Shining a Light on Small Data Centers in the U.S. Authors: Mohan Ganeshalingam, Arman Shehabi, Louis-Benoit Desroches Energy Analysis and Environmental Impacts Division Lawrence Berkeley National Laboratory June 2017 This work was supported by the Federal Energy Management Program of the U.S. Department of Energy under Lawrence Berkeley National Laboratory Contract No. DE-AC02-05CH1131. LBNL-2001025

Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

ShiningaLightonSmallDataCentersintheU.S.

Authors:

MohanGaneshalingam,ArmanShehabi,Louis-BenoitDesroches

EnergyAnalysisandEnvironmentalImpactsDivisionLawrenceBerkeleyNationalLaboratory

June2017

ThisworkwassupportedbytheFederalEnergyManagementProgramoftheU.S.DepartmentofEnergyunderLawrenceBerkeleyNationalLaboratoryContractNo.DE-AC02-05CH1131.

LBNL-2001025

Page 2: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

1

AbstractLargedatacentersarewellknownfortheirhigh-energyintensityandhavemadedramaticefficiencyimprovementsoverthepastdecade.Smallclosetandroomdatacentershavereceivedmuchlessattention,yetconstituteasignificantfractionofthetotalnumberofserversintheUnitedStates.Theoftenmakeshift,adhocnatureofsmalldatacentersoftenresultsinlittleattentionpaidtoenergyefficiencyandinadequatecoolingequipment.Thesmallphysicalfootprintofthesedatacenters,typicallyembeddedwithinalargerbuilding,makesitdifficulttoidentifyandtargetforefficiencymeasures.Theseconditionsmakesmalldatacentersnotoriouslyinefficientrelativetotheirlargercounterparts.Inthisreport,wepresentananalysisofsmallandmidsizedatacentersintheUS,drawingfromsurveysofcommercialbuildingstock.Wefindthatserversinsmalldatacentersmakeupapproximately40%ofinstalledserverstock,withthevastmajorityofsitesutilizingonly1-2servers.Weidentifyindustrieswheresmalldatacentersaremostprevalent,findingthatthehighestsaturationsareinmedical,retail,office,andeducationsectors.Smalldatacenterstypicallylackdedicatedcoolingequipment,oftenrelyingonbuildingairconditioningandventilationequipmentforcooling.Wefurtherfindthatthetypeofcoolingequipmentusedishighlycorrelatedwiththenumberofoperationalserverracks,withlessefficientcoolingoptionsusedwithfewerracks.WedevelopgeospatialmapsofsmallandmidsizedatacenterstovisuallyidentifyregionsofhighserverconcentrationandcalculateassociatedCO2emissions.Smalldatacentersconsume13billionkWhofenergyannually,emitting7millionmetrictons(MMT)ofcarbondioxide–theequivalentemissionsofapproximately2.3coal-firedplants.WediscussefficiencymeasuresthatcouldbeimplementedandestimatepotentialenergyandCO2savings.

Page 3: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

2

Acknowledgements

TheauthorswouldliketothankHeidiFuchsandBlakeRingeisenforusefuldiscussionsregardingtheservermarket.RichardBrownprovidedhelpfulsuggestionsandfeedbackthatimprovedtheclarityofthispaper.

Page 4: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

3

1. IntroductionThedigitizationofthemodernU.S.economyhasmadedatacentersessentialinfrastructureforcommercialbusinessesacrossallindustries.Moderndatacentersarepopulatedbycomputingequipment,whichoperatecontinuouslytosupporton-demandnetworkrequests.Theyrangeinsizefromindividualserversfoundinliteralclosetstoexpansivewarehousesfilledwiththousandsofservers.Datacentersofallsizesareusedtomanagecommunications,supportbusinessoperations,andcontrolaccesstodata.Attheheartofdatacenteroperationsareservers,networking,anddatastorageequipment.Serverstypicallyrundedicatedapplicationsandprocessrequestsreceivedviaadistributednetwork.Evenduringperiodsoflowutilization,thepowerdrawofaconventionalservermaybeasmuchas150-350W(Brownetal.,2008;Koomey,2011;Masanetetal.,2011;Shehabietal.,2016).Factoringinspaceconditioningandotherfacilityoverheadequipmentcandoubledatacenterelectricityconsumption(CenterofExpertiseforEnergyEfficiencyinDataCenters,n.d.).Consequently,buildingswithdatacentershaveahighenergyintensityrelativetoothertypesofcommercialbuildings(EIA,n.d.).Inaggregate,datacentersareestimatedtocurrentlyconsume70billionkWhintheU.S.alone,representingapproximately1.8%ofU.S.electricityconsumption(Shehabietal.,2016).Severalstudieshaveanalyzedtheevolvinglandscapeofdatacentersmostlyfocusingonlargestdatacentersthathousethousandsofservers(Brownetal.,2008;Koomey,2011;Masanetetal.,2011;Shehabietal.,2016).Inarecentstudy,Shehabietal.(2016)foundthatalthoughthereisoverallgrowthinthesizeandnumberofdatacentersovertime,thetotalenergyconsumptionattributedtodatacentershasremainedrelativelyconstantforthepastfewyears.Thisresultisaproductofconcertedeffortstooptimizeoperationsforthelargestdatacenters,whichareabletoreaplargeoperationalcostsavingsfromefficiencyimprovements.Technologycompaniesoperatinglargedatacentersbenefitfromeconomiesofscaleandhavetheresourcestoinvestinefficiencymeasures.Givenhighoperationalcostsoflargedatacenters,upfrontcapitalexpendituresonefficiencymeasuresarequicklyrecoupedbyoperatingcostsavings.Googlepresentsacasestudyinwhicha$25,000expenditureonefficiencymeasuresledtoannualsavingsof$67,000-apaybackof5months(Google,2011).Forthisparticulardatacenter,Googleestimatedayearlyenergysavingsof670MWh.Whenconsideringthelargenumberofdatacentersoperatedbysimilartechnologycompanies,undertakingefficiencymeasuresleadstomillionsofdollarsinsavings.Significantlylessattentionhasbeenpaidtosmall-scaledatacenters,typicallyreferredtoasdataclosetsanddatarooms(or“embedded”datacenters).Thesmallphysicalfootprintofthesedatacenters,typicallyembeddedwithinalargerbuilding,makesitdifficulttoidentifyandtargetforefficiencymeasures.Thesespacesaregenerallyrunbyinstitutionslessfamiliarwithinformationtechnologysystemsandbestpracticesfordatacentermanagement.Theoftenmakeshift,adhocnatureofsmalldatacentersresultsinlittleattentionpaidtoenergyefficiencyandinadequatecoolingequipment.Theseconditionsmakesmalldatacentersconsiderablylessefficientrelativetotheirlargecounterparts.

Page 5: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

4

AstudyperformedbyCheungetal.(2014)surveyed30smallserverclosetsandroomswithfoursitesselectedfordetailedassessments.Theauthorsfoundthatmostsiteswerenotdesignedforefficientserveroperationandnotedmanyexamplesofpoorserverroommanagement.Forexample,inmanycasesconditionedcoolairwasinefficientlydirectedwithintheserverroomleadingtomixingwithexhaustedwarmair.ManyofthepotentialefficiencymeasuresoutlinedinCheungetal.rangefromno-tolow-cost.However,theauthorsnotebarriersimpedingmoreefficientoperationareorganizationalratherthantechnological.Feworganizationshadpoliciestopromoteefficiencyandmostlackedproperlytrainedstafftoresearchandimplementefficiencymeasures.BennettandDelforge(2012)performedasurveyof30businessesoperatingsmalldatacenterslookingspecificallyatthepenetrationofefficientoperatingpractices.Thesurveycovereddatacentersoperatingbetween1-30servers.Ingeneral,theyfoundalackofawarenessandorganizationalprioritizationofefficiencymeasures.Datacenteroperatorsweretypicallynotresponsibleforpayingenergybills,limitingmotivationforpursuingefficiency.SimilartothefindingsofCheungetal.,barrierstoefficiencywereorganizationalasopposedtotechnological.BennettandDelforgehighlighttheneedforlocalandstatepolicymeasurestocreateincentivestopromoteefficiencymeasuresspecificallyaimedtowardssmalldatacenters.Todate,nostudyhasanalyzedarepresentativesampleofcommercialbusinessesoperatingsmalldatacentersduetoadearthofdata.Thelackofdatahaslimitedtheabilityofpolicymakerstoeffectivelycraftpolicytoaddressenergywasteinsmalldatacenters.Inthisreport,weuserecentlyreleasedsurveydataofcommercialbuildingstocktoanalyzecharacteristicsofsmallandmidsizedatacenters.Weusetherecentlyreleased2012CommercialBuildingEnergyConsumptionSurvey(CBECS)administeredbythefederalEnergyInformationAdministration(EIA)toanalyzehowserversaredistributedgeographicallyandinwhattypesofbuildingstheyarelocated(EIA,2015).ThesedatarepresentanationallyrepresentativesurveydetailingenergyconsumptionpracticesofU.S.commercialbuildings.CombiningthesedatawithoccupationdatafromtheBureauofLaborStatistics(BLS)weconstructmapsofgeographiclocationofsmalldatacentersincommercialenterprises,andofserverlocationforsmallanddatacentersintheU.S.Additionally,weperformananalysisofthe2014CommercialBuildingStockAssessment(CBSA)administeredbytheNorthwestEnergyEfficiencyAlliance(NEEA).1AlthoughlimitedtodatacentersinthePacificNorthwestregion,thesurveyprovidesadetailedglimpseintothespacecoolingandservervirtualizationpracticeswithinsmalldatacenters.Thereportisorganizedasfollows.InSection2,wediscussthedatasourcesandmethodologyusedinouranalysisofdatacenters.Althoughthefocusofthisreportissmalldatacenters,wealsoincludeanalysisofmidsizedatacenters,whichfallinthegapbetweensmalldataclosetsandroomsandlargehyper-scaledatacenters.InSection3,wediscusstheresultsofouranalysisoftheCBECSandCBSAsurveys.InSection4,wepresentgeospatialmapsofserverintensityofsmallandmidsizedatacenters.WethendiscussaggregateenergyandCO2emissionsfromsmalldatacenterconsumptionandpotential1http://neea.org/resource-center/regional-data-resources

Page 6: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

5

energysavingsfromefficiencymeasures.Section5providesasummaryofresultspresentedinthisreport.

