GRUNDFOS DATA BOOKLET

SLC, DLCSimplex and Duplex pump control panels

Page 2: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Ta

ble

of c

on

ten

ts

2

SLC, DLC

1. General description 3SLC and DLC pump control panels 3SLC - for one pump (Simplex) 3DLC - for two pumps (Duplex) 3Features and benefits 4Applications 5

2. Identification 6Nameplate 6Type key 7

3. Product range 8SLC, float-switch-controlled option 8SLC, transducer-controlled option 8DLC, float-switch-controlled option 9DLC, transducer-controlled option 9Additional options 9

4. Accessories 10Float switches 10Submersible, analog level pressure transducer 11

5. Functions 12SLC, float-switch-controlled option 12SLC, transducer-controlled option 12DLC, float-switch-controlled option 13DLC, transducer-controlled option 13Digital input and output screens 14Screen navigation 16Control panel operation 17Pump alternation 21Adjustable parameters 22

6. Construction 24SLC 24DLC 25

7. Wiring diagrams 26SLC, float-switch-controlled option 26SLC, transducer-controlled option 27DLC, float-switch-controlled option 28DLC, transducer-controlled option 29

8. Technical data 30

9. Grundfos Product Center 31

Page 3: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Ge

ne

ral

de

sc

rip

tio

n

SLC, DLC 1

1. General description

SLC and DLC pump control panelsThis document provides information about Grundfos SLC and DLC pump control panels including options, accessories, installation information, and product range.

Grundfos SLC and DLC pump control panels are designed for level control, monitoring and protection of pumps in wastewater, water supply and drainage systems.

SLC and DLC pump control panels are designed for emptying (water removal) applications. For boosting applications, see the Grundfos BoosterpaQ product line.

The SLC and DLC control panel product range comprises models up to 45 A / 15 hp (P2), direct-on-line starting (DOL).

Fig. 1 Grundfos DLC pump control panel

SLC - for one pump (Simplex)Float-switch-controlled option

The SLC, float-switch-controlled option, enables control of one (1) pump, utilizing the following inputs:

– high water-level alarm

– pump on

– pump off.

Transducer-controlled option

The SLC, transducer-controlled option, enables control of one (1) pump, utilizing an analog submersible level transducer with float-switch alarms:

– 4-20 mA (analog) water-level detection for duty and standby pump control

– high water-level alarm float switch

– low water-level alarm float switch.

DLC - for two pumps (Duplex)Float-switch-controlled option

The DLC, float-switch-controlled option, enables control of two (2) pumps, utilizing the following inputs:

– high water-level alarm

– duty pump on

– standby pump on

– pump(s) off.

Transducer-controlled option

The DLC, transducer-controlled option, enables control of two (2) pumps, utilizing an analog submersible level transducer with float-switch alarms:

– 4-20 mA (analog) water level detection for duty and standby pump control

– high water-level alarm float switch

– low water-level alarm float switch.TM

06

74

50

34

16

3

Page 4: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Ge

ne

ral d

es

crip

tion

SLC, DLC1

4

Features and benefitsThe SLC and DLC control panels are UL508a Listed as standard and incorporate the following items:

• a UL type 4X fiberglass hinged-door enclosure with dead-front inner door

• a programmable logic controller (PLC) with a dead-front, door-mounted, soft-button HMI operating panel (see fig. 3), displaying the following information for each pump:

– run time

– operating cycles (counter)

– seal-failure alarm

– high-temperature alarm.

• one (1) motor contactor per pump

• one (1) motor circuit protector per pump

• a 95 db audio alarm

• an Automatic-Manual-Off toggle switch for each pump

• an alarm beacon light

• a pump run light for each pump

• a specific pump alarm display text for each pump

• a push-to-silence alarm button

• auxiliary contacts (NO/NC) for alarm.

Additional options• Battery backup with charger (for alarm only)

• intrinsically safe with UL698A listing

• padlockable, supplemental main disconnect switch.

Fig. 2 Outer front door and dead-front inner door

Fig. 3 HMI operating panel with keypad and text display

TM

06

69

27

26

16

TM

06

68

47

25

16

Dead-frontinner door

Front door

Alarmbeacon

Page 5: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Ge

ne

ral

de

sc

rip

tio

n

SLC, DLC 1

Applications

Application examples

Fig. 4 Application examples

* As standard, transducer-controlled panels have high- and low-level float-switch backup inputs for pump operation and alarm conditions. It is optional to use these float switches.

TM

06

69

38

27

16

SLC, float-switch-controlled option

SLC, transducer-controlled option (analog, submersible transducer with float-switch backup)*

DLC, float-switch-controlled option

DLC, transducer-controlled option (analog, submersible transducer with float-switch backup)*

5

Page 6: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Ide

ntific

atio

n

SLC, DLC2

6

2. Identification

Nameplate

How to read the model designation

The actual control panel type, voltage variant, etc., are stated on the nameplate inside the control panel.

Fig. 5 Example of SLC nameplate

Fig. 6 Example of DLC nameplate

Panel model: ZGPCS230-3

Z = Electrical equipment

G = Grundfos

PC = Pump control panel

SD

=SimplexDuplex

230-3 = 230 V, 3-phase

TM

06

19

18

411

6T

M0

6 1

91

8 4

116

Page 7: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Ide

nti

fic

ati

on

SLC, DLC 2

Type key

Example Control SLC . 208/230 . A . 1 . B . 30/150 . T . FC

Type rangeControl SLC: Simplex control panelControl DLC: Duplex control panel

Voltage [V]208/230 V460 V575 V

Motor power [hp]

208-230 VA: 1.5 - 1.8 hpB: 2 - 7.5 hpC: 8-10 hpD: 12.5 - 15 hp

460 VE: 1.5 - 4 hpF: 5.5 - 10 hpD: 12.5 - 15 hp

575 VG: 1.5 hpH: 1.8 - 3 hpI: 4 - 5.5 hpJ: 7.5 hpC: 8-10 hpD: 12.5 - 15 hp

Phase1: Single-phase3: Three-phase

Operating current [A]

208/230 V - 460 VA: 2 - 6.3 AB: 5.7 - 18.9 AC: 9-30 AD: 15-45 A

575 VE: 1.6 - 2.5 AF: 2.5 - 4 AG: 4 - 6.3 AH: 6-10 AI: 9-14 AJ: 13-18 A

Run/starting capacitorBlank = no capacitor

OptionsT: Battery backupY: Intrinsically safe with UL698A listingZ: Padlockable main disconnect switch

Level detectionFC: Float-switch-controlledPT: Analog submersible pressure transducer-controlled

7

Page 8: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Pro

du

ct ra

ng

e

SLC, DLC3

8

3. Product range

SLC, float-switch-controlled option

SLC, transducer-controlled option

Description PhaseVoltage[VAC]

Motor shaft power[hp]

Overload range[A]

