Site & Building Water Use
Moscow City Halloow CCww www ww ll
Jamie Christensen, Cassie Burgess, Gwen Swanson
Moscow City Hall is federal building built in 1911 by James Knox Taylor. It was first a post office and community center and now currently the city hall.
It has been modified over the years to comply with code and accessibility requirements but still has room to grow to conserve more water.
History
City Hall
City of Hall is located on in the heart of downtown Moscow. It sits between 2nd and 3rd street.
It houses the city government, including the mayor, utility billing, and a variety city services.
Site DescriptionN
Building Materials
BrickLimestoneWoodGlassConcrete MetalTile
Average Rainfall
0
0.5
1
1.5
2
2.5
3
3.5
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Moscow Monthly Rainfall
Inches
Normal Annual precipitation is 27.37.
Rainfall is usually evenly distributed.
November is the month with the most rainfall.
N
Inventory of Stormwater Collection
Internal Down Spouts External Down Spouts
All water is directed to the cites underground stormwater gathering system.
Main spout thatgoes to the
underground system.
0 2 4 6 8 10 12 14
Toilets
Sinks
Urinals
Fountains
Totals:
3rd �oor
2nd �oor
1st �oor
Inventory of Water-Using Fixtures
Sloan Valve COSloan Valve COFlexi-Guard
Water-Using Fixtures Locations
1st Floor Plan
3rd Floor Plan
2nd Floor Plan
Conventional Water Supply
Fixtures # of Each WSFU Total (fu)Toilets 12 10 120Urinals 4 10 40Rest Room Sinks 8 2 16Non-Rest Room Sink 1 1.4 1.4Drinking Fountain 3 0.25 0.75
178.15
WU = total water usefu = total fixture units
GPFU[gal/day/supply fixture unit] = (WU)/(fu)
12.6GPFU = (WU)/(fu)
Fixures Total (FU) GPFToilets 120 1,512Urinals 40 504Rest Rooms Sinks 16 201.6Non-Rest Room Sinks 1.4 17.64Drinking Fountain 0.75 9.45
2,244.69
FU= weight in fixture unitsGPF[gal/day/ fixture] = (FU)(GPFU)
12.6GPFU = (WU)/(fu)
Conventional Water Supply
Conventional System
Redesign: Conserve Water
Kohler Kohler
Proposal: waterless urinals dual flush toilets motion sensor faucets cistern for roof run off
Sloan Valve COz
Redesign: Conventional Water
Fixtures # of Each WSFU Total (fu)Toilets - Dual Flush (.8/1.6 gallons) 12 1.6 230.4Urinals - Waterless 4 0 0Restroom Sink - Mo�on Sensors 8 0.7 44.8Non- Restroom Sinks 1 1.4 1.4Drinking Fountain 3 0.25 0.75
277.35
WU = total water usefu = total fixture units
GPFU[gal/day/supply fixture unit] = (WU)/(fu)
8.11GPFU = (WU)/(fu)
Redesign: Conventional Water Fixture Total (fu) GPFToilets - Dual Flush 230.4 155.7Urinals - Waterless 0 0Restroom Sinks - Mo�on 44.8 45.4Non-Restroom Sinks 1.4 11.3Drinking Fountains 0.75 6
218.4
8.11GPFU = (WU)/(fu)
FU= weight in fixture unitsGPF[gal/day/ fixture] = (FU)(GPFU)
Redesign: Conventional System
90% Savings
Redesign: Stormwater Collection
N
Internal Down Spouts External Down Spouts
The cistern can go where themain value comes from the building.
Proposal Size 20,000 gal.