2. DataandMethodsInthissectionwedescribethedatausedinouranalysisofsmallandmidsizedatacenters,aswellasthemethodologytoestimatenationalenergyconsumptionandCO2emissions.WewillusetheCBECSandCBSAstudiesofcommercialbuildingstocktocharacterizevariousaspectsofthesmallandmidsizedatacentermarket.WewillalsoutilizethenationallyrepresentativeCBECSdatatoestimatenationalenergyuseandCO2emissionsfromsmallandmidsizedatacenters.WestartwithU.S.commercialbuildingstocksurvey,estimatethenumberofservers,anddisaggregategeographicallybasedonregionalemploymentstatistics.

CommercialBuildingEnergyConsumptionSurvey2012CBECSisanationallyrepresentativesurveyofcommercialbuildingsintheUnitedStatesconductedbytheEIA.Thesurveyprovidesasnapshotofenergy-relatedbuildingcharacteristicsofU.S.commercialbuildingstock.CBECSdefinescommercialbuildingsasthosethatarenotprimarily(i.e.,>50%offloorspace)usedforresidential,industrial,oragriculturalpurposes.ForCBECS2012,EIAsurveyed6,720buildingsandweightedtheirsampletobenationallyrepresentativeofcommercialbuildingstock(EIA,2015).Thepubliclyreleasedmicrodatausedforthisanalysisisanonymizedtoremoveanycharacteristicsthatcouldpossiblybeusedtoidentifyindividualbuildings.Aspartofthisprocess,thelocationofbuildingsisonlymadeavailableattheCensusdivisionlevel(groupsof4-9states).

In2012,EIAincludedsurveyquestionstospecificallytargetserverusageincommercialbuildings.Whenquestioningrespondents,CBECSdefinedserversas“usuallyjusttheCPU,or‘case,’portionofacomputerthatmanagesnetworkresourcessuchascomputerfiles,printers,databases,ornetworktraffic;serversdonotrequiremuchhumanoperation,somostdonothavekeyboardsormonitors.”

Buildingswith500ormoreserversarecodedinCBECSwith‘9,995’inplaceoftheactualnumberofservers.Thesebuildingscorrespondto26recordsrepresentingapproximately2,000buildings.Thesesitesmayrepresentlargeenterpriseand‘hyper-scale’datacentersoutsidethescopeofthisreportandomittedfromouranalysis.However,theyarenotclearlyidentifiedasdatacentersbyactivityinthedataset.ItisalsopossiblethatthesedatacentersareclassifiedasindustrialfacilitiesoutsidethescopeofCBECS.

CBECScharacterizestheprincipalbuildingactivity(PBA)ofeachsampledbuildingintocategoriestogroupbuildingswithsimilarenergyconsumptionpatterns.Activitiescoverabroadrangeofcategoriesfrom‘Education’to‘WarehouseandStorage’.2,3AlthoughCBECS

2Fordefinitionsseehttp://www.eia.gov/consumption/commercial/building-type-definitions.cfm3CBECSalsoprovidesanadditionalmoredetailedcharacterizationofthebuildingactivitycodedasPBAPLUS.Forexample,the‘Education’PBAisfurthersubdividedinto‘elementary/middleschool’,‘highschool’,

Page 7: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

6

includesaPBAfor‘DataCenters’(separatefromaquestionofwhetherthereisadatacenterorserverfarminthebuilding),therearenobuildingscategorizedassuchinthedataset.

Forthiswork,weadoptaclassificationsystemofeitherasmallormidsizedatacenterforeachbuildinginCBECSwithatleastoneserverbasedonthenumberofreportedservers.OurclassificationisrootedinthedatacentertaxonomydefinedbymarketreportsreleasedbytheInternationalDataCorporation(IDC).IDCcategorizesdatacentersinto5types,rangingfromsmallclosets(1-4servers)toenterprise-level,high-enddatacenters(>500servers).Indescriptionsofeachspace,IDCreportsthatbothclosetandroomdatacentersarehousedinrelativelysmallspaces(<500squarefeet),oftenlackdedicatedspacecooling(Baileyetal.,2007),andareusedprimarilybysmallbusinesses.Forourpaper,wedefineasmalldatacenterashavingbetween1-25servers,capturingbothclosetandroomservers.Allotherdatacentershavingmorethan25servers,butlessthan500areclassifiedasamidsizedatacenter.Table1providestypicalpropertiesforIDC’sdatacentertaxonomydatacentersandtherelationshiptoourclassification.Table1:Datacentercharacteristics

ClassificationThisWork

TaxonomyIDC

SpaceDimensions(squarefeet)

TypicalNumberofServers

SmallDataCenter

Closet <=100 1-4Room 101-1000 5-25

MidsizeDatacenter

LocalizedDatacenter 1,001-2000 26-100

Mid-tierDatacenter 2,001-20,000 101-499

NotAnalyzed High-endDatacenter >20,000 >500

CBECSreportsdatacentersquarefootageforthosebuildingswhererespondentsidentifiedadedicatedspaceforservers.Ideally,thesedatacanbeusedtoinformourserverspacecategorization.However,wefindthesedatanotusefulforcategorizingserverspaceforallbuildingsthatreporthavingservers.Forexample,98%ofrespondentswith5orlessserversdidnotidentifyhavingadatacenterandthusdidnotreportadatacentersquarefootage.Respondentswhoidentifiedadatacenterintheirbuildingappearbiasedtolargerspacetypes.Basedonthelackofreportingforallbuildingswithservers,wedonotusethedatacentersquarefootageestimatesfromCBECSinourcategorizationofserverspacetype.

‘university/college’,and‘othereducation’.Ingeneral,ouranalysisdoesnotbenefitgreatlyfromtheextradetailprovidedbythesemorespecificPBAs.Ingeneral,wewillpresentresultsintermsofPBA.However,whennoteworthy,wehighlightinterestingtrendsbythemorespecificbuildingactivitywithindiscussionofresults.

Page 8: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

7

ItisunclearhowCBECSreportsbuildingswithmultipleseparatedatacenters.WeassumethatCBECSreportsthetotalnumberofserversinthebuildingcorrectly,butdoesnotdifferentiatebetweenmultipledatacenters.Althoughthisaddsalevelofuncertaintytoourestimatesofthenumberofdatacenters,wedonotexpectthistogreatlyimpactourdatacenterclassificationofbuildingsgiventhebroadcategorizationusedinourclassification.ItispossiblethatCBECSresultsmaysufferfromvariousformsofreportingbiasdependingonhowrespondentschosetoestimatethenumberofserversintheirbuilding.RespondentsansweringquestionsinCBECSarenotnecessarilytheindividualsmaintainingITequipment.CBECSreliesonestimatesfromrespondentsandresponsesarenotverifiedindependently.Inparticular,ourdatacentercategorizationsassumethattherespondentcan(1)positivelyidentifyserversand(2)provideareasonablyaccurateestimateofthenumberofserverson-premise.Thereislittlewecandotowardscharacterizinguncertaintiesduetothefirstassumption.Thesurveycouldpotentiallyunder-orover-reportthenumberofserversdependingoneachrespondent’sabilitytorecognizeandquantifyservers.Forthesecondassumption,ourclassificationofdatacentersaseithersmall,midsize,orhigh-endde-emphasizestheneedforexactestimatesforclassification.Forexample,arespondentmaypotentiallyconfuse5serversfor7or8servers,butisunlikelytoconfuse5serversformorethan25.

CommercialBuildingStockAssessment2014The2014CBSAsurveywasconductedbyNEEAinordertoprovideasnapshotofenergy-consumingdevicesfoundinregionalcommercialsites(NavigantConsulting,2014;NorthwestEnergyEfficiencyAlliance,2014).ThesurveyisspecifictocommercialbuildingsinthePacificNorthwestcoveringOregon,Washington,Idaho,andMontana.Detailedauditsofcommercialstockweregatheredfor859randomlyselectedcommercialsitesacrosstwelvebuildingtypes.Selectedsitescoveredbothurbanandruralcommerciallocations.DatawereanonymizedtoavoididentificationofindividualsitesandweightedtoberepresentativeofthePacificNorthwest.AlthoughlimitedtodatacentersinthePacificNorthwestregion,thesurveyprovidesadetailedglimpseintothespacecoolingandservervirtualizationpracticeswithinsmalldatacenters.CBSA2014includedmanyquestionsspecifictodatacentercharacteristicsandoperation.UnlikeCBECS,whichprovidesserverdataforeachbuilding,CBSAdataareprovidedatthedatacenterlevel,allowingforasinglecommercialsitetoreportmultipledatacenters.Foreachdatacenter,thesurveyrecordedthetotalnumberofracksintheserverroom,datacenterfloorspace,andtypeofspacecooling.Althoughtherewereadditionalquestionsregardingthepresenceofuninterruptiblepowersupplies(UPS),mostresponseswereleftblank.Thesurveydidnotincluderackdimensionsorthenumberofserversineachdatacenter,makingdirectcomparisonstoCBECSdifficult.NEEAspecificallysurveyedheating,ventilation,andairconditioning(HVAC)characteristicsforeachsite.Onsitesurveyorsrecordedthepresenceofdedicateddatacentercoolingandthetypeofconditioningprovided(e.g.,computerroomAC,buildingtransfer,waterchillers,etc.),evenifconditionedairwassharedwithspaceoutsideofthedatacenter.

