remote control of machines or installations which

    operate without personnel.The Modem communication interface supplied with5

    12...24 V, enables messages,telephone numbers and calling conditions to be stored, see pages 46 to 55.

    523409

    Connecting cable

    536

    135

    Bluetooth interface

    534944

    Memory cartridge

    540454

    Modbuscommunication module

    536136

    Ethernetcommunication module

    534941

    Modemcommunication interface

    534943

    AnaloguePSTN Modem

    534942

    GSM Modem

    Functions :pages 10 to 12

    Characteristics:pages 14 to 19

    Curves :pages 20 and 21

    References:pages 22 to 27

    Dimensions, schemes:pages 28 to 31

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    10/72

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    11/729

    Presentation(continued) 1 Zelio Logic smart relays 1Compact and modular smart relaysZelio Soft 2 programming software

    Version 4.1 of "Zelio Soft 2" software improves, amongst other things, the ease of

    use of user interfaces for the following functions:

    The wiring sheet can be split into 2. Splitting allows two separate parts of the wiringsheet to be displayed on the same screen.

    This makes it possible to:1

    Display the required function blocks in the top and bottom parts.1 Move the split bar as required.1 Connect the function blocks between the 2 parts of the wiring sheet.The split wiring sheet is structured as follows:1 View of top part2 Top window vertical scroll bar

    3 Top window horizontal scroll bar4 Split bar5 View of bottom part6 Bottom window vertical scroll bar7 Bottom window horizontal scroll bar

    A function allows a block to be replaced without losing the input and outputconnections.E.g.: Replacement of an "OR" block by a "NOR" block.

    Waiting

    zzzz

    LADDER or FBD program simulation mode allows the program to be debugged bysimulating it on the software workshop host computer.A function allows the time on the simulator clock to be modified by setting to 3seconds before the start of the next event.

    The Next event button 1 allows modification of the simulator clock 2.

    User interfaces

    "Split wiring sheet" function (FBD language)

    1

    2

    3

    4

    5

    6

    7

    Structure of a split wiring sheet

    "Replacement of a function block" (FBD language)

    1 "OR" block to be replaced

    1

    2 Move all links to the new "NOR" block

    Acceleration and simulation terminals" window"12

    2

    "Time Prog Simulation" function (LADDER and FBD languages)

    3 Delete the "OR" block and positionthe "NOR" block in its place

    Functions :pages 10 to 12

    Characteristics:pages 14 to 19

    Curves :pages 20 and 21

    References:pages 22 to 27

    Dimensions, schemes:pages 28 to 31

    3

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    12/7210

    Functions 1 Zelio Logic smart relays 1Compact and modular smart relaysZelio Soft 2 programming software

    LADDER languageDefinition

    Text function block

    Up/down counter

    Analogue comparator

    Control relay

    LCD backlighting

    Output coil

    Timer

    Fast counter

    Clock

    Counter comparator

    Summer/Winter time switching

    Message

    LADDER language enables a LADDER program to be written with elementaryfunctions, elementary function blocks and derived function blocks, as well as withcontacts, coils and variables.The contacts, coils and variables can be annotated. Text can be placed freely withinthe graphic.

    2

    22

    2

    Control scheme input modes

    Zelio input mode enables users who have directly programmed the Zelio Logicsmart relay to find the same user interface, even when using the software for the firsttime.Free input mode, which is more intuitive, is very user-friendly and incorporatesmany additional features.With LADDER programming language, two alternative types of symbol can be used:2 LADDER symbols,2 electrical symbols.Free input mode also allows the creation of mnemonics and notes associated witheach line of the program.

    Instant switching from one input mode to the other is possible at any time, by simplyclicking the mouse.Up to 120 control scheme lines can be programmed, with 5 contacts and 1 coil perprogram line

    2

    22

    2 Functions:

    2 16 Text function blocks,2 16 time delay function blocks; parameters of 11 different types can be set for eachof these (1/10th second to 9999 hours),2 16 up/down counter function blocks from 0 to 32767,2 1 fast counter (1 kHz),2 16 analogue comparator function blocks,2 8 clock function blocks, each with 4 channels,2 28 control relays,2 8 counter comparators,2 LCD screen with programmable backlighting,

    2

    automatic Summer/Winter time switching,2

    variety of functions: coil, latching (Set/Reset), impulse relay, contactor,2 28 message blocks (with communication interface, see page 46).

    Functions

    Function Electrical scheme LADDER language Notes

    Contact I corresponds to the real state of the contact connected to theinput of the smart relay.i corresponds to the inverse state of the contact connected to theinput of the smart relay.

    Standard coil The coil is energised when the contacts to which it is connectedare closed.

    Latch coil (Set) The coil is energised (set) when the contacts to which it isconnected are closed.It remains set even if the contacts are no longer closed.

    Unlatch coil(Reset)

    The coil is de-energised (reset) when the contacts to which it isconnected are closed.It remains disabled even if the contacts are no longer closed.

    13

    14

    22

    21

    or or

    I

    i

    A1

    A2

    A1

    A2

    S

    A1

    A2

    R

    Presentation:pages 6 to 9

    Characteristics:pages 14 to 19

    Curves :pages 20 and 21

    References:pages 22 to 27

    Dimensions, schemes:pages 28 to 31

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    13/7211

    Functions(continued) 1 Zelio Logic smart relays 1Compact and modular smart relaysZelio Soft 2 programming software

    Function block diagram language (FBD / Grafcet SFC / Logic functions) (1)Definition

    FBD language allows graphical programming based on the use of predefined function blocks; it provides the use of:1 32 functions for counting, time delay, timing, definition of switching threshold, (for example: temperature regulation), generation of impulses,time programming, multiplexing, display,1 7 SFC functions,1 6 logic functions.

    Pre-programmed functions

    Zelio Logic smart relays provide a high processing capacity, up to 200 function blocks, including 32 pre-programmed functions:

    TIMER AC TIMER BH TIMER Li TIMER BW

    Timer. Function A/C(ON-delay and OFF-delay)

    Timer. Function BH.(adjustable pulsed signal)

    Pulse generator(ON-delay, OFF-delay)

    Timer. Function BW(pulse on rising/falling edge)

    Timer. Function A/C with

    external preset adjustment(ON-delay and OFF-delay)

    Timer. Function BH with

    external preset adjustment(adjustable pulsed signal)

    Pulse generator

    with external preset adjustment(ON-delay, OFF-delay)

    BISTABLE SET- RESET BOOLEAN CAM PRESET COUNT

    Impulse relay funct ion Bistable latching - Pr ior ityassigned either to SET orRESET function

    Allows logic equations to becreated between connectedinputs

    Cam programmer Up/down counter

    UP DOWN COUNT PRESET H-METER TIME PROG GAIN TRIGGER

    Up/down counter with externalpreset

    Hour counter(hour, minute preset)

    Time programmer, weeklyand annual.

    Allows conversion of ananalogue value by change ofscale and offset.

    Defines an activation zonewith hysteresis

    MUX COMP IN ZONE ADD/SUB MUL/DIV TEXT

    Multiplexing functions on2 analogue values

    Zone comparison(Min. 5

    55

    5 Value 55 5

    5 Max.)Add and/or subtract function Multiply and/or divide function Display of 4 pieces of data:

    digital, analogue, date, time,messages for Human-Machine interface.

    DISPLAY COM COMPARE STATUS ARCHIVE

    Display of digital and analoguedata, date, time, messages forHuman-Machine interface.

    Sending of messages withcommunication interface(see page 46)

    Comparison of 2 analoguevalues using the operands=, >,

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    14/7212

    Functions(continued) 1 Zelio Logic smart relays 1Compact and modular smart relaysZelio Soft 2 programming software

    A Macro is a grouping of function blocks. It is characterised by its number, its name,its links, its internal function blocks (255 max.) and by its I/O connections.

    Seen from the outside, a Macro behaves like a function block with inputs and/oroutputs that can be connected to links.Once created, a Macro can be manipulated like a function block.

    1 Macro characteristics:2 The maximum number of Macros is 64.2

    A password dedicated to Macros can be used to protect their content,2 A Macro can be edited / duplicated,2 A Macro's comments can be edited.1 Macro properties:A "Macro properties" dialogue box allows the properties of a Macro to be entered oredited.

    The properties of a Macro are:2 Macro name (optional)2

    The block Symbol, which may be:- an identifier,- an image.

    2 Name of inputs.2

    Name of outputs.

