pag. 1/20
Current Transformers
SM6 24 cubicles
Feasibility rangeand referenced types
Catalogue 2004
Number: C019 rev. 1
pag. 2/20
CONTENTS
CURRENT TRANSFORMER
RECOMMENDATIONS FOR THE USE OF TABLES AND TECHNICALS NOTES Page 3,4,5 and 6
PANEL TYPE CRM
REFERENCED TYPES ARJP1/N2 F Page 7ARJP2/N2 F Page 11
CONFIGURED TYPES ARJP1/N1 F and ARJP1/N2 F Page 8 and 9ARJP2/N1 F, ARJP2/N2 F and ARJP2/N3 F Page 12 and 13
PANEL TYPE QMC
REFERENCED TYPES ARJP1/N2 F Page 7
CONFIGURED TYPES ARJP1/N1 F and ARJP1/N2 F Page 8 and 9
PANEL TYPE DMV-A, DMV-D, IMC
REFERENCED TYPES ARJP2/N2 F Page 11
CONFIGURED TYPES ARJP1/N1 F and ARJP1/N2 F Page 8 and 9ARJP2/N1 F, ARJP2/N2 F and ARJP2/N3 F Page 12 and 13
PANELS TYPE 1250A DM1-A, DM1-D, DM1-W, DM1-Z, GBC-A, GBC-B, DMV-A, DMV-D
REFERENCED TYPES ARJP3/N2 F Page 15
CONFIGURED TYPES ARJP3/N1 F, ARJP3/N2 F and ARJP3/N3 F Page 16
PANELS TYPE DM1-A, DM1-D, DM1-W, DM2, GBC-A, GBC-B
REFERENCED TYPES ARM3/N2 F Page 18
CONFIGURED TYPES ARM3/N1 F and ARM3/N2 F Page 19
NOTE: N1, N2 and N3 MEAN THE NUMBER OF SECONDARIESF MEANS THAT THERE IS NOT BASE PLATE
pag. 3/20
CURRENT TRANSFORMERS
PREFERABLY USE the equipment selected and marked as REFERENCED
RECOMMENDATIONS FOR THE USE OF THEFEASIBILITY AND COMPUTATION SUPPORTS
_______________
¶ CHECK NEEDS AND NECESSARY INFORMATIONACCURATELY
· USE EQUIPMENT MARKED AS REFERENCE
¸ CHECK READLY AVAILABLE FEASIBILITY SECTIONS DIRECTLY
TO APPLY KEYS TO FEASIBILITY TABLES CORRECTLY, PLEASE SEE ON PAGE 4
¹ USE ALSO ELONET TO CHECK FEASIBILITY
º CONSULT US IF FEASIBILITY RANGE IS NOT
AVAILABLE OR FOR OTHERS CHARACTERISTICS
pag. 4/20
KEYS TO THE VARIOUS TABLES TO DEFINE FEASIBILITY
1) Define Ipn rated primary currentUse primary values defined by standard (IEC):10, 12,5, 20, 25, 30, 40, 50, 60 and 75 A and their decimal multiples.
2) Define Ith rated short-time thermal current for 1 secondShort-circuit current usually lasts 1 second.Should this value be different (equal to a lenght "t"), calculate the following:
Ith (for 1 sec.) = Ith x √t
example: 25 kA for 3 sec. >> 25 x √3 = 43,3 kA for 1 sec.
3) Calculate coefficient "K"The above reperesents the key to the various tables
Ith for 1 sec.K = Ipn
example: Ipn = 100 A , Ith = 12,5 kA 1 sec. >> K = 12500 / 100 = 125
4) Finding position on the tableLocate column "K" and stop on the line corresponding to a value higher than K.
example: K calculate value = 125 >> ligne K = 150
5) Check feasibility A possible current transformer will feature the performances shown in the columns
identified by boxes :
For perotection secondary is true, only for choosing in the catalogue, the following formule:
VA x FL = constant
example: 10VA 5P10 ( VA x FL= 10 x 10= 100 ) >> 5VA 5P20 ( VA x FL= 5 x 20= 100 )
pag. 5/20
TECHNICAL NOTES
Diagrams of the terminals markings according to IEC standard.
SINGLE RATIO
P1 P2
S1 S2
P1 P2
1S1 1S2 2S1 2S2
P1 P2
1S1 1S2 2S1 2S2 3S1 3S2n da dn
CT with ONE CT with TWO CT with THREE SECONDARY WINDING SECONDARY WINDINGS SECONDARY WINDINGS
F WARNING !The secondary open winding of a CT is dangereus!The unused secondary windings of a CT must be short-circuited.
pag. 6/20
HBurden values are different for each of the two ratios
F WARNING !The secondary open winding of a CT is dangereus!The unused secondary windings of a CT must be short-circuited.