Page 9: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

8

Datacollectionforhospitalsanduniversitiesfollowedadifferentsurveyprotocolthanotherbuildingtypesduetothecomplexitiesinrecordingresultsforalargecampus.Forhospitalsanduniversities,CBSArecordsthedatacentersquarefootage,butdoesnotrecordthenumberofracks.Additionaldatafor521buildingswascollectedforthe‘CBSAOversampleStudy’(NorthwestEnergyEfficiencyAlliance,2014).Thesedatawerecollectedasautility-orstakeholder-fundedextensionoftheoriginalsurvey.Althoughthesedatarepresentasignificantadditionofthedataset,NEEArecommendsuseoftheCoredataset,presumablytoavoidintroducingbiasfromtheadditionoftargetedcommercialsites.OuranalysismakesuseoftheCoredataset.

EnergyCalculationsThemostcommonindustrymetricforquantifyingoveralldatacenterenergyefficiencyismeasurementofthePowerUsageEffectiveness(PUE)coefficient(TheGreenGrid,2012).PUEisdefinedastheratioofthetotalenergyusedfordatacenteroperationstotheelectricitydrawnbyITequipment:

𝑃𝑈𝐸 = 𝐸!"#"$%&#%'

𝐸!"

PUEcapturestheoverheadenergyrequiredtomaintaindatacenteroperationsincludingspacecooling,lighting,electricitydistribution,etc.Forexample,aPUEof2indicatesthatforeverykilowatt-hourdrawnbyITequipment,anotherkilowatt-hourisrequiredtomaintainserveroperations.TheenergydrawofITequipmentcanbeexpressedasthesumoftheenergyrequiredtopowerservers,network,anddatastorageequipment

𝐸!" = 𝐸!"#$"#! + 𝐸!"#$%&' + 𝐸!"#$%&' Thetotaldatacenterenergyconsumptioncanbeexpressedas

𝐸!"#"$%&#%' = 𝐸!" × 𝑃𝑈𝐸 𝐸!"#"$%&#%' = 𝐸!"#$"#! + 𝐸!"#$%&' + 𝐸!"#$%&' ×𝑃𝑈𝐸

Bytheverynatureofdatacenteroperations,serversoperatecontinuouslyinanactivemode.Serverpowerdrawdependsonutilization.Studieshavefoundthatserversrarelyoperateathighlevelsofutilization(Brownetal.,2008;WSPEnvironment&EnergyandNaturalResourcesDefenseCouncil,2012).Shehabietal.(2016)foundthatactiveserversinsmalldatacenterstypicallyoperateataround10-15%utilizationassuming10%ofserversare“zombie”serverswhichareconnectedtopowerbutneverutilized(KoomeyandTaylor,2015).Weassumethatatypicalserverfoundinasmallormidsizedatacenterconsumes,onaverage,approximately180W(Shehabietal.,2016),basedonthepower-

Page 10: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

9

scalingabilityandcomputationalprocessorcountgenerallyfoundinthesedatacentertypes.FollowingMasanetetal.(2011),weuseatop-downapproachtoestimateenergyconsumptionfromnetworkandstoragedevices.Weassumenetworkandexternalstorageenergyconsumptionisproportionaltotheenergyconsumptionofserverhardware.Weassumenoexternalstorageinsmalldatacentersand20%formidsizedatacentersbasedontheircalculationsforthenumberofexternalharddrivesderivedfromshipmentsinBaileyetal.(2007).Ontopoftheserverenergyconsumption,weattributeanadditional5%ofserverenergyconsumptiontonetworkequipmentinsmalldatacentersand10%ofserverenergyconsumptiontonetworkequipmentinmidsizedatacenters.PreviousworkhasfoundthatsmallerdatacentersaremorelikelytoexhibithigherPUEvaluesduetopoorspacecooling(Cheungetal.,2014;Shehabietal.,2016).DetailedonsitecasestudiesofsmalldatacentersperformedbyCheungetal.(2014)foundthatdataroomsandclosetswereoftenfashionedoutofrepurposedspacenotintendedforservers.Manyclosetsandroomsstartedastemporaryhousingforsmall-scaleserverneedswhichincrementallyexpandedovertimetoadedicatedserverspace.ThelackofattentionpaidtoproperspacecoolingledtowarmairexhaustfromITequipmentmixingwithcooledairfromHVACequipment.Insomecases,theauthorsnotedthatservercoolingwasprovidedbybuildingcoolingequipment,theimpactofwhichisreducedcoolingefficiency.DetailedassessmentsoffoursmalldataspacesfoundPUEsrangingfrom1.5-2.1,withtwodatacentershavingPUEsof2.1.Shehabietal.(2016)reportvaluesof2.5forclosetdatacentersand2.0forroomandlocalizeddatacenters.Forcomparison,verylargedatacenteroperatorsreportedPUEsaslowas1.1throughconcertedefficiencyefforts(Google,2016).Forthiswork,weadoptatypicalPUEvalueof2.1forsmallandmidsizedatacenters.

OccupationalEmploymentStatisticsCBECSprovidesgeographicdataattheresolutionofCensusdivision(i.e.,groupsof4-9states)allowingustoquantifyserverownershipasafunctionofcensusdivisionandPBA.Toproducehigherspatialresolutions,wemaketheassumptionthatserversarespatiallydistributedproportionallytoworkerswhowouldworkinabuildingwithaserver.Forthispurpose,wemakeuseofoccupationalemploymentdata,availableatahighergeographicresolution,toapproximatethenumberofserversbyU.S.zipcode.

WeutilizeOccupationEmploymentStatistics(OES)releasedinMay2014fromtheBureauofLaborStatistics(BLS,2015).Thesurveyisconductedsemi-annuallyviamailanddesignedtocollectemploymentandwageestimatesfor821occupations.Thedataareprovidedforover650geographicalareasthatareacombinationofmetropolitanstatisticalarea(MSA)andnon-metropolitanareas.TheU.S.OfficeofManagementandBudgetdefinesMSAsashavingarelativelyhighpopulationdensitywithcloseeconomictiesthroughthearea.MSAsgenerallyincludealargecityandassociatedsurroundingareas,oftencoveringmultiplecounties.RegionswithineachstatethatdonotfallintoanMSAaredefinedas“nonmetropolitanareas”.Althoughastatemayhavemultiplenon-metropolitanareas,wecombineemploymentstatisticsforallnon-metropolitanareaswithinastate.

Page 11: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

10

TheBLScollectsdataonthenumberofemployedpersonsin821detailedoccupationsthataregroupedinto22majoroccupationcategoriesforeachregionalunit.WeusethemajoroccupationcategoriesprovidedbyBLSandidentifyCBECSPBAswherethoseoccupationsaremostlikelytobefound.ForsomeoccupationsthereisadirectcorrespondencebetweenoccupationandPBA.Forexample,“LegalOccupations”canbemappeddirectlyto“Office”buildings.However,amajorityofoccupationsinOEShaveaone-to-manymappingofoccupationtoPBAs.Insuchcases,workersforthatoccupation,inagivenMSA/non-metropolitanarea,aresplitproportionallyaccordingthenumberofworkersinthoseCBECSPBAsforthecensusdivisioncorrespondingtothearea.Table2showsourmappingofoccupationscodestoPBA.Table2:MappingofOESjobcodestoCBECSPBA

OESJobCode CBECSPBAManagementOccupations OfficeBusinessandFinancialOperationsOccupations OfficeComputerandMathematicalOccupations Office,LaboratoryArchitectureandEngineeringOccupations Office,LaboratoryLife,Physical,andSocialScienceOccupations Office,LaboratoryCommunityandSocialServiceOccupations Office,ReligiousworshipLegalOccupations OfficeEducation,Training,andLibraryOccupations Education,PublicassemblyArts,Design,Entertainment,Sports,andMediaOccupations Publicassembly

HealthcarePractitionersandTechnicalOccupations

Outpatienthealthcare,Inpatienthealthcare,Nursing

HealthcareSupportOccupations Outpatienthealthcare,Inpatienthealthcare,Nursing

ProtectiveServiceOccupations PublicorderandsafetyFoodPreparationandServingRelatedOccupations Foodservice

BuildingandGroundsCleaningandMaintenanceOccupations Office,Laboratory,Lodging

PersonalCareandServiceOccupations Service

SalesandRelatedOccupationsFoodsales,Retailotherthanmall,Enclosedmall,Stripshoppingmall,Foodservice

OfficeandAdministrativeSupportOccupations Office,LodgingFarming,Fishing,andForestryOccupations AgriculturalConstructionandExtractionOccupations IndustrialInstallation,Maintenance,andRepairOccupations Other

ProductionOccupations Non-refrigeratedwarehouse,Refrigeratedwarehouse,Other

Page 12: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

11

TransportationandMaterialMovingOccupations Non-refrigeratedwarehouse,Other

Wefirstdeterminethenumberofworkersinagivenmetropolitan/non-metropolitanarea,𝑀𝑆𝐴! ,andinagivenPBA,𝑃𝐵𝐴! ,whichwedenoteas𝑁! 𝑀𝑆𝐴! ,𝑃𝐵𝐴! :

𝑁! 𝑀𝑆𝐴! ,𝑃𝐵𝐴! = 𝑇(𝑂𝐶𝐶! → 𝑃𝐵𝐴!) ×𝑁!(𝑀𝑆𝐴! ,𝑂𝐶𝐶!)Inthisequation,weapplyourmappingofoccupationstoPBA,𝑇(𝑂𝐶𝐶! → 𝑃𝐵𝐴!),to𝑁!(𝑀𝑆𝐴! ,𝑂𝐶𝐶!)whichisthenumberofworkersin𝑀𝑆𝐴! ineachoccupationcode,𝑂𝐶𝐶! .𝑇(𝑂𝐶𝐶! → 𝑃𝐵𝐴!)isamatrixof0sand1swhichdescribeshoweachoccupationcodeisrelatedtoeachPBA.Nextwecalculatetheparameter𝜂,whichisthefractionofworkersinagiven𝑀𝑆𝐴! and𝑃𝐵𝐴! relativetothetotalnumberofworkersassociatedwith𝑃𝐵𝐴! inthecensusdivisionthatcontains𝑀𝑆𝐴! ,𝐶𝐷𝐼𝑉!"!!:

𝜂 𝑀𝑆𝐴! ,𝑃𝐵𝐴! = 𝑁!(𝑀𝑆𝐴! ,𝑃𝐵𝐴!)

