SYMBOLS (NOT ALL USED) ABBREVIATIONS (NOT ALL USED)
APPLICABLE CODES AND STANDARDS
1. ALL WORK PERFORMED UNDER THIS CONTRACT SHALL CONFORM TO THE FOLLOWING CODES AND REGULATIONS:
2016 CALIFORNIA ADMINISTRATIVE CODE (CAC). PART 1, TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR)
2016 CALIFORNIA BUILDING CODE (CBC). PART 2, TITLE 24, CCR. BASED ON THE 2012 INTERNATIONAL BUILDING CODE (IBC)
2016 CALIFORNIA ELECTRICAL CODE (CEC). PART 3. TITLE 24, CCR. BASED ON THE 2011 NATIONAL ELECTRICAL CODE (NEC)
2016 CALIFORNIA MECHANICAL CODE (CMC). PART 4, TITLE 24, CCR. BASED ON THE 2012 UNIFORM MECHANICAL CODE (UMC)
2016 CALIFORNIA PLUMBING CODE. PART 5, TITLE 24, CCR. BASED ON THE 2012 UNIFORM PLUMBING CODE (UPC)
2016 CALIFORNIA FIRE CODE (CFC). PART 9, TITLE 24, CCR. BASED ON THE 2012 INTERNATIONAL FIRE CODE (IFC)
2. ALL EQUIPMENT (NEW AND TEMPORARY) SHALL BE LISTED, LABELED OR CERTIFIED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY [NRTL] AS
RECOGNIZED BY THE U.S. DEPARTMENT OF LABOR, OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION AND CAN CERTIFIED.
CIRCUIT BREAKER
FUSED SWITCH
TRANSFORMER
MOTOR
GROUND COINNECTION
BATTERY
METER
WIRING DEVICE LEGEND
GENERAL DUPLEX RECEPTACLE: NEMA 5-20R
DEDICATED DUPLEX RECEPTACLE: NEMA 5-20R
GENERAL QUAD RECEPTACLE: NEMA 5-20R
DEDICATED QUAD RECEPTACLE: NEMA 5-20R
+ = NON-STANDARD MOUNTING HEIGHT
G, GFI = GROUND FAULT CIRCUIT INTERRUPTER
#
SINGLE POLE TOGGLE SWITCH
#: 3 = THREE WAY, 4 = FOUR WAY, D = DIMMER SWITCH
FLUSH MOUNTED FLOOR POWER FURNITURE FEED
WALL MOUNTED POWER FURNITURE FEED
WALL MOUNTED DATA/TELEPHONE FURNITURE FEED
POWER POLE, PROVIDE J-BOX ABOVE CEILING
DATA OUTLET, COORDINATE ROUGH-INS WITH IT VENDOR
SURGE PROTECTION DEVICE
SINGLE LINE DIAGRAM LEGEND
AUTOMATIC TRANSFER SWITCH
GROUND FAULT PROTECTION
FEEDER TAG, REFER TO FEEDER SCHEDULE
BATTERY
UPS RECTIFIER/INVERTER
AVAILABLE FAULT CURRENT
NON-FUSED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
MAGNETIC MOTOR STARTER
POWER DISTRIBUTION LEGEND
TRANSFORMER
PANELBOARD, 120/208 VOLT
PANELBOARD, 277/480 VOLT
DISTRIBUTION BOARD
CONCEALED WIRING IN WALL OR CEILING
CONCEALED WIRING IN SLAB OR BELOW FLOOR
INDICATES CONDUIT DOWN
INDICATES CONDUIT UP
CAPPED CONDUIT, PROVIDE PULL STRING
CONDUIT WITH BUSHING, PROVIDE PULL STRING
COMBINATION METER/DISCONNECT SWITCH
NEUTRAL CONDUCTOR, #12 MINIMUM
ISOLATED GROUND, #12 MINIMUM
IMPLIED CONDUIT GROUND WIRE, #12 MINIMUM
G,GFI
DIMMING SWITCH/KEYPAD
