Section 1 : Basic knowledge

Section 2 : Application layer

Section 3 : Link layer

Section 4 : Physical layer

Page 3: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 3

QUIZ: Section 1 : Basic knowledge - Question 1QUIZ: Section 1 : Basic knowledge - Question 1

The CAN protocol was created on the initiative of automation product manufacturers.

TRUE

FALSE

Page 4: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 4

QUIZ: Section 1 : Basic knowledge - Question 2QUIZ: Section 1 : Basic knowledge - Question 2

CAL = CAN Application Layer ensures interoperability between products manufactured by different manufacturers.

TRUE

FALSE

Page 5: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 5

QUIZ: Section 1 : Basic knowledge - Question 3QUIZ: Section 1 : Basic knowledge - Question 3

Who developed the CANopen application layer?

The German equipment manufacturer BOSCH

The CiA association = CAN in Automation

The Allen Bradley company

Page 6: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 6

QUIZ: Section 1 : Basic knowledge - Question 4QUIZ: Section 1 : Basic knowledge - Question 4

The maximum length of a CANopen bus depends on the transmission speed.

TRUE

FALSE

Page 7: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 7

QUIZ: Section 1 : Basic knowledge - Question 5QUIZ: Section 1 : Basic knowledge - Question 5

What is the maximum number of devices that can be connected on a CANopen bus?

31

64

128

255

Page 8: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 8

QUIZ: Section 1 : Basic knowledge - Question 6QUIZ: Section 1 : Basic knowledge - Question 6

Which network access method does CANopen use?

Master - slave system

CSMA/CD (destructive collision)

CSMA/CA (non-destructive collision)

Page 9: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 9

QUIZ: Section 1 : Basic knowledge - Question 7QUIZ: Section 1 : Basic knowledge - Question 7

CANopen can transmit data with better safety and reliability.

TRUE

FALSE

Page 10: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 10

QUIZ: Section 1 : Basic knowledge - Question 8QUIZ: Section 1 : Basic knowledge - Question 8

Which service is used to send parameter-setting data (larger than 8 bytes)?

PDO

SDO

SFO

Page 11: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 11

QUIZ: Section 1 : Basic knowledge - Question 9QUIZ: Section 1 : Basic knowledge - Question 9

Which service is used to send process data (smaller than 8 bytes) quickly?

PDO

SDO

SFO

Page 12: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 12

QUIZ: Section 1 : Basic knowledge - Question 10QUIZ: Section 1 : Basic knowledge - Question 10

Which service is used to manage synchronizations, time-based references, fatal errors?

PDO

SDO

SFO

Page 13: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 13

QUIZ: Section 1 : Basic knowledge - Answer 1QUIZ: Section 1 : Basic knowledge - Answer 1

The CAN protocol was created on the initiative of automation product manufacturers.

FALSE

The automotive industry was behind the development of CAN in response to a need for communication between several on-board electronic subassemblies.

Page 14: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 14

QUIZ: Section 1 : Basic knowledge - Answer 2QUIZ: Section 1 : Basic knowledge - Answer 2

CAL = CAN Application Layer ensures interoperability between products manufactured by different manufacturers.

FALSE

CAL provides tools which can be used to develop a CAN application, and CANopen profiles ensure product interoperability.

Page 15: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 15

QUIZ: Section 1 : Basic knowledge - Answer 3QUIZ: Section 1 : Basic knowledge - Answer 3

Who developed the CANopen application layer?

The CiA association = CAN in Automation

Page 16: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 16

QUIZ: Section 1 : Basic knowledge - Answer 4QUIZ: Section 1 : Basic knowledge - Answer 4

The maximum length of a CANopen bus depends on the transmission speed.

TRUE

From 25 metres at 1Mbps to 1000 metres at 10 Kbps.

Page 17: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 17

QUIZ: Section 1 : Basic knowledge - Answer 5QUIZ: Section 1 : Basic knowledge - Answer 5

What is the maximum number of devices that can be connected on a CANopen bus?

128 devices1 master and 127 slaves

Page 18: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 18

QUIZ: Section 1 : Basic knowledge - Answer 6QUIZ: Section 1 : Basic knowledge - Answer 6

Which network access method does CANopen use?