𝑁!(𝑀𝑆𝐴! ,𝑃𝐵𝐴!)!"!!∈!"#!!"!!

FromCBECS,wehavethenumberofserversisagivencensusdivisionandPBA.Togetthenumberofserversinagiven𝑀𝑆𝐴! and𝑃𝐵𝐴! ,wemultiplythenumberofserversfoundinthe𝐶𝐷𝐼𝑉!"!! and𝑃𝐵𝐴! by𝜂:

𝑁! 𝑀𝑆𝐴! ,𝑃𝐵𝐴! = 𝑁! 𝐶𝐷𝐼𝑉!"!! ,𝑃𝐵𝐴! ×𝜂(𝑀𝑆𝐴! ,𝑃𝐵𝐴!)Andfinallytodeterminethenumberofserversin𝑀𝑆𝐴! ,wesumoverallPBAs:

𝑁! 𝑀𝑆𝐴! = 𝑁!(𝑀𝑆𝐴! ,𝑃𝐵𝐴!)!!!"" !"#$

Asimplifiedexamplefollowstoillustratetheprocess,beginningbymappingoccupationalcodestoagivenPBA.Considerauniversewheretherearetwooccupations(𝑂𝐶𝐶!and𝑂𝐶𝐶!)withtwopossiblePBAs(𝑃𝐵𝐴!and𝑃𝐵𝐴!).Allworkersin𝑂𝐶𝐶!areassumedtomaponto𝑃𝐵𝐴!.Workersin𝑂𝐶𝐶!canbeineither𝑃𝐵𝐴!or𝑃𝐵𝐴!.Weassumethat50%ofworkersin𝑂𝐶𝐶!willbein𝑃𝐵𝐴!and50%willbein𝑃𝐵𝐴!.Soifweassumethatthereare100workersin𝑂𝐶𝐶!and100in𝑂𝐶𝐶!,150workerswillbein𝑃𝐵𝐴!and50workerswillbein𝑃𝐵𝐴!.Next,consideracensusdivisionthatcontains3MSAs(𝑀𝑆𝐴!,𝑀𝑆𝐴!,and𝑀𝑆𝐴!).Inthiscensusdivision,wefind100serversassociatedwiththeretailPBA.Fromoccupationdata,wefind100workersin𝑀𝑆𝐴!,150in𝑀𝑆𝐴!,and250in𝑀𝑆𝐴!resultingin500totalworkersinourcensusdivisionassociatedwithretail.Wewouldthenassumethat20%(100/500)of

Page 13: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

12

the100serversassociatedwithretailarein𝑀𝑆𝐴!.Similarly,30serversarefoundin𝑀𝑆𝐴!and50serversarein𝑀𝑆𝐴!.Lastly,forthepurposesofcreatinggeospatialmaps,serverswithinanMSAaredistributedevenlyacrossthezipcodesinthatMSA.Ourmethodtodisaggregateserverlocationbyzipcodeexplicitlyassumesthatthespatialdistributionofemployedworkersinbuildingswithserversisareasonableproxyforservers.

eGRID2012TheEmissionsandGenerationIntegratedDatabase(eGRID)administeredbytheU.S.EnvironmentalProtectionAgency(EPA)collectselectricitygenerationandemissionsdataforthemajorityofpowerplantsthatsupplyelectricityontheU.S.electricgrid(EPA,n.d.).ThesedataprovidedetailedprofilesofelectricitygenerationandassociatedgreenhousegasemissionratesacrosstheU.S.Dataarecollectedatthepowerplantlevel,thenaggregatedinto26eGRIDsubregionsdefinedbytheEPA.Variationsinemissionfactorsamongsubregionsareduetothemixofresourcesusedtopowertheregionalgrid.Subregionswithanelectricityportfoliowithsignificantcontributionsfromrenewableresources(i.e.,hydro,wind,solar,nuclear)haveloweremissionfactorsincomparisontoregionsthatrelypredominantlyoncoalandnaturalgas.

eGRIDprovidesemissionfactorsforbothbaseloadandnon-baseloadelectricitydemand.Forourestimates,weusebaseloademissionfactorswhencalculatingcurrentCO2emissionsfromservers.Reductionsinelectricityconsumptionimpactpowersuppliedbyancillarypowerplantsthatoperatecoincidentlywithpeakdemand.Weusenon-baseloadfactorswhencalculatingpotentialreductionsinCO2fromreducedelectricitydemand.eGRIDemissionfactorsarebasedonelectricitygenerationatthepowerplantandnotatthepointofconsumption.Tocapturelossesfromdistributionandtransmissionfromthepowerplanttotheconsumer,eGRIDderivesgrossgridlossfactorsfor5sectionsoftheU.S.electricgrid:Alaska,Hawaii,EasternU.S.,WesternU.S.,andERCOTwhichcoversmostofTexas.Thegrossgridlossfactorsarethenmappedontothe26eGRIDsubregionsandappliedtoourestimatesforgreenhousegasemissionstoaccuratelyaccountforalllosses.TotalCO2emissionsaretherefore:

𝐶𝑂! 𝑒𝑚𝑖𝑠𝑠𝑖𝑜𝑛𝑠 =𝐸!"#$

1− 𝐺𝐺𝐿!"#$%&× 𝐹 !"#$%&

!!!

where𝐸!"#$ representsenergyatthepointofconsumption,𝐺𝐺𝐿!"#$%&isthegridlossfactor,and𝐹 !"#$%&

!!! istheemissionsfactorrelatingtheamountofCO2emittedperunitofelectricitygenerated.Notethat𝐺𝐺𝐿!"#$%&and𝐹 !"#$%&

!!! arefunctionsofeGridsubregionasdenotedbytheirsubscript.

Page 14: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

13

WeuseEPA’sPowerProfilerspreadsheettooltomapU.S.zipcodetoeGRIDsubregion(EPA,2015).Inaminorityofcases(2801outof41335),azipcodeiscoveredbymultipleutilitiesbelongingtodifferenteGRIDsubregions.Inthesecases,weusethelisted“PrimaryeGRIDSubregion”assumingthisrepresentsamajorityoftheelectricitysuppliedtothezipcode.

3. ResultsServersbydatacenterspacetypeInTable3,wereportgeneralstatisticsforsmallandmidsizedatacentersfoundinCBECS.Wefindapproximately3.7millionserversresideinsmalldatacenterscorrespondingto72%ofinstalledstockinCBECSbuildings.Smalldatacentersarereportedin31%ofallcommercialbuildingsinCBECSandin99%ofbuildingswithservers.Table3:SummaryoftheNumberofDatacentersandServersinCBECS*

DataCenterType

NumberofBuildings(millions)

NumberofServers(millions)

AverageNumber

ofServers

%ofServersinCBECS

NumberofCBECSRecords

Small(1-25servers)

1.725 3.70 2.1 72% 3163

Midsize(26-500servers)

0.021 1.47 69.4 28% 360

*Excludesbuildingsthatcontainmorethan500servers.IDCestimatesthetotalnumberofvolumeserversinstalledin2012acrossdatacentersofalltypestobe13.2million(IDC,2014a).OurestimateofthetotalnumberofserversinsmallandmidsizedatacentersinCBECSis5.2millionservers,implying40%ofserversarefoundinsmallandmidsizedatacenters.Figure1providesadetailedlookatthedistributioninthenumberofserverswithinourdatacenterclassifications.Thetoptwopanelsdisplaythedistributioninthenumberofserversperbuildingrelativetothetotalnumberofserversforsmallandmidsizedatacenters,respectively.Eachdistributionisnormalizedbythetotalnumberofserversinthatdatacenterspacetype.Thebottompanelsdisplaythedistributioninthenumberofserversperbuildingrelativetothenumberofsmallandmidsizedatacenters.Inthesepanels,eachdistributionisnormalizedbythetotalnumberofdatacentersineachdatacenterspacetype.

Page 15: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

14

Figure1:Distributioninthenumberofserversbydatacentertype

Thetop-leftpanelshowsthatapproximately30%ofthetotalnumberofserversinsmalldatacentersarefoundinlocationswithonlyoneserver.Datacenterswithasingleservermayrepresentausecasewhereoperatorsneedjustoneserverforfilesharingacrossanofficeorfore-mailorwebhosting.AswithotherresultsfromCBECS,thisresultisdependentonthereportingaccuracyfromthesurveyrespondent.Aninterestingfeatureinthetop-leftpanelofFigure1istheslight,yetsignificant,increaseinfrequencyat10and20servers.Thismaybeareportingbiastowardsavalueroundedtothenearest10orpossiblyanindicationthatserveroperatorsarebiasedtowardsowningserversinincrementsof10servers.Asseeninthebottom-leftpanel,anoverwhelmingmajorityofcommercialbuildingswithsmalldatacentersoperateoneserver(~70%).Thefrequencyofsmalldatacenterswithmultipleserversdropsoffdramatically,withlessthan6%havingmorethan5servers.Thisresultindicatesthatalthoughsingleserverdatacentersonlymakeup30%ofthefractionofserversinsmalldatacenters,suchdatacentersarefarmoreprevalentandrepresentapopularusecaseforbusinesses.