Current transformer with DOUBLE RATIO through primary coulping.types ARM3
Burden values are the same for both ratios.
SERIAL PRIMARY COUPLING
LOW RATIO
PARALLEL PRIMARY COUPLING
HIGH RATIO
Current transformer with DOUBLE RATIO through connection on secondary.types ARJP1, ARJP2, ARJP3
CT with ONE SECONDARY WINDING CT with TWO SECONDARY WINDINGS
S1-S2 LOW RATIO 1S1-1S2 2S1- 2S2 LOW RATIOS1-S3 HIGH RATIO 1S1-1S3 2S1- 2S3 HIGH RATIO
P1 C1 C2 P2
P1 C1 C2 P2
P1 P2
1S1 1S2 1S3 2S1 2S2 2S3
P1 P2
S1 S2 S3
pag. 7/20
For others characteristics see next page.
REFERENCED CURRENT TRANSFORMERS
Type ARJP1/N2 F
Panel type CRM - QMC
Dimensions Drawing n° H 103441
Characteristics Standard reference IEC 60044-1Rated highest voltage : 24 kVRated continous thermal current 1,2 x InFrequency 50 and 60 Hz
CTs type ARJP1/N2F Reference Ratio Short-time current 1st secondary 2nd secondary
number I th t(A/A) (kA) (s)
51238639F0 10/5-5 1,2 1 15 VA cl. 0,5 Fs<10 2,5 VA 5P20
51238640F0 20/5-5 2,4 1 15 VA cl. 0,5 Fs<10 2,5 VA 5P20
51238641F0 30/5-5 3,6 1 15 VA cl. 0,5 Fs<10 2,5 VA 5P20
51238643F0 50/5-5 6 1 15 VA cl. 0,5 Fs<10 2,5 VA 5P20
51238644F0 75/5-5 10 1 15 VA cl. 0,5 Fs<10 2,5 VA 5P20
51238645F0 100/5-5 10 1 15 VA cl. 0,5 Fs<10 2,5 VA 5P20
51238646F0 150/5-5 10 1 15 VA cl. 0,5 Fs<10 2,5 VA 5P20
51238647F0 200/5-5 10 1 15 VA cl. 0,5 Fs<10 2,5 VA 5P20
pag. 8/20
For others characteristics please contact us.
CONFIGURED CURRENT TRANSFORMER
Type ARJP1/N1 F - ARJP1/N2 FSingle Primary Ratio SR
Panels type CRM, DMV-A, DMV-D, IMC, QMC
Dimensions Drawing n° H 103441
Characteristics Standard reference IEC 60044-1Rated highest voltage : 7,2 - 12 - 17,5 - 24 KVRated continous thermal current 1,2 x InFrequency 50 or 60 HzRated secondary current standard 5 or 1 A.
Table of options:
N° of secondaries for CT 1 2STANDARD TYPE ARJP1/N1 F ARJP1/N2 F
1st measure secondary
Classe 0,5 Fs = 10VA
alternatively 5 7,5 10 15 20 20 30 30 30 30 30
"K" Ipn measure secondary protection secondary 2nd protection secondary
K=Ith/Ipn Rated primary Cl. 0,5 Fs=10 Cl. 5P Fl=10 Cl. 5P Fl=10 Ith max current [A] VA VA VA
25 kA for 1s SR 7,5 10 15 20 30 50 5 7,5 10 15 20 30 50 5 5 5 7,5 5 10 10 15 20 30 50
100 10 to 800
150 10 to 150
200 10 to 100
250 10 to 100
300 10 to 75
400 10 to 50
pag. 9/20
For others characteristics please contact us.
CONFIGURED CURRENT TRANSFORMER
Type ARJP1/N1 FDouble Primary Ratio DR
Panels type CRM, DMV-A, DMV-D, IMC, QMC
Dimensions Drawing n° H 103441
Characteristics Standard reference IEC 60044-1Rated highest voltage : 7,2 - 12 - 17,5 - 24 KVRated continous thermal current 1,2 x InFrequency 50 or 60 HzRated secondary current standard 5 or 1 A.Double primary ratio through connection to secondary.
Value “K=Ith/Ipn” must de fixed in comparison with the smaller rated primary current ratio .Values of outputs are gived for the smaller ratio, for the high ratio they are the double.