    Function block diagram language (FBD / Grafcet SFC / Logic functions) (continued)Macro Function

    Creation of a Macro

    Inside of a Macro

    1 Macro selection2 Edit properties3 Allows return to external view of a Macro4 Internal function block within the Macro

    5 Non connected inputs6 Non connected outputs

    1 5 2 3 4 6

    Outside of a Macro

    1 Input connections2 Output connection

    21

    Presentation:pages 6 to 9

    Characteristics:pages 14 to 19

    Curves :pages 20 and 21

    References:pages 22 to 27

    Dimensions, schemes:pages 28 to 31

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    15/7213

    Description 1 Zelio Logic smart relays 1Compact and modular smart relays

    Compact smart relaysWith display - 10, 12 and 20 I/O Without display - 10, 12 and 20 I/O

    Zelio Logic compact smart relays have thefollowing on their front panel:

    1 Two retractable fixing lugs.2 Two power supply terminals.3 Terminals for connection of the inputs.4 Backlit LCD display with 4 lines of 18

    characters.

    5 Slot for memory cartridge or connectionto a PC or Modem communicationinterface.

    6 6 buttons for programming andparameter entry.

    7 Terminals for connection of the outputs.

    Modular smart relaysWith display - 10 and 26 I/O

    Zelio Logic modular smart relays have thefollowing on their front panel:

    1 Two retractable fixing lugs.2 Two power supply terminals.3 Terminals for connection of the inputs.4 Backlit LCD display with 4 lines of 18

    characters.5 Slot for memory cartridge or connection

    to a PC or Modem communicationinterface.

    6 6 buttons for programming andparameter entry.

    7 Terminals for connection of the outputs.

    Discrete I/O extension modules6 discrete I/O 10 and 14 discrete I/O

    Discrete I/O extension modules have the

    following on their front panel:1 Two retractable fixing lugs.2 Terminals for connection of the inputs.3 Terminals for connection of the outputs.4 A connector for connection to the Zelio

    Logic smart relay (powered via the ZelioLogic smart relay).

    5 Locating pegs.

    1 2 3

    5

    17

    4

    6

    1 2 3

    5

    17

    1 2 3

    5

    17

    4

    6

    1 2

    5

    13

    5

    4

    1 2

    5

    13

    55

    4

    Presentation, functions:pages 6 to 12

    Characteristics:pages 14 to 19

    Curves :pages 20 and 21

    References:pages 22 to 27

    Dimensions, schemes:pages 28 to 31

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    16/7214

    Characteristics 1 Zelio Logic smart relays 1Compact and modular smart relays

    (1) Except for configuration SR3 B1 1 1 BD + SR3 MBU01BD + SR3 XT43BD orSR3 B1 1 1 BD + SR3 NET01BD + SR3 XT43BD class A (class B: work in progress).

    General environment characteristicsType SR2 A / SR2 B / SR2 D / SR2 E / SR3 B / SR3 XT

    Product certifications UL, CSA, GL, C-Tick

    Conformity with thelow voltage directive

    Conforming to 73/23/EEC EN (IEC) 61131-2 (open equipment)

    Conformity with theEMC directive

    Conforming to 89/336/EEC EN (IEC) 61131-2 (Zone B)EN (IEC) 61000-6-2, EN (IEC) 61000-6-3 (1) and EN (IEC) 61000-6-4

    Degree of protection Conforming to IEC/EN 60529 IP 20 (terminal block), IP 40 (front panel)

    Overvoltage category Conforming to IEC/EN 60664-1 3

    Degree of pollution Conforming to IEC/EN 61131-2 2

    Ambient air temperaturearound the deviceconforming to IEC 60028-2-1and IEC 60068-2-2

    Operation C - 20...+ 55 (+ 40 in non-ventilated enclosure)

    Storage C - 40...+ 70

    Maximum relative humidity Conforming to IEC/EN 60068-2-30 95% without condensation or dripping water

    Maximum operating altitude Operation m 2000

    Transport m 3048

    Mechanical resistance Immunity to vibration IEC/EN 60068-2-6, test Fc

    Immunity to mechanical shock IEC/EN 60068-2-27, test EaResistance toelectrostatic discharge

    Immunity toelectrostatic discharge

    IEC/EN 61000-4-2, level 3

    Resistance to HF interference(immunity)

    Immunity to electromagneticradiated fields

    IEC/EN 61000-4-3

    Immunity to fast transientsin bursts

    IEC/EN 61000-4-4, level 3

    Immunity to shock waves IEC/EN 61000-4-5

    Radio frequencyin common mode

    IEC/EN 61000-4-6, level 3

    Voltage dips and breaks (6

    ) IEC/EN 61000-4-11

    Immunity to dampedoscillation waves

    IEC/EN 61000-4-12

    Conducted andradiated emissions

    Conforming to EN 55022/11(Group 1)

    Class B (1)

    Screw terminals connectioncapacity

    Flexible cable with cable end mm2 1 conductor: 0.25...2.5, cable: AWG 24...AWG 142 conductors: 0.25...0.75, cable: AWG 24...AWG 18

    Semi-solid cable mm2 1 conductor: 0.25...2.5, cable: AWG 25...AWG 14

    Solid cable mm2 1 conductor: 0.25...2.5, cable: AWG 25...AWG 142 conductors: 0.2...1.5, cable: AWG 24...AWG 16

    Tightening torque N.m 0.5 (tightened using 3.5 mm screwdriver)

    Processing characteristicsNumber of controlscheme lines

    With LADDER programming 120

    Number of function blocks With FBD programming Up to 200

    Cycle time ms 6...90

    Response time ms Input acquisition time + 1 to 2 cycle times

    Back-up time(in the event of power failure)

    Day/time 10 years (lithium battery) at 25 C

    Program and adjustments inthe Zelio Logic smart relay andin EEPROM memory cartridge

    SR2 MEM01

    10 years

    Program memory checking On each power-up

    Clock drift 12 min/year (0 to 55 C)6 sec/month (at 25 C and calibration)

    Timer block accuracy 1% 2 of the cycle time

    Presentation:pages 6 to 9

    Functions :pages 10 to 12

    Curves :pages 20 and 21

    References:pages 22 to 27

    Dimensions, schemes:pages 28 to 31

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    17/72

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    18/7216

    Characteristics(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays

    Supply characteristics, 3 100...240 V productsType SR2

    2222

    101FUSR2

    2222

    121FUSR2

    2222

    201FU SR3 B101FU SR3 B261FU

    Nominal voltage V6 100240

    Voltage limits V6

    85264

    Nominal frequency Hz 50-60

    Nominal input current Without extensions mA 80/30 100/50 80/30 100/50

    With extensions mA 80/40 80/60

    Power dissipated Without extensions VA 7 11 7 12

    With extensions VA 12 17

    Micro-breaks Permissible duration ms 10

    rms insulation voltage V6

    1780

    Discrete input characteristics, 3 100...240 V productsType SR 2

    22

    2 2 2 2 2

    2 2 2 2 2 2 2 2

    2 2 2 2 FU

    Nominal value of inputs Voltage V6

    100... 240

    Current mA 0.6

    Frequencies Hz 47...53 and 57...63

    Input switching limit values At state 1 Voltage V 5 6 79

    Current mA > 0.17

    At state 0 Voltage V 4 6 40

    Current mA < 0.5

    Input impedance at state 1 k 350

    Responsetime

    LADDERlanguage

    State 0 to 1 (50/60 Hz) ms 50

    State 1 to 0 (50/60 Hz) ms 50

    FBDlanguage

    State 0 to 1 (50/60 Hz) ms 50 min... 255 max. (in increments of 10)

    State 1 to 0 (50/60 Hz) ms 50 min...255 max. (in increments of 10)

    Isolation Between supply and inputs None

    Between inputs None

    Protection Against inversion of terminals Yes (control instructions not executed)

    Relay output characteristics, 3 100...240 V products

    Type SR22

    22

    2

    101FUSR2

    2

    22

    2

    121FUSR3 B101FUSR3 XT101FU

    SR22

    22

    2

    201FU SR3 B 261FU SR3 XT61FU SR3 XT141FU

    Operating limit values V8

    5...30.6

    24...250

    Contact type N/O

    Thermal current A 4 outputs: 8 A 8 outputs: 8 A 8 outputs: 8 A2 outputs: 5 A

    2 outputs: 8 A 4 outputs: 8 A2 outputs: 5 A

    Electrical durability for500 000 operating cyclesConforming toIEC/EN 60947-5-1

    Utilisationcategory

    DC-12 V8

    24

    A 1.5

    DC-13 V8

    24 (L/R = 10 ms)

    A 0.6

    AC-12 V6

    230

    A 1.5

    AC-15 V6

    230

    A 0.9

    Minimum switching capacity At minimum voltage of 8 12 V mA 10

    Low power switchingreliability of contact

    8 12 V - 10 mA

    Maximum operating rate No-load Hz 10

    At Ie (operational current) Hz 0.1

    Mechanical life In millions of operating cycles 10

    Rated impulse withstandvoltage (Uimp)