Page 16: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

15

Whenlookingatmidsizedatacenters,mostlocationshavelessthan100servers.Thereisanotablerelativedearthofdatacenterswithintherangeof200-500serversindicatingthismaybeanintermediatescaleofinfrastructurethatdoesnotserveapracticalpurposeinbusinessorindustry.CBSAreports36,500datacentersinitssampleofPacificNorthwestcommercialsites.TheCBSAsurveydidnotrecordthenumberofserversineachdatacenter,insteadcountingthenumberofserverracksinoperation(seesection2fordetails).ThisdifferencefromCBECS,whichrecordsthenumberofservers,likelyindicatesthatCBSAmaybeexcludinglocationsthatoperatewithonlyafewservers.Asdiscussedpreviously,ourCBECSanalysisshowsthatsingle-serveroperationisamajorusecase.Figure2showsthedistributionofdatacentersasafunctionofthereportednumberofoperationalserverracks.Themajorityofdatacentersreporthavingbetween1-5racks(84%),withoverhalfhavingasinglerack(55%).Detailsregardingthedimensionsoftherackwerenotrecorded.Dependingonthesizeandtypeofrack,anindividualrackcouldholdanywherefrom1serverupto40serversmakingitdifficulttotranslaterackcounttoservercountforacomparisontoresultsfromCBECS.However,theseresultsqualitativelysupporttheassertionthatthemajorityofdatacentersarerelativelysmallinsize.

Figure2:DistributioninthenumberofracksinCBSAdatacenters

Notably,1%ofidentifieddatacenters(correspondingto11records)donotreporthavinganyoperationalracks.Thisleadstoquestionsregardinghowhardwareisoperatedandspaceconditioned.Thesesitesmaybeoperatinghardwareinadhocspacesnotintendedforserveroperationandmaybenefitfromsimpleefficiencymeasures.

Page 17: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

16

CBSAclassifieseachsiteaseitherurbanorruralbasedontheRural-UrbanContinuumCodeofthesitecounty.4Approximately33%ofsurveyeddatacentersarefoundinrurallocations.Figure3showstheurbanandruralbreakdownforeachrackcategory.Ofdatacentersthatreported0racks,59%arefoundinrurallocations,significantlymorethantheoverallbreakdown.Forotherdatacentersthatreportedhavingarack,thefractionofresponsesinrurallocationsisroughly33%,asexpectedfromtheoverallbreakdownbetweenurbanandrurallocations.Ruralareashavealargerfractionofdatacenterswith0rackscomparedtourbanareas.Theskewtowardssmaller,lessefficient(intermsofPUE)datacentersinruralareaspotentiallyindicatesanopportunityforenergysavings.

Figure3:UrbanandruralbreakdownbyracksizeinCBSAdata

ServersbyCensusDivisionInthissectionwereportgeographicresultsfromdatacentersinCBECSaggregatedbycensusdivision.Table4showsthepercentageofserversineachcensusdivisionfortheconsidereddatacentertypes.Wealsoshowthepercentageofcommercialbuildingsineachcensusdivision(CBECSWeight)forcomparison.Table4:GeographicdistributionofdatacentersbyCensusDivision.

CensusDivision SmallDatacenters

MidsizeDatacenters

CBECSWeight

NewEngland 5.8% 2.7% 5.4% MiddleAtlantic 9.2% 19% 9.1% EastNorthCentral 13% 12% 13% WestNorthCentral 6.7% 4.8% 9.0% 4Formoredetails,seehttp://www.ers.usda.gov/data-products/rural-urban-continuum-codes.aspx

Page 18: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

17

SouthAtlantic 21% 8.2% 20% EastNorthCentral 5.6% 7.3% 6.7% WestSouthCentral 13% 16% 14% Mountain 6.1% 10% 6.1% Pacific 20% 20% 17% ThespatialdistributionofsmalldatacentersgenerallytracksthedistributionofcommercialbuildingsinCBECSwithafewnotableexceptions.WefindthattherearemoresmalldatacentersintheSouthAtlanticandPacificrelativetothenumberofcommercialbuildings.TherearefewersmalldatacenterserversinWestSouthCentralandEastNorthCentralrelativetonumberofcommercialbuildings.Overall,thesimilarityinspatialdistributionsunderscorestheprevalenceofsmalldatacentershousedwithincommercialspacesacrosstheU.S.Contrarytoourfindingsforsmalldatacenters,thespatialdistributionofmidsizedatacentersdifferssignificantlyfromthatofcommercialbuildings.MidsizedatacentersaresignificantlyoverrepresentedintheMid-AtlanticandMountainrelativetothenumberofcommercialbuildingsintheseregions.Giventhatmidsizedatacentersarefoundlessfrequentlythansmalldatacenters(asshowninTable1),midsizedatacentersmayonlybeutilizedbycertainindustriesthatrequiresignificantcomputingpoweranddonotnecessarilytrackthegeographicdistributionofallCBECsbuildings.

ServersbyPrincipleBuildingActivityInthissectionweinvestigatehowserversaredistributedbyCBECSbuildingactivity.CBECSprovidesaprincipalbuildingactivitycodeandamorespecificbuildingactivitycode.Inouranalysis,weanalyzedresultsbybothPBAandspecificPBA.Fortheresultspresentedinthissection,wefocusourattentiononresultsbyPBAaslittlemeaningfulinformationisgainedbythefinergradationprovidedbythespecificbuildingactivitycode.However,whennoteworthy,wediscussresultsbyspecificbuildingactivity.Table5showsthepercentageofserversbyPBAforeachdatacentertype.Althoughsmalldatacentersarefoundinadiversevarietyofsettings,thepluralityofserversassociatedwithsmalldatacentersarefoundinofficebuildings.Thisisunsurprisinggiventheutilitythatserversprovidewithinofficesettingssuchasfilestorageacrossanetwork,accesstodatabases,andrunningsharedenterpriseapplications.LookingatspecificPBAswithinofficebuildings,wefindthat26%ofserversinsmalldatacentersarefoundinadministrativeoffices.Similartosmalldatacenters,serversinmidsizedatacentersareprimarilyfoundinofficebuildings,specificallywithinadministrativeoffices(38%).Medicalbuildingsalsohouseasignificantnumberofserverswithinlargedatacenters,withmostassociatedwithInpatientCare(12%).

Page 19: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

18

Table5:Percentageofserversbybuildingactivityforeachconsidereddatacentertype

BuildingActivity

SmallDataCenters

MidsizeDataCenters

Education 9.8% 7.4%FoodSales 1.8% 0.0%FoodService 3.0% 0.0%Lodging 1.2% 0.9%Medical 6.9% 22%Office 43% 57%PublicAssembly 3.3% 5.4%PublicOrder 2.1% 1.7%ReligiousWorship 2.0% 0.0%Retail 13% 0.1%Service 4.4% 0.2%Warehouse 8.2% 5.4%Vacant 0.71% 0.0%Other 1.4% 0.3%Total 100% 100%AnotherwayofinvestigatingtheprevalenceofdatacentersisbylookingatthemarketsaturationofdatacentersineachPBA.Foragivenbuildingactivity,thedatacentersaturationisdefinedastheratioofthenumberofbuildingsofthatactivitywithadatacentertothetotalnumberofbuildingsofthatactivity. Table6showssaturationratesofsmallandmidsizedatacentersacrossPBA.Forsmalldatacenters,saturationratesrangefrom14%forreligiousworshipupto59%formedicalcarefacilities(notincludingadministrativemedicaloffices)withtypicalvaluesbetween20-30%.Theseresultsshowthatsmalldatacentersarerelativelycommoninawiderangeofindustries.Again,wefindthatsmalldatacentersareespeciallyprevalentinofficesettings.Notethatwefindhighsaturationratesformedical(56%),courthouses(94%),andgovernmentbuildings(55%),whichhouseactivitieswherefederalprivacylawsmayimpedeadoptionofoff-sitecolocation,highlightingtheneedtocustomizeefficiencystrategiesforthesesmalldatacenters.Forexample,privacylawmaypreventmedicalcompaniesfrommovingtheirin-housedatacentertoacloud-basedsystemoperatingfromalarger,moreefficienthyperscaledatacenter.Insuchcases,therearepotentiallymethodsofleveragingthecomputationalpowerofhyperscaledatacentersthatinteractwithon-siteprotecteddata,whichcouldyieldsignificantenergysavings.Bycontrast,highsaturationratesforprivatebusinessesinofficeandretailspacesmayprovideanopportunityforsubstantialenergysavingsviacloud-basedsolutionswithouthavingtoaddressasmanyobstaclesregardingprivacy.

Page 20: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

19

Table6:Serversaturationbybuildingactivityforeachconsidereddatacentertype

BuildingActivity SmallDataCenters

MidsizeDataCenters

Education 38% 0.54%FoodSales 31% 0.0%FoodService 22% 0.0%Lodging 22% 0.21%Medical 59% 2.2%Office 56% 1.1%PublicAssembly 20% 0.21%PublicOrder 28% 0.55%ReligiousWorship 14% 0.0%Retail 40% 0.0%Service 19% 0.0%Warehouse 21% 0.24%Vacant 3.0% 0.0%Other 32% 0.0%

SpaceCoolinginDatacentersTheCBSAsurveyallowsustoanalyzeHVACequipmentasafunctionofspacetypeandnumberofserverracks.AlthoughthesedataareweightedtoberepresentativeofthePacificNorthwest,wenotethatthedatamaynotreflectspaceconditioningacrossothergeographicregions.DifferentgeographicregionswillhavedifferentspacecoolingrequirementswhendeterminingHVACneedsforthebuilding.ThePacificNorthwestcovers‘Marine’and‘Cold’climatezonesasdefinedbytheBuildingAmericaprogram(PacificNorthwestNationalLaboratory,2015),sponsoredbytheU.S.DepartmentofEnergy’sOfficeofEnergyEfficiencyandRenewableEnergy(EERE).Buildingsinthesezonesgenerallyhavelowercoolingloadscomparedtohighertemperatureclimatezones,whichwillbefactoredintoHVACsystemdesigns.Thiscouldpotentiallyimpactspaceconditioningfordatacentersites,particularlythosethatutilizeeconomizersforcooling.