Main disconnect switch required

[A]Product number

SLC.208/230.B.1-FC 1 208/230 2.0 10.0 - 40.0 15 99165671

SLC.208/230.A.3.A-FC 3 208/230 1.5 - 1.8 2.0 - 6.3 15 99107775

SLC.208/230.B.3.B-FC 3 208/230 2.0 - 3.0 5.7 - 18.9 15 99107776

SLC.208/230.B.3.C-FC 3 208/230 2.0 - 7.5 9.0 - 30 30 99107777

SLC.208/230.C.3.D-FC 3 208/230 8.0 - 10.0 15.0 - 45.0 40 99107778

SLC.208/230.D.3.D-FC 3 208/230 12.5 - 15.0 15.0 - 45.0 60 99107779

SLC.460.E.3.A-FC 3 460 1.5 - 4.0 2.0 - 6.3 15 99107780

SLC.460.F.3.B-FC 3 460 5.5 - 10.0 5.7 - 18.9 20 99107781

SLC.460.D.3.C-FC 3 460 12.5 - 15.0 9.0 - 30.0 25 99107782

SLC.575.G.3.E-FC 3 575 1.5 1.6 - 2.5 15 99153139

SLC.575.H.3.F-FC 3 575 1.8 - 3.0 2.5 - 4.0 15 99153140

SLC.575.I.3.G-FC 3 575 4.0 - 5.5 4.0 - 6.3 15 99153141

SLC.575.J.3.H-FC 3 575 7.5 6.0 - 10.0 20 99153142

SLC.575.C.3.I-FC 3 575 8.0 - 10.0 9.0 - 14.0 20 99153143

SLC.575.D.3.J-FC 3 575 12.5 - 15.0 13.0 - 18.0 25 99153144

Description PhaseVoltage[VAC]

Motor shaft power[hp]

Overload range[A]

Main disconnect switch required

[A]Product number

SLC.208/230.B.1-PT 1 208/230 2.0 10.0 - 40.0 15 99165673

SLC.208/230.A.3.A-PT 3 208/230 1.5 - 1.8 2.0 - 6.3 15 99107059

SLC.208/230.B.3.B-PT 3 208/230 2.0 - 3.0 5.7 - 18.9 15 99107060

SLC.208/230.B.3.C-PT 3 208/230 2.0 - 7.5 9.0 - 30.0 30 99107061

SLC.208/230.C.3.D-PT 3 208/230 8.0 - 10.0 15.0 - 45.0 40 99107062

SLC.208/230.D.3.D-PT 3 208/230 12.5 - 15.0 15.0 - 45.0 60 99107063

SLC.460.E.3.A-PT 3 460 1.5 - 4.0 2.0 - 6.3 15 99107064

SLC.460.F.3.B-PT 3 460 5.5 - 10.0 5.7 - 18.9 20 99107065

SLC.460.D.3.C-PT 3 460 12.5 - 15.0 9.0 - 30.0 25 99107066

SLC.575.G.3.E-PT 3 575 1.5 1.6 - 2.5 15 99153151

SLC.575.H.3.F-PT 3 575 1.8 - 3.0 2.5 - 4.0 15 99153152

SLC.575.I.3.G-PT 3 575 4.0 - 5.5 4.0 - 6.3 15 99153153

SLC.575.J.3.H-PT 3 575 7.5 6.0 - 10.0 20 99153154

SLC.575.C.3.I-PT 3 575 8.0 - 10.0 9.0 - 14.0 20 99153155

SLC.575.D.3.J-PT 3 575 12.5 - 15.0 13.0 - 18.0 25 99153156

Page 9: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Pro

du

ct

ran

ge

SLC, DLC 3

DLC, float-switch-controlled option

DLC, transducer-controlled option

Additional options

**Enclosure adder is requiredNote: Seal-failure sensor(s), overtemperature sensor(s) are standard. Condition messages, such as run time, alarms and pump cycles are displayed on the HMI operating panel.

Description PhaseVoltage[VAC]

Motor shaft power[hp]

Overload range[A]

Main disconnect switch required

[A]Product number

DLC.208/230.B.1-FC 1 208/230 2.0 10.0 - 40.0 25 99165672

DLC.208/230.A.3.A-FC 3 208/230 1.5 - 1.8 2.0 - 6.3 20 99107783

DLC.208/230.B.3.B-FC 3 208/230 2.0 - 3.0 5.7 - 18.9 20 99107784

DLC.208/230.B.3.C-FC 3 208/230 2.0 - 7.5 9.0 - 30.0 50 99107785

DLC.208/230.C.3.D-FC 3 208/230 8.0 - 10.0 15.0 - 45.0 75 99107786

DLC.208/230.D.3.D-FC 3 208/230 12.5 - 15.0 15.0 - 45.0 120 99107787

DLC.460.E.3.A-FC 3 460 1.5 - 4.0 2.0 - 6.3 20 99107788

DLC.460.F.3.B-FC 3 460 5.5 - 10.0 5.7 - 18.9 40 99107789

DLC.460.D.3.C-FC 3 460 12.5 - 15.0 9.0 - 30.0 50 99107790

DLC.575.G.3.E-FC 3 575 1.5 1.6 - 2.5 15 99153145

DLC.575.H.3.F-FC 3 575 1.8 - 3.0 2.5 - 4.0 15 99153146

DLC.575.I.3.G-FC 3 575 4.0 - 5.5 4.0 - 6.3 20 99153147

DLC.575.J.3.H-FC 3 575 7.5 6.0 - 10.0 25 99153148

DLC.575.C.3.I-FC 3 575 8.0 - 10.0 9.0 - 14.0 30 99153149

DLC.575.D.3.J-FC 3 575 12.5 - 15.0 13.0 - 18.0 40 99153150

Description PhaseVoltage[VAC]

Motor shaft power[hp]

Overload range[A]

Main disconnect switch required

[A]Product number

DLC.208/230.B.1-PT 1 208/230 2.0 10.0 - 40.0 25 99165674

DLC.208/230.A.3.A-PT 3 208/230 1.5 - 1.8 2.0 - 6.3 20 99107067

DLC.208/230.B.3.B-PT 3 208/230 2.0 - 3.0 5.7 - 18.9 20 99107068

DLC.208/230.B.3.C-PT 3 208/230 2.0 - 7.5 9.0 - 30.0 50 99107069

DLC.208/230.C.3.D-PT 3 208/230 8.0 - 10.0 15.0 - 45.0 75 99107070

DLC.208/230.D.3.D-PT 3 208/230 12.5 - 15.0 15.0 - 45.0 120 99107071

DLC.460.E.3.A-PT 3 460 1.5 - 4.0 2.0 - 6.3 20 99107072

DLC.460.F.3.B-PT 3 460 5.5 - 10.0 5.7 - 18.9 40 99107073

DLC.460.D.3.C-PT 3 460 12.5 - 15.0 9.0 - 30.0 50 99107074

DLC.575.G.3.E-PT 3 575 1.5 1.6 - 2.5 15 99153157

DLC.575.H.3.F-PT 3 575 1.8 - 3.0 2.5 - 4.0 15 99153158

DLC.575.I.3.G-PT 3 575 4.0 - 5.5 4.0 - 6.3 20 99153159

DLC.575.J.3.H-PT 3 575 7.5 6.0 - 10.0 25 99153160

DLC.575.C.3.I-PT 3 575 8.0 - 10.0 9.0 - 14.0 30 99153161

DLC.575.D.3.J-PT 3 575 12.5 - 15.0 13.0 - 18.0 40 99153162

SLC and DLC Product number

**Battery backup with charger (for alarm only)

Consult factory

**Intrinsically safe relay for float inputs with UL698A Listing (FC only)

**Intrinsically safe barrier/relay for pressure transducer and backup floats, UL698A (PT only)

Padlockable main disconnect switch

Phase monitor with fusing

304 Stainless steel panel

Enclosure adder

9

Page 10: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Ac

ce

ss

orie

s

SLC, DLC4

10

4. Accessories

Float switchesSLC and DLC control panels are available with float switches for automatic level control. Grundfos float switches are of the non-mercury type and are available for standard and explosion-proof pumps. The hermetically sealed polypropylene housing and polyurethane cable make Grundfos float switches resistant to many chemicals, e.g. alcohol, uric acid, sewage, oils, gasoline and fruit acid.

