GRUNDFOS DATA BOOKLET
SLC, DLCSimplex and Duplex pump control panels
Ta
ble
of c
on
ten
ts
2
SLC, DLC
1. General description 3SLC and DLC pump control panels 3SLC - for one pump (Simplex) 3DLC - for two pumps (Duplex) 3Features and benefits 4Applications 5
2. Identification 6Nameplate 6Type key 7
3. Product range 8SLC, float-switch-controlled option 8SLC, transducer-controlled option 8DLC, float-switch-controlled option 9DLC, transducer-controlled option 9Additional options 9
4. Accessories 10Float switches 10Submersible, analog level pressure transducer 11
5. Functions 12SLC, float-switch-controlled option 12SLC, transducer-controlled option 12DLC, float-switch-controlled option 13DLC, transducer-controlled option 13Digital input and output screens 14Screen navigation 16Control panel operation 17Pump alternation 21Adjustable parameters 22
6. Construction 24SLC 24DLC 25
7. Wiring diagrams 26SLC, float-switch-controlled option 26SLC, transducer-controlled option 27DLC, float-switch-controlled option 28DLC, transducer-controlled option 29
8. Technical data 30
9. Grundfos Product Center 31
Ge
ne
ral
de
sc
rip
tio
n
SLC, DLC 1
1. General description
SLC and DLC pump control panelsThis document provides information about Grundfos SLC and DLC pump control panels including options, accessories, installation information, and product range.
Grundfos SLC and DLC pump control panels are designed for level control, monitoring and protection of pumps in wastewater, water supply and drainage systems.
SLC and DLC pump control panels are designed for emptying (water removal) applications. For boosting applications, see the Grundfos BoosterpaQ product line.
The SLC and DLC control panel product range comprises models up to 45 A / 15 hp (P2), direct-on-line starting (DOL).
Fig. 1 Grundfos DLC pump control panel
SLC - for one pump (Simplex)Float-switch-controlled option
The SLC, float-switch-controlled option, enables control of one (1) pump, utilizing the following inputs:
– high water-level alarm
– pump on
– pump off.
Transducer-controlled option
The SLC, transducer-controlled option, enables control of one (1) pump, utilizing an analog submersible level transducer with float-switch alarms:
– 4-20 mA (analog) water-level detection for duty and standby pump control
– high water-level alarm float switch
– low water-level alarm float switch.
DLC - for two pumps (Duplex)Float-switch-controlled option
The DLC, float-switch-controlled option, enables control of two (2) pumps, utilizing the following inputs:
– high water-level alarm
– duty pump on
– standby pump on
– pump(s) off.
Transducer-controlled option
The DLC, transducer-controlled option, enables control of two (2) pumps, utilizing an analog submersible level transducer with float-switch alarms:
– 4-20 mA (analog) water level detection for duty and standby pump control
– high water-level alarm float switch
– low water-level alarm float switch.TM
06
74
50
34
16
3
Ge
ne
ral d
es
crip
tion
SLC, DLC1
4
Features and benefitsThe SLC and DLC control panels are UL508a Listed as standard and incorporate the following items:
• a UL type 4X fiberglass hinged-door enclosure with dead-front inner door
• a programmable logic controller (PLC) with a dead-front, door-mounted, soft-button HMI operating panel (see fig. 3), displaying the following information for each pump:
– run time
– operating cycles (counter)
– seal-failure alarm
– high-temperature alarm.
• one (1) motor contactor per pump
• one (1) motor circuit protector per pump
• a 95 db audio alarm
• an Automatic-Manual-Off toggle switch for each pump
• an alarm beacon light
• a pump run light for each pump
• a specific pump alarm display text for each pump
• a push-to-silence alarm button
• auxiliary contacts (NO/NC) for alarm.
Additional options• Battery backup with charger (for alarm only)
• intrinsically safe with UL698A listing
• padlockable, supplemental main disconnect switch.
Fig. 2 Outer front door and dead-front inner door
Fig. 3 HMI operating panel with keypad and text display
TM
06
69
27
26
16
TM
06
68
47
25
16
Dead-frontinner door
Front door
Alarmbeacon
Ge
ne
ral
de
sc
rip
tio
n
SLC, DLC 1
Applications
Application examples
Fig. 4 Application examples
* As standard, transducer-controlled panels have high- and low-level float-switch backup inputs for pump operation and alarm conditions. It is optional to use these float switches.
TM
06
69
38
27
16
SLC, float-switch-controlled option
SLC, transducer-controlled option (analog, submersible transducer with float-switch backup)*
DLC, float-switch-controlled option
DLC, transducer-controlled option (analog, submersible transducer with float-switch backup)*
5
Ide
ntific
atio
n
SLC, DLC2
6
2. Identification
Nameplate
How to read the model designation
The actual control panel type, voltage variant, etc., are stated on the nameplate inside the control panel.
Fig. 5 Example of SLC nameplate
Fig. 6 Example of DLC nameplate
Panel model: ZGPCS230-3
Z = Electrical equipment
G = Grundfos
PC = Pump control panel
SD
=SimplexDuplex
230-3 = 230 V, 3-phase
TM
06
19
18
411
6T
M0
6 1
91
8 4
116
Ide
nti
fic
ati
on
SLC, DLC 2
Type key
Example Control SLC . 208/230 . A . 1 . B . 30/150 . T . FC
Type rangeControl SLC: Simplex control panelControl DLC: Duplex control panel
Voltage [V]208/230 V460 V575 V
Motor power [hp]
208-230 VA: 1.5 - 1.8 hpB: 2 - 7.5 hpC: 8-10 hpD: 12.5 - 15 hp
460 VE: 1.5 - 4 hpF: 5.5 - 10 hpD: 12.5 - 15 hp
575 VG: 1.5 hpH: 1.8 - 3 hpI: 4 - 5.5 hpJ: 7.5 hpC: 8-10 hpD: 12.5 - 15 hp
Phase1: Single-phase3: Three-phase
Operating current [A]