    Conforming to IEC/EN 60947-1and IEC/EN 60664-1

    kV 4

    Response time Set ms 10

    Reset ms 5

    Built-in protection Against short-circuits None

    Against overvoltageand overload

    None

    Presentation:pages 6 to 9

    Functions :pages 10 to 12

    Curves :pages 20 and 21

    References:pages 22 to 27

    Dimensions, schemes:pages 28 to 31

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    19/7217

    Characteristics(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays

    Supply characteristics, 5 12 V productsType SR2 B121JD SR2 B201JD SR3 B261JD

    Nominal voltage V8 12

    Voltage limits Including ripple V8

    10.414.4

    Nominal input current Without extensions mA 120 200 250

    With extensions mA 400

    Power dissipated Without extensions W 1.5 2.5 3

    With extensions W 5

    Micro-breaks Permissible duration ms4

    1 (repeated 20 times)

    Protection Against reversed polarity Yes

    Discrete input characteristics, 5 12 V productsType SR

    2

    22

    2 2 2 2 2

    2 2 2 2 2 2 2 2

    2 2 2 2

    JD(inputs I1IA, IHIR)

    SR2

    22

    2 2 2 2 2

    2 2 2 2 2 2 2 2

    2 2 2 2

    JD(inputs IBIG used as discrete inputs)

    Nominal value of inputs Voltage V8

    128

    12

    Current mA 4 4

    Input switchinglimit values

    At state 1 Voltage V 5 8 5.6 5 8 7

    Current mA5

    25

    0.5

    At state 0 Voltage V4

    8

    2.44

    8

    3Current mA < 0.9 < 0.2

    Input impedance at state 1 k 2.7 14

    Conforming to IEC/EN 61131-2 Type 1 Type 1

    Sensor compatibility 3-wire Yes PNP Yes PNP

    2-wire No No

    Input type Resistive Resistive

    Isolation Between supply and inputs None None

    Between inputs None None

    Maximum counting frequency kHz 1 1

    Protection Against reversed polarity Yes (control instructions not executed) Yes (control instructions not executed)

    Analogue input characteristics, 5 12 V productsType SR

    2222 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

    JD (inputs IBIG used as analogue inputs)

    Input range V8 0...10 or 8 0...12

    Input impedance k 14

    Maximum non destructive voltage V 8 14.4

    Value of LSB 39 mV

    Input type Common mode

    Conversion Resolution 8 bits at maximum voltage

    Conversion time Smart relay cycle time

    Precision 5 % at 25 C and 6.2 % at 55 C

    Repeat accuracy 2 % at 55 C

    Isolation Between analogue channel and supply None

    Cabling distance m 10 max., with screened cable (sensor not isolated)

    Protection Against reversed polarity Yes

    Relay output characteristics, 5 12 V productsType SR2 B121JD

    SR3 XT101JDSR2 B201JD SR3 B 261JD SR3 X T61JD SR3 X T141JD

    Operating limit values V8 5...30, 6 24...250

    Contact type N/O

    Thermal current A 4 outputs: 8 A 8 outputs: 8 A 8 outputs: 8 A2 outputs: 5 A

    2 outputs: 8 A 4 outputs: 8 A2 outputs: 5 A

    Electrical durability for500 000 operating cyclesConforming toIEC/EN 60947-5-1

    Utilisation category DC-12 V8

    24

    A 1.5

    DC-13 V8

    24 (L/R = 10 ms)

    A 0.6

    AC-12 V6

    230

    A 1.5

    AC-15 V 6 230

    A 0.9

    Minimum switchingcapacity

    At minimum voltage of 8 12 V mA 10

    Low power switching reliability of contact8

    12 V - 10 mA

    Maximum operating rate No-load Hz 10

    At Ie (operational current) Hz 0.1

    Mechanical life In millions of operating cycles 10

    Rated impulse withstandvoltage (Uimp)

    Conforming to IEC/EN 60947-1and IEC/EN 60664-1

    kV 4

    Response time Set ms 10

    Reset ms 5

    Built-in protection Against short-circuits None

    Against overvoltage and overload None

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    20/7218

    Characteristics(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays

    Supply characteristics, 5 24 V productsType SR2

    2222

    12222

    1BDSR2B122BD

    SR22222

    201BDSR2B202BD

    SR3B101BD

    SR3B102BD

    SR3B261BD

    SR3B262BD

    Nominal voltage V8 24

    Voltage limits Including ripple V 19.230

    Nominal input current Without extensions mA 100 50 190 70

    With extensions mA 100 160 300 180

    Power dissipated Without extensions W 3 6 3 4 6 5

    With extensions W 8 10

    Micro-breaks Permissible duration ms4

    1 (repeated 20 times)

    Protection Against reversed polarity Yes

    Discrete input characteristics, 5 24 V productsType SR

    2

    22

    2 2 2 2 2

    2 2 2 2 2 2 2 2

    2 2 2 2

    BD(input I1IA, IHIR)

    SR2

    22

    2 2 2 2 2

    2 2 2 2 2 2 2 2

    2 2 2 2

    BD(input IBIG used as discrete input)

    Nominal value of inputs Voltage V 8 24 8 24

    Current mA 4 4

    Input switchinglimit values

    At state 1 Voltage V 5 8 15 5 8 15

    Current mA5

    2.25

    1.2

    At state 0 Voltage V 4 8 5 4 8 5

    Current mA < 0.75 < 0.5

    Input impedance at state 1 k 7.4 12

    Conforming to IEC/EN 61131-2 Type 1 Type 1

    Sensor compatibility 3-wire Yes PNP Yes PNP

    2-wire No No

    Input type Resistive Resistive

    Isolation Between supply and inputs None None

    Between inputs None None

    Maximum counting frequency kHz 1 1

    Protection Against reversed polarity Yes (control instructions not executed) Yes (control inst ructions not executed)

    Analogue input characteristics, 5 24 V productsType SR

    2222 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

    BD (input IBIG used as analogue inputs)

    Input range V8 0...10 or 8 0...24

    Input impedance k 12Maximum non destructive voltage V

    8 30

    Value of LSB 39 mV

    Input type Common mode

    Conversion Resolution 8 bits at maximum voltage

    Conversion time Smart relay cycle time

    Precision 5 % at 25 C and 6.2 % at 55 C

    Repeat accuracy 2 % at 55 C

    Isolation Between analogue channel andsupply

    None

    Cabling distance m 10 maximum, with screened cable (sensor not isolated)

    Protection Against reversed polarity Yes

    Presentation:pages 6 to 9

    Functions :pages 10 to 12

    Curves :pages 20 and 21

    References:pages 22 to 27

    Dimensions, schemes:pages 28 to 31

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    21/7219

    Characteristics(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays

    (1) If there is no volt-free contact between the Zelio Logic smart relay output and the load.

    Relay output characteristics, 5 24 V productsType SR2

    2222

    101BDSR2

    2222

    121BD

    SR3 B101BDSR3 XT101BD

    SR22222

    201BD SR3 B 261BD SR3 X T61BD SR3 X T141BD

    Operating limit values V8 5...30. 6 24...250

    Contact type N/O

    Thermal current A 4 outputs: 8 A 8 outputs: 8 A 8 outputs: 8 A2 outputs: 5 A

    2 outputs: 8 A 4 outputs: 8 A2 outputs: 5 A

    Electrical durability for500 000 operating cyclesConforming toIEC/EN 60947-5-1

    Utilisationcategory

    DC-12 V 8 24

    A 1.5

    DC-13 V 8 24 (L/R = 10 ms)

    A 0.6

    AC-12 V 6 230

    A 1.5

    AC-15 V 6 230

    A 0.9

    Minimum switching capacity At minimum voltage of 8 12 V mA 10

    Low power switchingreliability of contact

    8

    12 V - 10 mA

    Maximum operating rate No-load Hz 10

    At Ie (operational current) Hz 0.1

    Mechanical life In millions of operating cycles 10

    Rated impulse withstandvoltage (Uimp)

    Conforming to IEC/EN 60947-1and IEC/EN 60664-1

    kV 4

    Response time Set ms 10

    Reset ms 5

    Built-in protection Against short-circuits None

    Against overvoltageand overload

    None

    Transistor output characteristics, 5 24 V productsType SR

    2

    22

    2

    B2 2

    2 22 2

    2 2

    2BD

    Operating limit values V 8 19.2..0.30

    Load Nominal voltage V8

    24Nominal current A 0.5

    Maximum current A 0.625 at 30 V

    Residual voltage At state 1 V 4 8 2 for I = 0.5 A

    Response time Set ms4

    1

    Reset ms 4 1

    Built-in protection Against overload andshort-circuits

    Yes

    Against overvoltage (1) Yes

    Against inversions ofpower supply

    Yes

    Presentation:pages 6 to 9

    Functions :pages 10 to 12

    Curves :pages 20 and 21

    References:pages 22 to 27

    Dimensions, schemes:pages 28 to 31

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    22/7220

    Curves 1 Zelio Logic smart relays 1Compact and modular smart relays

    Electrical durability of relay outputs(in millions of operating cycles, conforming to IEC/EN 60947-5-1)

    d.c. loads

    DC-12 (1)

    DC-13 (2)

    (1) DC-12: switching resistive loads and photo-coupler isolated solid-state loads, L/R4

    1 ms.(2) DC-13: switching electromagnets, L/R

    4

    2 x (Ue x Ie) in ms, Ue: rated operational voltage,Ie: rated operational current (with a protection diode on the load, DC-12 curves must be usedwith a coefficient of 0.9 applied to the number in millions of operating cycles).