Page 21: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

20

Figure4:SpacecoolingcharacteristicsofdatacentersintheCBSA

ThetoppanelsofFigure4displayresultsfordatacenterswithdedicatedairconditioning.Whencategorizingdatacentersbysquarefootage(leftpanel),wefindthatamajorityofdatacenterslessthan101squarefeetdonothavededicatedspaceconditioning,relyingoncoolingsystemsthatservicealargerpartofthebuildingornocoolingsystem.Surprisingly,datacentersinthe101-1000squarefootrangehavealargerproportionofdedicatedcooling(79%)comparedtodatacenterslargerthan1000squarefeet(62%),althoughwe

Page 22: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

21

notethatthereareonly13recordsofdatacenterslargerthan1000squarefeetwithnodedicatedcooling.Furtherinvestigationfindsthatonlyonerecordofthe13reportshavingnotypeofHVACsystem.Inthetop,rightpanel,wefindthattheproportionofdatacenterswithoutdedicatedcoolingdecreasesasthenumberofoperationalserverracksincreases.ThebottompanelsshowtheproportionofdatacentersthatusedifferenttypesofHVACsystems.Notethatthesesystemsdonotnecessarilycorrespondtodedicatedconditioningforonlytheserverspaceandmayalsobeusedforconditioningotherpartsofthebuilding.Theleftpanelshowsthefractionofresponsesbysquarefootageandtherightpanelbynumberofoperationalserverracks.Amajorityofdatacenterslessthan1000squarefeetuseair-cooledcomputerroomairconditioners(CRACs),whicharelabeled‘AirDX’inthefigure.Asizablefractionofdatacenterslessthan1000squarefeetrelyonbuildingair-handlingunits(labeled‘BuildingTransfer’).Datacenterslessthan101squarefeethavethelargestfractionofrespondentsthatusenoconditioning(27%).Datacenterslargerthan1000squarefeetdatacentersrelymostlyonwater-cooleddirectexpansionsystems(42%).Thebottom,rightpanelshowssimilarresultsbynumberofoperationalserverracks.Over80%ofdatacenterswith0racksrepliedtheyhavenoHVACsystem.Curiously,wefind67recordsfordatacentersthatreporthavingeitheranair-cooledorwater-cooledCRAC,butalsoreporteitherhaving‘unknown’ornodedicatedairconditioning.ThisissurprisinggiventhatCRACsaredesignedspecificallyforuseindatacentersandwouldbeillsuitedforgeneralbuildingcooling.ItisunclearwhetherrespondentsansweredthequestionsincorrectlyincludingothertypesofcoolingsystemswithCRACsorifthereareofficeswhereCRACsarealsousedmoregenerallyinabuilding.

ServerVirtualizationServervirtualizationallowsasinglephysicalservertoactasmultiplevirtualmachinesrunningindependenttasksandapplications,ratherthandedicateindividualserversforeachapplication.Bycreatingvirtualmachines,datacenteroperatorscanconsolidatehardwareandmorefullyutilizeseverprocessingpower.However,previousresearchonsmallbusinessdatacenterpracticesindicatesthatservervirtualizationisnotheavilypracticed.BennettandDelforge(2012)foundonly37%ofsmallbusinessespracticeservervirtualizationinasurveyperformedin2011.Theauthorsnotethatmanysmallbusinesseshadneverheardofservervirtualizationordidnotthinktheinvestmentinvirtualizationwouldbecost-effective.Asurveyoflarge-scaleenterprisesin2011foundthatapproximately92%ofbusinessesutilizedvirtualization(VansonBourne,2011)andamorerecentsurveyin2016foundthat75%ofbusinessesofallsizesutilizedvirtualization(Spiceworks,n.d.).TheCBSAstudyrecordedthedegreeofvirtualizationundertakenbyITstaffforeachdatacenter.Unfortunately,itisunclearwhetherthedegreeofvirtualizationreferstothenumberofserversthatarevirtualserversorthenumberofphysicalserversthatcontainvirtualizationsoftware.Notably,mostsitesdidnotprovidearesponse.Giventhelackofvirtualizationinsmallbusinesseswithvirtualizationknowledge(BennettandDelforge,2012),itislikelythatmostofthesesitesdonotmakeuseofdatavirtualization.However,theremaybesomesiteswheretherespondentmaynothavebeenanITprofessional

Page 23: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

22

capableofproperlyansweringthequestion.Giventheuncertainty,unknownresponsesareseparatelyidentifiedinourreporting.InFigure5,weshowresultsforthereporteddegreeofvirtualizationbysquarefootage.Datacenterslessthan1000squarefeetshowahighproportionofunknownandnovirtualizationresponses.Only8%ofdatacenterslessthan101squarefeethaveanydegreeofvirtualization,with7%reportingmorethan50%virtualization.Approximately15%ofdatacentersoperatewithservervirtualization.Datacenterslargerthan1000squarefeetoperatewiththehighestproportionofservervirtualizationwith31%.Wewouldexpectthatlargercentershavemoreopportunitytoconsolidate,sincetheywouldberunningalargernumberofapplications,andwouldbenefitthemostfromvirtualization.

Figure5:Degreeofservervirtualizationbydatacenterspacetype

4. DiscussionSpatialDistributionofServersInthissectionwecombinedatafromCBECSandOEStoconstructspatialmapsofserverintensity(i.e.,serversperunitarea).AsdiscussedinSection2,occupationstatisticsatthezipcodelevelareusedasaproxytoestimatethespatialdistributionofservers.Figure6showsthecombinedgeographicserverintensityforbothsmallandmidsizedatacenters.Serverintensitycloselytrackspopulationcenterswithhighintensitiesinurbanareas.Thisisunsurprisinggiventhatmostjobsthatwouldutilizeaserverarefoundincities.

Page 24: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

23

MapsofCO2emissionintensitiesdisplayedaverysimilardistributiontowhatwefindforserverintensity.TheyarenotincludedherebecausedifferencesbetweentheserverintensityandCO2emissionmapswerehardtodiscern.However,itisworthmentioningthattherearesubtledifferencesbetweenthegeographicdistributionforserverandcarbondioxideemissionintensity.Forexample,thePacificNorthwesthasloweremissionsperserverduetotheregion’srelianceonhydropower.TheDenvermetropolitanregioninColoradohashigheremissionsperserverduetotheregion’srelianceoncoal.

Figure6:Geographicdistributionofservers

Inthenextsection,wewillcombineourderivedspatialdistributionofserverswithtypicalpowerconsumptionvaluesandgeographic-specificwithcarbonemissionfactorsfromeGridtoestimateregionalcarbondioxideemissions.

NationalEnergyUseandCarbonDioxideEmissionsInthissection,weaggregateourresultstoestimatetheannualenergyusedueonlytoservers,totalsiteenergyuseincludingenergyusedtomaintainandoperatethedatacenter,andtotalCO2emissionsincludinggrossgridlossesfortheconsidereddatacenters.ResultsforsmallandmidsizedatacenterscanbefoundinTable7.

Table7:AggregateannualenergyconsumptionandCO2emissionsbydatacentertype

DataCenterType

NumberofServers(millions)

ServerEnergyUse(billionkWh)

TotalEnergyUse(billionkWh)

TotalCO2Emissions(MMT)

Small 3.70 5.83 12.9 6.71Midsize 1.47 2.32 6.34 3.29Total 5.17 8.15 19.2 10.0

Page 25: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

24

Inaggregate,smallandmidsizedatacentersuseapproximately20billionkWhandemit10millionmetrictonsofCO2peryear,equivalenttotheannualelectricityuseof1.5millionhomes.5Theaverageserverinasmalldatacenterisresponsiblefor1.81metrictonsofCO2peryearandinamidsizedatacentertheaverageserverisresponsiblefor2.23metrictonsofCO2peryear.