208/230 V - 460 VA: 2 - 6.3 AB: 5.7 - 18.9 AC: 9-30 AD: 15-45 A
575 VE: 1.6 - 2.5 AF: 2.5 - 4 AG: 4 - 6.3 AH: 6-10 AI: 9-14 AJ: 13-18 A
Run/starting capacitorBlank = no capacitor
OptionsT: Battery backupY: Intrinsically safe with UL698A listingZ: Padlockable main disconnect switch
Level detectionFC: Float-switch-controlledPT: Analog submersible pressure transducer-controlled
7
Pro
du
ct ra
ng
e
SLC, DLC3
8
3. Product range
SLC, float-switch-controlled option
SLC, transducer-controlled option
Description PhaseVoltage[VAC]
Motor shaft power[hp]
Overload range[A]
Main disconnect switch required
[A]Product number
SLC.208/230.B.1-FC 1 208/230 2.0 10.0 - 40.0 15 99165671
SLC.208/230.A.3.A-FC 3 208/230 1.5 - 1.8 2.0 - 6.3 15 99107775
SLC.208/230.B.3.B-FC 3 208/230 2.0 - 3.0 5.7 - 18.9 15 99107776
SLC.208/230.B.3.C-FC 3 208/230 2.0 - 7.5 9.0 - 30 30 99107777
SLC.208/230.C.3.D-FC 3 208/230 8.0 - 10.0 15.0 - 45.0 40 99107778
SLC.208/230.D.3.D-FC 3 208/230 12.5 - 15.0 15.0 - 45.0 60 99107779
SLC.460.E.3.A-FC 3 460 1.5 - 4.0 2.0 - 6.3 15 99107780
SLC.460.F.3.B-FC 3 460 5.5 - 10.0 5.7 - 18.9 20 99107781
SLC.460.D.3.C-FC 3 460 12.5 - 15.0 9.0 - 30.0 25 99107782
SLC.575.G.3.E-FC 3 575 1.5 1.6 - 2.5 15 99153139
SLC.575.H.3.F-FC 3 575 1.8 - 3.0 2.5 - 4.0 15 99153140
SLC.575.I.3.G-FC 3 575 4.0 - 5.5 4.0 - 6.3 15 99153141
SLC.575.J.3.H-FC 3 575 7.5 6.0 - 10.0 20 99153142
SLC.575.C.3.I-FC 3 575 8.0 - 10.0 9.0 - 14.0 20 99153143
SLC.575.D.3.J-FC 3 575 12.5 - 15.0 13.0 - 18.0 25 99153144
Description PhaseVoltage[VAC]
Motor shaft power[hp]
Overload range[A]
Main disconnect switch required
[A]Product number
SLC.208/230.B.1-PT 1 208/230 2.0 10.0 - 40.0 15 99165673
SLC.208/230.A.3.A-PT 3 208/230 1.5 - 1.8 2.0 - 6.3 15 99107059
SLC.208/230.B.3.B-PT 3 208/230 2.0 - 3.0 5.7 - 18.9 15 99107060
SLC.208/230.B.3.C-PT 3 208/230 2.0 - 7.5 9.0 - 30.0 30 99107061
SLC.208/230.C.3.D-PT 3 208/230 8.0 - 10.0 15.0 - 45.0 40 99107062
SLC.208/230.D.3.D-PT 3 208/230 12.5 - 15.0 15.0 - 45.0 60 99107063
SLC.460.E.3.A-PT 3 460 1.5 - 4.0 2.0 - 6.3 15 99107064
SLC.460.F.3.B-PT 3 460 5.5 - 10.0 5.7 - 18.9 20 99107065
SLC.460.D.3.C-PT 3 460 12.5 - 15.0 9.0 - 30.0 25 99107066
SLC.575.G.3.E-PT 3 575 1.5 1.6 - 2.5 15 99153151
SLC.575.H.3.F-PT 3 575 1.8 - 3.0 2.5 - 4.0 15 99153152
SLC.575.I.3.G-PT 3 575 4.0 - 5.5 4.0 - 6.3 15 99153153
SLC.575.J.3.H-PT 3 575 7.5 6.0 - 10.0 20 99153154
SLC.575.C.3.I-PT 3 575 8.0 - 10.0 9.0 - 14.0 20 99153155
SLC.575.D.3.J-PT 3 575 12.5 - 15.0 13.0 - 18.0 25 99153156
Pro
du
ct
ran
ge
SLC, DLC 3
DLC, float-switch-controlled option
DLC, transducer-controlled option
Additional options
**Enclosure adder is requiredNote: Seal-failure sensor(s), overtemperature sensor(s) are standard. Condition messages, such as run time, alarms and pump cycles are displayed on the HMI operating panel.
Description PhaseVoltage[VAC]
Motor shaft power[hp]
Overload range[A]
Main disconnect switch required
[A]Product number
DLC.208/230.B.1-FC 1 208/230 2.0 10.0 - 40.0 25 99165672
DLC.208/230.A.3.A-FC 3 208/230 1.5 - 1.8 2.0 - 6.3 20 99107783
DLC.208/230.B.3.B-FC 3 208/230 2.0 - 3.0 5.7 - 18.9 20 99107784
DLC.208/230.B.3.C-FC 3 208/230 2.0 - 7.5 9.0 - 30.0 50 99107785
DLC.208/230.C.3.D-FC 3 208/230 8.0 - 10.0 15.0 - 45.0 75 99107786
DLC.208/230.D.3.D-FC 3 208/230 12.5 - 15.0 15.0 - 45.0 120 99107787
DLC.460.E.3.A-FC 3 460 1.5 - 4.0 2.0 - 6.3 20 99107788
DLC.460.F.3.B-FC 3 460 5.5 - 10.0 5.7 - 18.9 40 99107789
DLC.460.D.3.C-FC 3 460 12.5 - 15.0 9.0 - 30.0 50 99107790
DLC.575.G.3.E-FC 3 575 1.5 1.6 - 2.5 15 99153145
DLC.575.H.3.F-FC 3 575 1.8 - 3.0 2.5 - 4.0 15 99153146
DLC.575.I.3.G-FC 3 575 4.0 - 5.5 4.0 - 6.3 20 99153147
DLC.575.J.3.H-FC 3 575 7.5 6.0 - 10.0 25 99153148
DLC.575.C.3.I-FC 3 575 8.0 - 10.0 9.0 - 14.0 30 99153149
DLC.575.D.3.J-FC 3 575 12.5 - 15.0 13.0 - 18.0 40 99153150
Description PhaseVoltage[VAC]
Motor shaft power[hp]
Overload range[A]
Main disconnect switch required
[A]Product number
DLC.208/230.B.1-PT 1 208/230 2.0 10.0 - 40.0 25 99165674
DLC.208/230.A.3.A-PT 3 208/230 1.5 - 1.8 2.0 - 6.3 20 99107067
DLC.208/230.B.3.B-PT 3 208/230 2.0 - 3.0 5.7 - 18.9 20 99107068
DLC.208/230.B.3.C-PT 3 208/230 2.0 - 7.5 9.0 - 30.0 50 99107069
DLC.208/230.C.3.D-PT 3 208/230 8.0 - 10.0 15.0 - 45.0 75 99107070
DLC.208/230.D.3.D-PT 3 208/230 12.5 - 15.0 15.0 - 45.0 120 99107071
DLC.460.E.3.A-PT 3 460 1.5 - 4.0 2.0 - 6.3 20 99107072
DLC.460.F.3.B-PT 3 460 5.5 - 10.0 5.7 - 18.9 40 99107073
DLC.460.D.3.C-PT 3 460 12.5 - 15.0 9.0 - 30.0 50 99107074
DLC.575.G.3.E-PT 3 575 1.5 1.6 - 2.5 15 99153157
DLC.575.H.3.F-PT 3 575 1.8 - 3.0 2.5 - 4.0 15 99153158
DLC.575.I.3.G-PT 3 575 4.0 - 5.5 4.0 - 6.3 20 99153159
DLC.575.J.3.H-PT 3 575 7.5 6.0 - 10.0 25 99153160
DLC.575.C.3.I-PT 3 575 8.0 - 10.0 9.0 - 14.0 30 99153161
DLC.575.D.3.J-PT 3 575 12.5 - 15.0 13.0 - 18.0 40 99153162
SLC and DLC Product number
**Battery backup with charger (for alarm only)
Consult factory
**Intrinsically safe relay for float inputs with UL698A Listing (FC only)
**Intrinsically safe barrier/relay for pressure transducer and backup floats, UL698A (PT only)
Padlockable main disconnect switch
Phase monitor with fusing
304 Stainless steel panel
Enclosure adder
9
Ac
ce
ss
orie
s
SLC, DLC4
10
4. Accessories
Float switchesSLC and DLC control panels are available with float switches for automatic level control. Grundfos float switches are of the non-mercury type and are available for standard and explosion-proof pumps. The hermetically sealed polypropylene housing and polyurethane cable make Grundfos float switches resistant to many chemicals, e.g. alcohol, uric acid, sewage, oils, gasoline and fruit acid.
