SYMBOLS (NOT ALL USED) ABBREVIATIONS (NOT ALL USED) APPLICABLE CODES AND STANDARDS 1. ALL WORK PERFORMED UNDER THIS CONTRACT SHALL CONFORM TO THE FOLLOWING CODES AND REGULATIONS: x 2016 CALIFORNIA ADMINISTRATIVE CODE (CAC). PART 1, TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR) x 2016 CALIFORNIA BUILDING CODE (CBC). PART 2, TITLE 24, CCR. BASED ON THE 2012 INTERNATIONAL BUILDING CODE (IBC) x 2016 CALIFORNIA ELECTRICAL CODE (CEC). PART 3. TITLE 24, CCR. BASED ON THE 2011 NATIONAL ELECTRICAL CODE (NEC) x 2016 CALIFORNIA MECHANICAL CODE (CMC). PART 4, TITLE 24, CCR. BASED ON THE 2012 UNIFORM MECHANICAL CODE (UMC) x 2016 CALIFORNIA PLUMBING CODE. PART 5, TITLE 24, CCR. BASED ON THE 2012 UNIFORM PLUMBING CODE (UPC) x 2016 CALIFORNIA FIRE CODE (CFC). PART 9, TITLE 24, CCR. BASED ON THE 2012 INTERNATIONAL FIRE CODE (IFC) 2. ALL EQUIPMENT (NEW AND TEMPORARY) SHALL BE LISTED, LABELED OR CERTIFIED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY [NRTL] AS RECOGNIZED BY THE U.S. DEPARTMENT OF LABOR, OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION AND CAN CERTIFIED. CIRCUIT BREAKER FUSED SWITCH TRANSFORMER MOTOR GROUND COINNECTION BATTERY METER WIRING DEVICE LEGEND GENERAL DUPLEX RECEPTACLE: NEMA 5-20R DEDICATED DUPLEX RECEPTACLE: NEMA 5-20R GENERAL QUAD RECEPTACLE: NEMA 5-20R DEDICATED QUAD RECEPTACLE: NEMA 5-20R + = NON-STANDARD MOUNTING HEIGHT G, GFI = GROUND FAULT CIRCUIT INTERRUPTER # SINGLE POLE TOGGLE SWITCH #: 3 = THREE WAY, 4 = FOUR WAY, D = DIMMER SWITCH FLUSH MOUNTED FLOOR POWER FURNITURE FEED WALL MOUNTED POWER FURNITURE FEED WALL MOUNTED DATA/TELEPHONE FURNITURE FEED POWER POLE, PROVIDE J-BOX ABOVE CEILING DATA OUTLET, COORDINATE ROUGH-INS WITH IT VENDOR SURGE PROTECTION DEVICE SINGLE LINE DIAGRAM LEGEND AUTOMATIC TRANSFER SWITCH GROUND FAULT PROTECTION FEEDER TAG, REFER TO FEEDER SCHEDULE BATTERY UPS RECTIFIER/INVERTER AVAILABLE FAULT CURRENT NON-FUSED DISCONNECT SWITCH FUSED DISCONNECT SWITCH MAGNETIC MOTOR STARTER POWER DISTRIBUTION LEGEND TRANSFORMER PANELBOARD, 120/208 VOLT PANELBOARD, 277/480 VOLT DISTRIBUTION BOARD CONCEALED WIRING IN WALL OR CEILING CONCEALED WIRING IN SLAB OR BELOW FLOOR INDICATES CONDUIT DOWN INDICATES CONDUIT UP CAPPED CONDUIT, PROVIDE PULL STRING CONDUIT WITH BUSHING, PROVIDE PULL STRING COMBINATION METER/DISCONNECT SWITCH NEUTRAL CONDUCTOR, #12 MINIMUM ISOLATED GROUND, #12 MINIMUM IMPLIED CONDUIT GROUND WIRE, #12 MINIMUM G,GFI DIMMING SWITCH/KEYPAD CEILING MOUNTED OCCUPANCY SENSOR, 360 DEGREE COVERAGE CEILING MOUNTED DAYLIGHT SENSOR WALL MOUNTED OCCUPANCY SENSOR CEILING MOUNTED DIRECTIONAL OCCUPANCY SENSOR WP WP = WEATHER PROOF a = SWITCH LEG LIGHTING CONTROL LEGEND WALL MOUNTED DIRECTIONAL OCCUPANCY SENSOR %VD PERCENT VOLTAGE DROP CONTROLLED RECEPTACLE RELAY CR LIGHTING LEGEND a F2 = FIXTURE TYPE, P-22 = POWER SOURCE, a = LAMP SWITCH CEILING MOUNTED EXIT LIGHT, DIRECTIONAL ARROWS WHERE INDICATED, SHADED AREAS INDICATE ILLUMINATED FACES WALL MOUNTED EXIT LIGHT, DIRECTIONAL ARROWS WHERE INDICATED, SHADED AREAS INDICATE ILLUMINATED FACES LIGHT FIXTURE, CEILING MOUNTED LIGHT FIXTURE, WALL MOUNTED LIGHT FIXTURE, SIZE APPROXIMATELY AS SHOWN, CEILING MOUNTED EMERGENCY LIGHT FIXTURE LIGHT FIXTURE(S), POLE MOUNTED LIGHT FIXTURE, SIZE APPROXIMATELY AS SHOWN, WALL MOUNTED P-22 F2 A B M DM a D P + P D PP TV 65,000A SPD GFP M M DIMMER SWITCH D FLUSH MOUNTED FURNITURE FEEDS, COMBINATION POWER/DATA, PROVIDE PULL STRING AUDIO/VISUAL RECEPTACLE, CABLE BY OTHERS TIME CLOCK AV TC P D FLOOR BOX LEGEND FLOOR BOX DUPLEX/DATA, PROVIDE PULL STRING FLOOR BOX RAISED DUPLEX/DATA, PROVIDE PULL STRING POKE-THRU FLUSH DUPLEX/DATA, PROVIDE PULL STRING POKE-THRU FLUSH DEDICATED DUPLEX/DATA, PROVIDE PULL STRING POKE-THRU FLUSH QUAD/DATA, PROVIDE PULL STRING