SLCSLC can be fitted with up to three float switches:

• Minimum: Stops the pump.

• Maximum: Starts the pump.

• Alarm (optional): Indicates high water-level or pump failure.

DLCDLC can be fitted with up to four float switches:

• Minimum: Stops both pumps.

• Maximum 1: Starts one pump.

• Maximum 2: Starts the other pump.

• Alarm (optional): Indicates high water-level or pump failure.

Locating and positioning the float switchesThe float switches must be installed in the water collecting tank or pit floating on the pumped liquid. A float switch is an accepted way of controlling liquid levels in tanks, pits, etc.

The position of the float switches determines when SLC or DLC will start and stop the pump(s).

Function of the float switchesThe float switch, encased in a drop-shaped polypropylene housing is suspended at the desired height by its own three-core cable. When the liquid reaches a certain level, the float switch will tip either up or down, causing the contact to open or close.

• When the float switch is pointing up, the float switch contact will be closed and the pump will start.

• When the float switch is pointing down, the float switch contact will be opened and the pump will stop.

Fig. 7 Float-switch positions

TM

00

66

78

34

97

ON

OFF

Grundfos level switches for non-explosion risk environment Product number

TM

05

66

47

50

12

Grundfos float switch MS1 UL with 33 ft (10 m) cable 98365984

Grundfos float switch MS1 UL with 40 ft (12 m) cable 98365985

Grundfos float switch MS1 UL with 60 ft (18 m) cable 98365986

Cable support of stainless steel for two float switches 98365987

Grundfos level switches for explosion-risk environment Product number

Grundfos float switch MS1 Ex IECex with 33 ft (10 m) cable 98372085

Grundfos float switch MS1 Ex IECex with 40 ft (12 m) cable 98372086

Grundfos float switch MS1 Ex IECex with 60 ft (18 m) cable 98372087

Cable support of stainless steel for two float switches 98365987

Page 11: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Ac

ce

ss

ori

es

SLC, DLC 4

Submersible, analog level pressure transducer

Applications• Level measurement in rivers and lakes

• level measurement in vessel and storage systems

• control of sewage lifting and pumping stations

• monitoring of sewage, settling and storm water retention basins

• optimized for simple measuring requirements in level measurement

• suitable for permanent level measurement up to a 328 ft (100 m) water column.

Transducer features• Hermetically sealed, robust stainless-steel case

• fully-welded construction ensuring long life and permanent sealing

• enclosure class IP68

• 4-20 mA output as standard

• accuracy of 0.5 %

• 65 ft (19.8 m) PUR cable

• measuring range:0-9 psi (0 - 0.62 bar) / 0 - 20.1 ft (6.04 m)

• temperature ranges

– liquid: 14-122 °F (-10 to +50 °C)

– ambient: 14-122 °F (-10 to +50 °C)

– storage: -22 to +176 °F (-30 to +80 °C)

• power supply: DC 24 V.

Birdcage featuresThe birdcage sensor guard protects the sensor from floating debris. Its weight provides the sensor with stability, even in light turbulence.

• Birdcage maximum temperature:-4 to +212 °F (-20 to +100 °C)

• thread: G 1/2B

• weight: approximately 3 lb (1360 g)

• height: 1.97 in.

• diameter: 3.81 in.

• material: stainless steel AISI 304 (similar to EN 1.4301).

SLC or DLC with pressure transducer can be set up with float-switch backup.

You must order two float switches for optional high- and low-level backup of the transducer.

Fig. 8 Grundfos submersible, analog level pressure transducer kit (sensor and birdcage)

Fig. 9 Sensor dimensions

Fig. 10 Birdcage dimensions

TM

06

68

91

25

16

TM

06

68

96

26

16

TM

06

68

95

26

16

3.94

in. (

100

mm

)

0.393 in.(10 mm)

0.1.06 in.(27 mm)

G1/2B

0.708 in.(18 mm)

3.81 in. (97 mm)

1.97

in. (

50 m

m)

3.81

in. (

97 m

m)

Wt 3 lb(1360 g)

0.20 in.(5 mm)

0.79 in.(20 mm)

Grundfos submersible, analog level pressure transducer kit. See fig. 8. Product number

65 ft (19.8 m) PUR cable,0-9 psi (0 - 0.62 bar) / 0 - 20.1 ft (6.1 m) measuring range,stainless-steel birdcage.

99045076

11

Page 12: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Fu

nc

tion

s

SLC, DLC5

12

5. Functions

The SLC and DLC control panels include an easy-to-use programmable logic unit that incorporates many timing and logic functions.

The pump control panel features alarm and data screens to assist with monitoring and troubleshooting. The up- and down-arrow buttons allow you to navigate between the screens.

See the following table and screen navigation section for more details.

The alarm screen will only be displayed when alarms are active. The alarm screen shows the date and time when the alarm started.

SLC, float-switch-controlled option

SLC, transducer-controlled option

Alarm screen Alarm text Description

1 High Level Alarm High-level alarm

2 Pump Fail Alarm Pump-failure alarm

Data screen System data Description

3 Pump CT & ETM Pump cycles are shown at the top of the screen and the pump run time beneath

4 High Lvl CT High-level alarm events

5 Power Fault Counters Power failures are shown at the top of the screen and the hours in service beneath

6 Pump Fault Counters Pump-failure events

Alarm screen Alarm text Description

1 Xducer Sig Is activated when the transducer signal is below 3 mA

2 High Level Alarm When lifted, this float switch activates the alarm indication on the screen and the audible alarm.

3 Low Level Alarm When lowered, this float switch stops the pump and activates the indication on the screen.

4 Pump Fail AlarmIs activated when the pump overtemperature sensor, seal-failure sensor or overload relay has tripped.

Data screen System data Description

5 Current Tank Level Liquid level in tank or pit in feet

6 Pump CT & ETMThe pump cycle counter is shown at the top of the screen and the pump run time in minutes beneath

7 High Lvl CT & Low Level CTThe high-level alarm counter is shown at the top of the screen and low-level alarm counter beneath

8 Power Faults & Operating Hr The power failure counter is shown at the top of the screen and operating hours beneath

9 Transducer Signal "Raw value of transducer reading", in mA

10 On/Off Level Settings Pump-on and -off level setpoints

11 High/Low Level Settings High- and low-level alarm setpoints

12 Transducer Input Transducer range and offset settings

13 Minimum Run Time Minimum pump run time per cycle

14 High Level Pump Run Time Minimum high level pump run time per cycle

15 High Level Alarm Delay Elapsed time between high level point and alarm activation

Page 13: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Fu

nc

tio

ns

SLC, DLC 5

DLC, float-switch-controlled optionThe alarm screen will only be displayed when alarms are active. The alarm screen shows the date and time when the alarm started.