SLCSLC can be fitted with up to three float switches:
• Minimum: Stops the pump.
• Maximum: Starts the pump.
• Alarm (optional): Indicates high water-level or pump failure.
DLCDLC can be fitted with up to four float switches:
• Minimum: Stops both pumps.
• Maximum 1: Starts one pump.
• Maximum 2: Starts the other pump.
• Alarm (optional): Indicates high water-level or pump failure.
Locating and positioning the float switchesThe float switches must be installed in the water collecting tank or pit floating on the pumped liquid. A float switch is an accepted way of controlling liquid levels in tanks, pits, etc.
The position of the float switches determines when SLC or DLC will start and stop the pump(s).
Function of the float switchesThe float switch, encased in a drop-shaped polypropylene housing is suspended at the desired height by its own three-core cable. When the liquid reaches a certain level, the float switch will tip either up or down, causing the contact to open or close.
• When the float switch is pointing up, the float switch contact will be closed and the pump will start.
• When the float switch is pointing down, the float switch contact will be opened and the pump will stop.
Fig. 7 Float-switch positions
TM
00
66
78
34
97
ON
OFF
Grundfos level switches for non-explosion risk environment Product number
TM
05
66
47
50
12
Grundfos float switch MS1 UL with 33 ft (10 m) cable 98365984
Grundfos float switch MS1 UL with 40 ft (12 m) cable 98365985
Grundfos float switch MS1 UL with 60 ft (18 m) cable 98365986
Cable support of stainless steel for two float switches 98365987
Grundfos level switches for explosion-risk environment Product number
Grundfos float switch MS1 Ex IECex with 33 ft (10 m) cable 98372085
Grundfos float switch MS1 Ex IECex with 40 ft (12 m) cable 98372086
Grundfos float switch MS1 Ex IECex with 60 ft (18 m) cable 98372087
Cable support of stainless steel for two float switches 98365987
Ac
ce
ss
ori
es
SLC, DLC 4
Submersible, analog level pressure transducer
Applications• Level measurement in rivers and lakes
• level measurement in vessel and storage systems
• control of sewage lifting and pumping stations
• monitoring of sewage, settling and storm water retention basins
• optimized for simple measuring requirements in level measurement
• suitable for permanent level measurement up to a 328 ft (100 m) water column.
Transducer features• Hermetically sealed, robust stainless-steel case
• fully-welded construction ensuring long life and permanent sealing
• enclosure class IP68
• 4-20 mA output as standard
• accuracy of 0.5 %
• 65 ft (19.8 m) PUR cable
• measuring range:0-9 psi (0 - 0.62 bar) / 0 - 20.1 ft (6.04 m)
• temperature ranges
– liquid: 14-122 °F (-10 to +50 °C)
– ambient: 14-122 °F (-10 to +50 °C)
– storage: -22 to +176 °F (-30 to +80 °C)
• power supply: DC 24 V.
Birdcage featuresThe birdcage sensor guard protects the sensor from floating debris. Its weight provides the sensor with stability, even in light turbulence.
• Birdcage maximum temperature:-4 to +212 °F (-20 to +100 °C)
• thread: G 1/2B
• weight: approximately 3 lb (1360 g)
• height: 1.97 in.
• diameter: 3.81 in.
• material: stainless steel AISI 304 (similar to EN 1.4301).
SLC or DLC with pressure transducer can be set up with float-switch backup.
You must order two float switches for optional high- and low-level backup of the transducer.
Fig. 8 Grundfos submersible, analog level pressure transducer kit (sensor and birdcage)
Fig. 9 Sensor dimensions
Fig. 10 Birdcage dimensions
TM
06
68
91
25
16
TM
06
68
96
26
16
TM
06
68
95
26
16
3.94
in. (
100
mm
)
0.393 in.(10 mm)
0.1.06 in.(27 mm)
G1/2B
0.708 in.(18 mm)
3.81 in. (97 mm)
1.97
in. (
50 m
m)
3.81
in. (
97 m
m)
Wt 3 lb(1360 g)
0.20 in.(5 mm)
0.79 in.(20 mm)
Grundfos submersible, analog level pressure transducer kit. See fig. 8. Product number
65 ft (19.8 m) PUR cable,0-9 psi (0 - 0.62 bar) / 0 - 20.1 ft (6.1 m) measuring range,stainless-steel birdcage.
99045076
11
Fu
nc
tion
s
SLC, DLC5
12
5. Functions
The SLC and DLC control panels include an easy-to-use programmable logic unit that incorporates many timing and logic functions.
The pump control panel features alarm and data screens to assist with monitoring and troubleshooting. The up- and down-arrow buttons allow you to navigate between the screens.
See the following table and screen navigation section for more details.
The alarm screen will only be displayed when alarms are active. The alarm screen shows the date and time when the alarm started.
SLC, float-switch-controlled option
SLC, transducer-controlled option
Alarm screen Alarm text Description
1 High Level Alarm High-level alarm
2 Pump Fail Alarm Pump-failure alarm
Data screen System data Description
3 Pump CT & ETM Pump cycles are shown at the top of the screen and the pump run time beneath
4 High Lvl CT High-level alarm events
5 Power Fault Counters Power failures are shown at the top of the screen and the hours in service beneath
6 Pump Fault Counters Pump-failure events
Alarm screen Alarm text Description
1 Xducer Sig Is activated when the transducer signal is below 3 mA
2 High Level Alarm When lifted, this float switch activates the alarm indication on the screen and the audible alarm.
3 Low Level Alarm When lowered, this float switch stops the pump and activates the indication on the screen.
4 Pump Fail AlarmIs activated when the pump overtemperature sensor, seal-failure sensor or overload relay has tripped.
Data screen System data Description
5 Current Tank Level Liquid level in tank or pit in feet
6 Pump CT & ETMThe pump cycle counter is shown at the top of the screen and the pump run time in minutes beneath
7 High Lvl CT & Low Level CTThe high-level alarm counter is shown at the top of the screen and low-level alarm counter beneath
8 Power Faults & Operating Hr The power failure counter is shown at the top of the screen and operating hours beneath
9 Transducer Signal "Raw value of transducer reading", in mA
10 On/Off Level Settings Pump-on and -off level setpoints
11 High/Low Level Settings High- and low-level alarm setpoints
12 Transducer Input Transducer range and offset settings
13 Minimum Run Time Minimum pump run time per cycle
14 High Level Pump Run Time Minimum high level pump run time per cycle
15 High Level Alarm Delay Elapsed time between high level point and alarm activation
Fu
nc
tio
ns
SLC, DLC 5
DLC, float-switch-controlled optionThe alarm screen will only be displayed when alarms are active. The alarm screen shows the date and time when the alarm started.