CEILING MOUNTED OCCUPANCY SENSOR, 360 DEGREE COVERAGE
CEILING MOUNTED DAYLIGHT SENSOR
WALL MOUNTED OCCUPANCY SENSOR
CEILING MOUNTED DIRECTIONAL OCCUPANCY SENSOR
WP
WP = WEATHER PROOF
a = SWITCH LEG
LIGHTING CONTROL LEGEND
WALL MOUNTED DIRECTIONAL OCCUPANCY SENSOR
%VD PERCENT VOLTAGE DROP
CONTROLLED RECEPTACLE RELAY
CR
LIGHTING LEGEND
a
F2 = FIXTURE TYPE, P-22 = POWER SOURCE, a =
LAMP SWITCH
CEILING MOUNTED EXIT LIGHT, DIRECTIONAL
ARROWS WHERE INDICATED, SHADED AREAS
INDICATE ILLUMINATED FACES
WALL MOUNTED EXIT LIGHT, DIRECTIONAL
ARROWS WHERE INDICATED, SHADED AREAS
INDICATE ILLUMINATED FACES
LIGHT FIXTURE, CEILING MOUNTED
LIGHT FIXTURE, WALL MOUNTED
LIGHT FIXTURE, SIZE APPROXIMATELY AS SHOWN,
CEILING MOUNTED
EMERGENCY LIGHT FIXTURE
LIGHT FIXTURE(S), POLE MOUNTED
LIGHT FIXTURE, SIZE APPROXIMATELY AS SHOWN,
WALL MOUNTED
P-22
F2
A
B
M
DM
a
D
P
+
P
D
PP
TV
65,000A
SPD
GFP
M
M
DIMMER SWITCHD
FLUSH MOUNTED FURNITURE FEEDS, COMBINATION
POWER/DATA, PROVIDE PULL STRING
AUDIO/VISUAL RECEPTACLE, CABLE BY OTHERS
TIME CLOCK
AV
TC
P D
FLOOR BOX LEGEND
FLOOR BOX DUPLEX/DATA, PROVIDE PULL STRING
FLOOR BOX RAISED DUPLEX/DATA, PROVIDE PULL STRING
POKE-THRU FLUSH DUPLEX/DATA, PROVIDE PULL STRING
POKE-THRU FLUSH DEDICATED DUPLEX/DATA, PROVIDE
PULL STRING
POKE-THRU FLUSH QUAD/DATA, PROVIDE PULL STRING
FLOOR BOX DEDICATED DUPLEX/DATA, PROVIDE PULL
STRING
FLOOR BOX RAISED DEDICATED DUPLEX/DATA, PROVIDE
PULL STRING
FLOOR BOX RAISED QUAD/DATA, PROVIDE PULL STRING
FLUSH MOUNTED FLOOR BOX, POWER/DATA/TELEPHONE
TELEPHONE BACKBOARD, LENGTH APPROXIMATELY AS
SHOWN
JUNCTION BOX, CEILING MOUNTED
JUNCTION BOX, WALL MOUNTED
HAND HOLE
PULL BOX
J
J
PB
HH
AUTOMATIC TRANSFER SWITCH WITH DOUBLE
ISOLATION BYPASS
SECURITY/ALARM OUTLET, COORDINATE ROUGH-INS WITH
SECURITY VENDOR
COAXIAL TV OUTLET, COORDINATE ROUGH-INS WITH AV
VENDOR
FLUSH MOUNTED FLOOR DATA/TELEPHONE FURNITURE
FEED
COMBINATION DATA/TELEPHONE OUTLET, COORDINATE
ROUGH-INS WITH IT VENDOR
TELEPHONE OUTLET, COORDINATE ROUGH-INS WITH IT
VENDOR
CR = CONTROLLED RECEPTACLE, PROVIDE DISTINCT
MARKING
EQUIPMENT RECEPTACLE, COORDINATE NEMA TYPE WITH
EQUIPMENT
CEILING MOUNTED DUAL DIRECTIONAL OCCUPANCY
SENSOR, HALLWAY COVERAGE
MANUAL MOTOR STARTER WITH THERMAL OVERLOAD
PROTECTION
COMBINATION MAGNETIC MOTOR STARTER AND
DISCONNECT SWITCH
PHASE CONDUCTOR(S), QUANTITY AS SHOWN, #12
MINIMUM
HOMERUN BACK TO PANEL/CIRCUIT INDICATED AT
ARROWHEAD
EQUIPMENT TAG: A = EQUIPMENT TYPE, B = EQUIPMENT