ComparisontoIDCMarketReportMarketresearchfirmIDCauthoreda2014studyanalyzingthestateofthedatacenterindustry(IDC,2014b).ThestudyprovidesacensusofUSdatacentersbasedonin-depthinterviewswithITbuyersandsuppliersincludingvendorsthatmanufacturepower,cooling,server,storage,andnetworkingequipment.Thestudypresentshistoricaldataandprojectionsofthedatacentermarketbasedonunderlyingindustrytrends.WeusedatapresentedintheIDCstudytocomparetotheestimatesderivedfromCBECS.IDCreportsthenumberofdatacentersbyspacetypeusingataxonomythatcapturestherelativelybroaddefinitionofdatacenter.Fromsmallesttolargest,theirtaxonomyincludescloset,room,localizedinternal,mid-tierinternal,andhigh-endinternaldatacenters.AsdescribedinSection2,thetaxonomyusedinthisworkcombinesclosetandroomdatacentersinto“small”andlocalizedinternalandmid-tierinternalinto“midsize”.InTable8,wecomparethenumberofdatacentersreportedbyIDCandourestimatesfromCBECS.Therearelargediscrepanciesbetweenthetwodatasets.IDCreportsnearlyonemillionmoresmalldatacenterscomparedtothenumberofbuildingsclassifiedasasmalldatacenterinCBECS.Formidsizedatacenters,CBECSreportsroughlyaquarterofdatacentersfoundbyIDC.Table4:SummaryofcomparisonindatacentercountsbetweenIDCandthiswork

Withinsmalldatacenters,IDCreportsaroughlyevensplitbetweenclosetandroomdatacenters.However,assumingbuildingsinCBECSwithfewerthan5serverscorrespondtoaclosetdatacenter,wefindthat91%ofsmalldatacentersareclosets.Theskewtowards

5UsingEPA’sgreenhousegasequivalencycalculator:https://www.epa.gov/energy/greenhouse-gas-equivalencies-calculator

IDCTaxonomy IDCDataCenterCount

Taxonomy(thiswork)

IDCDataCenterCount

CBECS(thiswork)

Closet 1,512,829 Small 2,846,125 1,724,783Room 1,333,296Localized 70,419 Midsize 80,383 21,203

Mid-tier 9,964

High-end 8,283 NotAnalyzed

8,283 NotAnalyzed

Page 26: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

25

closetdatacenterscanbeseeninthebottomleftpanelofFigure1whichshowsthevastmajorityofsmalldatacentershaveonly1server.IfweapplytheIDCdefinitionofclosetdatacentertoCBECSbuildings(i.e.,adatacenterwithlessthan5servers),weestimate1.56millionclosetdatacenters.ThisvalueisveryclosetoIDC’sreportedestimateof1.51milliondatacenters.However,asinthecaseofmidsizeandhigh-enddatacenters,CBECSreportssignificantlyfewerroomdatacentersbyapproximatelyafactorof8.IDC’srangeinthenumberofserversisintendedasaroughguidetocategorizedatacentersandnotasastrictdefinition.However,itisdifficulttoseehowmisalignedclassificationsofdatacentersinCBECScouldpotentiallyexplainthedifferenceforlargeandhigh-enddatacentersbetweenthetwodatasets.Forthesedatacenters,CBECSreportsroughlyaquarterfewerdatacenters.OnepossibleexplanationforthedifferenceisCBECSgivesacountbybuilding,whereasIDCisestimatingthenumberofdatacenters.Thatis,abuildinginCBECSwithmultipledatacenterswouldbeaggregatedandrecordedasasinglerecord.AsCBECSgivesestimatesofthetotalnumberofserversineachbuilding,wehavenowayofinferringthetruenumberofdatacentersinbuildingswithmultipleseparatedatacenters.ThesystematicdifferencescouldpotentiallyberelatedtodifferencesinsurveymethodologybetweenIDCandCBECS.IDCreliesoninformationfromtheITindustrytodevelopestimatesofdatacenters,whereasCBECSrespondentsarecommercialbuildingownersandoperators.However,notethatsinceourenergyuseandCO2calculationsrelyonthenumberofservers,ourestimatesarenotsensitivetothisdiscrepancyinthenumberofdatacenters.InadditiontotheIDCdatacenterreport,wealsoobtaineddataoninstalledserverstock(IDC,2014a).IDCestimatesapproximately13.4millionserversin2012.FromCBECSdata,weestimate5.17millionserversinstalledinsmallandmidsizedatacentersimplyingtheseembeddeddatacenterspacetypesaccountforapproximately40%ofserverstock.Thelargefractionofserversinsmallandmidsizedatacentersagainunderscorestheneedtobetterunderstandthesetypesofdatacenterstoachieveenergysavingspotential.

EnergySavingOpportunities

ServerVirtualizationResultsfromtheCBSA2014showthatservervirtualizationremainsmostlyunderutilizedinsmallandmidsizedatacenters.Similarly,BennettandDelforge(2012)report26%servervirtualizationsaturationinsmallbusinessessurveyedin2011.OuranalysisofCBSAdatainSection3foundapproximately10%ofdatacentersutilizedsomelevelofservervirtualization.Theselowestimatesofvirtualizationindicatethereissignificantavailableenergysavingspotentialfromincreasingsaturation.BennettandDelforge(2012)estimatethatdatacenterswith10ormoreserverswouldbenefitfromvirtualization.Asascenario,weassumethat50%ofdatacenterswith10ormoreserversinCBECSareabletoreachvirtualizationratioof5to1,reportedasan

Page 27: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

26

“average”usecasebyWSPandtheNationalResourceDefenseCouncil(2012).Inthisscenario,weestimateannualsiteenergysavingsof3.8billionkWh,correspondingto2millionmetrictonsofCO2emissions.Therearemanybarrierstotheadoptionofvirtualizedserversinsmallbusinesses.Inmanycases,businessespayaflatfeeforenergyserviceseliminatingenergycostsasanincentivetoreduceenergydemand.OrganizationbarriersmayincludelackofcapitaltoupgradeandlackofITknowledge.Additionally,virtualizationwillnotbenefitsmalldatacentersthatoperatefewserverswithlittleroomtoeliminateexcesshardware.

CloudComputingTheriseofcloudcomputingoverthepastdecadehasprovidedanewmeansforbusinessestomeetITneeds.TheavailabilityofSoftwareasaService(SaaS),InfrastructureasaService(IaaS),andPlatformasaService(PaaS)cloudsolutionshasmovedcomputingdemandawayfromsmall,on-premisedatacentersintohighlyoptimizedcloud-computingdatacenters.Inasmalldatacenter,individualserversareoftenusedforrunningindividualapplicationsortasks.Thisleadstoserversthat,onaverage,operateatverylowutilizationlevels.Inlarge,hyper-scaledatacenters,applicationsandtasksaredistributedacrossahugenumberofserversandoperationalizedtorunatutilizationlevelscloserto50%(Shehabietal.,2016).Cloud-computingdatacentersbenefitfromeconomiesofscaleandareabletomakeupfrontinfrastructureinvestmentstosupportefficientdatacenteroperations(WSPEnvironment&EnergyandNaturalResourcesDefenseCouncil,2012).Giventhelargecostofoperatingthousandsofservers,evensmallimprovementsinefficiencycanleadtosignificantoperatingcostsavings.TheUptimeInstitute(2014)estimatedanaveragePUEof1.7fordatacentersthatself-reportedthePUEfortheirlargestdatacenter.SomecloudcomputingdatacentershaveachievedevenlowerPUEs.Forexample,Googlehasreachedafleet-wideaveragePUEof1.12(Google,2016).Pushingthelimitsevenfurther,Gao(2014)presentsaframeworkforapplyingmachine-learningartificialintelligencetooperationaldatatopotentiallydecreaseGoogledatacenterPUEsbelow1.10.Forcomparison,smalldatacentershavetypicalPUEscloserto2.0(Cheungetal.,2014;Shehabietal.,2016).Hereweperformasimpleanalysistoapproximatethepotentialsavingsfrommovingcomputingneedsawayfromasmalldatacentertoacloud-computingdatacenter.Weassumethatserverloadsfromprivate-runofficeandretailstorescanbeeasilyshiftedfromin-housedatacenterstocloudcomputingdatacenters.Shehabietal.(2016)estimateacloud-computingserverrunningundertypicalconditionsconsumesapproximately360W.However,movinganapplicationortaskfromasmalldatacentertoacloud-computingserverwillonlyconsumeamarginalfractionoftheserver’scomputingpower.Previousstudiesestimatethattheloadofasmalldatacenterserverisapproximatelyequivalentto1/5theloadofhigh-endcloudserver(Masanet,2014;Shehabietal.,2016).Ifweassumeconservativelya10%reductioninserversfromindustriesotherthanfinancial,health,andgovernmentrelatedfields,weestimateapotential1.2billionkWhreductioninenergyconsumptionand0.85MMTofCO2emissionsperyear.

Page 28: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

27

Asurveyofbusinessownerswithsmalldatacentersfoundthatformanyowners,amainbarriertocloudadoptionstemsfromprivacyandsecurityconcerns(BennettandDelforge,2012).However,theseareconcernsthatarenotnecessarilyrootedinreality.Cloudcomputingdatacentersoftentakemoremeasurestoensurecustomerdataismaintainedsecurelyanddedicatestaffresourcesforthispurpose.Additionally,manycloudcomputingoperatorsofferprivatecloudsolutionsforcompaniesthatwishtosilotheirdatafrompubliccloudresources.IncreasingpenetrationofclouddeploymentwithinsmallerdatacenterswilltakeaconcertedefforttoeducateITprofessionals.Althoughcloudcomputingoffersenergysavingspotentialbyshiftingloadsawayfromsmalldatacenterstomoreefficienthyperscaledatacenters,easyaccesstocloudservicescouldleadtoincreaseddemandforcomputingneedsthatwerenotneededpreviously.Forexample,businessesthatpreviouslyreliedonpaperrecordsthatmovetocloudserviceswilladdtooverallenergydemandorstartprovidingservicesthatrequirecloud-computingresources.Thesebusinesseswilllikelybenefitfromtheefficiencyofdigitizingrecordsandonlinemanagement.Forsomenewusers,thecloudoffersaneaseofsetupandmaintenanceinthatitdoesnotrequireadedicatedITprofessionaltoinstallanewsystem.