DLC, transducer-controlled optionThe alarm screen will only be displayed when alarms are active. The alarm screen shows the date and time when the alarm started.
Alarm screen Alarm text Description
1 High Level Alarm High level alarm
2 Pump 1 Fail Alarm Pump 1 failure alarm
3 Pump 2 Fail Alarm Pump 2 failure alarm
Data screen System data Description
4 Pump 1 CT & ETM Pump 1 cycles are shown at the top of the screen and pump 1 run time beneath
5 Pump 2 CT & ETM Pump 2 cycles are shown at the top of the screen and pump 2 run time beneath
6 High Lvl CT High level alarm events
7 Pump 1 & 2 Lag Event CountersPump 1 lag (standby) events are shown at the top of the screen and pump 2 lag (standby) events beneath
8 Power Fault Counters Power failures are shown at the top of the screen and hours in service beneath
9 Pump 1 & 2 Fault Counters Pump 1 failure events are shown at the top of the screen and pump 2 failure events beneath
Alarm screen Alarm text Description
1 Xducer Sig Is activated when the transducer signal is below 3 mA
2 High Level Alarm When lifted, this float switch activates the alarm indication on the screen and the audible alarm.
3 Low Level Alarm When lowered, this float switch stops the pump and activates the indication on the screen.
4 Pump 1 Fail AlarmIs activated when pump 1 overtemperature sensor, seal failure sensor or overload relay has tripped.
5 Pump 2 Fail AlarmIs activated when pump 2 overtemperature sensor, seal failure sensor or overload relay has tripped
Data screen System data Description
6 Current Tank Level Liquid level in tank or pit in feet
7 Pump 1 CT & ETM Pump 1 cycle counter is shown at the top of the screen and pump 1 run time in minutes beneath
8 Pump 2 CT & ETM Pump 2 cycle counter is shown at the top of the screen and pump 2 run time in minutes beneath
9 High Lvl CT & Low Level CT High level alarm counter is shown at the top of the screen and low level alarm counter beneath
10 Power Faults & Operating Hr Power failure counter is shown at the top of the screen and operating hours beneath
11 Transducer Signal Raw value of transducer reading, in mADC
12 On/Off Level Settings Pump on and off level setpoints
13 Lag Level Setting Lag (standby) pump on level setpoint
14 High/Low Level Settings High- and low-level alarm setpoints
15 Transducer Input Transducer range and offset settings
16 Minimum Run Time Minimum pump run time per cycle
17 High Level Pump Run Time Minimum high level pump run time per cycle
18 High Level Alarm Delay Elapsed time between high level point and alarm activation
13
Fu
nc
tion
s
SLC, DLC5
14
Digital input and output screensThe pump control panel will activate various input and output screens as it operates. See fig. 11. These screens are a helpful when installing and troubleshooting the control panel. The input screens will vary according to the mode of operation of the panel.
See the following tables to identify the conditions that activate the various screens.
Fig. 11 Example, digital input and output screens
SLC, float-switch-controlled option
SLC, transducer-controlled option
TM
06
72
17
29
16
Input screen Function Activation condition
1 Pump Off Float Float switch in up position
2 Pump On Float Float switch in up position
3 High Level Alarm Float Float switch in up position
4 Push To Silence Push button is pressed
5 Pump Fault Pump seal-failure sensor, overtemperature sensor, or overload protection has tripped.
Output screen Function Activation condition
6 Pump Pump is called to run
7 Alarm Light Alarm light is activated
8 Audible Alarm Audible alarm is activated
Input screen Function Activation condition
1 Redundant Off and Low Level Alarm Float Float switch in up position
2 High Level Float Float switch in up position
3 Push to Silence Push button is pressed
4 Pump Fault Pump seal-failure sensor, overtemperature sensor, or overload protection has tripped.
5 Not Used NA
6 Not Used NA
7 Transducer (analog signal) 4-20 mADC
Output screen Function Activation condition
8 Pump 1 Pump is called to run
9 Pump 2 Pump is called to run
10 Level Alarm Light Level alarm condition exists
11 Audible Alarm Audible alarm is activated
Activated input
Inputs 1-9
Inputs 10-19
Inputs 20-24
Input screen Output screen
Outputs 1-9
Outputs 10-16
Activated output
Fu
nc
tio
ns
SLC, DLC 5
DLC, float-switch-controlled option
DLC, transducer-controlled option
Inputs Function Activation condition
1 Pump(s) Off Float Float switch in up position
2 Lead Pump On Float Float switch in up position
3 Lag Pump On Float Float switch in up position
4 High Level Alarm Float Float switch in up position
5 Push To Silence Push button is pressed
6 Pump 1 Fault Pump 1 seal-failure sensor, overtemperature sensor, or overload protection has tripped.
7 Pump 2 Fault Pump 2 seal-failure sensor, overtemperature sensor, or overload protection has tripped.
Outputs Function Activation condition
8 Pump 1 Pump is called to run
9 Pump 2 Pump is called to run
10 Alarm Light Alarm light is activated
11 Audible Alarm Audible alarm is activated
Input screen Function Activation condition
1 Redundant Off and Low Level Alarm Float Float switch in up position
2 High Level Float Float switch in up position
3 Push to Silence Push button is pressed
4 Pump 1 Fault Pump 1 seal-failure sensor, overtemperature sensor, or overload protection has tripped.
5 Pump 2 Fault Pump 2 seal-failure sensor, overtemperature sensor, or overload protection has tripped.
6 Not Used NA
7 Transducer (analog signal) 4-20 mADC
Output screen Function Activation condition
8 Pump 1 Pump is called to run
9 Pump 2 Pump is called to run
10 Level Alarm Light Level alarm condition exists
11 Audible Alarm Audible alarm is activated
15
Fu
nc
tion
s
SLC, DLC5
16
Screen navigationThe screens are arranged in the order shown in fig. 12. You can use the up and down arrow buttons to navigate between the screens. Frequently used screens are outlined in bold. Some screens may not be applicable.