CSMA/CA

Non-destructive collision

Page 19: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 19

QUIZ: Section 1 : Basic knowledge - Answer 7QUIZ: Section 1 : Basic knowledge - Answer 7

CANopen can transmit data with better safety and reliability.

TRUE

It is one of the safest and most reliable industrial local area networks.

Page 20: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 20

QUIZ: Section 1 : Basic knowledge - Answer 8QUIZ: Section 1 : Basic knowledge - Answer 8

Which service is used to send parameter-setting data (larger than 8 bytes)?

The SDO Service Data Object service

which is used to segment data larger than 8 bytes on the basis of a client-server model.

Page 21: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 21

QUIZ: Section 1 : Basic knowledge - Answer 9QUIZ: Section 1 : Basic knowledge - Answer 9

Which service is used to send process data (smaller than 8 bytes) quickly?

The PDO Process Data Object service

which operates on the basis of the producer-consumer model.

Page 22: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 22

QUIZ: Section 1 : Basic knowledge - Answer 10QUIZ: Section 1 : Basic knowledge - Answer 10

Which service is used to manage synchronizations, time-based references, fatal errors?

The SFO Special Function Object service

Page 23: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 23

QUIZ: Section 2 : Application layer - Question 1QUIZ: Section 2 : Application layer - Question 1

CAL is the name of the CANopen application layer.

TRUE

FALSE

Page 24: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 24

QUIZ: Section 2 : Application layer - Question 2QUIZ: Section 2 : Application layer - Question 2

CMS, NMT, LMT and DBT are services belonging to the CANopen profiles.

TRUE

FALSE

Page 25: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 25

QUIZ: Section 2 : Application layer - Question 3QUIZ: Section 2 : Application layer - Question 3

Which identifier has the highest priority?

COB-ID =220

COB-ID =2031

COB-ID =1150

COB-ID =0

Page 26: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 26

QUIZ: Section 2 : Application layer - Question 4QUIZ: Section 2 : Application layer - Question 4

COB-ID is used to point at an address in a product’s object dictionary.

TRUE

FALSE

Page 27: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 27

QUIZ: Section 2 : Application layer - Question 5QUIZ: Section 2 : Application layer - Question 5

What is the EDS file?

A user manual

An ordered ASCII file which describes the device

The electrical characteristics of a device

Page 28: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 28

QUIZ: Section 2 : Application layer - Question 6QUIZ: Section 2 : Application layer - Question 6

Which service is used to set the device parameters?

NMT

SDO

PDO

SYNC

Page 29: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 29

QUIZ: Section 2 : Application layer - Question 7QUIZ: Section 2 : Application layer - Question 7

PDOs = Process Data Objects operate on the producer consumer model.

TRUE

FALSE

Page 30: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 30

QUIZ: Section 2 : Application layer - Question 8QUIZ: Section 2 : Application layer - Question 8

SDOs = Service Data Objects operate on the Client Server model and need 2 COB-IDs.

TRUE

FALSE

Page 31: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 31

QUIZ: Section 2 : Application layer - Question 9QUIZ: Section 2 : Application layer - Question 9

PDOs = Process Data Objects are used to transport more than 8 bytes.

TRUE

FALSE

Page 32: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 32

QUIZ: Section 2 : Application layer - Question 10QUIZ: Section 2 : Application layer - Question 10

What is the SYNC object used for?

Monitoring the network

Providing a time reference

Synchronizing a process

Page 33: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 33

QUIZ: Section 2 : Application layer - Question 11QUIZ: Section 2 : Application layer - Question 11

What is Life guarding?

The communication monitoring system at the master end

The communication monitoring system at the slave end

Page 34: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 34

QUIZ: Section 2 : Application layer - Question 12QUIZ: Section 2 : Application layer - Question 12

CANopen offers a system for allocating default identifiers.

TRUE

FALSE

Page 35: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 35

QUIZ: Section 2 : Application layer - Answer 1QUIZ: Section 2 : Application layer - Answer 1

CAL is the name of the CANopen application layer.