5. ConclusionTargetingsmallerdatacentersremainschallengingduetotheadhocnatureofsmalldatacenters,whichareoftensituatedinconfinedspaceswithinlargerbuildings.WemakeuseofrecentlyreleaseddataonserversanddatacentersincommercialbuildingstocharacterizethesmallandmidsizedatacentermarketandconstructspatialmapsoftheirlocationsacrosstheUnitedStates.Wecategorizebuildingswithlessthan25serversassmalldatacentersandbuildingswithmorethan25butfewerthan500datacentersasmidsizedatacenters.Wefindapproximately5millionservers(approximately40%ofinstalledstock)insmallandmidsizedatacenters,consistentwithpreviousestimates(Baileyetal.,2007;DelforgeandWhitney,2014).Thevastmajorityofserversinsmall&mediumdatacentersarefoundinsmalldatacenters.Amajorityofsmalldatacentersarefoundinofficesandretailbuildings.Thehighestsaturationsareinmedical,retail,office,andeducationsectors.Wefindthatapproximately26%ofserversinsmalldatacentersarefoundinadministrativeoffices.BasedondatafromtheCBSAconductedinthePacificNorthwest,amajorityofsmalldatacenterswithmorethanoneoperationalrackmakeuseofair-cooleddirectexpansionCRACsforspaceconditioning.ThemajorityofdatacenterswithoneorlessoperationalserverrackdidnotreportusinganyspecializedcoolingsystemandarelikelyrelyingonthebuildingHVACsystem.Siteswithtwoormoreoperationrackstendtorelyondedicatedspacecoolingwithair-cooledCRACsbeingthemostcommon.Water-cooledCRACsaremainlyusedindatacentersthatarelargerthan1000squarefeet,makingupapproximately40%ofcoolingunitsinthesesites.

Page 29: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

28

Inaggregate,wefindthatsmallandmidsizedatacentersconsumeapproximately20billionkWhofsiteenergy.UsingdatafromtheBureauofLaborofStatistics,wecorrelatethenumberofserversfoundintheCBECSdatasetstoemploymentdatawithinoccupationalfieldsidentifiedasusingdatacenters.ThisallowsustodisaggregateresultsbyzipcodetocreatedetailedgeospatialmapsofserverintensityacrosstheUS.Unsurprisingly,highestserverintensitiesarelocatedindensemetropolitanareas,withhighestconcentrationsontheEastandWestCoasts.Intotal,smallandmidsizedatacentersemitover10MMTonCO2emissionsannually.Servervirtualizationprovidesameansforanindividualservertoactasmultiplemachinesallowingforserverconsolidation.Althoughapracticalmeanstodecreasedatacenterenergyconsumption,wefindthatitisnotacommonpracticeinsmalldatacenters.Thevastmajorityofdatacentersrespondedthattheydidnotemployvirtualizationordidnotknowthedegreeofvirtualizationwithintheirdatacenter.Only15%ofsmalldatacentersreportedhavinganylevelofvirtualizationwithintheirfleet.Modestconsolidationofhardwarethroughvirtualizationindatacenterswithmorethan10serverscouldsave3.8billionkWhannually,correspondingto2millionmetrictonsofCO2.Themostchallengingbarriertoadoptionofvirtualizationisnottechnical.Mostsmallbusinesseshaveeitherneverheardofservervirtualizationordidnotthinktheinvestmentinvirtualizationwouldbecost-effective(BennettandDelforge,2012).Theeraofcloudcomputingrepresentsanopportunitytoshiftresourcesfrominefficientsmalldatacenterstohighlyoptimizedhyper-scaledatacenters.Although,thereareindustrieswhereprivacyregulationsmaypreventtheuseofthirdpartyclouddatacenters,suchasinhealthcare,manyindustriesthatcurrentlyrelyonsmalldatacentersshouldbeabletomovecomputingtocloudcenters.Assumingofficesotherthanfinancial,healthcare,andgovernmentofficescanshift10%oftheirloadtocloud-computingresources,wecalculateapproximateenergysavingsof1.2billionkWhperyear.Despiteincreasingconsolidationofsmalldatacentersintolargerones,thereremainasizablenumberofsmallandmidsizedatacenters.Thisreporttakesafirststeptowardsidentifyingandcharacterizinghowthesecentersoperate.However,asdiscussedthroughoutthisreport,amainbarrierimpedingefficientoperationislackofeducationaboutbestpracticesandopportunities.Futureprogresswillbemadebymeasuresandpoliciesthatareabletodirectlytargetsmalldatacenters.

Page 30: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

29

ReferencesBailey,M.,Eastwood,M.,Grieser,L.,Turner,V.,Gray,R.C.,2007.IDCSpecialStudy:Data

CenteroftheFuture(No.IDC#06C4799).InternationalDataCorporation(IDC).Bennett,D.,Delforge,P.,2012.SmallServerRooms,BigEnergySavings:Opportunitiesand

BarrierstoEnergyEfficiencyontheSmallServerRoomMarket.NaturalResourcesDefenseCouncil.

BLS,2015.OccupationalEmploymentStatisticsHomePage[WWWDocument].URLhttps://www.bls.gov/oes/(accessed6.27.17).

Brown,R.,Energy,A.toS.,Incorporated,I.C.F.,Incorporated,E.R.G.,Agency,U.S.E.P.,2008.ReporttoCongressonServerandDataCenterEnergyEfficiency:PublicLaw109-431.LawrenceBerkeleyNatl.Lab.

CenterofExpertiseforEnergyEfficiencyinDataCenters,n.d.CenterofExpertiseforEnergyEfficiencyinDataCenters[WWWDocument].URLhttps://datacenters.lbl.gov/(accessed3.27.17).

Cheung,I.,Greenberg,S.,Mahdavi,R.,Brown,R.,Tschudi,W.,2014.EnergyEfficiencyinSmallServerRooms:FieldSurveysandFindings.Presentedatthe2014ACEEESummerStudyonEnergyEfficiencyinBuildings.

Delforge,P.,Whitney,J.,2014.DataCenterEfficiencyAssessment-ScalingUpEnergyEfficiencyAcrosstheDataCenterIndustry-EvaluatingKeyDriversandBarriers.NaturalResourcesDefenseCouncil.

EIA,2015.EnergyInformationAdministration(EIA)-CommercialBuildingsEnergyConsumptionSurvey(CBECS)Data[WWWDocument].URLhttps://www.eia.gov/consumption/commercial/data/2012/index.php?view=microdata(accessed6.27.17).

EIA,n.d.Officebuildingswithdatacentersusesignificantlymoreelectricitythanotheroffices-TodayinEnergy-U.S.EnergyInformationAdministration(EIA)[WWWDocument].URLhttps://www.eia.gov/todayinenergy/detail.php?id=28232(accessed5.8.17).

EPA,2015.PowerProfilerZipcodeTool[WWWDocument].URLfromhttp://www2.epa.gov/sites/production/files/2015-10/power_profiler_zipcode_tool_2012_v6-0.xlsx(accessed10.21.16).

EPA,n.d.Emissions&GenerationResourceIntegratedDatabase(eGRID)[WWWDocument].URLhttps://www.epa.gov/energy/emissions-generation-resource-integrated-database-egrid(accessed5.8.17).

Gao,J.,2014.MachineLearningApplicationsforDataCenterOptimization.Google,2016.Efficiency:Howwedoit–DataCenters–Google[WWWDocument].URL

https://www.google.com/about/datacenters/efficiency/internal/(accessed9.1.16).

Google,2011.Google’sGreenDataCenters:NetworkPOPCaseStudy.IDC,2014a.IDC’sWorldwideQuaterlyServerShipmentTracker,2010-2018.International

DataCorporation(IDC),Framingham,MA.IDC,2014b.U.S.DatacenterCensusandConstruction2014–2018Forecast:Realigning

Workloads,ManagingObsolescence,andLeveragingHyperscale(No.252712).Koomey,J.,2011.Growthindatacenterelectricityuse2005to2010.Rep.Anal.Press

Complet.Req.N.Y.Times9.

Page 31: Small Data Centers · includes a PBA for ‘Data Centers’ (separate from a question of whether there is a data center or server farm in the building), there are no buildings categorized

30

Koomey,J.,Taylor,J.,2015.Newdatasupportsfindingthat30percentofserversare“Comatose”,indicatingthatnearlyathirdofcapitalinenterprisedatacentersiswasted.

Masanet,E.,2014.TheEnergyEfficiencyPotentialofCloud-BasedSoftware:AU.S.CaseStudy.eScholarship.

Masanet,E.R.,Brown,R.E.,Shehabi,A.,Koomey,J.G.,Nordman,B.,2011.EstimatingtheenergyuseandefficiencypotentialofUSdatacenters.Proc.IEEE99,1440–1453.

NavigantConsulting,2014.2014CommercialBuildingStockAssessment:FinalReport.NorthwestEnergyEfficiencyAlliance.

NorthwestEnergyEfficiencyAlliance,2014.NorthwestEnergyEfficiencyAlliance:2014CBSADatabase[Dataset].Portland,OR.

PacificNorthwestNationalLaboratory,2015.GuidetoDeterminingClimateRegionsbyCounty,BuildingAmericaBestPracties.

Shehabi,A.,Smith,S.J.,Horner,N.,Azevedo,I.,Brown,R.,Koomey,J.,Masanet,E.,Sartor,D.,Herrlin,M.,Lintner,W.,2016.UnitedStatesDataCenterEnergyUsageReport(No.LBNL-1005775).

Spiceworks,n.d.2016LatestTrendsinIT&TechnologyAdoption[WWWDocument].URLhttps://www.spiceworks.com/marketing/resources/reports/2016-state-of-it/(accessed5.8.17).

TheGreenGrid,2012.PUE:AComprehensiveExaminationoftheMetric.UptimeInstitute,2014.2014DataCenterIndustrySurvey[WWWDocument].UptimeInst.

EJournal.URLhttps://journal.uptimeinstitute.com/2014-data-center-industry-survey/(accessed9.9.16).

VansonBourne,2011.VeeamlaunchesV-indextomeasurevirtualizationpenetrationrate[WWWDocument].VeeamSoftw.URLhttps://www.veeam.com/news/veeam-launches-v-index-to-measure-virtualization-penetration-rate.html(accessed9.8.16).

WSPEnvironment&Energy,NaturalResourcesDefenseCouncil,2012.TheCarbonEmissionsofServerComputingforSmall-toMedium-SizedOrganizations:APerformanceStudyofOn-Premisevs.TheCloud.WSPEnvironment&EnergyandNaturalResourcesDefenseCouncil.