NUMBER REFER TO EQUIPMENT SCHEDULE FOR MORE
INFORMATION
A, AMP AMPERE
AF AMP FUSE, AMP FRAME
AFC AMPERE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AS AMPERE SWITCH
AUTO AUTOMATIC
AWG AMERICAN WIRE GAUGE
BLDG BUILDING
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CLG CEILING
CO CONDUIT ONLY
COMM COMMUNICATION
CU COPPER
(D) EXISTING TO BE REMOVED
DB DISTRIBUTION BOARD
DISC DISCONNECT
DMU DIGITAL METER UNIT
DWG DRAWING
(E) EXISTING TO REMAIN
(ER) EXISTING TO BE RELOCATED
EA EACH
ELEC ELECTRICAL
EMT ELECTRICAL METALLIC TUBING
EQPT EQUIPMENT
FIXT FIXTURE
FLR FLOOR
FLEX FLEXIBLE
FMC FLEXIBLE METAL CONDUIT
FT FOOT OR FEET
G, GND GROUND
G, GFI GROUND FAULT INTERRUPTER
HP HORSEPOWER
HZ HERTZ
IC INTERRUPTING CAPACITY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
J, JB JUNCTION BOX
KAFC THOUSAND AMPERE FAULT CURRENT
KAIC THOUSAND AMPERE INTERRUPTING CURRENT
KV KILOVOLT
KVA KILOVOLT AMPERE
LTG LIGHTING
MAX MAXIMUM
MC METAL CLAD CABLE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MECH MECHANICAL
MIN MINIMUM
MLO MAIN LUGS ONLY
(N) NEW
N NEUTRAL
N1 NEMA TYPE '1' INDOOR ENCLOSURE
N3R NEMA TYPE '3R' OUTSOOR ENCLOSURE
NER NETWORK ELECTRICAL ROOM
NC NORMALLY CLOSED
NO NORMALLY OPEN
NTS NOT TO SCALE
OCPD OVERCURRENT PROTECTION DEVICE
OS OCCUPANCY SENSOR
P POLE
PB PULL BOX
PH, Ø PHASE
PLUM PLUMBING
PNL PANEL
PWR POWER
(RE) RELOCATED EXISTING
RCPT RECEPTACLE
RM ROOM
RMC RIGID METAL CONDUIT
SCHD SCHEDULE
SD SMOKE DETECTOR
SECT SECTION
SPEC SPECIFICATION
SPKR SPEAKER
SW SWITCH
SWBD SWITCHBOARD
TC TIME CLOCK
TEL TELEPHONE
TELCOM TELECOMMUNICATION
TX TRANSFORMER
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLT
VA VOLT AMPERE
VM VOLTMETER
W WATT
WP WEATHERPROOF
WS WORK STATION
XFMR TRANSFORMER
SHEET INDEX
GENERAL NOTES
DESCRIPTIONSHEET SCALE
E-0.0 ELECTRICAL COVER SHEET NONE
E-1.0 ELECTRICAL SPECIFICATIONS NONE
E-2.0 ELECTRICAL POWER PLAN AND PANEL SCHEDULE 1/2"=1'-0"
A
ENERGY METER
1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO CURRENT KAISER
STANDARDS, NATIONAL ELECTRIC CODE, CALIFORNIA ELECTRICAL CODE,
TITLE 24 COMPLIANCE REQUIREMENTS, AND ALL APPLICABLE CODES AND
REGULATIONS, INCLUDING REQUIREMENTS OF THE AUTHORITIES HAVING
JURISDICTION. WHERE REQUIREMENTS BETWEEN GOVERNING CODES,
REGULATIONS, AND SPECIFICATIONS VARY, THE MORE STRINGENT SHALL
APPLY.
2. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY RECOGNIZED ELECTRICAL
TESTING LABORATORY OR APPROVED BY THE DEPARTMENT OF BUILDING
INSPECTION.