    0 1,51 20,5

    0,0

    0,5

    1,0

    1,5

    2,0

    2,5

    3,0

    24 V

    48 V

    onsoo

    peratngcyces

    Current (A)

    0,1 0,3 0,5 0,7 0,9 10,2 0,4 0,6 0,8

    0,0

    1,4

    1,2

    1,0

    0,8

    0,6

    0,4

    0,2

    L/R = 10 ms 24 V

    L/R = 10 ms 48 V

    L/R = 60 ms 48 V

    L/R = 60 ms 24 V

    onsoo

    peratngcyces

    Current (A)

    Presentation:pages 6 to 9

    Functions :pages 10 to 12

    Characteristics:pages 14 to 19

    References:pages 22 to 27

    Dimensions, schemes:pages 28 to 31

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    23/7221

    Curves(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays

    Electrical durability of relay outputs (continued)(in millions of operating cycles, conforming to IEC/EN 60947-5-1)

    a.c. loads

    AC-12 (1)

    AC-14 (2)

    AC-15 (3)

    (1) AC-12: switching resistive loads and photo-coupler isolated solid-state loads, cos5

    0.9.(2) AC-14: switching small electromagnetic loads

    4

    72 VA, make: cos = 0.3, break: cos = 0.3.(3) AC-15: switching electromagnetic loads > 72 VA, make: cos = 0.7, break: cos = 0.4.

    0 0,5 1,5 2,5 3,5 4,51,0 2,0 3,0 4,0 50,0

    0,5

    1,0

    1,5

    2,0

    2,5

    3,0

    24 V

    48 V

    110 V

    230 V

    Millionsofoperatingcycles

    Current (A)

    0 0,2 0,6 1,0 1,4 1,80,4 0,8 1,2 1,6 20,0

    0,5

    1,0

    1,5

    2,0

    2,5

    24 V48 V

    110 V

    230 V

    Millionsofoperatingcycles

    Current (A)

    0,5 0,90,7 1,31,1 1,71,5 1,90,0

    0,1

    0,2

    0,3

    0,4

    0,5

    0,6

    0,7

    0,8

    0,9

    1,0

    230 V 48 V

    110 V

    Millionsofoperatingcycles

    Current (A)

    Presentation:pages 6 to 9

    Functions :pages 10 to 12

    Characteristics:pages 14 to 19

    References:pages 22 to 27

    Dimensions, schemes:pages 28 to 31

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    24/72

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    25/7223

    References(continued) 1 Zelio Logic smart relays 1Compact smart relays

    Compact smart relays without displayNumberof

    I/O

    Discreteinputs

    Including4

    4 4

    4

    0-10 V

    analogueinputs

    Relayoutputs

    Transistoroutputs

    Clock Reference Weight

    kg

    Supply3

    33

    3

    24 V

    12 8 0 4 0 Yes SR2 E121B 0.220

    20 12 0 8 0 Yes SR2 E201B 0.350

    Supply 333

    3 100...240 V

    10 6 0 4 0 No SR2 D101FU (1) 0.220

    12 8 0 4 0 Yes SR2 E121FU 0.220

    20 12 0 8 0 No SR2 D201FU (1) 0.350

    Yes SR2 E201FU 0.350

    Supply 4444 24 V10 6 0 4 0 No SR2 D101BD (1) 0.220

    12 8 4 4 0 Yes SR2 E121BD 0.220

    20 12 2 8 0 No SR2 D201BD (1) 0.350

    6 8 0 Yes SR2 E201BD 0.350

    Zelio Soft 2 software for PCDescription Application Reference Weight

    kg

    Programming softwareZelio Soft 2 software,multi-language

    For PC, supplied onCD-Rom (2), compatible withWindows 98, NT, 2000, XP

    SR2 SFT01 0.200

    AccessoriesConnection accessories

    Description Application Length Reference Weightkg

    Connecting cable Between the PC(USB connector)and the Zelio Logicsmart relay

    3 m SR2 USB01 0.100

    Other accessories: see pages 26 and 27

    Modem communication interfaceSupply

    4444

    12...24 V

    Description Application Reference Weightkg

    Modem communicationinterface

    For SR2 E See page 52 0.200

    (1) Programming on Zelio Logic smart relay in LADDER language only.(2) CD-ROM comprising Zelio Soft 2 software, an application library, a self-training manual,

    installation instructions and a users manual.

    109442

    SR2 E121BD

    SR2 SFT01

    536307

    SR2 USB01

    523109

    536306

    Modem communication interface

    Presentation:pages 6 to 9

    Functions :pages 10 to 12

    Characteristics:pages 14 to 19

    Curves :pages 20 and 21

    Dimensions, schemes:pages 28 to 31

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    26/7224

    References 1 Zelio Logic smart relays 1Modular smart relays

    Modular smart relays with displayNumberof

    I/O

    Discreteinputs

    Including4

    44

    4

    0-10 V

    analogueinputs

    Relayoutputs

    Transistoroutputs

    Clock Reference Weight

    kg

    Supply3

    33

    3

    24 V

    10 6 0 4 0 Yes SR3 B101B 0.250

    26 16 0 10 (1) 0 Yes SR3 B261B 0.400

    Supply 333

    3 100...240 V

    10 6 0 4 0 Yes SR3 B101FU 0.250

    26 16 0 10 (1) 0 Yes SR3 B261FU 0.400

    Supply4

    44

    4

    12 V

    26 16 6 10 (1) 0 Yes SR3 B261JD (2) 0.400

    Supply 444

    4 24 V

    10 6 4 4 0 Yes SR3 B101BD 0.250

    0 4 Yes SR3 B102BD 0.220

    26 16 6 10 (1) 0 Yes SR3 B261BD 0.400

    0 10 Yes SR3 B262BD 0.300

    Zelio Soft 2 software for PCDescription Application Reference Weight

    kg

    Programming softwareZelio Soft 2 software,multi-language

    For PC, supplied onCD-ROM (3),compatible withWindows 98, NT, 2000, XP

    SR2 SFT01 0.200

    AccessoriesConnection accessoriesDescription Application Length Reference Weight

    kg

    Connecting cable Between the PC(USB connector)and the Zelio Logicsmart relay

    3 m SR2 USB01 0.100

    Other accessories: see pages 26 and 27

    Modular discovery packsNumberofI/O

    Pack contents:- Compact smart relay with display- Zelio Soft 2 programming software supplied onCD-Rom- Cable PC SR2 USB01 for connection to PC(4)

    Reference Weight

    Description of compact smart relay with display kg

    Supply3

    33

    3

    100...240 V10 SR3 B101FU SR3 PACKFU 0.700

    26 SR3 B261FU SR3 PACK2FU 0.850

    Supply 444

    4 24 V

    10 SR3 B101BD SR3 PACKBD 0.700

    26 SR3 B261BD SR3 PACK2BD 0.850

    (1) Including 8 outputs at maximum current of 8 A and 2 outputs at maximum current of 5 A.(2) Can only be used with "Zelio Soft 2" software version

    5

    V 3.1.(3) CD-ROM comprising Zelio Soft 2 software, an application library, a self-training manual,

    installation instructions and a users manual.(4) Replaces cable SR2 CBL01 which is still available separately, as an accessory (see page 26).

    Note:The Zelio Logic smart relay and its associated extensions must have an identical voltage.