Fig. 12 Screen navigation
TM
06
72
18
311
6
System alarm screen
System data screen
Time and Date
Digital Inputs(1-24)
Digital Outputs(1-16)
Analog Inputs(1-3)
Analog Inputs(4-6)
Analog Inputs(7-8)
Analog Outputs
(1-2)
Memory(1-27)
ESC+C
Fu
nc
tio
ns
SLC, DLC 5
Control panel operation
SLC, float-switch-controlled optionThe control panel supports two different modes of operation based on selected parameter settings. See Adjustable parameters on page 22 for information on how to change the mode of operation and other adjustable parameters.
Your control panel can perform the functions listed below. Depending on the application, some functions may be omitted or combined.
* To determine a pump seal failure, overtemperature or overload trip, open the dead-front inner door and look for the following relay conditions:Overload relay = When the overload relay trips, the trip indicator is present on the device. The overload relay can be reset by pressing the blue reset button. The overload relay can be switched to manual or automatic resetting.K02 = This relay is active when the overtemperature sensor in the pump has tripped.K03 = This relay is active when the seal-failure sensor in the pump has tripped.
High Level Alarm
• This float switch activates the alarm indication on the screen and the audible alarm when lifted for longer than the high-level alarm delay.
• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the float switch is lowered, and the audible alarm will
reactivate in 12 hours if the alarm condition is not corrected.
Pump On• This float switch starts the pump when lifted.• The pump will run for the duration of the minimum run time or until the pump-off float switch (if used) is lowered.
Pump Off • This float switch stops the pump(s) when lowered if the minimum run time has elapsed.
Pump Fault*
• The pump failure is activated when the pump overtemperature sensor, seal failure sensor, or overload protection has tripped.
• A pump failure will activate the alarm indictor light, the audible alarm, and an alarm message on the user's screen.• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.
17
Fu
nc
tion
s
SLC, DLC5
18
SLC, transducer-controlled optionThe control panel can perform the functions listed below. Depending on the number of float switches for your application, some functions may be omitted or combined.
* To determine a pump seal failure, overtemperature or overload trip, open the dead-front inner door and look for the following relay conditions:Overload relay = When the overload relay trips, the trip indicator is present on the device. The overload relay can be reset by pressing the blue reset button. The overload relay can be switched to manual or automatic resetting.K02 = This relay is active when the overtemperature sensor in the pump has tripped.K03 = This relay is active when the seal-failure sensor in the pump has tripped.
High Level Alarm
• This preset level activates the alarm indication on the screen and the audible alarm when the liquid level is high for longer than the high-level alarm delay (factory-set for 5 seconds).
• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the level is lowered, and the audible alarm will reactivate in
12 hours if the alarm condition is not corrected.
Pump On• The pump will start at the preset pressure of the level sensor for pump operation.• The pump will run until the level sensor pressure is reduced below the preset pump-off level.
Pump Off• The pump will stop when the level sensor pressure falls below the preset pump-off level if the minimum time delay
has elapsed.
Redundant Off and Low Level alarm
• The pump will stop when the liquid level is lowered to this level for more than two seconds.• Pumping will be disabled in both the automatic modes.• The alarm indication on the screen and the audible alarm will be activated.• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the liquid level is raised.• The audible alarm will reactivate in 12 hours if the alarm condition is not corrected.
Transducer Failure• If the transducer signal drops below 3 mADC, a transducer failure alarm will be activated.• The alarm indication on the screen and the audible alarm will be activated.• A message will be shown on the screen.
Backup floats
High Level Alarm
• This float switch activates the alarm indication on the screen and the audible alarm when lifted for longer than the high-level alarm delay (factory set for 5 seconds).
• This float switch also starts the pump.• The pump will run until the high-level pump run time has elapsed.• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the float switch is lowered, and the audible alarm will
reactivate in 12 hours if the alarm condition is not corrected.
Redundant Off and Low Level Alarm
• This float switch stops the pump when lowered for more than two seconds.• This float switch is a backup float switch which will operate if the transducer fails.• Pumping will be disabled in both the automatic and manual modes.• This float switch also activates the alarm indication on the screen and the audible alarm.• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the float switch is lifted.• The audible alarm will reactivate in 12 hours if the alarm condition is not corrected.
Pump Fault*
• The pump failure is activated when the pump overtemperature sensor, seal failure sensor, or overload relay has tripped.
• A pump failure will activate the alarm indication on the screen, the audible alarm, and an alarm message on the user's screen.
• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.
Fu
nc
tio
ns
SLC, DLC 5
DLC, float-switch-controlled optionThe control panel supports two different modes of operation based on selected parameter settings. See Adjustable parameters on page 22 for information on how to change the mode of operation and other adjustable parameters.
Your control panel can perform the functions listed below. Depending on the application, some functions may be omitted or combined.
* To determine a pump seal failure, overtemperature or overload failure trip, open the dead-front inner door and look for the following relay conditions:Overload relay = When the overload relay trips, the trip indicator is present on the device. The overload relay can be reset by pressing the blue reset button. The overload relay can be switched to manual or automatic resetting.K02 = This relay is active when the overtemperature sensor in the pump has tripped.K03 = This relay is active when the seal-failure sensor in the pump has tripped.K04 = This relay is active when the overtemperature sensor in the pump has tripped.K05 = This relay is active when the seal-failure sensor in the pump has tripped.
High Level Alarm
• This float switch activates the alarm indication on the screen and the audible alarm when lifted for longer than the high-level alarm delay.
• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the float switch is lowered, and the audible alarm will
reactivate in 12 hours if the alarm condition is not corrected.
Lag Pump On• This float switch starts the lag (standby) pump when lifted (both pumps will be on).• Both pumps will run until the pump(s) off float switch (if used) is lowered.
Lead Pump On• This float switch starts the lead (duty) pump when lifted.• The pump will run for the duration of the minimum run time or until the pump(s) off float switch (if used) is lowered.
Pump(s) Off • This float switch stops the pump(s) when lowered if the minimum run time has elapsed.
Pump Fault*
• The pump failure is activated when the pump overtemperature sensor, seal failure sensor, or overload relay has tripped.
• A pump failure will activate the alarm indication on the screen, the audible alarm, and an alarm message on the user's screen.
• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.
19
Fu
nc
tion
s
SLC, DLC5
20
DLC, transducer-controlled optionThe control panel can perform the functions listed below. Depending on the number of float switches for your application, some functions may be omitted or combined.
* To determine a pump seal failure, overtemperature or overload failure trip, open the dead-front inner door and look for the following relay conditions:Overload relay = When the overload relay trips, the trip indicator is present on the device. The overload relay can be reset by pressing the blue reset button. The overload relay can be switched to manual or automatic resetting.K02 = This relay is active when the overtemperature sensor in the pump has tripped.K03 = This relay is active when the seal-failure sensor in the pump has tripped.K04 = This relay is active when the overtemperature sensor in the pump has tripped.K05 = This relay is active when the seal-failure sensor in the pump has tripped.
High Level Alarm
• This preset level activates the alarm indication on the screen and the audible alarm when the level is high for longer than the high-level alarm delay (factory set for 5 seconds).
• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the level is lowered, and the audible alarm will reactivate in
12 hours if the alarm condition is not corrected.