Table of options:N° o f secondar ies fo r CT
S T A N D A R D T Y P E
" K " I p n measure secondary
K=Ith/ Ipn Rated Class 0,5
pr imary Fs = 10
I th max current [A] VA
25 kA for 1s D R 7 ,5 10 15 2 0 3 0 5 0 5 7,5 1 0 1 5 2 0 30 50
100 10-20 to 400 -800
150 10-20 to 150 -300
200 10-20 to 100 -200
250 10-20 to 100 -200
300 10-20 to 75-150
400 10-20 to 50-100
alternatively
ARJP1 /N1 F1
protect ion secondaryClass 5P
F l = 1 0VA
pag. 11/20For others characteristics see next page.
Panels type DMV-A, DMV-D, IMC
CTs type ARJP2/N2F
Reference Ratio Short-time current 1st secondary 2nd secondarynumber I th t
(A/A) (kA) (s)
51238223F0 50 / 5-5 25 1 10VA cl.0,5 Fs10 2,5VA 5P20
REFERENCED CURRENT TRANSFORMERS
Type ARJP2/N2 F
Dimensions Drawing n° H 103442
Characteristics Standard reference IEC 60044-1Rated highest voltage : 24 kVRated continous thermal current 1,2 x InFrequency 50 and 60 Hz
Panel type CRM
CTs type ARJP2/N2F
Reference Ratio Short-time current 1st secondary 2nd secondarynumber I th t
(A/A) (kA) (s)
51238223F0 50 / 5-5 25 1 10VA cl.0,5 Fs10 2,5VA 5P20
51238224F0 100 / 5-5 25 1 15VA cl.0,5 Fs10 2,5VA 5P20
51238225F0 200 / 5-5 25 1 15VA cl.0,5 Fs10 5VA 5P20
51238226F0 400 / 5-5 25 1 15VA cl.0,5 Fs10 5VA 5P20
3730519 600 / 5-5 25 1 20VA cl.0,5 Fs<10 7,5VA 5P20
pag. 12/20
For others characteristics please contact us.
CONFIGURED CURRENT TRANSFORMER
Type ARJP2/N1 F - ARJP2/N2 F - ARJP2/N3 F Single Primary Ratio SR
Panels type CRM, DMV-A, DMV-D, IMC
Dimensions Drawing n° H 103442
Characteristics Standard reference IEC 60044-1Rated highest voltage : 7,2 - 12 - 17,5 - 24 KVRated continous thermal current 1,2 x InFrequency 50 or 60 HzRated secondary current standard 5 or 1 A.
Table of options:
n° of secondaries for CT 1 2 3STANDARD TYPE ARJP2/N1 F ARJP2/N2 F ARJP2/N3 F
1st measure sec.Class 0,5Fs = 10
VA
5 10 15 20 30
1st measure secondary 2nd protection sec.Class 0,5 Class 5PFs = 10 Fl = 10
VA VA
alternatively 5 7,5 10 15 20 20 30 30 30 30 30 5 5 7,5 10 15
"K" Ipn measure secondary protection secondary 2nd protection secondary 3rd protection sec.
K=Ith/Ipn Rated Class 0,5 Class 5P Class 5P Class 5P
primary Fs = 10 Fl = 10 FI = 10 Fl = 15
Ith max current [A] VA VA VA VA
25 kA for 1sec. SR 7,5 10 15 20 30 50 5 7,5 10 15 20 30 50 5 5 5 7,5 5 10 10 15 20 30 50 5 5 7,5 10 15
100 10 to 800
150 10 to 300200 10 to 250
250 10 to 200
300 10 to 150
400 10 to 100500 10 to 100
Switch to smaller type ARJP1
pag. 13/20For others characteristics please contact us.
CONFIGURED CURRENT TRANSFORMER
Type ARJP2/N1 F - ARJP2/N2 F Double Primary Ratio DR
Panels type CRM, DMV-A, DMV-D, IMC
Dimensions Drawing n° H 103442
Characteristics Standard reference IEC 60044-1Rated highest voltage : 7,2 - 12 - 17,5 - 24 KVRated continous thermal current 1,2 x InFrequency 50 or 60 HzRated secondary current standard 5 or 1 A.Double primary ratio through connection to secondary.
Value “K=Ith/Ipn” must de fixed in comparison with the smaller rated primary current ratio .Values of outputs are gived for the smaller ratio, for the high ratio they are the double.