    109444

    SR3 B101BD

    SR2 SFT01

    536307

    SR2 USB01

    523109

    SR2 PACK1 1 1

    536308

    Presentation:pages 6 to 9

    Functions :pages 10 to 12

    Characteristics:pages 14 to 19

    Curves :pages 20 and 21

    Dimensions, schemes:pages 28 to 31

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    27/7225

    References(continued) 1 Zelio Logic smart relays 1Modular smart relays

    Modbus and Ethernet communication module (1)4

    44

    4 24 V supply (via smart relays SR3B...BD)

    For use with Network Reference Weightkg

    Zelio Logic modular smart relaysSR3 B

    2 22 22 22 2

    1BD and SR3 B2 22 22 22 2

    2BDModbus See page 40

    0.110

    Ethernet See page 40 0.110

    SR3NET

    Ethernetcommunication module

    524132

    Modbuscommunication module

    Analogue I/O extension module (2)Supply 4

    44

    4 24 V (via Zelio Logic smart relay SR3 B...BD)

    NumberofI/O

    Inputs Including4444

    Inclu-dingPt100

    Output4444

    0-10 VReference Weight

    kg

    0 - 10 V 0 - 20 mA

    4 2 (3) 2 max 2 max 1 max 2 See page 44 0.110

    Discrete I/O extension modules

    Numberof I/O

    Discrete inputs Relay outputs Reference Weightkg

    Supply 333

    3 24 V (via Zelio Logic smart relays SR3 B 1 1 11 1 11 1 1

    1 1 1 B)

    6 4 2 SR3 XT61B 0.125

    10 6 4 SR3 XT101B 0.200

    14 8 6 (4) SR3 XT141B 0.220

    Supply 333

    3 100-240 V (via Zelio Logic smart relays SR3 B 1 1 11 1 11 1 1

    1 1 1 FU)

    6 4 2 SR3 XT61FU 0.125

    10 6 4 SR3 XT101FU 0.200

    14 8 6 (4) SR3 XT141FU 0.220

    Supply 4444 12 V (via Zelio Logic smart relay SR3 B261JD)6 4 2 SR3 XT61JD 0.125

    10 6 4 SR3 XT101JD 0.200

    14 8 6 (4) SR3 XT141JD 0.220

    Supply 444

    4 24 V (via Zelio Logic smart relays SR3 B 1 1 11 1 11 1 1

    1 1 1 BD)

    6 4 2 SR3 XT61BD 0.125

    10 6 4 SR3 XT101BD 0.200

    14 8 6 (4) SR3 XT141BD 0.220

    Modem communication interface (5)Supply 4

    44

    4 12...24 V

    Description Reference Weightkg

    Modem communication interface See page 52 0.200

    (1) See pages 32 to 41.(2) See pages 42 to 45.(3) See page 45.(4) Including 4 outputs at maximum current of 8 A and 2 outputs at maximum current of 5 A.(5) See pages 46 to 55.

    Note:The Zelio Logic smart relay and its associated extensions must have an identical voltage.

    109363

    SR3 XT61BD

    109369

    SR3 XT141BD

    Modem communication interface

    536306

    Presentation:pages 6 to 9

    Functions :pages 10 to 12

    Characteristics:pages 14 to 19

    Curves :pages 20 and 21

    Dimensions, schemes:pages 28 to 31

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    28/7226

    References 1 Zelio Logic smart relays 1Compact and modular smart relays

    ProgrammingZelio Soft 2 software for PC

    Description Application Reference Weightkg

    Programming softwareZelio Soft 2 software,multi-language

    For PC, supplied onCD-ROM (1), compatible withWindows 98, NT, 2000, XP

    SR2 SFT01 0.200

    Connection accessories

    Description Application Reference Weightkg

    Connecting cables Between the PC (SUB-D, 9-pinconnector) and the Zelio Logicsmart relay. Length: 3 m

    SR2 CBL01 0.150

    Between the PC (USB connector)and the Zelio Logic smart relay.PC compatible withWindows 2000, XPLength: 3 m

    SR2 USB01 0.100

    Bluetooth interfacefor Zelio Logic smart relays Between the PC (wireless link)and the Zelio Logic smart relay.Range 10 m (class 2)

    SR2 BTC01 (2) 0.015

    Bluetooth adapterfor non-equipped PC

    To be used in conjunction withSR2 BTC01 when the PC is notequipped with Bluetoothtechnology.Connection to the USB porton the PC.PC compatible withWindows 98SE, 2000, XPRange of 10 m (class 2)

    VW3 A8115 0.290

    Memory cartridges(3)

    Description Application Reference Weightkg

    EEPROMmemory cartridges

    For firmware (software embeddedin the smart relay) version

    4

    2.4SR2 MEM01 0.010

    For firmware (software embeddedin the smart relay) version 5 3.0

    SR2 MEM02 0.010

    DocumentationDescription/application Language Reference

    Weightkg

    Users manualfor direct programming onthe Zelio Logic smart relay

    English SR2 MAN01EN 0.100

    French SR2 MAN01FR 0.100

    German SR2 MAN01DE 0.100

    Spanish SR2 MAN01ES 0.100

    Italian SR2 MAN01IT 0.100

    Portuguese SR2 MAN01P0 0.100

    (1) CD-ROM comprising Zelio Soft 2 software, an application library, a self-training manual,installation instructions and a users manual.

    (2) Can only be used with "Zelio Soft 2" software version2

    V 4.1.(3) Program loading using memory cartridge SR2 MEM02 is incompatible with Modem

    communication interface SR2 COM01.

    SR2 SFT01

    536307

    SR2 USB01

    523109

    SR2 BTC01

    536135

    SR2 MEM02

    534944

    Presentation:pages 6 to 9

    Functions :pages 10 to 12

    Characteristics:pages 14 to 19

    Curves :pages 20 and 21

    Dimensions, schemes:pages 28 to 31

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    29/7227

    References(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays

    Regulated switch mode power supplies (1)Inputvoltage

    Nominaloutput voltage

    Reference Weightkg

    6 100...240 V (50/60 Hz) 8 5 V, 8 12 V or 8 24 V See page 69

    Converters (2)Description Reference Weight

    kg

    Converters for J and K type thermocouples,for Pt100 probes and voltage/current

    See page 62

    Mounting accessories (3)Description/application Mounting capacity Reference Weight

    kg

    Dust and damp-proofenclosurewith split blanking platearrangement, fitted with anIP 55 dust and damp-proofwindow with hinged flap, formounting through a door

    - 1 or 2 SR2 smart relays with10 or 12 I/O or- 1 SR2 smart relay with 20 I/O or- 1 SR3 smart relay with 10 I/O+ 1 I/O extension module(6, 10 or 14 I/O) or- 1 SR3 smart relay with 26 I/O+ 1 I/O extension module (6 I/O).

    14210 0.350

    Fixing bracket andsymmetrical mounting rail

    For mounting enclosure 14210through a door panel

    14211 0.210

    (1) See pages 64 to 69.(2) See pages 58 to 63.(3) Products marketed under the Merlin Gerin brand.

    Regulated switch modepower supplie

    540472

    Converters forthermocouples

    10900

    14210

    14211

    DF563990

    Presentation:pages 6 to 9

    Functions :pages 10 to 12

    Characteristics:pages 14 to 19

    Curves :pages 20 and 21

    Dimensions, schemes:pages 28 to 31

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    30/72

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    31/7229

    Schemes 1 Zelio Logic smart relays 1Compact and modular smart relays

    Connection of smart relays on 5 supplySR 1 5 1 1 1

    1 5 1 1 1 1 5 1 1 1

    1 5 1 1 1 1BD, SR 1 5 1 1 1 1 5 1 1 1 1 5 1 1 1

    1 5 1 1 1 1JD SR2 B 1 11 11 1

    1 1 2BD and SR3 B 1 11 11 1

    1 1 2BD

    SR3 B2611

    D

    (1) 1 A quick-blow fuse or circuit-breaker.(2) Fuse or circuit-breaker.(3) Inductive load.(4) Q9 and QA: 5 A (max. current in terminal C: 10 A).

    Discrete input used for 3-wire sensors

    (1) 1 A quick-blow fuse or circuit-breaker.

    +

    SRpppppJDc 12 V

    SRpppppBDc 24 V

    (1)

    +

    Q1 Q2 Q3 Q4

    z 12240 V

    50/60 Hz

    c 1224 V

    L /+

    N / z 24240 V50/60 Hz

    c 1224 V

    (2)(3)

    U

    (3)

    U

    or

    Q7 C Q8 Q9 QA

    5 A(4)

    +

    +

    c 24 V

    c 24 V

    +

    (1)

    +Q1 Q2 Q3 Q4

    (2)

    +

    z 12240 V

    50/60 Hz

    c 1224 V

    (3)

    U

    (3)

    U

    BN

    BK

    BLBN

    BK

    BL

    +

    (1)

    +

    Presentation:pages 6 to 9

    Functions :pages 10 to 12

    Characteristics:pages 14 to 19

    Curves :pages 20 and 21

    References:pages 22 to 27

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    32/7230

    Schemes(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays

    Connection of smart relays on 5 supply (continued)Analogue inputs

    (1) 1 A quick-blow fuse or circuit-breaker.(2) Ca: Analogue sensor / Ta: Analogue transmitter.(3) Recommended values: 2.2 k/ 0.5 W (10 kmax.).(4) Screened cables, maximum length 10 m.(5) Analogue inputs according to Zelio Logic to smart relay, see table below:

    Smart relays Analogue inputs

    SR22

    22

    2

    122 2

    2 22 2

    2 2

    D IBIE

    SR2 A201BD IB and IC

    SR2 D201BD IB and IC

    SR2 B202 22 22 22 2

    D IBIG

    SR2 E201BD IBIG

    SR3 B102222

    BD IBIE

    SR3 B262 2

    2 22 2

    2 2

    D IBIG

    Connection of smart relays on 5 supply, with discrete I/O extension modulesSR3 B

    1 1 1

    1 1 11 1 1

    1 1 1

    JD + SR3 XT1 1 1

    1 1 11 1 1

    1 1 1

    JD, SR3 B1 1 1

    1 1 11 1 1

    1 1 1

    BD + SR3 XT1 1 1

    1 1 11 1 1

    1 1 1

    BD

    (1) 1 A quick-blow fuse or circuit-breaker.(2) Ca: Analogue sensor / Ta: Analogue transmitter.(3) Recommended values: 2.2 k/ 0.5 W (10 kmax.).(4) Screened cables, maximum length 10 m.