Lag Pump On• The lag (standby) pump (both pumps will be on) will start at the preset pressure of the level sensor for lag
(standby) operation.• Both pumps will continue to run together until the level sensor pressure reduces below the preset Pumps Off level.
Lead Pump On• The lead (duty) pump will start at the preset pressure of the level sensor for lead (duty) pump operation.• The lead (duty) pump will run until the level sensor pressure is reduced below the preset pumps-off level.
Pumps Off• Both pumps will stop when the level sensor pressure is reduced below the preset pumps-off level if the delay has
elapsed.
Redundant Off & Low Level Alarm
• The pumps will stop when the liquid level is lowered to this level for more than two seconds.• Pumping will be disabled in both the automatic modes.• The alarm indication on the screen and the audible alarm will be activated.• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the liquid level is raised.• The audible alarm will reactivate in 12 hours if the alarm condition is not corrected.
Transducer Failure• If the transducer signal drops below 3 mADC, a transducer failure alarm will be activated.• The alarm indication on the screen and the audible alarm will be activated.• A message will be shown on the screen.
Backup floats
High Level Alarm
• This float switch activates the alarm indication on the screen and the audible alarm when lifted for longer than the high-level alarm delay (factory set for 5 seconds).
• This float switch also starts both pumps. Both pumps will run until the high-level pump run time has elapsed.• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the float switch is lowered, and the audible alarm will
reactivate in 12 hours if the alarm condition is not corrected.
Redundant Off and Low Level Alarm
• This float switch stops the pumps when lowered for more than two seconds.• This float switch is a backup float switch which will operate if the transducer fails.• Pumping will be disabled in both the automatic and manual modes.• This float switch also activates the alarm indication on the screen and the audible alarm.• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the float switch is lifted. • The audible alarm will reactivate in 12 hours if the alarm condition is not corrected.
Pump Fault*
• The pump failure is activated when the pump overtemperature sensor, seal failure sensor, or overload relay has tripped.
• A pump failure will activate the alarm indication on the screen, the audible alarm, and an alarm message on the user's screen.
• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.
Fu
nc
tio
ns
SLC, DLC 5
Pump alternationDLC pump control panels support four different modes of operation relating to pump alternation which are based on selected parameter settings. Additionally, the panel can be set to alternate pumps in the event of a failure.
See Adjustable parameters on page 22 for information on how to adjust these parameters.
Alternating (default)• Parameters "Pmp1Lead" and "Pmp2Lead" are set to "Off".• The (duty) and lag (standby) pumps will alternate for each cycle.• This mode provides equal wear on both pumps and is recommended for most applications.
Pump 1 Lead
• Parameter "Pmp1Lead" is set to "On" and parameter "Pmp2Lead" is set to "Off".• The lead (duty) pump function is locked to pump 1 and the lag (standby) pump function is locked to pump 2.• No alternation will occur.• Pump 1 will be the primary pump for the system.• Pump 2 will only be used during high-flow conditions.
Pump 2 Lead
• Parameter "Pmp1Lead" is set to "Off" and parameter "Pmp2Lead" is set to "On".• The lead (duty) pump function is locked to pump 2 and the lag (standby) pump function is locked to pump 1.• No alternation will occur.• Pump 2 will be the primary pump for the system.• Pump 1 will only be used during high flow conditions.
Both Pumps • Parameters "Pmp1Lead" and "Pmp2Lead" are set to "On". Both pumps will run in every cycle.
21
Fu
nc
tion
s
SLC, DLC5
22
Adjustable parametersSLC and DLC pump control panels include an easy-to-use programmable logic unit that incorporates many timing and logic functions.
The unit has been programmed from factory for the control functions required. The unit includes adjustable operational parameters and viewable monitoring information. Some operational parameters may need changing for your particular application.
SLC and DLC pump control panels use block names to identify the various parameters. Please refer to the screen of the logic controller face inside the enclosure.
Block names, SLC float-switch-controlled optionThe following block names are used for SLC, float-switch-controlled option.
All adjustable parameters DO NOT use the same type of blocks. Check the block types below to determine which steps apply to your application.
Block names, SLC, transducer-controlled optionThe following block names are used for SLC, transducer-controlled option.
All adjustable parameters DO NOT use the same type of blocks. Check the block types below to determine which steps apply to your application.
Block names Description Factory default setting Time range Block Type Timed/Demand
HLA Dly High-level alarm delay 5 seconds MM:SS Timer Both
MinRunT Minimum pump run time 1 second MM:SS Timer Demand
Screen names DescriptionUnits of
measurementDefault setting
On Level Tank level at which the lead (duty) pump starts. feet 12.0
Off Level Tank level at which the pump stops. feet 9.0
High Level Alarm Tank level at which the high-level alarm is activated. feet 14.0
Low Level Alarm Tank level at which the low-level alarm is activated. feet 3.0
Xducer RangeThe full range of the transducer (NOT the tank height), i.e. the 4-20 mA signal from the transducer equals 0 - Xducer Range.
feet 15.0
Xducer Offset The distance between the bottom of the transducer and the bottom of the tank. feet 0.5
Minimum Run Time The minimum pump run time for an automatic cycle. seconds 2.0
High Level Pump Run Time The minimum pump run time during a high-level state. minutes 1.0
High Level Alarm Delay The time between the high-level state and alarm status. seconds 5.0
Fu
nc
tio
ns
SLC, DLC 5
Block names, DLC, float-switch-controlled optionThe following block types are used.
All adjustable parameters DO NOT use the same type of blocks. Check the block types below to determine which steps apply to your application.
Block names, DLC, transducer-controlled optionThe following block types are used.
All adjustable parameters DO NOT use the same type of blocks. Check the block types below to determine which steps apply to your application.
Block names Description Factory default setting Time range Block Type Timed/Demand
HLA Dly High-level alarm delay 5 seconds MM:SS Timer Both
MinRunT Minimum pump run time 1 second MM:SS Timer Demand
Pmp1Lead Pump 1 as lead (duty) pump Off On/Off Soft button Both
Pmp2Lead Pump 2 as lead (duty) pump Off On/Off Soft button Both
Screen names DescriptionUnits of
measurementDefault setting
On Level Tank level at which the lead (duty) pump starts. feet 12.0
Off Level Tank level at which the lead (duty) pump stops. feet 9.0
Lag Level Tank level at which the lag (standby) pump starts feet 13.0
High Level Alarm Tank level at which the high-level alarm is activated. feet 14.0
Low Level Alarm Tank level at which the low-level alarm is activated. feet 3.0
Xducer RangeThe full range of the transducer (NOT the tank height), i.e. the 4-20 mA signal from the transducer equals 0 - Xducer Range.
feet 15.0
Xducer Offset The distance between the bottom of the transducer and the bottom of the tank. feet 0.5
Minimum Run Time The minimum pump run time for an automatic cycle. seconds 2.0
High Level Pump Run Time The minimum pump run time during a high-level state. minutes 1.0
High Level Alarm Delay The time between the high-level state and alarm status. seconds 5.0
DLC adjustable parameter soft-button blocks
Block names Description Factory default setting Block type
Pmp1Lead Pump 1 as lead (duty) pump Off Soft button
Pmp2Lead Pump 2 as lead (duty) pump Off Soft button
23
Co
ns
truc
tion
SLC, DLC6
24
6. Construction
SLCThe description covers all SLC models, both float-switch-controlled and transducer-controlled.
