SM
PANDUIT Advisory Services
FlexPod Site ReadinessAssessment Services
SM
Service Value Proposition
FlexPod site readiness assessment services
verify that all required Layer 1 Physical
Infrastructure items are in-place, properly
installed, and correctly configured to ensure a
smooth, efficient, and successful FlexPod
deployment and operation.
PANDUIT Advisory Services
2
SM
Service overview• Assess seven (7) key aspects of the
data center physical infrastructure• Power• Thermal / Cooling• Network Connectivity• Pathways• Space• Floor loading• Telecommunications Bonding
• Determine if each area is “ready to receive” a FlexPod – “Yes” or “No”
• For “No” areas, determine “level of fix” required and recommend improvement actions
• Provide written “Site Readiness” report
PANDUIT Advisory Services
3
What we do…
SM
Service overview
PANDUIT Advisory Services
4
Areas assessed…
Item Question answered
Power Is the data center providing the proper power feeds for the FlexPod – Voltage, current rating, phase, frequency, plug style, agency approval?
Cooling Do proper airflow, cabinet arrangement, aisle widths, and temperature conditions exist for the FlexPod?
Data Communications Are the required data cables – quantity, type, media, connector style, uplink ports, communications protocol – in place for the FlexPod ?
Pathways Are suitable under floor or overhead pathways present to accommodate all data and power cables going to / coming from the FlexPod?
Space Will FlexPod fit in the space provided?
Floor loading Will the raised floor support the weight of the FlexPod?
Telecommunications Bonding
Is a proper room-level telecommunications bonding & grounding system installed with available hook-ups for the FlexPod?
SM
FlexPod site readiness - Power
• Assess 17 detailed aspects needed to properly power the desired FlexPod
• Specific to each FlexPod model• Unique to each site’s FlexPod
configuration
• Ensure proper equipment, POU, and room power configuration:
• Voltage• Amperage (current)• Frequency• Single vs. 3-Phase• Delta vs. Wye topology • POU feeder plug style
• Determine if each item is 100% ready to power the FlexPod – if not, advise on needed upgrades or modifications
PANDUIT Advisory Services
5
What we do…
A
B
1
2
LNK LNKIOM6
IOM6
LNK LNKIOM6
IOM6
DC AC
x22
DC AC
x22
A
B
1
2
LNK LNKIOM6
IOM6
LNK LNKIOM6
IOM6
DC AC
x22
DC AC
x22
1
5
10
15
20
25
30
35
40
2
3
4
6
7
8
9
11
12
13
14
16
17
18
19
21
22
23
24
26
27
28
29
31
32
33
34
36
37
38
39
41
42
1
5
10
15
20
25
30
35
40
2
3
4
6
7
8
9
11
12
13
14
16
17
18
19
21
22
23
24
26
27
28
29
31
32
33
34
36
37
38
39
41
42
FAN STATUS
FAN STATUS
FAN STATUS
FAN STATUS
FAN STATUS
FAN STATUS
FAN STATUS
FAN STATUS
CHS A56
FAN 1 FAN 5 FAN 2 FAN 6 FAN 3 FAN 7 FAN 4 FAN 8
!
FAN STATUS
FAN STATUS
FAN STATUS
FAN STATUS
FAN STATUS
FAN STATUS
FAN STATUS
FAN STATUS
CHS A56
FAN 1 FAN 5 FAN 2 FAN 6 FAN 3 FAN 7 FAN 4 FAN 8
!
4
3
2
1
UCS 2104XP
4
3
2
1
UCS 2104XP
4
3
2
1
UCS 2104XP
4
3
2
1
UCS 2104XP
CONSOLE
Cisco UCS 6120XP
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20L1 L2 MGMT0 MGMT1
1 2 3 4 1 2 3 4
1 /2/4 G F IB R E C H A N N E L
N10-E0440
SLO
T2
PS2 PS1
CONSOLE
Cisco UCS 6120XP
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20L1 L2 MGMT0 MGMT1
1 2 3 4 1 2 3 4
1 /2/4 G F IB R E C H A N N E L
N10-E0440
SLO
T2
PS2 PS1
3
CISCO NEXUS N5548P 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
STAT
ID
3
CISCO NEXUS N5548P 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
STAT
ID
1 2 3 4 5 6
25 26 27 28 29 30
7 8 9 10 11 12
31 32 33 34 35 36
13 14 15 16 17 18
37 38 39 40 41 42
19 20 21 22 23 24
43 44 45 46 47 48
1
5
10
15
20
25
30
35
40
2
3
4
6
7
8
9
11
12
13
14
16
17
18
19
21
22
23
24
26
27
28
29
31
32
33
34
36
37
38
39
41
42
1
5
10
15
20
25
30
35
40
2
3
4
6
7
8
9
11
12
13
14
16
17
18
19
21
22
23
24
26
27
28
29
31
32
33
34
36
37
38
39
41
42
Front Elevation
Rear Elevation
FAN STATUS
FAN STATUS
FAN STATUS
FAN STATUS
FAN STATUS
FAN STATUS
FAN STATUS
FAN STATUS
CHS A56
FAN 1 FAN 5 FAN 2 FAN 6 FAN 3 FAN 7 FAN 4 FAN 8
!
SLOT
1
SLOT
5
SLOT
3
SLOT7
SLOT
2
SLOT6
SLOT
4
SLOT
8
!