    +

    +

    (1)

    (3)

    (5)

    +

    +

    (1)

    Ca / Ta (2)

    (5)

    (4)

    1 0-10 VANALOG.

    +

    (1)

    (3)

    Ca / Ta (2)

    QF QG

    +

    BN

    BK

    BL

    BN

    BK

    BL

    (4)

    Warning: QF and QG: 5 A for SR3 XT1411 11 11 11 1

    Presentation:pages 6 to 9

    Functions :pages 10 to 12

    Characteristics:pages 14 to 19

    Curves :pages 20 and 21

    References:pages 22 to 27

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    33/7231

    Schemes(continued) 1 Zelio Logic smart relays 1Compact and modular smart relays

    Connection of smart relays on 3 supplySR 1 5 1 1 1

    1 5 1 1 1 1 5 1 1 1

    1 5 1 1 1 1B, SR 1 5 1 1 1 1 5 1 1 1 1 5 1 1 1

    1 5 1 1 1 1FU

    SR3 B261B and SR3 B261FU

    (1) 1 A quick-blow fuse or circuit-breaker.(2) Fuse or circuit-breaker.(3) Inductive load.(4) Q9 and QA: 5 A (max. current in terminal C: 10 A).

    With discrete I/O extension module

    SR3 B2 2 2

    2 2 22 2 2

    2 2 2

    B + SR3 XT2 2 2

    2 2 22 2 2

    2 2 2

    B, SR3 B2 2 2

    2 2 22 2 2

    2 2 2

    FU + SR3 XT2 2 2

    2 2 22 2 2

    2 2 2

    FU

    (1) 1 A quick-blow fuse or circuit-breaker.

    L

    L N

    SRp ppppFU

    a 100240 V

    50/60 Hz

    SRp ppppB

    a 24 V

    N

    (1)

    Q1 Q2 Q3 Q4

    z 12240 V

    50/60 Hz

    c 1224 V

    L /+

    N / z 12240 V50/60 Hz

    c 1224 V

    (2)(3)

    U

    (3)

    U

    or

    Q7 C Q8 Q9 QA

    5 A(4)

    QF QG

    +

    L

    N

    (1)

    Module Extension

    Warning: QF and QG: 5 A for SR3 XT141 1 11 11 11 1

    Presentation:pages 6 to 9

    Functions :pages 10 to 12

    Characteristics:pages 14 to 19

    Curves :pages 20 and 21

    References:pages 22 to 27

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    34/7232

    Presentation 1 Zelio Logic smart relays 1Communication

    In order to communicate with an intelligent environment, Zelio Logic smart relays andtheir I/O extension and communication modules are equipped with various types ofcommunication port.

    1 Compact and modular smart relays offer:2 1 RS 232 serial port for connection of the PC, the Modem communication interfaceor a memory cartridge slot.1 Zelio Logic modular smart relay I/O extension and communication modules offer:2 1 Modbus RS 485 port on communication module SR3 MBU01BD,2 1 Ethernet 10/100 base T port supporting the Modbus TCP protocol oncommunication module SR3 NET01BD.

    These three ports allow Zelio Logic compact or modular smart relays to use 3communication protocols:1 Programming,1 Modbus,1 Ethernet.

    Presentation109449

    Smart relay

    6

    7

    Communication ports on Zelio Logic smart relays and their I/O extension and

    communication modules

    Communicationport

    Serial port Modbus port oncommunicationmoduleSR3 MBU01BD

    Ethernet port oncommunicationmoduleSR3 NET01BD

    Modemcommunicationinterface port

    Physical layer RS 232 RS 485 10/100 base T RS 232

    Connector Specific to Zelio RJ45 RJ45 Specific to Zelio

    Compactsmart relays

    All types(connection and

    isolation via cableSR2 CBL01 orSR2 USB01)

    All modules withclock

    SR2 B1 1 1 1 1

    SR2 E1 1 1 1 1 (see page52)

    Modularsmart relays

    All types(connection andisolation via cableSR2 CBL01 orSR2 USB01)

    All modules with8

    24 V supplySR3 B

    1 1 1

    BD

    All modules with8

    24 V supplySR3 B

    1 1 1

    BD

    All types(see page52)

    000003-2

    6

    1 3

    1

    11

    1

    The order shown above must be observed when usinga Modbus slave or Ethernet server communicationmodule and a discrete or analogue I/O extension module.An I/O extension module cannot be fitted before theModbus slave or Ethernet server communication module.

    2

    4

    5

    1 Modular smart relay(10 or 26 I/O).

    2 RS 232 serial port, Zelio Logic typeconnector.

    3 Modbus slave or Ethernet servercommunication module.

    4 RJ45 connector for Modbus or Ethernetnetwork connection.

    5 I/O extension module: discrete(6,10 or 14 I/O) or analogue (4 I/O).

    6 Modem communication interface.7 GSM (or analogue PSTN) Modem.

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    35/7233

    Description,characteristics 1

    Zelio Logic smart relays 1CommunicationProgramming protocol

    Description Link by cable

    1 Programming PC.2 RS 232 serial link cable (SR2 CBL01) or USB cable (SR2 USB01) (1).3 Zelio Logic compact or modular smart relay.

    Wireless link

    4 Programming PC with integrated Bluetooth technology (or Bluetooth adapterVW3 A8115 for PC not equipped with Bluetooth technology) (1).

    5 Bluetooth interface (SR2 BTC01) for Zelio Logic smart relay (1).

    6 Zelio Logic compact or modular smart relay.

    Link by Modem

    7 Programming PC.8 Modem interface connecting cable supplied with SR2 COM01 (2).9 Modem for transmitting/receiving data SR2 MOD01 or SR2 MOD02 (2).10 Telephone or radio link.11 Communication interface SR2 COM01.12 Zelio Logic compact or modular smart relay.

    (1) See page 26.(2) See page 52.

    Serial link characteristicsProduct type All Zelio Logic smart relays

    Flow rate Kbit/s 115.2

    Data bits 7

    Stop bits 1

    Parity Pair

    Physical layer RS 232

    Type of connector Specific to Zelio Logic

    1

    3

    2

    4

    5

    6

    7

    9

    10

    9 128

    11

    524107

    524106

    524108

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    36/7234

    Presentation,description 1

    Zelio Logic smart relays 1CommunicationModbus slave communication protocol

    Presentation

    The Modbus communication protocol is of the master/slave type.Two exchange methods are possible:1 Request/reply:2

    The request from the master is addressed to a specific slave.2 The master waits for the reply to be returned by the slave polled.1 Distribution:2 The master distributes a request to all the slave stations on the bus.These stations execute the instruction without sending a reply.

    Zelio Logic modular smart relays are connected to the Modbus network via theModbus slave communication module. This module is a slave that is not electricallyisolated.The Modbus slave communication module must be connected to an SR3 B

    6 6 6

    BDmodular smart relay, with a 5 24 V supply.

    Configuration

    The Modbus slave communication module can be configured:1 independently, using the buttons on the smart relay (1).1 on a PC, using Zelio Soft 2 software, see page 9.

    When using a PC, programming can be performed either in LADDER language or infunction block diagram (FBD) language, see pages 10 to 13.

    Connection example

    Modbus communication module

    5

    4

    4

    7

    6

    1

    5bis

    2

    2

    2

    3

    4

    3

    3 1 XBT N401 display unit.

    2 Modular smart relay SR3 B 1 1 1 BD.

    3 Modbus communication module SR3 MBU01BD.

    4 Modbus network (cables VW3 A8 306R6 6

    ).

    5 Junction box TWD XCA T3RJ (polarisation and line end adapter activated).

    5bis Junction box TWD XCA T3RJ (line end adapter activated).

    6 T-junction 170 XTS 04100.

    7 T-junction VW3 A8 306TF6 6 .

    Function description

    1 The Modbus slave communication module is connected to a 2-wire or 4-wireModbus network (2).1

    The maximum length of the network is 1000 m (9600 bauds max., AWG 26).1 A maximum of 32 slaves can be connected to the Modbus network, or a maximumof 247 slaves with repeaters.1 Line end adaptors must be fitted to both ends of the line(1 nF/10 V, 120 /0.25 W in series).1 The line must be polarised (470 /0.25 W resistors) (3).1 The connection cable and its RJ45 male connectors must be screened.1 The 7 terminal on the module must be connected directly to the protective earthat one point on the bus.