3. ALL ELECTRICAL MATERIALS SHALL BE NEW, BEAR THE UNDERWRITERS
(AND/OR EQUIVALENT TESTING AGENCY) LABEL AND BE APPROVED BY
AUTHORITY HAVING JURISDICTION.
4. ALL WORK SHALL BE PERMITTED. CONTRACTOR SHALL OBTAIN AND PAY FOR
ALL NECESSARY PERMITS, FEES, AND LICENSES.
5. PROVIDE ELECTRONIC PDF COPIES OF SUBMITTAL MATERIAL WITH
DESCRIPTIVE DATA FOR ALL PRODUCTS AND MATERIALS. ALLOW FIVE (5)
WORKING DAYS FOR ENGINEER TO REVIEW SUBMITTALS.
6. FURNISH FINAL CERTIFICATE OF INSPECTION OR WRITTEN EVIDENCE OF
ACCEPTANCE BY INSPECTION AUTHORITIES FOR ALL WORK INSTALLED.
7. THE CONTRACTOR WILL BE REQUIRED TO DO HIS WORK IN FULL
COOPERATION WITH THE OTHER CONSTRUCTION TRADES.
8. ALL DRAWINGS AND LAYOUTS ARE DIAGRAMMATIC TO SHOW DESIGN INTENT
ONLY. ALL SYMBOLS SHOWN ON SYMBOL LIST ARE NOT NECESSARILY USED
ON THIS PROJECT.
9. VERIFY ALL EXISTING CONDITIONS PRIOR TO PERFORMING ALL WORK. NOTIFY
ENGINEER OF ANY ADVERSE FIELD CONDITIONS IMMEDIATELY. COORDINATE
ENTIRE INSTALLATION WITH ALL OTHER NEW WORK AND EXISTING
CONDITIONS. DETERMINE EXACT CONDUIT ROUTING, CONDUIT BENDS,
AUXILIARY JUNCTION BOXES, SUPPORTS, AND UNDEFINED CONSTRUCTION
DETAILS FOR INSTALLATION IN ACCORDANCE WITH APPLICABLE CODE
REQUIREMENTS.
10. EXAMINE COMPLETE SET OF DRAWINGS AND SPECIFICATIONS FOR ALL
TRADES, INCLUDING ARCHITECTURAL, MECHANICAL, AND STRUCTURAL PRIOR
TO SUBMITTING BID AND START OF WORK. VERIFY ALL DIMENSIONS FOR
SPACE REQUIREMENTS AND POINT OF CONNECTION TO ALL EQUIPMENT.
MAKE ANY MINOR ADJUSTMENTS NECESSARY TO AVOID CONFLICTS WITH THE
BUILDING STRUCTURE AND THE WORK OF OTHER TRADES.
11. COORDINATE THE ENTIRE INSTALLATION OF ELECTRICAL SYSTEM WITH THE
WORK OF ALL OTHER TRADES PRIOR TO INSTALLATION.
12. COORDINATE EXACT EQUIPMENT REQUIREMENTS FOR APPROPRIATE
WIRE/LUG LANDING.
13. NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT
SHALL BE PERMITTED TO BE LOCATED WITHIN THE DEDICATED SPACE ABOVE
ELECTRICAL EQUIPMENT, PER NEC.
14. PROVIDE UPDATED TYPE WRITTEN PANEL SCHEDULES. SCHEDULES SHALL BE
MOUNTED ON THE INSIDE OF ALL PANEL COVER DOORS. SCHEDULE TO
MATCH THOSE SHOWN ON DRAWINGS AND CONTRACT DOCUMENTS.
15. LABEL ALL PANELBOARD, EQUIPMENT, ETC. PER BUILDING STANDARDS. AT
MINIMUM, EACH EQUIPMENT, BOARD, ETC. SHALL HAVE LABELS WITH 3/8"
LETTERING STATING VOLTAGE, AMP, SOURCE, AND DEVICE NAME.
16. ALL PANELS, SWITCHES, ETC. SHALL HAVE SUFFICIENT GUTTER SPACE AND
LUGS TO ACCOMMODATE CONDUCTORS SHOWN.