FALSE

CAL defines a certain number of tools without giving their instructions for use.

The CANopen application is made up of CAL and also CANopen profiles defined by the CiA.

Page 36: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 36

QUIZ: Section 2 : Application layer - Answer 2QUIZ: Section 2 : Application layer - Answer 2

CMS, NMT, LMT and DBT are services belonging to the CANopen profiles.

FALSE

CMS, NMT, LMT, and DBT are services offered by CAL.

Page 37: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 37

QUIZ: Section 2 : Application layer - Answer 3QUIZ: Section 2 : Application layer - Answer 3

Which identifier has the highest priority?

COB-ID = 0

The identifier with the highest priority is the one with the lowest value.

Page 38: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 38

QUIZ: Section 2 : Application layer - Answer 4QUIZ: Section 2 : Application layer - Answer 4

COB-ID is used to point at an address in a product’s object dictionary.

FALSEThe COB-ID corresponds to a communication object or message carried at the beginning of the frame. An index coded on 16 bits is used to point to the object dictionary, followed if necessary by a sub-index coded on 8 bits.

Page 39: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 39

QUIZ: Section 2 : Application layer - Answer 5QUIZ: Section 2 : Application layer - Answer 5

What is the EDS file?

An ordered ASCII file which describes the device

Page 40: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 40

QUIZ: Section 2 : Application layer - Answer 6QUIZ: Section 2 : Application layer - Answer 6

Which service is used to set the device parameters?

SDO objects = Service Data Objects

Page 41: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 41

QUIZ: Section 2 : Application layer - Answer 7QUIZ: Section 2 : Application layer - Answer 7

PDOs = Process Data Objects operate on the producer consumer model.

TRUE

Page 42: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 42

QUIZ: Section 2 : Application layer - Answer 8QUIZ: Section 2 : Application layer - Answer 8

SDOs = Service Data Objects operate on the Client Server model and need 2 COB-IDs.

TRUE

Page 43: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 43

QUIZ: Section 2 : Application layer - Answer 9QUIZ: Section 2 : Application layer - Answer 9

PDOs = Process Data Objects are used to transport more than 8 bytes

FALSE8 bytes maximum. SDO objects are used to transmit

more than 8 bytes

Page 44: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 44

QUIZ: Section 2 : Application layer - Answer 10QUIZ: Section 2 : Application layer - Answer 10

What is the SYNC object used for?

Synchronizing a process

Page 45: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 45

QUIZ: Section 2 : Application layer - Answer 11QUIZ: Section 2 : Application layer - Answer 11

What is Life guarding?

The communication monitoring system at the slave end

Page 46: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 46

QUIZ: Section 2 : Application layer - Answer 12QUIZ: Section 2 : Application layer - Answer 12

CANopen offers a system for allocating default identifiers.

TRUEThis system is used to simplify system configuration.

Page 47: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 47

QUIZ: Section 3 : Link layer - Question 1QUIZ: Section 3 : Link layer - Question 1

How large is the identifier field of a CAN 2.0.A standard format frame?

8 bits

11 bits

16 bits

29 bits

Page 48: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 48

QUIZ: Section 3 : Link layer - Question 2QUIZ: Section 3 : Link layer - Question 2

Which of these fields is used to differentiate a Data Frame from a Remote Frame?

The identifier

The RTR

The CTR

The data

Page 49: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 49

QUIZ: Section 3 : Link layer - Question 3QUIZ: Section 3 : Link layer - Question 3

Which mechanism is used to check the structure of a CAN frame?

The CRC

The ACK slot

The delimiters

The stuffing bit

Page 50: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 50

QUIZ: Section 3 : Link layer - Question 4QUIZ: Section 3 : Link layer - Question 4

The error counters on each station are incremented by one unit for each communication error detected.

TRUE

FALSE

Page 51: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 51

QUIZ: Section 3 : Link layer - Question 5QUIZ: Section 3 : Link layer - Question 5

When a node detects a communication error, it systematically sends an Error Frame with an ACTIVE ERROR FLAG field.