    (1) Programming from the front panel and buttons on the smart relay is only possible in LADDER

    language.(2) Please refer to installation instructions supplied with the product.(3) The polarisation resistors must be managed by the master.

    DescriptionModbus slave communication module SR3 MBU01BD comprises:

    1 Two retractable fixing lugs.2 A Modbus network connection (RJ45 screened female connector).3 A communication LED (COM).4 A Power on LED (PWR).5 A screw terminal block for the protective earth connection.6 A spring for clip-on mounting on a 35 mm mounting rail.7 Two locating pegs.8 Two locating pegs for clip-on fixing.

    COM

    SR3 MBU01BD

    MB485-V1

    PWR

    6 1

    8

    8

    2

    5

    3

    4

    1

    7

    7

    Characteristics:page 35

    Functions :page 36

    References :page 40

    Dimensions, mounting :page 41

    532522

    524121

    524131

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    37/7235

    Characteristics 1 Zelio Logic smart relays 1CommunicationModbus slave communication protocol

    (1) Except for the configuration SR3 B1 1 1

    BD + SR3 MBU01BD + SR3 XT43BD class A (class B:work in progress).

    Environment characteristicsType SR3 MBU01BD

    Product certifications UL, CSA, GL, C-TICK

    Conformity with thelow voltage directive

    Conforming to 73/23/EEC EN (IEC) 61131-2 (open equipment)

    Conformity with theEMC directive

    Conforming to 89/336/EEC EN (IEC) 61131-2 (Zone B)EN (IEC) 61000-6-2, EN (IEC) 61000-6-3 (1) and EN (IEC) 61000-6-4

    Degree of protection Conforming to IEC/EN 60529 IP 20 (terminal block)IP 40 (front panel)

    Overvoltage category Conforming to IEC/EN 60664-1 3

    Degree of pollution Conforming to IEC/EN 61131-2 2

    Ambient air temperaturearound the deviceConforming toIEC/EN 60068-2-1 andIEC/EN 60068-2-2

    Operation C - 20... + 55 (+ 40 in non-ventilated enclosure)

    Storage C - 40... + 70

    Max. relative humidity Conforming to IEC/EN 60068-2-30 95% without condensation or dripping water

    Maximum operating altitude Operation m 2000

    Transport m 3048

    Mechanical resistance Immunity to vibration IEC/EN 60068-2-6, test Fc

    Immunity to mechanical shock IEC/EN 60068-2-27, tes t Ea

    Resistance toelectrostatic discharge

    Immunity toelectrostatic discharge

    IEC/EN 61000-4-2, level 3

    Resistance to HF interference(immunity)

    Immunity toelectromagnetic radiated fields

    IEC/EN 61000-4-3

    Immunity to fast transientsin bursts

    IEC/EN 61000-4-4, level 3

    Immunity to shock waves IEC/EN 61000-4-5

    Radio frequencyin common mode

    IEC/EN 61000-4-6, level 3

    Voltage dips and breaks (6

    ) IEC/EN 61000-4-11

    Immunity to dampedoscillation waves

    IEC/EN 61000-4-12

    Conducted and radiatedemissions

    Conforming to EN 55022/11(Group 1)

    Class B (1)

    Earthing Yes (please refer to installation instructions supplied with the product).

    Presentation, description :page 34

    Functions :page 36

    References :page 40

    Dimensions, mounting :page 41

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    38/7236

    Functions 1 Zelio Logic smart relays 1CommunicationModbus slave communication protocol

    (1) Programming from the front panel and buttons on the smart relay is only possible in LADDERlanguage.

    Parameter entryParameters can be entered either using Zelio Soft 2 software or directly using thebuttons on the Zelio Logic smart relay (1).When the RUN instruction is given, the Zelio Logic smart relay initialises theModbus slave communication module in a configuration previously defined in thebasic program.

    The Modbus slave communication module has 4 parameters:1 number of UART wires and format of the frames on the Modbus network,1 transmission speed,1 parity,1 network address of the Modbus module.

    The default parameter settings are as follows: 2-wire, RTU, 19 200 bauds, evenparity, address n1.

    Parameter entry Options

    Number of wires 2 or 4

    Frame format RTU or ASCII

    Transmission speedin bauds

    1200, 2400, 4800, 9600, 19 200, 28 800, 38 400, 57 600

    Parity None, even, odd

    Network address 1 to 247

    Software workshopparameter entry window

    Addressing of Modbus exchangesLADDER programming

    In LADDER mode, the 4 data words (16 bits) to be exchanged cannot be accessedby the application. Transfers with the master are implicit and are effected in a waythat is totally transparent.

    Modbus exchanges Code Number of words

    Image of smart relay I/O Read03

    4

    Clock words Read/Write16, 06 or 03

    4

    Status words Read03

    1

    Function block diagram (FBD) programming

    In FBD mode, the 4 input data words (16 bits) (J1XT1 to J4XT1) and the 4 outputdata words (O1XT1 to O4XT1) can be accessed by the application. Dedicatedfunction blocks make it possible to:1 break down a complete type input (16 bits) into 16 separate bit type outputs.2 example: break down a J1XT1 to J4XT1 type input and copy these status valuesto discrete outputs.1 make up a complete type output (16 bits) from 16 separate bit type inputs.2 example: transfer the status value of the discrete inputs or the status of a function

    to an O1XT1 to O4XT1 type output.

    Modbus exchanges Code Number of words

    Input words Read/Write16, 06 or 03

    4

    Output words Read03

    4

    Clock words Read/Write16, 06 or 03

    4

    Status words

    Read03

    1

    J1

    XT1

    J2

    XT1

    J3

    XT1

    J4

    XT1

    3

    72

    3

    72

    3

    72

    3

    72

    01

    XT1

    02

    XT1

    03

    XT1

    04

    XT1

    09

    34

    09

    34

    09

    34

    09

    34

    Presentation, description :page 34

    Characteristics:page 35

    References :page 40

    Dimensions, mounting :page 41

    524121

    524110

    Input words Output words

    FDB program Editing window

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    39/7237

    Presentation,description 1

    Zelio Logic smart relays 1CommunicationEthernet server communication protocol

    Presentation

    Zelio Logic modular smart relays are connected to the Ethernet network via theEthernet server communication module.Communication module SR3 NET01BD allows communication on the Ethernetnetwork under the Modbus TCP protocol.

    The Ethernet server communication module must be connected to an SR3 B6 6 6 BDmodular smart relay, with a 5 24 V supply.

    Configuration

    The Ethernet server communication module is configured from a PC with "Zelio Soft"software, see page 9.On the PC, programming is effected in function block (FDB) language, see pages 12and 13.

    Connection example

    1 Twido client, 40 I/O compact base controller TWD LCAE 40DRF.2 Ethernet network (cables 490 NTW 0006 6 ).3 ConneXium 499 NES 251 00 Switch.4 Zelio Logic modular smart relay SR3 B6 6 6 BD.5 Communication interface SR2COM01.6 Connecting cable SR2 CBL07 (supplied with the Modem communication

    interface).7 GSM (or analogue PSTN) Modem.8 Ethernet server communication module SR3 NET01BD.9 Analogue I/O extension module SR3 XT43BD.

    Function description

    1 The Ethernet server communication module is connected to a local LAN typenetwork.1 The maximum cable length between 2 devices is 100 m.1 The connection cable must be at least category 5, and its RJ45 male connectorsmust be screened.1

    The7

    terminal must be connected directly to the protective earth.

    Description

    Ethernet server communication module SR3 NET01BD comprises:

    1 Two retractable fixing lugs.2 An Ethernet network connection (RJ45 screened female connector).3 A communication LED (LK/ACT 10/100).4 A status LED (STS).5 A screw terminal block for the protective earth connection.6 A spring for clip-on mounting on a 35 mm mounting rail.7 Two locating pegs.8 Two locating pegs for clip-on fixing.

    Ethernet servercommunication module

    1

    24

    3

    2 2

    4

    9

    8

    8

    4

    8

    7

    6

    5

    2

    LK/ACT 10/100

    SR3 NET01BD

    STS

    6 1

    8

    8

    2

    5

    3

    4

    1

    7

    7

    Characteristics:page 38

    Functions :page 39

    References :page 40

    Dimensions, mounting :page 41

    53631

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    40/7238

    Characteristics 1 Zelio Logic smart relays 1CommunicationEthernet server communication module

    (1) Except for the configuration SR3 B1 1 1

    BD + SR3 NET01BD + SR3 XT43BD class A(class B: work in progress).