DLC, transducer-controlled optionThe alarm screen will only be displayed when alarms are active. The alarm screen shows the date and time when the alarm started.

Alarm screen Alarm text Description

1 High Level Alarm High level alarm

2 Pump 1 Fail Alarm Pump 1 failure alarm

3 Pump 2 Fail Alarm Pump 2 failure alarm

Data screen System data Description

4 Pump 1 CT & ETM Pump 1 cycles are shown at the top of the screen and pump 1 run time beneath

5 Pump 2 CT & ETM Pump 2 cycles are shown at the top of the screen and pump 2 run time beneath

6 High Lvl CT High level alarm events

7 Pump 1 & 2 Lag Event CountersPump 1 lag (standby) events are shown at the top of the screen and pump 2 lag (standby) events beneath

8 Power Fault Counters Power failures are shown at the top of the screen and hours in service beneath

9 Pump 1 & 2 Fault Counters Pump 1 failure events are shown at the top of the screen and pump 2 failure events beneath

Alarm screen Alarm text Description

1 Xducer Sig Is activated when the transducer signal is below 3 mA

2 High Level Alarm When lifted, this float switch activates the alarm indication on the screen and the audible alarm.

3 Low Level Alarm When lowered, this float switch stops the pump and activates the indication on the screen.

4 Pump 1 Fail AlarmIs activated when pump 1 overtemperature sensor, seal failure sensor or overload relay has tripped.

5 Pump 2 Fail AlarmIs activated when pump 2 overtemperature sensor, seal failure sensor or overload relay has tripped

Data screen System data Description

6 Current Tank Level Liquid level in tank or pit in feet

7 Pump 1 CT & ETM Pump 1 cycle counter is shown at the top of the screen and pump 1 run time in minutes beneath

8 Pump 2 CT & ETM Pump 2 cycle counter is shown at the top of the screen and pump 2 run time in minutes beneath

9 High Lvl CT & Low Level CT High level alarm counter is shown at the top of the screen and low level alarm counter beneath

10 Power Faults & Operating Hr Power failure counter is shown at the top of the screen and operating hours beneath

11 Transducer Signal Raw value of transducer reading, in mADC

12 On/Off Level Settings Pump on and off level setpoints

13 Lag Level Setting Lag (standby) pump on level setpoint

14 High/Low Level Settings High- and low-level alarm setpoints

15 Transducer Input Transducer range and offset settings

16 Minimum Run Time Minimum pump run time per cycle

17 High Level Pump Run Time Minimum high level pump run time per cycle

18 High Level Alarm Delay Elapsed time between high level point and alarm activation

13

Page 14: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Fu

nc

tion

s

SLC, DLC5

14

Digital input and output screensThe pump control panel will activate various input and output screens as it operates. See fig. 11. These screens are a helpful when installing and troubleshooting the control panel. The input screens will vary according to the mode of operation of the panel.

See the following tables to identify the conditions that activate the various screens.

Fig. 11 Example, digital input and output screens

SLC, float-switch-controlled option

SLC, transducer-controlled option

TM

06

72

17

29

16

Input screen Function Activation condition

1 Pump Off Float Float switch in up position

2 Pump On Float Float switch in up position

3 High Level Alarm Float Float switch in up position

4 Push To Silence Push button is pressed

5 Pump Fault Pump seal-failure sensor, overtemperature sensor, or overload protection has tripped.

Output screen Function Activation condition

6 Pump Pump is called to run

7 Alarm Light Alarm light is activated

8 Audible Alarm Audible alarm is activated

Input screen Function Activation condition

1 Redundant Off and Low Level Alarm Float Float switch in up position

2 High Level Float Float switch in up position

3 Push to Silence Push button is pressed

4 Pump Fault Pump seal-failure sensor, overtemperature sensor, or overload protection has tripped.

5 Not Used NA

6 Not Used NA

7 Transducer (analog signal) 4-20 mADC

Output screen Function Activation condition

8 Pump 1 Pump is called to run

9 Pump 2 Pump is called to run

10 Level Alarm Light Level alarm condition exists

11 Audible Alarm Audible alarm is activated

Activated input

Inputs 1-9

Inputs 10-19

Inputs 20-24

Input screen Output screen

Outputs 1-9

Outputs 10-16

Activated output

Page 15: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Fu

nc

tio

ns

SLC, DLC 5

DLC, float-switch-controlled option

DLC, transducer-controlled option

Inputs Function Activation condition

1 Pump(s) Off Float Float switch in up position

2 Lead Pump On Float Float switch in up position

3 Lag Pump On Float Float switch in up position

4 High Level Alarm Float Float switch in up position

5 Push To Silence Push button is pressed

6 Pump 1 Fault Pump 1 seal-failure sensor, overtemperature sensor, or overload protection has tripped.

7 Pump 2 Fault Pump 2 seal-failure sensor, overtemperature sensor, or overload protection has tripped.

Outputs Function Activation condition

8 Pump 1 Pump is called to run

9 Pump 2 Pump is called to run

10 Alarm Light Alarm light is activated

11 Audible Alarm Audible alarm is activated

Input screen Function Activation condition

1 Redundant Off and Low Level Alarm Float Float switch in up position

2 High Level Float Float switch in up position

3 Push to Silence Push button is pressed

4 Pump 1 Fault Pump 1 seal-failure sensor, overtemperature sensor, or overload protection has tripped.

5 Pump 2 Fault Pump 2 seal-failure sensor, overtemperature sensor, or overload protection has tripped.

6 Not Used NA

7 Transducer (analog signal) 4-20 mADC

Output screen Function Activation condition

8 Pump 1 Pump is called to run

9 Pump 2 Pump is called to run

10 Level Alarm Light Level alarm condition exists

11 Audible Alarm Audible alarm is activated

15

Page 16: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Fu

nc

tion

s

SLC, DLC5

16

Screen navigationThe screens are arranged in the order shown in fig. 12. You can use the up and down arrow buttons to navigate between the screens. Frequently used screens are outlined in bold. Some screens may not be applicable.

Fig. 12 Screen navigation

TM

06

72

18

311

6

System alarm screen

System data screen

Time and Date

Digital Inputs(1-24)

Digital Outputs(1-16)

Analog Inputs(1-3)

Analog Inputs(4-6)

Analog Inputs(7-8)

Analog Outputs

(1-2)

Memory(1-27)

ESC+C

Page 17: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Fu

nc

tio

ns

SLC, DLC 5

Control panel operation

SLC, float-switch-controlled optionThe control panel supports two different modes of operation based on selected parameter settings. See Adjustable parameters on page 22 for information on how to change the mode of operation and other adjustable parameters.