FLOOR BOX DEDICATED DUPLEX/DATA, PROVIDE PULL STRING FLOOR BOX RAISED DEDICATED DUPLEX/DATA, PROVIDE PULL STRING FLOOR BOX RAISED QUAD/DATA, PROVIDE PULL STRING FLUSH MOUNTED FLOOR BOX, POWER/DATA/TELEPHONE TELEPHONE BACKBOARD, LENGTH APPROXIMATELY AS SHOWN JUNCTION BOX, CEILING MOUNTED JUNCTION BOX, WALL MOUNTED HAND HOLE PULL BOX J J PB HH AUTOMATIC TRANSFER SWITCH WITH DOUBLE ISOLATION BYPASS SECURITY/ALARM OUTLET, COORDINATE ROUGH-INS WITH SECURITY VENDOR COAXIAL TV OUTLET, COORDINATE ROUGH-INS WITH AV VENDOR FLUSH MOUNTED FLOOR DATA/TELEPHONE FURNITURE FEED COMBINATION DATA/TELEPHONE OUTLET, COORDINATE ROUGH-INS WITH IT VENDOR TELEPHONE OUTLET, COORDINATE ROUGH-INS WITH IT VENDOR CR = CONTROLLED RECEPTACLE, PROVIDE DISTINCT MARKING EQUIPMENT RECEPTACLE, COORDINATE NEMA TYPE WITH EQUIPMENT CEILING MOUNTED DUAL DIRECTIONAL OCCUPANCY SENSOR, HALLWAY COVERAGE MANUAL MOTOR STARTER WITH THERMAL OVERLOAD PROTECTION COMBINATION MAGNETIC MOTOR STARTER AND DISCONNECT SWITCH PHASE CONDUCTOR(S), QUANTITY AS SHOWN, #12 MINIMUM HOMERUN BACK TO PANEL/CIRCUIT INDICATED AT ARROWHEAD EQUIPMENT TAG: A = EQUIPMENT TYPE, B = EQUIPMENT NUMBER REFER TO EQUIPMENT SCHEDULE FOR MORE INFORMATION A, AMP AMPERE AF AMP FUSE, AMP FRAME AFC AMPERE FAULT CURRENT AFF ABOVE FINISHED FLOOR AS AMPERE SWITCH AUTO AUTOMATIC AWG AMERICAN WIRE GAUGE BLDG BUILDING C CONDUIT CB CIRCUIT BREAKER CKT CIRCUIT CLG CEILING CO CONDUIT ONLY COMM COMMUNICATION CU COPPER (D) EXISTING TO BE REMOVED DB DISTRIBUTION BOARD DISC DISCONNECT DMU DIGITAL METER UNIT DWG DRAWING (E) EXISTING TO REMAIN (ER) EXISTING TO BE RELOCATED EA EACH ELEC ELECTRICAL EMT ELECTRICAL METALLIC TUBING EQPT EQUIPMENT FIXT FIXTURE FLR FLOOR FLEX FLEXIBLE FMC FLEXIBLE METAL CONDUIT FT FOOT OR FEET G, GND GROUND G, GFI GROUND FAULT INTERRUPTER HP HORSEPOWER HZ HERTZ IC INTERRUPTING CAPACITY IG ISOLATED GROUND IMC INTERMEDIATE METAL CONDUIT J, JB JUNCTION BOX KAFC THOUSAND AMPERE FAULT CURRENT KAIC THOUSAND AMPERE INTERRUPTING CURRENT KV KILOVOLT KVA KILOVOLT AMPERE LTG LIGHTING MAX MAXIMUM MC METAL CLAD CABLE MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MECH MECHANICAL MIN MINIMUM MLO MAIN LUGS ONLY (N) NEW N NEUTRAL N1 NEMA TYPE '1' INDOOR ENCLOSURE N3R NEMA TYPE '3R' OUTSOOR ENCLOSURE NER NETWORK ELECTRICAL ROOM NC NORMALLY CLOSED NO NORMALLY OPEN NTS NOT TO SCALE OCPD OVERCURRENT PROTECTION DEVICE OS OCCUPANCY SENSOR P POLE PB PULL BOX 3+ PHASE PLUM PLUMBING PNL PANEL PWR POWER (RE) RELOCATED EXISTING RCPT RECEPTACLE RM ROOM RMC RIGID METAL CONDUIT SCHD SCHEDULE SD SMOKE DETECTOR SECT SECTION SPEC SPECIFICATION SPKR SPEAKER SW SWITCH SWBD SWITCHBOARD TC TIME CLOCK TEL TELEPHONE TELCOM TELECOMMUNICATION TX TRANSFORMER TYP TYPICAL UON UNLESS OTHERWISE NOTED V VOLT VA VOLT AMPERE VM VOLTMETER W WATT WP WEATHERPROOF WS WORK STATION XFMR TRANSFORMER SHEET INDEX GENERAL NOTES DESCRIPTION SHEET SCALE E-0.0 ELECTRICAL COVER SHEET NONE E-1.0 ELECTRICAL SPECIFICATIONS NONE E-2.0 ELECTRICAL POWER PLAN AND PANEL SCHEDULE 1/2"=1'-0" A ENERGY METER 1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO CURRENT KAISER STANDARDS, NATIONAL ELECTRIC CODE, CALIFORNIA ELECTRICAL CODE, TITLE 24 COMPLIANCE REQUIREMENTS, AND ALL APPLICABLE CODES AND REGULATIONS, INCLUDING REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. WHERE REQUIREMENTS BETWEEN GOVERNING CODES, REGULATIONS, AND SPECIFICATIONS VARY, THE MORE STRINGENT SHALL APPLY. 2. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY RECOGNIZED ELECTRICAL TESTING LABORATORY OR APPROVED BY THE DEPARTMENT OF BUILDING INSPECTION. 3. ALL ELECTRICAL MATERIALS SHALL BE NEW, BEAR THE UNDERWRITERS (AND/OR EQUIVALENT TESTING AGENCY) LABEL AND BE APPROVED BY AUTHORITY HAVING JURISDICTION. 4. ALL WORK SHALL BE PERMITTED. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL NECESSARY PERMITS, FEES, AND LICENSES. 5. PROVIDE ELECTRONIC PDF COPIES OF SUBMITTAL MATERIAL WITH DESCRIPTIVE DATA FOR ALL PRODUCTS AND MATERIALS. ALLOW FIVE (5) WORKING DAYS FOR ENGINEER TO REVIEW SUBMITTALS. 6. FURNISH FINAL CERTIFICATE OF INSPECTION OR WRITTEN EVIDENCE OF ACCEPTANCE BY INSPECTION AUTHORITIES FOR ALL WORK INSTALLED. 7. THE CONTRACTOR WILL BE REQUIRED TO DO HIS WORK IN FULL COOPERATION WITH THE OTHER CONSTRUCTION TRADES. 8. ALL DRAWINGS AND LAYOUTS ARE DIAGRAMMATIC TO SHOW DESIGN INTENT ONLY. ALL SYMBOLS SHOWN ON SYMBOL LIST ARE NOT NECESSARILY USED ON THIS PROJECT. 9. VERIFY ALL EXISTING CONDITIONS PRIOR TO PERFORMING ALL WORK. NOTIFY ENGINEER OF ANY ADVERSE FIELD CONDITIONS IMMEDIATELY. COORDINATE ENTIRE INSTALLATION WITH ALL OTHER NEW WORK AND EXISTING CONDITIONS. DETERMINE EXACT CONDUIT ROUTING, CONDUIT BENDS, AUXILIARY JUNCTION BOXES, SUPPORTS, AND UNDEFINED CONSTRUCTION DETAILS FOR INSTALLATION IN ACCORDANCE WITH APPLICABLE CODE REQUIREMENTS. 10. EXAMINE COMPLETE SET OF DRAWINGS AND SPECIFICATIONS FOR ALL TRADES, INCLUDING ARCHITECTURAL, MECHANICAL, AND STRUCTURAL PRIOR TO SUBMITTING BID AND START OF WORK. VERIFY ALL DIMENSIONS FOR SPACE REQUIREMENTS AND POINT OF CONNECTION TO ALL EQUIPMENT. MAKE ANY MINOR ADJUSTMENTS NECESSARY TO AVOID CONFLICTS WITH THE BUILDING STRUCTURE AND THE WORK OF OTHER TRADES. 11. COORDINATE THE ENTIRE INSTALLATION OF ELECTRICAL SYSTEM WITH THE WORK OF ALL OTHER TRADES PRIOR TO INSTALLATION. 12. COORDINATE EXACT EQUIPMENT REQUIREMENTS FOR APPROPRIATE WIRE/LUG LANDING. 13. NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALL BE PERMITTED TO BE LOCATED WITHIN THE DEDICATED SPACE ABOVE ELECTRICAL EQUIPMENT, PER NEC. 14. PROVIDE UPDATED TYPE WRITTEN PANEL SCHEDULES. SCHEDULES SHALL BE MOUNTED ON THE INSIDE OF ALL PANEL COVER DOORS. SCHEDULE TO MATCH THOSE SHOWN ON DRAWINGS AND CONTRACT DOCUMENTS. 15. LABEL ALL PANELBOARD, EQUIPMENT, ETC. PER BUILDING STANDARDS. AT MINIMUM, EACH EQUIPMENT, BOARD, ETC. SHALL HAVE LABELS WITH 3/8" LETTERING STATING VOLTAGE, AMP, SOURCE, AND DEVICE NAME. 16. ALL PANELS, SWITCHES, ETC. SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS TO ACCOMMODATE CONDUCTORS SHOWN. 17. VERIFY NAMEPLATE RATING OF ALL MOTORS AND APPLIANCES WITH DRAWINGS. NOTIFY ARCHITECT/ENGINEER IMMEDIATELY WITH ANY DISCREPANCIES BEFORE START OF WORK. 18. CONTRACTOR SHALL COORDINATE LOCATION OF ALL OUTLET BOXES FOR SWITCHES, RECEPTACLES, SPEAKERS, JUNCTION BOXES, LIGHTING FIXTURES, SWITCHES, ETC. WITH OWNER AND ARCHITECT. VERIFY EXACT LOCATION OF EQUIPMENT CONNECTION PRIOR TO ROUGH IN. PROVIDE FINISH TRIM ON ALL FLOOR ELECTRICAL BOXES. FINISH REQUIREMENTS SHALL MATCH EXISTING UNLESS OTHERWISE DIRECTED BY ARCHITECT. FOR ALL WIRING DEVICES, VERIFY FINISH COLOR WITH ARCHITECT. 19. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR LAYING OUT ALL J-BOX LOCATIONS FOR LIGHTING, OUTLETS, AND CONTROLS IN PRE-CAST PANELS PRIOR TO CASTING. 20. ALL J-BOXES SHALL BE SIZED PER NEC TABLE 314-28. ALL JUNCTION BOXES AND PULL BOXES SHALL BE OF CODE GAUGE AND THE REQUIRED SIZE TO ACCOMMODATE NUMBER OF CONDUCTORS SHOWN.ALL WALL JUNCTION BOXES SHALL BE MOUNTED FLUSH WITH FINISHED FACE OF WALL AND SHALL BE INSTALLED WITH MOUNTING HOLES AT TOP AND BOTTOM, UNLESS OTHERWISE NOTED. PROVIDE MIN 6" SEPARATION FOR BACK TO BACK OUTLET BOXES. EXTEND WIRING FROM ALL JUNCTION BOXES, RECEPTACLES, SWITCHES, ETC. AND MAKE FINAL CONNECTION AS REQUIRED TO ALL EQUIPMENT REQUIRING ELECTRICAL CONNECTION.PROVIDE EXTENSION BOXES AT WALLS WITH APPLIED ACOUSTIC PANELS. 21. FLEXIBLE CONNECTIONS SHALL BE PROVIDED FOR ALL EQUIPMENT CONNECTIONS SUBJECT TO MOTION OR VIBRATION. 