17. VERIFY NAMEPLATE RATING OF ALL MOTORS AND APPLIANCES WITH
DRAWINGS. NOTIFY ARCHITECT/ENGINEER IMMEDIATELY WITH ANY
DISCREPANCIES BEFORE START OF WORK.
18. CONTRACTOR SHALL COORDINATE LOCATION OF ALL OUTLET BOXES FOR
SWITCHES, RECEPTACLES, SPEAKERS, JUNCTION BOXES, LIGHTING FIXTURES,
SWITCHES, ETC. WITH OWNER AND ARCHITECT. VERIFY EXACT LOCATION OF
EQUIPMENT CONNECTION PRIOR TO ROUGH IN. PROVIDE FINISH TRIM ON ALL
FLOOR ELECTRICAL BOXES. FINISH REQUIREMENTS SHALL MATCH EXISTING
UNLESS OTHERWISE DIRECTED BY ARCHITECT. FOR ALL WIRING DEVICES,
VERIFY FINISH COLOR WITH ARCHITECT.
19. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR LAYING OUT ALL
J-BOX LOCATIONS FOR LIGHTING, OUTLETS, AND CONTROLS IN PRE-CAST
PANELS PRIOR TO CASTING.
20. ALL J-BOXES SHALL BE SIZED PER NEC TABLE 314-28. ALL JUNCTION BOXES
AND PULL BOXES SHALL BE OF CODE GAUGE AND THE REQUIRED SIZE TO
ACCOMMODATE NUMBER OF CONDUCTORS SHOWN.ALL WALL JUNCTION
BOXES SHALL BE MOUNTED FLUSH WITH FINISHED FACE OF WALL AND SHALL
BE INSTALLED WITH MOUNTING HOLES AT TOP AND BOTTOM, UNLESS
OTHERWISE NOTED. PROVIDE MIN 6" SEPARATION FOR BACK TO BACK OUTLET
BOXES. EXTEND WIRING FROM ALL JUNCTION BOXES, RECEPTACLES,
SWITCHES, ETC. AND MAKE FINAL CONNECTION AS REQUIRED TO ALL
EQUIPMENT REQUIRING ELECTRICAL CONNECTION.PROVIDE EXTENSION
BOXES AT WALLS WITH APPLIED ACOUSTIC PANELS.
21. FLEXIBLE CONNECTIONS SHALL BE PROVIDED FOR ALL EQUIPMENT
CONNECTIONS SUBJECT TO MOTION OR VIBRATION.
22. PROVIDE FLEXIBLE CONDUIT FOR ALL TEMPORARY, PERMANENT, OR
RE-ROUTED FEEDERS CROSSING SEISMIC JOINTS. ALLOW FOR MINIMUM OF 4”
OF MOVEMENT IN ANY DIRECTION; COORDINATE EXACT DISTANCES WITH
CONTRACT DOCUMENTS.
23. MINIMUM CONDUIT SIZE SHALL BE 3/4" UNLESS OTHERWISE NOTED. PROVIDE
PULL CORDS IN EMPTY CONDUITS. WHERE MORE THAN ONE CONDUIT
TERMINATES IN A JUNCTION BOX, IDENTIFY EACH JUNCTION BOX AND
CONDUIT IN A MANNER ALLOWING IDENTIFICATION OF JUNCTION BOXES AND
CONDUITS AFTER ALL WALL FINISHES HAVE BEEN APPLIED.
24. ALL CONDUCTORS SHALL BE COPPER TYPE WITH THHN INSULATION.
ALUMINUM CONDUCTORS SHALL BE ACCEPTABLE FOR FEEDERS ONLY;
CONTRACTOR IS RESPONSIBLE FOR SUBMITTING PROPOSED FEEDER
SCHEDULES AND VOLTAGE DROP CALCULATIONS FOR ALUMINUM
SUBSTITUTION.
25. MULTI-WIRE BRANCH CIRCUITS SHALL NOT BE PERMITTED UNLESS EXPLICITLY
CALLED OUT FOR INDIVIDUAL MANUFACTURER'S WRITTEN INSTALLATION
INSTRUCTIONS. PROVIDE A DEDICATED NEUTRAL FOR EACH BRANCH
CIRCUIT. WHERE MULTI-WIRE BRANCH CIRCUITS ARE REQUIRED, PROVIDE
MULTIPLE-POLE BREAKERS OR BREAKER TIE HANDLES TO SIMALTANEOUSLY
DISCONNECT ALL UNGROUNDED CONDUCTORS.