UCS 5108
OK FAIL OK FAIL OK FAIL OK FAIL
4
3
2
1
UCS 2104XP
4
3
2
1
UCS 2104XP
! ResetConsole
! !UCS B200 M1
PS1
PS2
FAN STAT FA
N1FA
N2
FAN STAT
STAT
OK
FAIL
N10-PAC1-550W
OK
FAIL
N10-PAC1-550W
PS1
PS2
FAN STAT FA
N1FA
N2
FAN STAT
STAT
OK
FAIL
N10-PAC1-550W
OK
FAIL
N10-PAC1-550W
! ResetConsole
! !UCS B200 M1
! Reset Console
UCS B230 M1
!2!1
A03-D0100 SSD -LH 100 GB SSD SATA>> A03-D0100 SSD -LH 100 GB SSD SATA>>! ResetConsole
! !UCS B250 M1
! ResetConsole
! !UCS B250 M1
! ResetConsole
! !UCS B250 M1
SLOT
1
SLOT
5
SLOT
3
SLOT7
SLOT
2
SLOT6
SLOT
4
SLOT
8
!
UCS 5108
OK FAIL OK FAIL OK FAIL OK FAIL
! ResetConsole
! !UCS B200 M1
! ResetConsole
! !UCS B200 M1
! Reset Console
UCS B230 M1
!2!1
A03-D0100 SSD -LH 100 GB SSD SATA>> A03-D0100 SSD -LH 100 GB SSD SATA>>! ResetConsole
! !UCS B250 M1
! ResetConsole
! !UCS B250 M1
! ResetConsole
! !UCS B250 M1
SLOT
1
SLOT
5
SLOT
3
SLOT7
SLOT
2
SLOT6
SLOT
4
SLOT
8
!
UCS 5108
OK FAIL OK FAIL OK FAIL OK FAIL
! ResetConsole
! !UCS B200 M1
! ResetConsole
! !UCS B200 M1
! Reset Console
UCS B230 M1
!2!1
A03-D0100 SSD -LH 100 GB SSD SATA>> A03-D0100 SSD -LH 100 GB SSD SATA>>! ResetConsole
! !UCS B250 M1
! ResetConsole
! !UCS B250 M1
! ResetConsole
! !UCS B250 M1
0a 0bLNK LNK
0c
0d e0b
e0a
c0b
c0a1
2
0a 0bLNK LNK
0c
0d e0b
e0a
c0b
c0a1
2
FAS3210FAS3210
A
B
1
2
LNK LNKIOM6
IOM6
LNK LNKIOM6
IOM6
DC AC
x22
DC AC
x22
A
B
1
2
LNK LNKIOM6
IOM6
LNK LNKIOM6
IOM6
DC AC
x22
DC AC
x22
A
B
1
2
LNK LNKIOM6
IOM6
LNK LNKIOM6
IOM6
DC AC
x22
DC AC
x22
4 5 6 70 1 2 3 12 13 14 158 9 10 11 20 21 22 2316 17 18 19
DS2246
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
4 5 6 70 1 2 3
12 13 14 158 9 10 11
20 21 22 2316 17 18 19
DS2246
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
4 5 6 70 1 2 3 12 13 14 158 9 10 11 20 21 22 2316 17 18 19
DS2246
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
FAN STAT
FAN STAT FAN1
FAN2
PS1
PS2
FAIL
OK
FAIL
OK
CONSOLEL2
MGMT0L1
STAT
ID
FAN STAT
FAN STAT FAN1
FAN2
PS1
PS2
FAIL
OK
FAIL
OK
CONSOLEL2
MGMT0L1
STAT
ID
Cable Pass-through
M
ï¡ ï¡ ï
1 /M 2
! ! ! !
PSU MEM CPU !Console Reset
UCS C200 M1
M
ï¡ ï¡ ï
1 /M 2
! ! ! !
PSU MEM CPU !Console Reset
UCS C200 M1
A
B
1
2
LNK LNKIOM6
IOM6
LNK LNKIOM6
IOM6
DC AC
x22
DC AC
x22
4 5 6 70 1 2 3 12 13 14 158 9 10 11 20 21 22 2316 17 18 19
DS2246
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
600GB
SM
FlexPod site readiness - Cooling
PANDUIT Advisory Services
6
What we do…• Measure 41 inter-related parameters to
ensure proper thermal performance for the FlexPod
• Overall layout and room conditions• Raised floor air handling capabilities• Overhead air return performance• Room-level or in-row cooling unit capacities and
operating conditions• Recirculation or by-pass air issues
• Target specific air temperature ranges, air flow speeds, and air volume numbers
• Particular to each FlexPod model• Dependent on each site and FlexPod
configuration
• Verify that the data center can properly cool the FlexPod or if there will be thermal issues that require additional attention
SM
FlexPod site readiness – Networking
• Confirm that the proper data communications links are available and ready to connect to the FlexPod
• Production data connections• Management port channels• Topology and redundancy• Data cabling type, grade, and connector style• Cable routing and pathways• 36 point detailed assessment
• Get specific regarding port availability and channel counts
• Precise requirements for each FlexPod model, and individual configuration
• Detail needed improvements or additions
• Action plan for required modifications• Data communications upgrade kits available
PANDUIT Advisory Services
7
What we do…
SM
Engagement Fee
PANDUIT Advisory Services
8
FlexPod models Site Readiness Assessment Fee Panduit P/N Includes
Custom FlexPod
1 Cab Flexpod Assessment$ 3,776
2 Cab FlexpodAssessment$ 4,602
GSDCAFLXPA
• Pre-visit coordination• On-site Assessment• Travel time to and
from site• All travel expenses• Readiness Report
generation• Site improvement
action plan• Review with Partner
and End User
SM
Next Steps Discussion