    Environment characteristicsType SR3 NET01BD

    Product certifications UL, CSA, GL (pending), C-TICK (pending)

    Conformity with thelow voltage directive

    Conforming to 73/23/EEC EN (IEC) 61131-2 (open equipment)

    Conformity with theEMC directive

    Conforming to 89/336/EEC EN (IEC) 61131-2 (Zone B)EN (IEC) 61000-6-2, EN (IEC) 61000-6-3 (1) and EN (IEC) 61000-6-4

    Degree of protection Conforming to IEC/EN 60529 IP 20 (terminal block)IP 40 (front panel)

    Overvoltage category Conforming to IEC/EN 60664-1 3

    Degree of pollution Conforming to IEC/EN 61131-2 2

    Ambient air temperaturearound the deviceConforming toIEC/EN 60068-2-1 andIEC/EN 60068-2-2

    Operation C 0... + 55 (+ 40 in non-ventilated enclosure)

    Storage C - 40... + 70

    Max. relative humidity Conforming to IEC/EN 60068-2-30 95% without condensation or dripping water

    Maximum operating altitude Operation m 2000

    Transport m 3048

    Mechanical resistance Immunity to vibration IEC/EN 60068-2-6, test Fc

    Immunity to mechanical shock IEC/EN 60068-2-27, test Ea

    Resistance toelectrostatic discharge

    Immunity toelectrostatic discharge

    IEC/EN 61000-4-2, level 3

    Resistance to HF interference(immunity)

    Immunity toelectromagnetic radiated fields

    IEC/EN 61000-4-3

    Immunity to fast transientsin bursts

    IEC/EN 61000-4-4, level 3

    Immunity to shock waves IEC/EN 61000-4-5

    Radio frequencyin common mode

    IEC/EN 61000-4-6, level 3

    Voltage dips and breaks (6

    ) IEC/EN 61000-4-11

    Immunity to dampedoscillation waves

    IEC/EN 61000-4-12

    Conducted andradiated emissions

    Conforming to EN 55022/11(Group 1)

    Class B(1)

    Earthing Yes (please refer to installation instructions supplied with the product).

    Presentation, description :page 37

    Functions :page 39

    References :page 40

    Dimensions, mounting :page 41

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    41/7239

    Functions 1 Zelio Logic smart relays 1CommunicationEthernet server communication module

    Parameter entryParameter entry must be carried out using Zelio Soft 2 software.When the RUN instruction is given, the Zelio Logic smart relay initialises theEthernet server communication module in a configuration previously defined in thebasic program.

    The Ethernet server communication module has 6 parameters:1 type of addressing (dynamic or static).1 IP address,1 sub-network mask,1 gateway address,1 reserved address,1 time out.

    Addressing of Ethernet exchanges

    Function block diagram (FBD) programming In FBD mode, the 4 input data words (16 bits) (J1XT1 to J4XT1) and the 4 output

    data words (O1XT1 to O4XT1) can be accessed by the application. Dedicatedfunction blocks make it possible to:1 break down a complete type input (16 bits) into 16 separate bit type outputs.2 example: break down a J1XT1 to J4XT1 type input and copy these status valuesto discrete outputs.1 make up a complete type output (16 bits) from 16 separate bit type inputs.2 example: transfer the status value of the discrete inputs or the status of a functionto an O1XT1 to O4XT1 type output.

    Ethernet exchanges Code Number of words

    Input words Read/Write16, 06 or 03

    4

    Output words Read03

    4

    Clock words Read/Write16, 06 or 03

    4

    Statuswords Read03

    1

    Ethernet communication module configuration window

    J1

    XT1

    J2

    XT1

    J3

    XT1

    J4

    XT1

    3

    72

    3

    72

    3

    72

    3

    72

    01

    XT1

    02

    XT1

    03

    XT1

    04

    XT1

    09

    34

    09

    34

    09

    34

    09

    34

    Presentation, description :page 37

    Characteristics:page 38

    References :page 40

    Dimensions, mounting :page 41

    Input words Output words

    FDB program Editing window

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    42/7240

    References 1 Zelio Logic smart relays 1Communication

    8 Available: 1st quarter 2007

    Modbus slave and Ethernet server communication modulesFor use with Network Reference Weight

    kg

    Modular smart relaysSR3 B

    2 2

    2 22 2

    2 2

    1BD and SR3 B2 2

    2 22 2

    2 2

    2BD (1)Modbus SR3 MBU01BD 0.110

    Ethernet SR3 NET01BD(2), (3)

    0.110

    Connection accessoriesAccessory Description Network Length Reference Weight

    m kg

    T-junctions3 2 x RJ45 connectors3 1 cable with integratedRJ45 connector

    Modbus 0.3 VW3 A8 306TF03 0.190

    1 VW3 A8 306TF10 0.210

    3

    2 x RJ45 femaleconnectors3

    1 x RJ45 male connector

    Modbus Withoutcable

    170 XTS 04100 0.020

    Junction

    boxes

    3 Screw terminal block

    for main cable3 1 x RJ45 connectorfor tap link3 Isolation of RS 485serial link

    2

    Polarisation and

    line end adapter2 Supply 5 24 V2

    Mounting on 35 mm

    9

    rail

    Modbus TWD XCA ISO8

    0.100

    3

    3 x RJ45 connectors3

    Polarisation and lineend adapter

    2

    Mounting on 35 mm

    9 rail

    Modbus TWD XCA T3RJ8

    0.080

    Line endadapter

    For RJ45 connectorR = 120 , C = 1 nf

    Modbus VW3 A8306RC 0.200

    RS 485cables

    2 x RJ45 connectors Modbus 0.3 VW3 A8306R03 0.030

    1 VW3 A8306R10 0.050

    3 VW3 A8306R30 0.150

    Straightshieldedtwisted paircable

    2 x RJ45 connectors Ethernet 2 490 NTW 000 02 (4)

    5 490 NTW 000 05 (4)

    12 490 NTW 000 12 (4)

    40 490 NTW 000 40 (4)

    80 490 NTW 000 80 (4)

    conneXiumswitch

    Ethernet 499 NES 251 00 0.190

    (1) Compatible withSR3 B1 11 11 11 1

    2BDfeaturing hardware version H1.0.01, available since June2005.

    (2) Can only be used in FBD language.(3) Can only be used with "Zelio Soft 2" software version

    2

    V 4.1.(4) Cable conforming to EIA/TIA-568 standard category 5 and IEC 1180/EN 50 173, class D.

    For UL and CSA 22.1 approved cables, add the letter Uat the end of the reference.

    499 NES 251 00

    SR3 MBU01BD

    SR3 NET01BD

    TWD XCA ISO

    TWD XCA T3RJ

    Presentation, description :pages 34 to 37

    Characteristics:pages 35 to 38

    Functions :pages 36 to 39

    Dimensions, mounting :page 41

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    43/7241

    Dimensions,mounting 1

    Zelio Logic smart relays 1Communication

    Communication modules SR3 66601BDCommon side view Rail mounting Screw mounting (retractable lugs)

    57

    52,5

    70

    44 15

    90

    35

    27.

    5

    27.

    5

    108

    35

    25

    35

    100

    2 x 4

    Presentation, description :pages 34 to 37

    Characteristics:pages 35 to 38

    Functions :pages 36 to 39

    References:page 40

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    44/7242

    Presentation,description 1

    Zelio Logic smart relays 1Analogue I/O extension modules

    PresentationModular smart relays and analogue I/O extension modules

    To improve performance and flexibility, Zelio Logic modular smart relays can be fittedwith analogue I/O extension modules with 10-bit resolution.The inputs accept 0-10 V, 0-20 mA and Pt 100 type signals.

    Using a Zelio Logic modular smart relay with 5 24 V supply in conjunction with ananalogue 4 I/O extension module makes it possible to obtain up to 30 I/O, including8 analogue inputs and 2 analogue outputs.

    The analogue I/O extension module must be connected to an SR3 6 6 6 BD modularsmart relay with a 5 24 V supply.

    Description

    The analogue I/O extension module has thefollowing on its front panel:1 Two retractable fixing lugs.2 Terminals for connection of the inputs.3 Terminals for connection of the outputs.4 A connector for connection to the smart

    relay (powered via the smart relay).5 Locating pegs.

    536279

    Analogue I/Oextension modules

    524127

    1 2

    1 Modular smart relay(10 or 26 I/O)

    2 Analogue I/O extension module(4 I/O)

    524128

    1 2

    1 Modular smart relay(10 or 26 I/O)

    2 Modbus or Ethernet communication modules3 Analogue I/O extension module (4 I/O)

    3

    1 2

    5

    13

    5

    4

    Characteristics:page 43

    References, dimensions :page 44

    Schemes:page 45

    Combination of modular smart relays with

    communication and I/O extension modules

    1

    11

    1

    The order shown above must be observed when usinga network communication module and an analogue I/Oextension module.An I/O extension module cannot be fitted before thenetwork communication module.

  • 8/4/2019 Smart Relay Zelio Logic SR2 SR3 SR2PACK SR3PACK Module Extension Zelio

    45/7243

    Characteristics 1 Zelio Logic smart relays 1Analogue I/O extension modules

    (1) Except for configuration SR3 B1 1 1

    BD + SR3 MBU01BD + SR3 XT43BDor SR3 B

    1 1 1

    BD + SR3 NET01BD + SR3 XT4