TRUE

FALSE

Page 52: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 52

QUIZ: Section 3 : Link layer - Question 6QUIZ: Section 3 : Link layer - Question 6

A node is permanently disconnected from the network when its TEC counter reaches the value 255.

TRUE

FALSE

Page 53: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 53

QUIZ: Section 3 : Link layer - Answer 1QUIZ: Section 3 : Link layer - Answer 1

How large is the identifier field of a CAN 2.0.A standard format frame?

11 bits

Page 54: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 54

QUIZ: Section 3 : Link layer - Answer 2QUIZ: Section 3 : Link layer - Answer 2

Which of these fields is used to differentiate a Data Frame from a Remote Frame?

The RTRThe value of the RTR is dominant for a Data Frame and recessive for a Remote Frame. If a request frame is repeated, the response to this request therefore takes priority.

Page 55: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 55

QUIZ: Section 3 : Link layer - Answer 3QUIZ: Section 3 : Link layer - Answer 3

Which mechanism is used to check the structure of a CAN frame?

The delimitersCRC Delimiter, ACK Delimiter, End of Frame, Error Delimiter, and Overload Delimiter are integrated in the frames so that the structure can be checked.

Page 56: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 56

QUIZ: Section 3 : Link layer - Answer 4QUIZ: Section 3 : Link layer - Answer 4

The error counters on each station are incremented by one unit for each communication error detected.

FALSEThese counters are incremented and decremented using a sophisticated weighting mechanism etched in the silicon.

Page 57: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 57

QUIZ: Section 3 : Link layer - Answer 5QUIZ: Section 3 : Link layer - Answer 5

When a node detects a communication error, it systematically sends an Error Frame with an ACTIVE ERROR FLAG field.

FALSEThe reaction of the node depends on its status: Active errors, Passive errors or bus OFF.

Page 58: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 58

QUIZ: Section 3 : Link layer - Answer 6QUIZ: Section 3 : Link layer - Answer 6

A node is permanently disconnected from the network when its TEC counter reaches the value 255.

FALSEThe node is disconnected and monitors the bus. If 128 occurrences of 11 consecutive recessive bits are detected (frames without errors), the node reverts to Active Error mode.

Page 59: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 59

QUIZ: Section 4 : Physical layer - Question 1QUIZ: Section 4 : Physical layer - Question 1

What is the maximum length of a CANopen bus at 1 Mbps?

25 metres

40 metres

60 metres

100 metres

Page 60: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 60

QUIZ: Section 4 : Physical layer - Question 2QUIZ: Section 4 : Physical layer - Question 2

On CANopen, the cable cross-section is selected according to the number of slaves and the length of the bus.

TRUE

FALSE

Page 61: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 61

QUIZ: Section 4 : Physical layer - Question 3QUIZ: Section 4 : Physical layer - Question 3

On CANopen, there is free choice of network topology.

TRUE

FALSE

Page 62: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 62

QUIZ: Section 4 : Physical layer - Question 4QUIZ: Section 4 : Physical layer - Question 4

CANopen products can have different connections.

TRUE

FALSE

Page 63: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 63

QUIZ: Section 4 : Physical layer - Answer 1QUIZ: Section 4 : Physical layer - Answer 1

What is the maximum length of a CANopen bus at 1 Mbps?

25 metres

Page 64: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 64

QUIZ: Section 4 : Physical layer - Answer 2QUIZ: Section 4 : Physical layer - Answer 2

On CANopen, the cable cross-section is selected according to the number of slaves and the length of the bus.

TRUE

Page 65: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 65

QUIZ: Section 4 : Physical layer - Answer 3QUIZ: Section 4 : Physical layer - Answer 3

On CANopen, there is free choice of network topology.

FALSE

The topology should be bus type with the shortest possible tap links.

Page 66: Slide 1 Industrial Automation - Customer View - Training PhW - CANopen_en 02/ 2002 CANopen QUIZ CANopen QUIZ

Industrial Automation - Customer View - TrainingPhW - CANopen_en 02/ 2002

Slide 66

QUIZ: Section 4 : Physical layer - Answer 4QUIZ: Section 4 : Physical layer - Answer 4

CANopen products can have different connections.

TRUE