Your control panel can perform the functions listed below. Depending on the application, some functions may be omitted or combined.

* To determine a pump seal failure, overtemperature or overload trip, open the dead-front inner door and look for the following relay conditions:Overload relay = When the overload relay trips, the trip indicator is present on the device. The overload relay can be reset by pressing the blue reset button. The overload relay can be switched to manual or automatic resetting.K02 = This relay is active when the overtemperature sensor in the pump has tripped.K03 = This relay is active when the seal-failure sensor in the pump has tripped.

High Level Alarm

• This float switch activates the alarm indication on the screen and the audible alarm when lifted for longer than the high-level alarm delay.

• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the float switch is lowered, and the audible alarm will

reactivate in 12 hours if the alarm condition is not corrected.

Pump On• This float switch starts the pump when lifted.• The pump will run for the duration of the minimum run time or until the pump-off float switch (if used) is lowered.

Pump Off • This float switch stops the pump(s) when lowered if the minimum run time has elapsed.

Pump Fault*

• The pump failure is activated when the pump overtemperature sensor, seal failure sensor, or overload protection has tripped.

• A pump failure will activate the alarm indictor light, the audible alarm, and an alarm message on the user's screen.• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.

17

Page 18: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Fu

nc

tion

s

SLC, DLC5

18

SLC, transducer-controlled optionThe control panel can perform the functions listed below. Depending on the number of float switches for your application, some functions may be omitted or combined.

* To determine a pump seal failure, overtemperature or overload trip, open the dead-front inner door and look for the following relay conditions:Overload relay = When the overload relay trips, the trip indicator is present on the device. The overload relay can be reset by pressing the blue reset button. The overload relay can be switched to manual or automatic resetting.K02 = This relay is active when the overtemperature sensor in the pump has tripped.K03 = This relay is active when the seal-failure sensor in the pump has tripped.

High Level Alarm

• This preset level activates the alarm indication on the screen and the audible alarm when the liquid level is high for longer than the high-level alarm delay (factory-set for 5 seconds).

• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the level is lowered, and the audible alarm will reactivate in

12 hours if the alarm condition is not corrected.

Pump On• The pump will start at the preset pressure of the level sensor for pump operation.• The pump will run until the level sensor pressure is reduced below the preset pump-off level.

Pump Off• The pump will stop when the level sensor pressure falls below the preset pump-off level if the minimum time delay

has elapsed.

Redundant Off and Low Level alarm

• The pump will stop when the liquid level is lowered to this level for more than two seconds.• Pumping will be disabled in both the automatic modes.• The alarm indication on the screen and the audible alarm will be activated.• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the liquid level is raised.• The audible alarm will reactivate in 12 hours if the alarm condition is not corrected.

Transducer Failure• If the transducer signal drops below 3 mADC, a transducer failure alarm will be activated.• The alarm indication on the screen and the audible alarm will be activated.• A message will be shown on the screen.

Backup floats

High Level Alarm

• This float switch activates the alarm indication on the screen and the audible alarm when lifted for longer than the high-level alarm delay (factory set for 5 seconds).

• This float switch also starts the pump.• The pump will run until the high-level pump run time has elapsed.• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the float switch is lowered, and the audible alarm will

reactivate in 12 hours if the alarm condition is not corrected.

Redundant Off and Low Level Alarm

• This float switch stops the pump when lowered for more than two seconds.• This float switch is a backup float switch which will operate if the transducer fails.• Pumping will be disabled in both the automatic and manual modes.• This float switch also activates the alarm indication on the screen and the audible alarm.• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the float switch is lifted.• The audible alarm will reactivate in 12 hours if the alarm condition is not corrected.

Pump Fault*

• The pump failure is activated when the pump overtemperature sensor, seal failure sensor, or overload relay has tripped.

• A pump failure will activate the alarm indication on the screen, the audible alarm, and an alarm message on the user's screen.

• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.

Page 19: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Fu

nc

tio

ns

SLC, DLC 5

DLC, float-switch-controlled optionThe control panel supports two different modes of operation based on selected parameter settings. See Adjustable parameters on page 22 for information on how to change the mode of operation and other adjustable parameters.

Your control panel can perform the functions listed below. Depending on the application, some functions may be omitted or combined.

* To determine a pump seal failure, overtemperature or overload failure trip, open the dead-front inner door and look for the following relay conditions:Overload relay = When the overload relay trips, the trip indicator is present on the device. The overload relay can be reset by pressing the blue reset button. The overload relay can be switched to manual or automatic resetting.K02 = This relay is active when the overtemperature sensor in the pump has tripped.K03 = This relay is active when the seal-failure sensor in the pump has tripped.K04 = This relay is active when the overtemperature sensor in the pump has tripped.K05 = This relay is active when the seal-failure sensor in the pump has tripped.

High Level Alarm

• This float switch activates the alarm indication on the screen and the audible alarm when lifted for longer than the high-level alarm delay.

• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the float switch is lowered, and the audible alarm will

reactivate in 12 hours if the alarm condition is not corrected.

Lag Pump On• This float switch starts the lag (standby) pump when lifted (both pumps will be on).• Both pumps will run until the pump(s) off float switch (if used) is lowered.

Lead Pump On• This float switch starts the lead (duty) pump when lifted.• The pump will run for the duration of the minimum run time or until the pump(s) off float switch (if used) is lowered.

Pump(s) Off • This float switch stops the pump(s) when lowered if the minimum run time has elapsed.

Pump Fault*

• The pump failure is activated when the pump overtemperature sensor, seal failure sensor, or overload relay has tripped.

• A pump failure will activate the alarm indication on the screen, the audible alarm, and an alarm message on the user's screen.

• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.

19

Page 20: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Fu

nc

tion

s

SLC, DLC5

20

DLC, transducer-controlled optionThe control panel can perform the functions listed below. Depending on the number of float switches for your application, some functions may be omitted or combined.

* To determine a pump seal failure, overtemperature or overload failure trip, open the dead-front inner door and look for the following relay conditions:Overload relay = When the overload relay trips, the trip indicator is present on the device. The overload relay can be reset by pressing the blue reset button. The overload relay can be switched to manual or automatic resetting.K02 = This relay is active when the overtemperature sensor in the pump has tripped.K03 = This relay is active when the seal-failure sensor in the pump has tripped.K04 = This relay is active when the overtemperature sensor in the pump has tripped.K05 = This relay is active when the seal-failure sensor in the pump has tripped.

High Level Alarm

• This preset level activates the alarm indication on the screen and the audible alarm when the level is high for longer than the high-level alarm delay (factory set for 5 seconds).

• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the level is lowered, and the audible alarm will reactivate in

12 hours if the alarm condition is not corrected.

Lag Pump On• The lag (standby) pump (both pumps will be on) will start at the preset pressure of the level sensor for lag

(standby) operation.• Both pumps will continue to run together until the level sensor pressure reduces below the preset Pumps Off level.