22. PROVIDE FLEXIBLE CONDUIT FOR ALL TEMPORARY, PERMANENT, OR 5(5287(' )(('(56 &5266,1* 6(,60,& -2,176 $//2: )25 0,1,080 2) ´ OF MOVEMENT IN ANY DIRECTION; COORDINATE EXACT DISTANCES WITH CONTRACT DOCUMENTS. 23. MINIMUM CONDUIT SIZE SHALL BE 3/4" UNLESS OTHERWISE NOTED. PROVIDE PULL CORDS IN EMPTY CONDUITS. WHERE MORE THAN ONE CONDUIT TERMINATES IN A JUNCTION BOX, IDENTIFY EACH JUNCTION BOX AND CONDUIT IN A MANNER ALLOWING IDENTIFICATION OF JUNCTION BOXES AND CONDUITS AFTER ALL WALL FINISHES HAVE BEEN APPLIED. 24. ALL CONDUCTORS SHALL BE COPPER TYPE WITH THHN INSULATION. ALUMINUM CONDUCTORS SHALL BE ACCEPTABLE FOR FEEDERS ONLY; CONTRACTOR IS RESPONSIBLE FOR SUBMITTING PROPOSED FEEDER SCHEDULES AND VOLTAGE DROP CALCULATIONS FOR ALUMINUM SUBSTITUTION. 25. MULTI-WIRE BRANCH CIRCUITS SHALL NOT BE PERMITTED UNLESS EXPLICITLY CALLED OUT FOR INDIVIDUAL MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS. PROVIDE A DEDICATED NEUTRAL FOR EACH BRANCH CIRCUIT. WHERE MULTI-WIRE BRANCH CIRCUITS ARE REQUIRED, PROVIDE MULTIPLE-POLE BREAKERS OR BREAKER TIE HANDLES TO SIMALTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS. 26. PROVIDE EMT CONDUIT HOMERUNS FOR GROUPS OF (12) BRANCH CIRCUITS; LOCATE JUNCTION BOX IN CORRIDORS WITH ACCESSIBLE CEILINGS, IN CLOSE PROXIMITY TO EQUIPMENT SERVED. FROM HOMERUN JUNCTION BOX TO THE POINT OF USE, AC OR MC CABLE MAY BE USED IN NON-PATIENT AREAS. 27. COORDINATE SEQUENCE OF WORK TO AVOID CUTTING AND PATCHING IN NEW WORK. ELECTRICAL CONTRACTOR SHALL UTILIZE RESPONSIBLE TRADES FOR ALL PATCHING, FIRE STOPPING, AND RE-FINISHING. ALL PATCHING SHALL BE OF THE SAME MATERIALS, WORKMANSHIP AND FINISH AS EXISTING AND SHALL ACCURATELY MATCH ALL SURROUNDING WORK. 28. PROVIDE WRITTEN WARRANTY TO REPLACE ALL FAULTY MATERIALS AND/OR CORRECT FAULTY INSTALLATION, AT NO COST TO OWNER INCLUDING PARTS AND LABOR, FOR A PERIOD OF ONE (1) YEAR FROM DATE OF OWNER'S WRITTEN ACCEPTANCE. 29. DAMAGE TO OTHER WORK: REPAIR ANY DAMAGE CAUSED BY DIVISION 16 CONTRACTOR TO WORK OF OTHER DIVISIONS. DAMAGE TO FIRE PROOFING: REPAIR ANY DAMAGED FIRE PROOFING CAUSED BY DIVISION 16 CONTRACTOR TO INTEGRITY OF ORIGINAL CONSTRUCTION. 30. UPON COMPLETION OF WORK, CONTRACTOR SHALL CLEAN AND REMOVE ALL DEBRIS ASSOCIATED WITH HIS/HER WORK AND DISPOSE OF IT. ALL DISPOSAL COSTS SHALL BE BORNE BY THE CONTRACTOR. AREA SHALL BE LEFT IN A CONDITION ACCEPTABLE TO OWNER. 31. PROVIDE RED-LINED AS BUILT DRAWINGS AT THE CONCLUSION OF WORK. 32. INSTALLATION OF PULL BOXES & CONDUITS SHALL COMPLY WITH CEC 110.26(F)(1)(a) REQUIREMENT. 33. IN ACCORDANCE WITH 2013 CBC 1117B.6, ITEM #5.1, INSTALLATION OF CONTROLS AND SWITCHES INTENDED TO BE USED BY OCCUPANTS OF THE ROOM OR AREA SHALL BE LOCATED NO MORE THAN 48", MEASURED FROM THE TOP OF THE OUTLET BOX, AND NO LESS THAN 15", MEASURED FROM THE BOTTOM OF THE OUTLET BOX. 34. IN ACCORDANCE WITH 2013 CBC 1117B.6, ITEM #5.2, INSTALLATION OF ELECTRICAL RECEPTACLE OUTLETS ON BRANCH CIRCUITS OF 30 AMPERES OR LESS AND COMMUNICATION SYSTEM RECEPTACLES SHALL BE NO MORE THAN 48", MEASURED FROM THE TOP OF THE RECEPTACLE OUTLET BOX OR RECEPTACLE HOUSING, AND NO LESS THAN 15", MEASURED FROM THE BOTTOM OF THE RECEPTACLE OUTLET BOX OR RECEPTACLE HOUSING, TO THE LEVEL OF THE FINISHED FLOOR OR WORKING PLATFORM. 35. CONTRACTOR SHALL BE RESPONSIBLE FOR CONFORMING TO REQUIREMENTS OF LEED MATRIX ADOPTED BY THIS PROJECT. 36. CONTRACTOR TO PROVIDE METHOD OF PROCEDURE (MOP) FOR ELECTRICAL PANEL SHUTDOWNS. E-0.0 ELECTRICAL COVER SHEET QUALITY AND EXELLENCE IN ENGINEERING AND DESIGN SOLUTIONS 18672 FLORIDA STREET, UNIT201A HUNTINGTON BEACH, CA 92648 PHONE: 714-847-1102 FAX: 714-242-9499 STEAM SYSTEM BOILER REPLACEMENT PROJECT 4032 S. ELLESFORD AVENUE WEST COVINA, CALIFORNIA 91792 RUTH RICHARD FOOD CENTER ROWLAND UNIFIED SCHOOL DISTRICT