Note: During a pump failure, check the relays to determine pump overtemperature or seal failure. The relay LED will be on, if active.
CR1 = Pump overtemperature
CR2 = Pump seal failure.
TM
06
68
61
37
16
HIGH LEVELALARM
During a pump faultcheck the relays to
determine over tempor seal fail. The relaysLED will be on if "OK".
G
PUMP RUN
F1 F2 F3 F4
LOGO! TD
HAND OFF AUTO
K02 = P1 OvertempK03 = P1 Seal FailK04 = P2 OvertempK05 = P2 Seal Fail
ESC OK
35
0ff/O
L N
+V-V
i
17.31 in. (440 mm)
19.3
1 in
. (49
0 m
m)
18.7
4 in
. (47
6 m
m)
pane
l mou
ntin
g
12 in. (305 mm)panel mounting
9.58
in. (
243
mm
)
1
2
3
5
4
6
7 8 910
12
1617
14
11 13
15
Dead-front inner-door layout
FRP Type 4X enclosureFiberglass
Front door layout
Back panel layout
Side view
Bottom view
Panel mounting
Pos. Description
1 Alarm beacon and alarm indicator
2 Keypad and text display
3 Pump run indicator
4 Hand - Off - Auto switch
5 Push-to-Silence alarm button
6 Audible alarm
7 Transformer
8 Fuses
9 Control panel circuit breaker
10 Pump circuit breaker
11 PLC
12 Relays
13 DC power supply
14 Motor starter
15 Overload relay
16 Terminals
17 Main power distribution blocks
Co
ns
tru
cti
on
SLC, DLC 6
DLCThe description covers all DLC models, both float-switch-controlled and transducer-controlled.
Note: During a pump failure, check the relays to determine pump overtemperature or seal failure. The relay LED will be on, if active.
K02 = Pump 1 overtemperature
K03 = Pump 1 seal failure
K04 = Pump 2 overtemperature
K05 = Pump 2 seal failure.
TM
06
68
60
37
16
HAND OFF AUTO
During a pump fault check the relays to
determine over temp or seal fail. The relays LED will be on if "OK".
GG
PUUMP 1 RUN PUMP 2 RUN
F1 F2 F3 F4
LOGO! TD
HAND OFF AUTO
K02 = P1 OvertempK03 = P1 Seal FailK04 = P2 OvertempK05 = P2 Seal Fail
ESC OK
X 23 4
wohner
+V-V
OUTPUT30W
HIGH LEVELALARM
FRP Type 4X enclosureFiberglass
Front door layout
Dead-front inner-door layout
Back panel layout
Side view
Bottom view
Panel mounting
Pos. Description
1 Alarm beacon and alarm indicator
2 Keypad and text display
3 Pump 2 run indicator
4 Hand - Off - Auto switch, pump 2
5 Pump 1 run indicator
6 Hand - Off - Auto switch, pump 1
7 Push-to-Silence alarm button
8 Audible alarm
9 Transformer
10 Fuses
11 Pump circuit breaker
12 PLC
13 Relays
14 DC power supply
15 Motor starters
16 Overload relay
17 Terminals
18 Main power distribution blocks
25
Wirin
g d
iag
ram
s
SLC, DLC7
26
7. Wiring diagrams
SLC, float-switch-controlled option
Fig. 13 Wiring diagram, SLC with float switches
TM
06
68
55
25
16
H*H1
X1 X2
F1 F2
L1 N
+ -
L1
L3
L2 T2L2
T1L1
L3 T3
OLRxxA
CB xxA K11
1
CB 10A
L+ M
i5
1 i14
NIBP
21 22K02
i6
+ -
L1
L2
L3
i334
i224
21 22K03
98
K011112 1411
10
K11A1
Q1
Q4
+ -A
A2
K02A2A1
GX2X1
11 14K02
K03A2A1
6 596 95
OLR
R
K01A2A1
7
11 14K03
Q3
Factory wireField wire
PumpXXX VAC, 3-phase, XX hp
High-level alarm float switch
Pump on float switch
Pump off float switch
Pump fault
Pump overtemperature sensor
Seal sensor
Push-to-Silence alarm
Fuses 2A
Control panel transformerXXXV - 120 V, 100 VA
Control panel115 VAC
PLC text display
24 VDC power supply
PLC
Motor contactor
Pump run light
Beacon alarm light
Alarm relay
Audible alarm
Pump overload relay or overtemperature sensor
Pump seal-failure sensor
Hand Auto
OFF
From main power panelXXX VAC, 3-phase, 60 HzMain disconnect switch provided by others
Ground wire
To LOGO
From display screen
24 Vpower supply
LOGO
Alarm contact
Wir
ing
dia
gra
ms
SLC, DLC 7
SLC, transducer-controlled option
Fig. 14 Wiring diagram, SLC with submersible analog level pressure transducer
TM
06
68
58
25
16
H*H1
X1 X2
F1 F2
L1 N
+ -
L1
L3
L2 T2L2
T1L1
L3 T3
OLRxxA
CB xxA K11
1
CB 10A
L+ M
i5
NIBP
21 22K02
i6
+ -
L1
L2
L3
21 22K03
1 i1
i2
i8
500Ohm
3
23
Trans+
24V --
87
K011112 1411
9
K11A1
Q1
Q4
+ -A
A2
K02A2A1
GX2X1
11 14K02
K03A2A1
5 496 95
OLR
R
K01A2A1
6
11 14K03
Q3
Factory wireField wire
PumpXXX VAC, 3-phase, XX hp
High-level alarm float switch
Pressure transducer
Low-level alarm float switch
Pump failure
Pump over-temperature sensor
Seal sensor
Push-to-Silence alarm
Fuses 2A
Control panel - transformerXXXV - 120 V, 100 VA
Controls115 VAC
PLCtext display
24 VDCpower supply
PLC
Motor contactor
Pump run light
Beacon alarm light
Alarm relay
Audible alarm
Pump overload relay or overtemperature sensor
Pump seal-failure sensor
Hand Auto
OFF
From main power panelXXX VAC, 3-phase, 60 HzMain disconnect switch provided by others
Ground wire
To LOGO
Fromdisplay screen
24 Vpower supply
Alarm contact
LOGO
27
Wirin
g d
iag
ram
s
SLC, DLC7
28
DLC, float-switch-controlled option
Fig. 15 Wiring diagram, DLC with float switches
TM
06
68
54
25
16
1312
K011112 1411
14
K11A1
Q1
K12
Q2
Q3
Q4
+ -A
A2
A1 A2
K02A2A1
GX2X1
GX2X1
11 14K02
11 14K04
21 22K04
i7
K03A2A1
7 6
K04A2A1
K05A2A1
10 9
11
96 95OLR1
96 95OLR2
R
K01A2A1
8
11 14K03
11 14K05
21 22K03
21 22K03
H*H1
X1 X2
F1 F2
L1 N
+ -
L1
L3
L2
CB xxA
T2L2
T1L1
L3 T3
T2L2
T1L1
L3 T3
OLR2XXA
OLR1xxA
CB xxA K11
K12
1
2
CB 10A
L+ M
i5
1 i1
i4
5
45
NIBP
21 22K02
i6
+ -
L1
L2
L3
i335
i225
Factory wireField wire
PumpsXXX VAC, 3-phaseXX hp
High-level alarm float switch
Standby pump on float switch
Duty pump on float switch
Pumps-off float switch
Pump 1 failure
Pump 2 failure
Pump 1 over-temperature sensor
Seal sensor 1
Pump 2 over-temperature sensor
Seal sensor 2
Push-to-Silence alarm
Fuses 2A
Controls - transformerXXXV - 120 V, 100 VA
Control panel 115 VAC
PLC text display
24 VDCpower supply
PLC
Motor contactor
Pump run light
Motor contactor
Pump run light
Beacon Alarm Light
Alarm relay
Audible Alarm
Alarm contact
Pump 1 overload relay or overtemperature sensorPump 1 seal-failure sensor
Hand
Hand
Auto
Off
Off
Auto
From main power panelXXX VAC, 3-phase, 60 HzMain disconnect switch provided by others.