Lead Pump On• The lead (duty) pump will start at the preset pressure of the level sensor for lead (duty) pump operation.• The lead (duty) pump will run until the level sensor pressure is reduced below the preset pumps-off level.

Pumps Off• Both pumps will stop when the level sensor pressure is reduced below the preset pumps-off level if the delay has

elapsed.

Redundant Off & Low Level Alarm

• The pumps will stop when the liquid level is lowered to this level for more than two seconds.• Pumping will be disabled in both the automatic modes.• The alarm indication on the screen and the audible alarm will be activated.• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the liquid level is raised.• The audible alarm will reactivate in 12 hours if the alarm condition is not corrected.

Transducer Failure• If the transducer signal drops below 3 mADC, a transducer failure alarm will be activated.• The alarm indication on the screen and the audible alarm will be activated.• A message will be shown on the screen.

Backup floats

High Level Alarm

• This float switch activates the alarm indication on the screen and the audible alarm when lifted for longer than the high-level alarm delay (factory set for 5 seconds).

• This float switch also starts both pumps. Both pumps will run until the high-level pump run time has elapsed.• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the float switch is lowered, and the audible alarm will

reactivate in 12 hours if the alarm condition is not corrected.

Redundant Off and Low Level Alarm

• This float switch stops the pumps when lowered for more than two seconds.• This float switch is a backup float switch which will operate if the transducer fails.• Pumping will be disabled in both the automatic and manual modes.• This float switch also activates the alarm indication on the screen and the audible alarm.• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.• The alarm indication on the screen will remain on until the float switch is lifted. • The audible alarm will reactivate in 12 hours if the alarm condition is not corrected.

Pump Fault*

• The pump failure is activated when the pump overtemperature sensor, seal failure sensor, or overload relay has tripped.

• A pump failure will activate the alarm indication on the screen, the audible alarm, and an alarm message on the user's screen.

• Press the Push-to-Silence button on the side of the control panel to silence the audible alarm.

Page 21: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Fu

nc

tio

ns

SLC, DLC 5

Pump alternationDLC pump control panels support four different modes of operation relating to pump alternation which are based on selected parameter settings. Additionally, the panel can be set to alternate pumps in the event of a failure.

See Adjustable parameters on page 22 for information on how to adjust these parameters.

Alternating (default)• Parameters "Pmp1Lead" and "Pmp2Lead" are set to "Off".• The (duty) and lag (standby) pumps will alternate for each cycle.• This mode provides equal wear on both pumps and is recommended for most applications.

Pump 1 Lead

• Parameter "Pmp1Lead" is set to "On" and parameter "Pmp2Lead" is set to "Off".• The lead (duty) pump function is locked to pump 1 and the lag (standby) pump function is locked to pump 2.• No alternation will occur.• Pump 1 will be the primary pump for the system.• Pump 2 will only be used during high-flow conditions.

Pump 2 Lead

• Parameter "Pmp1Lead" is set to "Off" and parameter "Pmp2Lead" is set to "On".• The lead (duty) pump function is locked to pump 2 and the lag (standby) pump function is locked to pump 1.• No alternation will occur.• Pump 2 will be the primary pump for the system.• Pump 1 will only be used during high flow conditions.

Both Pumps • Parameters "Pmp1Lead" and "Pmp2Lead" are set to "On". Both pumps will run in every cycle.

21

Page 22: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Fu

nc

tion

s

SLC, DLC5

22

Adjustable parametersSLC and DLC pump control panels include an easy-to-use programmable logic unit that incorporates many timing and logic functions.

The unit has been programmed from factory for the control functions required. The unit includes adjustable operational parameters and viewable monitoring information. Some operational parameters may need changing for your particular application.

SLC and DLC pump control panels use block names to identify the various parameters. Please refer to the screen of the logic controller face inside the enclosure.

Block names, SLC float-switch-controlled optionThe following block names are used for SLC, float-switch-controlled option.

All adjustable parameters DO NOT use the same type of blocks. Check the block types below to determine which steps apply to your application.

Block names, SLC, transducer-controlled optionThe following block names are used for SLC, transducer-controlled option.

All adjustable parameters DO NOT use the same type of blocks. Check the block types below to determine which steps apply to your application.

Block names Description Factory default setting Time range Block Type Timed/Demand

HLA Dly High-level alarm delay 5 seconds MM:SS Timer Both

MinRunT Minimum pump run time 1 second MM:SS Timer Demand

Screen names DescriptionUnits of

measurementDefault setting

On Level Tank level at which the lead (duty) pump starts. feet 12.0

Off Level Tank level at which the pump stops. feet 9.0

High Level Alarm Tank level at which the high-level alarm is activated. feet 14.0

Low Level Alarm Tank level at which the low-level alarm is activated. feet 3.0

Xducer RangeThe full range of the transducer (NOT the tank height), i.e. the 4-20 mA signal from the transducer equals 0 - Xducer Range.

feet 15.0

Xducer Offset The distance between the bottom of the transducer and the bottom of the tank. feet 0.5

Minimum Run Time The minimum pump run time for an automatic cycle. seconds 2.0

High Level Pump Run Time The minimum pump run time during a high-level state. minutes 1.0

High Level Alarm Delay The time between the high-level state and alarm status. seconds 5.0

Page 23: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Fu

nc

tio

ns

SLC, DLC 5

Block names, DLC, float-switch-controlled optionThe following block types are used.

All adjustable parameters DO NOT use the same type of blocks. Check the block types below to determine which steps apply to your application.

Block names, DLC, transducer-controlled optionThe following block types are used.

All adjustable parameters DO NOT use the same type of blocks. Check the block types below to determine which steps apply to your application.

Block names Description Factory default setting Time range Block Type Timed/Demand

HLA Dly High-level alarm delay 5 seconds MM:SS Timer Both

MinRunT Minimum pump run time 1 second MM:SS Timer Demand

Pmp1Lead Pump 1 as lead (duty) pump Off On/Off Soft button Both

Pmp2Lead Pump 2 as lead (duty) pump Off On/Off Soft button Both

Screen names DescriptionUnits of

measurementDefault setting

On Level Tank level at which the lead (duty) pump starts. feet 12.0

Off Level Tank level at which the lead (duty) pump stops. feet 9.0

Lag Level Tank level at which the lag (standby) pump starts feet 13.0

High Level Alarm Tank level at which the high-level alarm is activated. feet 14.0

Low Level Alarm Tank level at which the low-level alarm is activated. feet 3.0

Xducer RangeThe full range of the transducer (NOT the tank height), i.e. the 4-20 mA signal from the transducer equals 0 - Xducer Range.

feet 15.0

Xducer Offset The distance between the bottom of the transducer and the bottom of the tank. feet 0.5

Minimum Run Time The minimum pump run time for an automatic cycle. seconds 2.0

High Level Pump Run Time The minimum pump run time during a high-level state. minutes 1.0

High Level Alarm Delay The time between the high-level state and alarm status. seconds 5.0

DLC adjustable parameter soft-button blocks

Block names Description Factory default setting Block type

Pmp1Lead Pump 1 as lead (duty) pump Off Soft button

Pmp2Lead Pump 2 as lead (duty) pump Off Soft button

23

Page 24: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Co

ns

truc

tion

SLC, DLC6

24

6. Construction

SLCThe description covers all SLC models, both float-switch-controlled and transducer-controlled.