SINGLE LINE DIAGRAM LEGEND SHEET DESCRIPTION SCALE …

  • Upload
    others

  • View
    16

  • Download
    0

Embed Size (px)

Citation preview

Page 1: SINGLE LINE DIAGRAM LEGEND SHEET DESCRIPTION SCALE …

SYMBOLS (NOT ALL USED) ABBREVIATIONS (NOT ALL USED)

APPLICABLE CODES AND STANDARDS

1. ALL WORK PERFORMED UNDER THIS CONTRACT SHALL CONFORM TO THE FOLLOWING CODES AND REGULATIONS:

2016 CALIFORNIA ADMINISTRATIVE CODE (CAC). PART 1, TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR)

2016 CALIFORNIA BUILDING CODE (CBC). PART 2, TITLE 24, CCR. BASED ON THE 2012 INTERNATIONAL BUILDING CODE (IBC)

2016 CALIFORNIA ELECTRICAL CODE (CEC). PART 3. TITLE 24, CCR. BASED ON THE 2011 NATIONAL ELECTRICAL CODE (NEC)

2016 CALIFORNIA MECHANICAL CODE (CMC). PART 4, TITLE 24, CCR. BASED ON THE 2012 UNIFORM MECHANICAL CODE (UMC)

2016 CALIFORNIA PLUMBING CODE. PART 5, TITLE 24, CCR. BASED ON THE 2012 UNIFORM PLUMBING CODE (UPC)

2016 CALIFORNIA FIRE CODE (CFC). PART 9, TITLE 24, CCR. BASED ON THE 2012 INTERNATIONAL FIRE CODE (IFC)

2. ALL EQUIPMENT (NEW AND TEMPORARY) SHALL BE LISTED, LABELED OR CERTIFIED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY [NRTL] AS

RECOGNIZED BY THE U.S. DEPARTMENT OF LABOR, OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION AND CAN CERTIFIED.