26. PROVIDE EMT CONDUIT HOMERUNS FOR GROUPS OF (12) BRANCH CIRCUITS;
LOCATE JUNCTION BOX IN CORRIDORS WITH ACCESSIBLE CEILINGS, IN CLOSE
PROXIMITY TO EQUIPMENT SERVED. FROM HOMERUN JUNCTION BOX TO THE
POINT OF USE, AC OR MC CABLE MAY BE USED IN NON-PATIENT AREAS.
27. COORDINATE SEQUENCE OF WORK TO AVOID CUTTING AND PATCHING IN NEW
WORK. ELECTRICAL CONTRACTOR SHALL UTILIZE RESPONSIBLE TRADES FOR
ALL PATCHING, FIRE STOPPING, AND RE-FINISHING. ALL PATCHING SHALL BE
OF THE SAME MATERIALS, WORKMANSHIP AND FINISH AS EXISTING AND
SHALL ACCURATELY MATCH ALL SURROUNDING WORK.
28. PROVIDE WRITTEN WARRANTY TO REPLACE ALL FAULTY MATERIALS AND/OR
CORRECT FAULTY INSTALLATION, AT NO COST TO OWNER INCLUDING PARTS
AND LABOR, FOR A PERIOD OF ONE (1) YEAR FROM DATE OF OWNER'S
WRITTEN ACCEPTANCE.
29. DAMAGE TO OTHER WORK: REPAIR ANY DAMAGE CAUSED BY DIVISION 16
CONTRACTOR TO WORK OF OTHER DIVISIONS. DAMAGE TO FIRE PROOFING:
REPAIR ANY DAMAGED FIRE PROOFING CAUSED BY DIVISION 16 CONTRACTOR
TO INTEGRITY OF ORIGINAL CONSTRUCTION.
30. UPON COMPLETION OF WORK, CONTRACTOR SHALL CLEAN AND REMOVE ALL
DEBRIS ASSOCIATED WITH HIS/HER WORK AND DISPOSE OF IT. ALL DISPOSAL
COSTS SHALL BE BORNE BY THE CONTRACTOR. AREA SHALL BE LEFT IN A
CONDITION ACCEPTABLE TO OWNER.
31. PROVIDE RED-LINED AS BUILT DRAWINGS AT THE CONCLUSION OF WORK.
32. INSTALLATION OF PULL BOXES & CONDUITS SHALL COMPLY WITH CEC
110.26(F)(1)(a) REQUIREMENT.
33. IN ACCORDANCE WITH 2013 CBC § 1117B.6, ITEM #5.1, INSTALLATION OF
CONTROLS AND SWITCHES INTENDED TO BE USED BY OCCUPANTS OF THE
ROOM OR AREA SHALL BE LOCATED NO MORE THAN 48", MEASURED FROM
THE TOP OF THE OUTLET BOX, AND NO LESS THAN 15", MEASURED FROM THE
BOTTOM OF THE OUTLET BOX.
34. IN ACCORDANCE WITH 2013 CBC § 1117B.6, ITEM #5.2, INSTALLATION OF
ELECTRICAL RECEPTACLE OUTLETS ON BRANCH CIRCUITS OF 30 AMPERES
OR LESS AND COMMUNICATION SYSTEM RECEPTACLES SHALL BE NO MORE
THAN 48", MEASURED FROM THE TOP OF THE RECEPTACLE OUTLET BOX OR
RECEPTACLE HOUSING, AND NO LESS THAN 15", MEASURED FROM THE
BOTTOM OF THE RECEPTACLE OUTLET BOX OR RECEPTACLE HOUSING, TO
THE LEVEL OF THE FINISHED FLOOR OR WORKING PLATFORM.
35. CONTRACTOR SHALL BE RESPONSIBLE FOR CONFORMING TO REQUIREMENTS
OF LEED MATRIX ADOPTED BY THIS PROJECT.