Note: During a pump failure, check the relays to determine pump overtemperature or seal failure. The relay LED will be on, if active.

CR1 = Pump overtemperature

CR2 = Pump seal failure.

TM

06

68

61

37

16

HIGH LEVELALARM

During a pump faultcheck the relays to

determine over tempor seal fail. The relaysLED will be on if "OK".

G

PUMP RUN

F1 F2 F3 F4

LOGO! TD

HAND OFF AUTO

K02 = P1 OvertempK03 = P1 Seal FailK04 = P2 OvertempK05 = P2 Seal Fail

ESC OK

35

0ff/O

L N

+V-V

i

17.31 in. (440 mm)

19.3

1 in

. (49

0 m

m)

18.7

4 in

. (47

6 m

m)

pane

l mou

ntin

g

12 in. (305 mm)panel mounting

9.58

in. (

243

mm

)

1

2

3

5

4

6

7 8 910

12

1617

14

11 13

15

Dead-front inner-door layout

FRP Type 4X enclosureFiberglass

Front door layout

Back panel layout

Side view

Bottom view

Panel mounting

Pos. Description

1 Alarm beacon and alarm indicator

2 Keypad and text display

3 Pump run indicator

4 Hand - Off - Auto switch

5 Push-to-Silence alarm button

6 Audible alarm

7 Transformer

8 Fuses

9 Control panel circuit breaker

10 Pump circuit breaker

11 PLC

12 Relays

13 DC power supply

14 Motor starter

15 Overload relay

16 Terminals

17 Main power distribution blocks

Page 25: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Co

ns

tru

cti

on

SLC, DLC 6

DLCThe description covers all DLC models, both float-switch-controlled and transducer-controlled.

Note: During a pump failure, check the relays to determine pump overtemperature or seal failure. The relay LED will be on, if active.

K02 = Pump 1 overtemperature

K03 = Pump 1 seal failure

K04 = Pump 2 overtemperature

K05 = Pump 2 seal failure.

TM

06

68

60

37

16

HAND OFF AUTO

During a pump fault check the relays to

determine over temp or seal fail. The relays LED will be on if "OK".

GG

PUUMP 1 RUN PUMP 2 RUN

F1 F2 F3 F4

LOGO! TD

HAND OFF AUTO

K02 = P1 OvertempK03 = P1 Seal FailK04 = P2 OvertempK05 = P2 Seal Fail

ESC OK

X 23 4

wohner

+V-V

OUTPUT30W

HIGH LEVELALARM

FRP Type 4X enclosureFiberglass

Front door layout

Dead-front inner-door layout

Back panel layout

Side view

Bottom view

Panel mounting

Pos. Description

1 Alarm beacon and alarm indicator

2 Keypad and text display

3 Pump 2 run indicator

4 Hand - Off - Auto switch, pump 2

5 Pump 1 run indicator

6 Hand - Off - Auto switch, pump 1

7 Push-to-Silence alarm button

8 Audible alarm

9 Transformer

10 Fuses

11 Pump circuit breaker

12 PLC

13 Relays

14 DC power supply

15 Motor starters

16 Overload relay

17 Terminals

18 Main power distribution blocks

25

Page 26: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Wirin

g d

iag

ram

s

SLC, DLC7

26

7. Wiring diagrams

SLC, float-switch-controlled option

Fig. 13 Wiring diagram, SLC with float switches

TM

06

68

55

25

16

H*H1

X1 X2

F1 F2

L1 N

+ -

L1

L3

L2 T2L2

T1L1

L3 T3

OLRxxA

CB xxA K11

1

CB 10A

L+ M

i5

1 i14

NIBP

21 22K02

i6

+ -

L1

L2

L3

i334

i224

21 22K03

98

K011112 1411

10

K11A1

Q1

Q4

+ -A

A2

K02A2A1

GX2X1

11 14K02

K03A2A1

6 596 95

OLR

R

K01A2A1

7

11 14K03

Q3

Factory wireField wire

PumpXXX VAC, 3-phase, XX hp

High-level alarm float switch

Pump on float switch

Pump off float switch

Pump fault

Pump overtemperature sensor

Seal sensor

Push-to-Silence alarm

Fuses 2A

Control panel transformerXXXV - 120 V, 100 VA

Control panel115 VAC

PLC text display

24 VDC power supply

PLC

Motor contactor

Pump run light

Beacon alarm light

Alarm relay

Audible alarm

Pump overload relay or overtemperature sensor

Pump seal-failure sensor

Hand Auto

OFF

From main power panelXXX VAC, 3-phase, 60 HzMain disconnect switch provided by others

Ground wire

To LOGO

From display screen

24 Vpower supply

LOGO

Alarm contact

Page 27: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Wir

ing

dia

gra

ms

SLC, DLC 7

SLC, transducer-controlled option

Fig. 14 Wiring diagram, SLC with submersible analog level pressure transducer

TM

06

68

58

25

16

H*H1

X1 X2

F1 F2

L1 N

+ -

L1

L3

L2 T2L2

T1L1

L3 T3

OLRxxA

CB xxA K11

1

CB 10A

L+ M

i5

NIBP

21 22K02

i6

+ -

L1

L2

L3

21 22K03

1 i1

i2

i8

500Ohm

3

23

Trans+

24V --

87

K011112 1411

9

K11A1

Q1

Q4

+ -A

A2

K02A2A1

GX2X1

11 14K02

K03A2A1

5 496 95

OLR

R

K01A2A1

6

11 14K03

Q3

Factory wireField wire

PumpXXX VAC, 3-phase, XX hp

High-level alarm float switch

Pressure transducer

Low-level alarm float switch

Pump failure

Pump over-temperature sensor

Seal sensor

Push-to-Silence alarm

Fuses 2A

Control panel - transformerXXXV - 120 V, 100 VA

Controls115 VAC

PLCtext display

24 VDCpower supply

PLC

Motor contactor

Pump run light

Beacon alarm light

Alarm relay

Audible alarm

Pump overload relay or overtemperature sensor

Pump seal-failure sensor

Hand Auto

OFF

From main power panelXXX VAC, 3-phase, 60 HzMain disconnect switch provided by others