CIRCUIT BREAKER

FUSED SWITCH

TRANSFORMER

MOTOR

GROUND COINNECTION

BATTERY

METER

WIRING DEVICE LEGEND

GENERAL DUPLEX RECEPTACLE: NEMA 5-20R

DEDICATED DUPLEX RECEPTACLE: NEMA 5-20R

GENERAL QUAD RECEPTACLE: NEMA 5-20R

DEDICATED QUAD RECEPTACLE: NEMA 5-20R

+ = NON-STANDARD MOUNTING HEIGHT

G, GFI = GROUND FAULT CIRCUIT INTERRUPTER

#

SINGLE POLE TOGGLE SWITCH

#: 3 = THREE WAY, 4 = FOUR WAY, D = DIMMER SWITCH

FLUSH MOUNTED FLOOR POWER FURNITURE FEED

WALL MOUNTED POWER FURNITURE FEED

WALL MOUNTED DATA/TELEPHONE FURNITURE FEED

POWER POLE, PROVIDE J-BOX ABOVE CEILING

DATA OUTLET, COORDINATE ROUGH-INS WITH IT VENDOR

SURGE PROTECTION DEVICE

SINGLE LINE DIAGRAM LEGEND

AUTOMATIC TRANSFER SWITCH

GROUND FAULT PROTECTION

FEEDER TAG, REFER TO FEEDER SCHEDULE

BATTERY

UPS RECTIFIER/INVERTER

AVAILABLE FAULT CURRENT

NON-FUSED DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

MAGNETIC MOTOR STARTER

POWER DISTRIBUTION LEGEND

TRANSFORMER

PANELBOARD, 120/208 VOLT

PANELBOARD, 277/480 VOLT

DISTRIBUTION BOARD

CONCEALED WIRING IN WALL OR CEILING

CONCEALED WIRING IN SLAB OR BELOW FLOOR

INDICATES CONDUIT DOWN

INDICATES CONDUIT UP

CAPPED CONDUIT, PROVIDE PULL STRING

CONDUIT WITH BUSHING, PROVIDE PULL STRING

COMBINATION METER/DISCONNECT SWITCH

NEUTRAL CONDUCTOR, #12 MINIMUM

ISOLATED GROUND, #12 MINIMUM

IMPLIED CONDUIT GROUND WIRE, #12 MINIMUM

G,GFI

DIMMING SWITCH/KEYPAD

CEILING MOUNTED OCCUPANCY SENSOR, 360 DEGREE COVERAGE

CEILING MOUNTED DAYLIGHT SENSOR

WALL MOUNTED OCCUPANCY SENSOR

CEILING MOUNTED DIRECTIONAL OCCUPANCY SENSOR

WP

WP = WEATHER PROOF

a = SWITCH LEG

LIGHTING CONTROL LEGEND

WALL MOUNTED DIRECTIONAL OCCUPANCY SENSOR

%VD PERCENT VOLTAGE DROP

CONTROLLED RECEPTACLE RELAY

CR

LIGHTING LEGEND

a

F2 = FIXTURE TYPE, P-22 = POWER SOURCE, a =

LAMP SWITCH

CEILING MOUNTED EXIT LIGHT, DIRECTIONAL

ARROWS WHERE INDICATED, SHADED AREAS

INDICATE ILLUMINATED FACES

WALL MOUNTED EXIT LIGHT, DIRECTIONAL

ARROWS WHERE INDICATED, SHADED AREAS

INDICATE ILLUMINATED FACES

LIGHT FIXTURE, CEILING MOUNTED

LIGHT FIXTURE, WALL MOUNTED

LIGHT FIXTURE, SIZE APPROXIMATELY AS SHOWN,

CEILING MOUNTED

EMERGENCY LIGHT FIXTURE

LIGHT FIXTURE(S), POLE MOUNTED

LIGHT FIXTURE, SIZE APPROXIMATELY AS SHOWN,

WALL MOUNTED

P-22

F2

A

B

M

DM

a

D

P

+

P

D

PP

TV

65,000A

SPD

GFP

M

M

DIMMER SWITCHD

FLUSH MOUNTED FURNITURE FEEDS, COMBINATION

POWER/DATA, PROVIDE PULL STRING

AUDIO/VISUAL RECEPTACLE, CABLE BY OTHERS

TIME CLOCK

AV

TC

P D

FLOOR BOX LEGEND

FLOOR BOX DUPLEX/DATA, PROVIDE PULL STRING

FLOOR BOX RAISED DUPLEX/DATA, PROVIDE PULL STRING

POKE-THRU FLUSH DUPLEX/DATA, PROVIDE PULL STRING

POKE-THRU FLUSH DEDICATED DUPLEX/DATA, PROVIDE

PULL STRING

POKE-THRU FLUSH QUAD/DATA, PROVIDE PULL STRING

FLOOR BOX DEDICATED DUPLEX/DATA, PROVIDE PULL

STRING

FLOOR BOX RAISED DEDICATED DUPLEX/DATA, PROVIDE

PULL STRING

FLOOR BOX RAISED QUAD/DATA, PROVIDE PULL STRING

FLUSH MOUNTED FLOOR BOX, POWER/DATA/TELEPHONE

TELEPHONE BACKBOARD, LENGTH APPROXIMATELY AS

SHOWN

JUNCTION BOX, CEILING MOUNTED

JUNCTION BOX, WALL MOUNTED

HAND HOLE

PULL BOX

J

J

PB

HH

AUTOMATIC TRANSFER SWITCH WITH DOUBLE

ISOLATION BYPASS

SECURITY/ALARM OUTLET, COORDINATE ROUGH-INS WITH

SECURITY VENDOR

COAXIAL TV OUTLET, COORDINATE ROUGH-INS WITH AV

VENDOR

FLUSH MOUNTED FLOOR DATA/TELEPHONE FURNITURE

FEED

COMBINATION DATA/TELEPHONE OUTLET, COORDINATE

ROUGH-INS WITH IT VENDOR

TELEPHONE OUTLET, COORDINATE ROUGH-INS WITH IT

VENDOR

CR = CONTROLLED RECEPTACLE, PROVIDE DISTINCT

MARKING

EQUIPMENT RECEPTACLE, COORDINATE NEMA TYPE WITH

EQUIPMENT

CEILING MOUNTED DUAL DIRECTIONAL OCCUPANCY

SENSOR, HALLWAY COVERAGE

MANUAL MOTOR STARTER WITH THERMAL OVERLOAD

PROTECTION

COMBINATION MAGNETIC MOTOR STARTER AND

DISCONNECT SWITCH

PHASE CONDUCTOR(S), QUANTITY AS SHOWN, #12

MINIMUM

HOMERUN BACK TO PANEL/CIRCUIT INDICATED AT

ARROWHEAD

EQUIPMENT TAG: A = EQUIPMENT TYPE, B = EQUIPMENT

NUMBER REFER TO EQUIPMENT SCHEDULE FOR MORE

INFORMATION

A, AMP AMPERE

AF AMP FUSE, AMP FRAME

AFC AMPERE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AS AMPERE SWITCH

AUTO AUTOMATIC

AWG AMERICAN WIRE GAUGE

BLDG BUILDING

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CLG CEILING

CO CONDUIT ONLY

COMM COMMUNICATION

CU COPPER

(D) EXISTING TO BE REMOVED

DB DISTRIBUTION BOARD

DISC DISCONNECT

DMU DIGITAL METER UNIT

DWG DRAWING

(E) EXISTING TO REMAIN

(ER) EXISTING TO BE RELOCATED

EA EACH

ELEC ELECTRICAL

EMT ELECTRICAL METALLIC TUBING

EQPT EQUIPMENT

FIXT FIXTURE

FLR FLOOR

FLEX FLEXIBLE

FMC FLEXIBLE METAL CONDUIT

FT FOOT OR FEET

G, GND GROUND

G, GFI GROUND FAULT INTERRUPTER

HP HORSEPOWER

HZ HERTZ

IC INTERRUPTING CAPACITY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

J, JB JUNCTION BOX

KAFC THOUSAND AMPERE FAULT CURRENT

KAIC THOUSAND AMPERE INTERRUPTING CURRENT

KV KILOVOLT

KVA KILOVOLT AMPERE

LTG LIGHTING

MAX MAXIMUM

MC METAL CLAD CABLE

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MECH MECHANICAL

MIN MINIMUM

MLO MAIN LUGS ONLY

(N) NEW

N NEUTRAL

N1 NEMA TYPE '1' INDOOR ENCLOSURE

N3R NEMA TYPE '3R' OUTSOOR ENCLOSURE

NER NETWORK ELECTRICAL ROOM

NC NORMALLY CLOSED

NO NORMALLY OPEN

NTS NOT TO SCALE

OCPD OVERCURRENT PROTECTION DEVICE

OS OCCUPANCY SENSOR

P POLE

PB PULL BOX

PH, Ø PHASE

PLUM PLUMBING

PNL PANEL

PWR POWER

(RE) RELOCATED EXISTING

RCPT RECEPTACLE

RM ROOM

RMC RIGID METAL CONDUIT

SCHD SCHEDULE

SD SMOKE DETECTOR

SECT SECTION

SPEC SPECIFICATION

SPKR SPEAKER

SW SWITCH

SWBD SWITCHBOARD

TC TIME CLOCK

TEL TELEPHONE

TELCOM TELECOMMUNICATION

TX TRANSFORMER

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

V VOLT

VA VOLT AMPERE

VM VOLTMETER

W WATT

WP WEATHERPROOF

WS WORK STATION

XFMR TRANSFORMER

SHEET INDEX

GENERAL NOTES

DESCRIPTIONSHEET SCALE

E-0.0 ELECTRICAL COVER SHEET NONE

E-1.0 ELECTRICAL SPECIFICATIONS NONE

E-2.0 ELECTRICAL POWER PLAN AND PANEL SCHEDULE 1/2"=1'-0"

A

ENERGY METER

1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO CURRENT KAISER

STANDARDS, NATIONAL ELECTRIC CODE, CALIFORNIA ELECTRICAL CODE,

TITLE 24 COMPLIANCE REQUIREMENTS, AND ALL APPLICABLE CODES AND

REGULATIONS, INCLUDING REQUIREMENTS OF THE AUTHORITIES HAVING

JURISDICTION. WHERE REQUIREMENTS BETWEEN GOVERNING CODES,

REGULATIONS, AND SPECIFICATIONS VARY, THE MORE STRINGENT SHALL

APPLY.

2. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY RECOGNIZED ELECTRICAL

TESTING LABORATORY OR APPROVED BY THE DEPARTMENT OF BUILDING

INSPECTION.

3. ALL ELECTRICAL MATERIALS SHALL BE NEW, BEAR THE UNDERWRITERS

(AND/OR EQUIVALENT TESTING AGENCY) LABEL AND BE APPROVED BY

AUTHORITY HAVING JURISDICTION.

4. ALL WORK SHALL BE PERMITTED. CONTRACTOR SHALL OBTAIN AND PAY FOR

ALL NECESSARY PERMITS, FEES, AND LICENSES.

5. PROVIDE ELECTRONIC PDF COPIES OF SUBMITTAL MATERIAL WITH

DESCRIPTIVE DATA FOR ALL PRODUCTS AND MATERIALS. ALLOW FIVE (5)

WORKING DAYS FOR ENGINEER TO REVIEW SUBMITTALS.