Table of options:
N ° o f s e c o n d a r i e s f o r C T 1 2S T A N D A R D T Y P E A R J P 2 / N 1 F A R J P 2 / N 2 F
1 s t m e a s u r e s e c o n d a r y
C l . 0 , 5 F s = 1 0V A
al ternat ive ly 5 7 ,5 1 0 1 5 2 0 2 0 3 0 3 0 3 0 3 0 3 0" K " I p n m e a s u r e s e c o n d a r y p r o t e c t i o n s e c o n d a r y 2 n d p r o t e c t i o n s e c o n d a r y
K= I th / Ipn R a t e d p r i m a r y C l . 0 , 5 F s = 1 0 C l . 5 P F l = 1 0 C l . 5 P F l = 1 0 I t h m a x c u r r e n t [ A ] V A VA V A
2 5 k A f o r 1 s D R 7,5 1 0 1 5 2 0 3 0 5 0 5 7,5 1 0 1 5 2 0 3 0 5 0 5 5 5 7 ,5 5 1 0 1 0 1 5 2 0 3 0 5 0
1 0 0 1 0 - 2 0 t o 4 0 0 - 8 0 0
1 5 0 1 0 - 2 0 t o 1 5 0 - 3 0 0
2 0 0 1 0 - 2 0 t o 1 0 0 - 2 0 0
2 5 0 1 0 - 2 0 t o 1 0 0 - 2 0 0
3 0 0 1 0 - 2 0 t o 7 5 - 1 5 0
4 0 0 1 0 - 2 0 t o 5 0 - 1 0 0
5 0 0 1 0 - 2 0 t o 5 0 - 1 0 0
S w i t c h t o t h e s m a l l e r t y p e A R J P 1
pag. 15/20For others characteristics see next page.
REFERENCED CURRENT TRANSFORMERS
Type ARJP3/N2 F
Panels type DM1-A 1250A, DM1-D 1250A, DM1-W 1250A, DM1-Z 1250A,GBC-A 1250A, GBC-B 1250A, DMV-A 1250A, DMV-D 1250A
Dimensions Drawing n° H 103443
Characteristics Standard reference IEC 60044-1Rated highest voltage : 24 kVRated continous thermal current 1,2 x InFrequency 50 and 60 Hz
CTs type ARJP3/N2F
Reference Ratio Short-time current 1st secondary 2nd secondarynumber I th t
(A/A) (kA) (s)
3730521 1000 / 5-5 25 1 30 VA cl. 0,5 Fs<10 10 VA 5P20
3730522 1250 / 5-5 25 1 30 VA cl. 0,5 Fs<10 10 VA 5P20
3730525 1000 / 1-1 25 1 30 VA cl. 0,5 Fs<10 10 VA 5P20
3730526 1250 / 1-1 25 1 30 VA cl. 0,5 Fs<10 10 VA 5P20
pag. 16/20
CONFIGURED CURRENT TRANSFORMER
Type ARJP3/N1 F - ARJP3/N2 F - ARJP3/N3 FSingle and Double Primary Ratio
Panels type DM1-A 1250A, DM1-D 1250A, DM1-W 1250A, DM1-Z 1250A,GBC-A 1250A, GBC-B 1250A, DMV-A 1250A, DMV-D 1250A
Dimensions Drawing n° H 103443
Characteristics Standard reference IEC 60044-1Rated highest voltage : 7,2 - 12 - 17,5 - 24 KVRated continous thermal current 1,2 x InFrequency 50 or 60 HzRated secondary current standard 5 or 1 A.Double primary ratio through connection to secondary.
Values of outputs are gived for the smaller ratio, for the high ratio they are the double.
Table of options:
For others characteristics please contact us.
N° of secondaries for CT 1 2 3STANDARD TYPE ARJP3/N1 F ARJP3/N2 F ARJP3/N3 F
1st measure sec.Cl. 0,5 Fs=10
VA
5 10 15 20 30
1st measure secondary 2nd protection sec.Class 0,5 Cl. 5P Fl=10
VA VA
alternatively 5 7,5 10 15 20 20 30 30 30 30 30 5 5 7,5 10 15
Ipn measure secondary protection secondary 2nd protection secondary 3rd protection sec.
Rated primary Cl. 0,5 Fs=10 Cl. 5P Fl=10 Cl. 5P Fl=10 Cl. 5P Fl=15
current [A] VA VA VA VA
SR DR 7,5 10 15 20 30 50 5 7,5 10 15 20 30 50 5 5 5 7,5 5 10 10 15 20 30 50 5 5 7,5 10 15
750
800
1000
1200
1250
400-800
500-1000
600-1200
pag. 18/20For others characteristics see next page.