36. CONTRACTOR TO PROVIDE METHOD OF PROCEDURE (MOP) FOR ELECTRICAL
PANEL SHUTDOWNS.
E-0.0
ELECTRICAL
COVER SHEET
Q U A L I T Y A N D E X E L L E N C E
I N E N G I N E E R I N G A N D
D E S I G N S O L U T I O N S
1 8 6 7 2 F L O R I D A S T R E E T , U N I T 2 0 1 A
H U N T I N G T O N B E A C H , C A 9 2 6 4 8
P H O N E : 7 1 4 - 8 4 7 - 1 1 0 2
F A X : 7 1 4 - 2 4 2 - 9 4 9 9
ST
EA
M S
YS
TE
M B
OIL
ER
RE
PL
AC
EM
EN
T P
RO
JE
CT
40
32
S
. E
LL
ES
FO
RD
A
VE
NU
E
WE
ST
C
OV
IN
A, C
AL
IF
OR
NIA
9
17
92
RU
TH
R
IC
HA
RD
F
OO
D C
EN
TE
R
RO
WL
AN
D U
NIF
IE
D S
CH
OO
L D
IS
TR
IC
T
1.01 DESCRIPTION
PART 1 - GENERAL
1.02 JOB CONDITIONS
1.05 MAINTENANCE MANUALS AND AS-BUILT DRAWINGS
PART 2 - PRODUCTS
2.01 GENERAL
1.04 SUBMITTALS
PART 4 - OTHER APPLICABLE SPECIFICATIONS
1.03 PRODUCT DELIVERY, STORAGE, AND HANDLING
2.02 MATERIALS
PART 3 - EXECUTION
3.01 INSTALLATION
E-1.0
ELECTRICAL
SPECIFICATIONS
Q U A L I T Y A N D E X E L L E N C E
I N E N G I N E E R I N G A N D
D E S I G N S O L U T I O N S
1 8 6 7 2 F L O R I D A S T R E E T , U N I T 2 0 1 A
H U N T I N G T O N B E A C H , C A 9 2 6 4 8
P H O N E : 7 1 4 - 8 4 7 - 1 1 0 2
F A X : 7 1 4 - 2 4 2 - 9 4 9 9
ST
EA
M S
YS
TE
M B
OIL
ER
RE
PL
AC
EM
EN
T P
RO
JE
CT
40
32
S
. E
LL
ES
FO
RD
A
VE
NU
E
WE
ST
C
OV
IN
A, C
AL
IF
OR
NIA
9
17
92
RU
TH
R
IC
HA
RD
F
OO
D C
EN
TE
R
RO
WL
AN
D U
NIF
IE
D S
CH
OO
L D
IS
TR
IC
T
(E)BT-1
ST-1
TMV-1
RCP-1
(E)HW-1
(E)RCP-2
B-1
CT-1
M
(E)BFP
(E)METER
(E)FS
(E)FS
M
(E)RCP
(E)BRINE
TANK
SOFTNER
TANKS
ST-2
Q U A L I T Y A N D E X E L L E N C E
I N E N G I N E E R I N G A N D
D E S I G N S O L U T I O N S
1 8 6 7 2 F L O R I D A S T R E E T , U N I T 2 0 1 A
H U N T I N G T O N B E A C H , C A 9 2 6 4 8
P H O N E : 7 1 4 - 8 4 7 - 1 1 0 2
F A X : 7 1 4 - 2 4 2 - 9 4 9 9
ST
EA
M S
YS
TE
M B
OIL
ER
RE
PL
AC
EM
EN
T P
RO
JE
CT
4032 S
. E
LL
ES
FO
RD
A
VE
NU
E
WE
ST
C
OV
IN
A, C
AL
IF
OR
NIA
91792
RU
TH
R
IC
HA
RD
F
OO
D C
EN
TE
R
RO
WL
AN
D U
NIF
IE
D S
CH
OO
L D
IS
TR
IC
T
E-2.0
ELECTRICAL
POWER PLAN AND
PANEL SCHEDULE
1
ELECTRICAL POWER PLAN
1/2"=1'-0"
2
ELECTRICAL PANEL SCHEDULE
NTS