6. FURNISH FINAL CERTIFICATE OF INSPECTION OR WRITTEN EVIDENCE OF

ACCEPTANCE BY INSPECTION AUTHORITIES FOR ALL WORK INSTALLED.

7. THE CONTRACTOR WILL BE REQUIRED TO DO HIS WORK IN FULL

COOPERATION WITH THE OTHER CONSTRUCTION TRADES.

8. ALL DRAWINGS AND LAYOUTS ARE DIAGRAMMATIC TO SHOW DESIGN INTENT

ONLY. ALL SYMBOLS SHOWN ON SYMBOL LIST ARE NOT NECESSARILY USED

ON THIS PROJECT.

9. VERIFY ALL EXISTING CONDITIONS PRIOR TO PERFORMING ALL WORK. NOTIFY

ENGINEER OF ANY ADVERSE FIELD CONDITIONS IMMEDIATELY. COORDINATE

ENTIRE INSTALLATION WITH ALL OTHER NEW WORK AND EXISTING

CONDITIONS. DETERMINE EXACT CONDUIT ROUTING, CONDUIT BENDS,

AUXILIARY JUNCTION BOXES, SUPPORTS, AND UNDEFINED CONSTRUCTION

DETAILS FOR INSTALLATION IN ACCORDANCE WITH APPLICABLE CODE

REQUIREMENTS.

10. EXAMINE COMPLETE SET OF DRAWINGS AND SPECIFICATIONS FOR ALL

TRADES, INCLUDING ARCHITECTURAL, MECHANICAL, AND STRUCTURAL PRIOR

TO SUBMITTING BID AND START OF WORK. VERIFY ALL DIMENSIONS FOR

SPACE REQUIREMENTS AND POINT OF CONNECTION TO ALL EQUIPMENT.

MAKE ANY MINOR ADJUSTMENTS NECESSARY TO AVOID CONFLICTS WITH THE

BUILDING STRUCTURE AND THE WORK OF OTHER TRADES.

11. COORDINATE THE ENTIRE INSTALLATION OF ELECTRICAL SYSTEM WITH THE

WORK OF ALL OTHER TRADES PRIOR TO INSTALLATION.

12. COORDINATE EXACT EQUIPMENT REQUIREMENTS FOR APPROPRIATE

WIRE/LUG LANDING.

13. NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT

SHALL BE PERMITTED TO BE LOCATED WITHIN THE DEDICATED SPACE ABOVE

ELECTRICAL EQUIPMENT, PER NEC.

14. PROVIDE UPDATED TYPE WRITTEN PANEL SCHEDULES. SCHEDULES SHALL BE

MOUNTED ON THE INSIDE OF ALL PANEL COVER DOORS. SCHEDULE TO

MATCH THOSE SHOWN ON DRAWINGS AND CONTRACT DOCUMENTS.

15. LABEL ALL PANELBOARD, EQUIPMENT, ETC. PER BUILDING STANDARDS. AT

MINIMUM, EACH EQUIPMENT, BOARD, ETC. SHALL HAVE LABELS WITH 3/8"

LETTERING STATING VOLTAGE, AMP, SOURCE, AND DEVICE NAME.

16. ALL PANELS, SWITCHES, ETC. SHALL HAVE SUFFICIENT GUTTER SPACE AND

LUGS TO ACCOMMODATE CONDUCTORS SHOWN.

17. VERIFY NAMEPLATE RATING OF ALL MOTORS AND APPLIANCES WITH

DRAWINGS. NOTIFY ARCHITECT/ENGINEER IMMEDIATELY WITH ANY

DISCREPANCIES BEFORE START OF WORK.

18. CONTRACTOR SHALL COORDINATE LOCATION OF ALL OUTLET BOXES FOR

SWITCHES, RECEPTACLES, SPEAKERS, JUNCTION BOXES, LIGHTING FIXTURES,

SWITCHES, ETC. WITH OWNER AND ARCHITECT. VERIFY EXACT LOCATION OF

EQUIPMENT CONNECTION PRIOR TO ROUGH IN. PROVIDE FINISH TRIM ON ALL

FLOOR ELECTRICAL BOXES. FINISH REQUIREMENTS SHALL MATCH EXISTING

UNLESS OTHERWISE DIRECTED BY ARCHITECT. FOR ALL WIRING DEVICES,

VERIFY FINISH COLOR WITH ARCHITECT.

19. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR LAYING OUT ALL

J-BOX LOCATIONS FOR LIGHTING, OUTLETS, AND CONTROLS IN PRE-CAST

PANELS PRIOR TO CASTING.

20. ALL J-BOXES SHALL BE SIZED PER NEC TABLE 314-28. ALL JUNCTION BOXES

AND PULL BOXES SHALL BE OF CODE GAUGE AND THE REQUIRED SIZE TO

ACCOMMODATE NUMBER OF CONDUCTORS SHOWN.ALL WALL JUNCTION

BOXES SHALL BE MOUNTED FLUSH WITH FINISHED FACE OF WALL AND SHALL

BE INSTALLED WITH MOUNTING HOLES AT TOP AND BOTTOM, UNLESS

OTHERWISE NOTED. PROVIDE MIN 6" SEPARATION FOR BACK TO BACK OUTLET

BOXES. EXTEND WIRING FROM ALL JUNCTION BOXES, RECEPTACLES,

SWITCHES, ETC. AND MAKE FINAL CONNECTION AS REQUIRED TO ALL

EQUIPMENT REQUIRING ELECTRICAL CONNECTION.PROVIDE EXTENSION

BOXES AT WALLS WITH APPLIED ACOUSTIC PANELS.

21. FLEXIBLE CONNECTIONS SHALL BE PROVIDED FOR ALL EQUIPMENT

CONNECTIONS SUBJECT TO MOTION OR VIBRATION.

22. PROVIDE FLEXIBLE CONDUIT FOR ALL TEMPORARY, PERMANENT, OR

RE-ROUTED FEEDERS CROSSING SEISMIC JOINTS. ALLOW FOR MINIMUM OF 4”

OF MOVEMENT IN ANY DIRECTION; COORDINATE EXACT DISTANCES WITH

CONTRACT DOCUMENTS.