CTs type ARM3/N2F Reference Ratio Short-time current 1st secondary 2nd secondary
number I th t
(A/A) (kA) (s)
51303122F0 40-20 / 5-1 12,5 0,8 7,5VA 0,5s Fs<10 1VA 10P30
51303123F0 100-50 / 5-1 12,5 0,8 7,5VA 0,5s Fs<10 1VA 10P30
51303124F0 200-100 / 5-1 12,5 1 7,5VA 0,5s Fs<10 1VA 10P30
51303125F0 400-200 / 5-1 12,5 1 7,5VA 0,5s Fs<10 1VA 10P30
3731090 10-20 / 5-5 5 1 7,5 VA cl. 0,5 Fs<10 5 VA 5P10
3731092 15-30 / 5-5 8 1 7,5 VA cl. 0,5 Fs<10 5 VA 5P10
3731094 20-40 / 5-5 12,5 0,8 7,5 VA cl. 0,5 Fs<10 5 VA 5P10
3731096 25-50 / 5-5 12,5 1 7,5 VA cl. 0,5 Fs<10 5 VA 5P10
3731097 25-50 / 5-5 12,5 0,8 7,5 VA cl. 0,5 Fs<10 5 VA 5P10
3731098 50-100 / 5-5 21 1 7,5 VA cl. 0,5 Fs<10 5 VA 5P15
3731099 50-100 / 5-5 14,5 1 30 VA cl. 0,5 Fs<10 5 VA 5P15 - 7,5 VA 5P10
3731100 75-150 / 5-5 25 1 7,5 VA cl. 0,5 Fs<10 5 VA 5P15
3731101 75-150 / 5-5 16 1 30 VA cl. 0,5 Fs<10 5 VA 5P15 - 7,5 VA 5P10
25 120 2
3731103 100-200 / 5-5 16 1 30 VA cl. 0,5 Fs<10 7,5 VA 5P15 - 15 VA 5P10
25 120 2
3731105 200-400 / 5-5 25 1 30 VA cl. 0,5 Fs<10 7,5 VA 5P15 - 15 VA 5P10
25 120 2
3730426 300-600 / 5-5 25 1 30 VA cl. 0,5 Fs<10 7,5 VA 5P15 - 15 VA 5P10
3731708 300-600 / 5-5 7,5 VA cl. 0,5 Fs<10 5 VA 5P15
3731104 200-400 / 5-5 7,5 VA cl. 0,5 Fs<10 5 VA 5P15
3731102 100-200 / 5-5 7,5 VA cl. 0,5 Fs<10 5 VA 5P15
REFERENCED CURRENT TRANSFORMERS
Type ARM3/N2 F
Panel type DM1-A, DM1-D, DM1-W, DM2, GBC-A, GBC-B
Dimensions Drawing n° H 103005
Characteristics Standard reference IEC 60044-1Rated highest voltage : 24 kVRated continous thermal current 1,2 x InFrequency 50 and 60 HzDouble primary ratio through primary coupling.
pag. 19/20
For others characteristics please contact us.
CONFIGURED CURRENT TRANSFORMER
Type ARM3/N1 F - ARM3/N2 FSingle and Double Primary Ratio
Panels type DM1-A, DM1-D, DM1-W, DM2, GBC-A, GBC-B
Dimensions Drawing n° H 103005
Characteristics Standard reference IEC 60044-1Rated highest voltage : 7,2 - 12 - 17,5 - 24 KVRated continous thermal current 1,2 x InFrequency 50 or 60 HzRated secondary current standard 5 or 1 ADouble primary ratio through primary coupling.
Value “K=Ith/Ipn” must de fixed in comparison with the smaller rated primary current ratio .
Table of options:
N° of secondaries for CT 1 2STANDARD TYPE ARM3/N1 F ARM3/N2 F
1st measure secondary
Cl 0,5 Fs=10VA
alternatively 5 7,5 10 15 20 20 30 30 30 30 30"K" Ipn measure secondary protection secondary 2nd protection secondary
K=Ith/Ipn Rated primary Cl 0,5 Fs=10 Cl 5P Fl=10 Cl 5P Fl=10
Ith max current [A] VA VA VA
25 kA for 1s SR DR 7,5 10 15 20 30 50 5 7,5 10 15 20 30 50 5 5 5 7,5 5 10 10 15 20 30 50
100 10 to 800 10-20 to 400-800
150 10 to 300 10-20 to 300-600
200 10 to 300 10-20 to 300-600
250 10 to 200 10-20 to 200-400
300 10 to 150 10-20 to 150-300
400 10 to 100 10-20 to 100-200
500 10 to 50 10-20 to 100-200