Ground wire

To LOGO

Fromdisplay screen

24 Vpower supply

Alarm contact

LOGO

27

Page 28: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Wirin

g d

iag

ram

s

SLC, DLC7

28

DLC, float-switch-controlled option

Fig. 15 Wiring diagram, DLC with float switches

TM

06

68

54

25

16

1312

K011112 1411

14

K11A1

Q1

K12

Q2

Q3

Q4

+ -A

A2

A1 A2

K02A2A1

GX2X1

GX2X1

11 14K02

11 14K04

21 22K04

i7

K03A2A1

7 6

K04A2A1

K05A2A1

10 9

11

96 95OLR1

96 95OLR2

R

K01A2A1

8

11 14K03

11 14K05

21 22K03

21 22K03

H*H1

X1 X2

F1 F2

L1 N

+ -

L1

L3

L2

CB xxA

T2L2

T1L1

L3 T3

T2L2

T1L1

L3 T3

OLR2XXA

OLR1xxA

CB xxA K11

K12

1

2

CB 10A

L+ M

i5

1 i1

i4

5

45

NIBP

21 22K02

i6

+ -

L1

L2

L3

i335

i225

Factory wireField wire

PumpsXXX VAC, 3-phaseXX hp

High-level alarm float switch

Standby pump on float switch

Duty pump on float switch

Pumps-off float switch

Pump 1 failure

Pump 2 failure

Pump 1 over-temperature sensor

Seal sensor 1

Pump 2 over-temperature sensor

Seal sensor 2

Push-to-Silence alarm

Fuses 2A

Controls - transformerXXXV - 120 V, 100 VA

Control panel 115 VAC

PLC text display

24 VDCpower supply

PLC

Motor contactor

Pump run light

Motor contactor

Pump run light

Beacon Alarm Light

Alarm relay

Audible Alarm

Alarm contact

Pump 1 overload relay or overtemperature sensorPump 1 seal-failure sensor

Hand

Hand

Auto

Off

Off

Auto

From main power panelXXX VAC, 3-phase, 60 HzMain disconnect switch provided by others.

Ground wire

To LOGO

From display screen

24 Vpower supply

LOGO

Pump 2 overload relay or overtemperature sensorPump 2 seal-failure sensor

Page 29: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Wir

ing

dia

gra

ms

SLC, DLC 7

DLC, transducer-controlled option

Fig. 16 Wiring diagram, DLC with submersible analog level pressure transducer

TM

06

68

59

26

16

H*H1

X1 X2

F1 F2

L1 N

+ -

L1

L3

L2

CB xxA

T2L2

T1L1

L3 T3

T2L2

T1L1

L3 T3

OLR2XXA

OLR1xxA

CB xxA K11

K12

1

2

CB 10A

L+ M

i5

NIBP

21 22K02

i6

+ -

L1

L2

L3

1 i1

i2

i8

500Ohm

3

23

Trans+

24V --

1110

K011112 1411

12

K11A1

Q1

K12

Q2

Q3

Q4

+ -A

A2

A1 A2

K02A2A1

GX2X1

GX2X1

11 14K02

11 14K04

21 22K04

i7

K03A2A1

5 4

K04A2A1

K05A2A1

8 7

9

96 95OLR1

96 95OLR2

R

K01A2A1

6

11 14K03

11 14K05

21 22K03

21 22K03

Factory wireField wire

PumpsXXX VAC, 3-phaseXX hp

Pump 1 over-temperature sensor

Seal sensor 1

Pump 2 over-temperature sensor

Seal sensor 2

Fuses 2A

Control panel - transformerXXXV - 120 V 100 VA

Controls115 VAC

PLC text display

24 VDC power supply

PLC

Motor contactor

Pump run light

Motor contactor

Pump run light

Beacon Alarm Light

Alarm relay

Audible Alarm

Alarm contact

Pump 1 overload relay or overtemperature sensor

Pump 1 seal-failure sensor

Pump 2 overload relay or overtemperature sensor

Hand

Hand

Auto

Off

Off

Auto

From main power panelXXX VAC, 3-phase, 60 HzMain disconnect switch provided by others

Ground wire

To LOGO

Fromdisplay screen

24 Vpower supply

Pump 2 seal-failure sensor

LOGO

High-level alarm float switch

Pressure transducer

Low-level alarm float switch

Pump 1 failure

Push-to-Silence alarm

Pump 2 failure

29

Page 30: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Te

ch

nic

al d

ata

SLC, DLC8

30

8. Technical data

Voltage tolerance:- 15 %/+ 10 % of rated voltage (3 x 208/230 VAC, 3 x 460 VAC, 3 x 575 VAC)

+ 10 %/- 1 % of rated voltage (1 x 230 VAC)

Mains frequency: 60 Hz

Ambient temperature:• During operation: - 22 °F to +122 °F (- 30 °C to +50 °C)

(must not be exposed to direct sunlight)

• During transport and storage: - 22 °F to +140 °F (- 30 °C to + 60 °C)

Enclosure class: NEMA4X

Outputs for alarm devices:Max. 120 VAC / max. 8 A / min. 10 mA / AC 1NO/NC contact

Approvals: Listed per UL 508A

Page 31: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Gru

nd

fos

Pro

du

ct

Ce

nte

r

SLC, DLC 9

31

9. Grundfos Product Center

Subject to alterations.

All the information you need in one place Downloads

Performance curves, technical specifications, pictures, dimensional drawings, motor curves, wiring diagrams, spare parts, service kits, 3D drawings, documents, system parts. The Product Center displays any recent and saved items — including complete projects — right on the main page.

On the product pages, you can download Installation and Operating Instructions, Data Booklets, Service Instructions, etc. in PDF format.

"SIZING" enables you to size a pump based on entered data and selection choices.

Online search and sizing tool to help you make the right choice.

http://product-selection.grundfos.com

"REPLACEMENT" enables you to find a replacement product.Search results will include information on

• the lowest purchase price• the lowest energy consumption• the lowest total life cycle cost.

"CATALOG" gives you access to the Grundfos product catalog.

"LIQUIDS" enables you to find pumps designed for aggressive, flammable or other special liquids.

Page 32: SLC, DLC - Grundfosnet.grundfos.com/Appl/ccmsservices/public/literature/... · General description SLC, DLC 1 5 Applications Application examples Fig. 4 Application examples * As

Th

e n

am

e G

run

dfo

s, t

he

Gru

nd

fos

log

o,

an

d b

e t

hin

k i

nn

ov

ate

are

re

gis

tere

d t

rad

em

ark

s o

wn

ed

by

Gru

nd

fos

Ho

ldin

g A

/S o

r G

run

dfo

s A

/S,

De

nm

ark

. A

ll ri

gh

ts r

ese

rve

d w

orl

dw

ide

Co

pyr

igh

t G

run

dfo

s H

old

ing

A/S

L-SLC-PG-01

98436499 XX17

ECM: XXXXXXX

GRUNDFOS Chicago3905 Enterprise CourtP.O. Box 6620Aurora, IL 60598-0620Phone: +1-630-236-5500Fax: +1-630-236-5511

GRUNDFOS Kansas City17100 West 118th TerraceOlathe, Kansas 66061Phone: +1-913-227-3400Fax: +1-913-227-3500www.grundfos.us

GRUNDFOS Canada2941 Brighton RoadOakville, Ontario L6H 6C9 CanadaPhone: +1-905 829 9533Fax: +1-905 829 9512www.grundfos.ca

GRUNDFOS México Boulevard TLC No. 15Parque Industrial Stiva AeropuertoC.P. 66600 Apodaca, N.L MexicoPhone: +011-52-81-8144 4000Fax: +011-52-81-8144 4010www.grundfos.mx