Ground wire
To LOGO
From display screen
24 Vpower supply
LOGO
Pump 2 overload relay or overtemperature sensorPump 2 seal-failure sensor
Wir
ing
dia
gra
ms
SLC, DLC 7
DLC, transducer-controlled option
Fig. 16 Wiring diagram, DLC with submersible analog level pressure transducer
TM
06
68
59
26
16
H*H1
X1 X2
F1 F2
L1 N
+ -
L1
L3
L2
CB xxA
T2L2
T1L1
L3 T3
T2L2
T1L1
L3 T3
OLR2XXA
OLR1xxA
CB xxA K11
K12
1
2
CB 10A
L+ M
i5
NIBP
21 22K02
i6
+ -
L1
L2
L3
1 i1
i2
i8
500Ohm
3
23
Trans+
24V --
1110
K011112 1411
12
K11A1
Q1
K12
Q2
Q3
Q4
+ -A
A2
A1 A2
K02A2A1
GX2X1
GX2X1
11 14K02
11 14K04
21 22K04
i7
K03A2A1
5 4
K04A2A1
K05A2A1
8 7
9
96 95OLR1
96 95OLR2
R
K01A2A1
6
11 14K03
11 14K05
21 22K03
21 22K03
Factory wireField wire
PumpsXXX VAC, 3-phaseXX hp
Pump 1 over-temperature sensor
Seal sensor 1
Pump 2 over-temperature sensor
Seal sensor 2
Fuses 2A
Control panel - transformerXXXV - 120 V 100 VA
Controls115 VAC
PLC text display
24 VDC power supply
PLC
Motor contactor
Pump run light
Motor contactor
Pump run light
Beacon Alarm Light
Alarm relay
Audible Alarm
Alarm contact
Pump 1 overload relay or overtemperature sensor
Pump 1 seal-failure sensor
Pump 2 overload relay or overtemperature sensor
Hand
Hand
Auto
Off
Off
Auto
From main power panelXXX VAC, 3-phase, 60 HzMain disconnect switch provided by others
Ground wire
To LOGO
Fromdisplay screen
24 Vpower supply
Pump 2 seal-failure sensor
LOGO
High-level alarm float switch
Pressure transducer
Low-level alarm float switch
Pump 1 failure
Push-to-Silence alarm
Pump 2 failure
29
Te
ch
nic
al d
ata
SLC, DLC8
30
8. Technical data
Voltage tolerance:- 15 %/+ 10 % of rated voltage (3 x 208/230 VAC, 3 x 460 VAC, 3 x 575 VAC)
+ 10 %/- 1 % of rated voltage (1 x 230 VAC)
Mains frequency: 60 Hz
Ambient temperature:• During operation: - 22 °F to +122 °F (- 30 °C to +50 °C)
(must not be exposed to direct sunlight)
• During transport and storage: - 22 °F to +140 °F (- 30 °C to + 60 °C)
Enclosure class: NEMA4X
Outputs for alarm devices:Max. 120 VAC / max. 8 A / min. 10 mA / AC 1NO/NC contact
Approvals: Listed per UL 508A
Gru
nd
fos
Pro
du
ct
Ce
nte
r
SLC, DLC 9
31
9. Grundfos Product Center
Subject to alterations.
All the information you need in one place Downloads
Performance curves, technical specifications, pictures, dimensional drawings, motor curves, wiring diagrams, spare parts, service kits, 3D drawings, documents, system parts. The Product Center displays any recent and saved items — including complete projects — right on the main page.
On the product pages, you can download Installation and Operating Instructions, Data Booklets, Service Instructions, etc. in PDF format.
"SIZING" enables you to size a pump based on entered data and selection choices.
Online search and sizing tool to help you make the right choice.
http://product-selection.grundfos.com
"REPLACEMENT" enables you to find a replacement product.Search results will include information on
• the lowest purchase price• the lowest energy consumption• the lowest total life cycle cost.
"CATALOG" gives you access to the Grundfos product catalog.
"LIQUIDS" enables you to find pumps designed for aggressive, flammable or other special liquids.
Th
e n
am
e G
run
dfo
s, t
he
Gru
nd
fos
log
o,
an
d b
e t
hin
k i
nn
ov
ate
are
re
gis
tere
d t
rad
em
ark
s o
wn
ed
by
Gru
nd
fos
Ho
ldin
g A
/S o
r G
run
dfo
s A
/S,
De
nm
ark
. A
ll ri
gh
ts r
ese
rve
d w
orl
dw
ide
.©
Co
pyr
igh
t G
run
dfo
s H
old
ing
A/S
L-SLC-PG-01
98436499 XX17
ECM: XXXXXXX
GRUNDFOS Chicago3905 Enterprise CourtP.O. Box 6620Aurora, IL 60598-0620Phone: +1-630-236-5500Fax: +1-630-236-5511
GRUNDFOS Kansas City17100 West 118th TerraceOlathe, Kansas 66061Phone: +1-913-227-3400Fax: +1-913-227-3500www.grundfos.us
GRUNDFOS Canada2941 Brighton RoadOakville, Ontario L6H 6C9 CanadaPhone: +1-905 829 9533Fax: +1-905 829 9512www.grundfos.ca
GRUNDFOS México Boulevard TLC No. 15Parque Industrial Stiva AeropuertoC.P. 66600 Apodaca, N.L MexicoPhone: +011-52-81-8144 4000Fax: +011-52-81-8144 4010www.grundfos.mx