23. MINIMUM CONDUIT SIZE SHALL BE 3/4" UNLESS OTHERWISE NOTED. PROVIDE

PULL CORDS IN EMPTY CONDUITS. WHERE MORE THAN ONE CONDUIT

TERMINATES IN A JUNCTION BOX, IDENTIFY EACH JUNCTION BOX AND

CONDUIT IN A MANNER ALLOWING IDENTIFICATION OF JUNCTION BOXES AND

CONDUITS AFTER ALL WALL FINISHES HAVE BEEN APPLIED.

24. ALL CONDUCTORS SHALL BE COPPER TYPE WITH THHN INSULATION.

ALUMINUM CONDUCTORS SHALL BE ACCEPTABLE FOR FEEDERS ONLY;

CONTRACTOR IS RESPONSIBLE FOR SUBMITTING PROPOSED FEEDER

SCHEDULES AND VOLTAGE DROP CALCULATIONS FOR ALUMINUM

SUBSTITUTION.

25. MULTI-WIRE BRANCH CIRCUITS SHALL NOT BE PERMITTED UNLESS EXPLICITLY

CALLED OUT FOR INDIVIDUAL MANUFACTURER'S WRITTEN INSTALLATION

INSTRUCTIONS. PROVIDE A DEDICATED NEUTRAL FOR EACH BRANCH

CIRCUIT. WHERE MULTI-WIRE BRANCH CIRCUITS ARE REQUIRED, PROVIDE

MULTIPLE-POLE BREAKERS OR BREAKER TIE HANDLES TO SIMALTANEOUSLY

DISCONNECT ALL UNGROUNDED CONDUCTORS.

26. PROVIDE EMT CONDUIT HOMERUNS FOR GROUPS OF (12) BRANCH CIRCUITS;

LOCATE JUNCTION BOX IN CORRIDORS WITH ACCESSIBLE CEILINGS, IN CLOSE

PROXIMITY TO EQUIPMENT SERVED. FROM HOMERUN JUNCTION BOX TO THE

POINT OF USE, AC OR MC CABLE MAY BE USED IN NON-PATIENT AREAS.

27. COORDINATE SEQUENCE OF WORK TO AVOID CUTTING AND PATCHING IN NEW

WORK. ELECTRICAL CONTRACTOR SHALL UTILIZE RESPONSIBLE TRADES FOR

ALL PATCHING, FIRE STOPPING, AND RE-FINISHING. ALL PATCHING SHALL BE

OF THE SAME MATERIALS, WORKMANSHIP AND FINISH AS EXISTING AND

SHALL ACCURATELY MATCH ALL SURROUNDING WORK.

28. PROVIDE WRITTEN WARRANTY TO REPLACE ALL FAULTY MATERIALS AND/OR

CORRECT FAULTY INSTALLATION, AT NO COST TO OWNER INCLUDING PARTS

AND LABOR, FOR A PERIOD OF ONE (1) YEAR FROM DATE OF OWNER'S

WRITTEN ACCEPTANCE.

29. DAMAGE TO OTHER WORK: REPAIR ANY DAMAGE CAUSED BY DIVISION 16

CONTRACTOR TO WORK OF OTHER DIVISIONS. DAMAGE TO FIRE PROOFING:

REPAIR ANY DAMAGED FIRE PROOFING CAUSED BY DIVISION 16 CONTRACTOR

TO INTEGRITY OF ORIGINAL CONSTRUCTION.

30. UPON COMPLETION OF WORK, CONTRACTOR SHALL CLEAN AND REMOVE ALL

DEBRIS ASSOCIATED WITH HIS/HER WORK AND DISPOSE OF IT. ALL DISPOSAL

COSTS SHALL BE BORNE BY THE CONTRACTOR. AREA SHALL BE LEFT IN A

CONDITION ACCEPTABLE TO OWNER.

31. PROVIDE RED-LINED AS BUILT DRAWINGS AT THE CONCLUSION OF WORK.

32. INSTALLATION OF PULL BOXES & CONDUITS SHALL COMPLY WITH CEC

110.26(F)(1)(a) REQUIREMENT.

33. IN ACCORDANCE WITH 2013 CBC § 1117B.6, ITEM #5.1, INSTALLATION OF

CONTROLS AND SWITCHES INTENDED TO BE USED BY OCCUPANTS OF THE

ROOM OR AREA SHALL BE LOCATED NO MORE THAN 48", MEASURED FROM

THE TOP OF THE OUTLET BOX, AND NO LESS THAN 15", MEASURED FROM THE

BOTTOM OF THE OUTLET BOX.

34. IN ACCORDANCE WITH 2013 CBC § 1117B.6, ITEM #5.2, INSTALLATION OF

ELECTRICAL RECEPTACLE OUTLETS ON BRANCH CIRCUITS OF 30 AMPERES

OR LESS AND COMMUNICATION SYSTEM RECEPTACLES SHALL BE NO MORE

THAN 48", MEASURED FROM THE TOP OF THE RECEPTACLE OUTLET BOX OR

RECEPTACLE HOUSING, AND NO LESS THAN 15", MEASURED FROM THE

BOTTOM OF THE RECEPTACLE OUTLET BOX OR RECEPTACLE HOUSING, TO

THE LEVEL OF THE FINISHED FLOOR OR WORKING PLATFORM.

35. CONTRACTOR SHALL BE RESPONSIBLE FOR CONFORMING TO REQUIREMENTS

OF LEED MATRIX ADOPTED BY THIS PROJECT.

36. CONTRACTOR TO PROVIDE METHOD OF PROCEDURE (MOP) FOR ELECTRICAL

PANEL SHUTDOWNS.

E-0.0

ELECTRICAL

COVER SHEET

Q U A L I T Y A N D E X E L L E N C E

I N E N G I N E E R I N G A N D

D E S I G N S O L U T I O N S

1 8 6 7 2 F L O R I D A S T R E E T , U N I T 2 0 1 A

H U N T I N G T O N B E A C H , C A 9 2 6 4 8

P H O N E : 7 1 4 - 8 4 7 - 1 1 0 2

F A X : 7 1 4 - 2 4 2 - 9 4 9 9

ST

EA

M S

YS

TE

M B

OIL

ER

RE

PL

AC

EM

EN

T P

RO

JE

CT

40

32

S

. E

LL

ES

FO

RD

A

VE

NU

E

WE

ST

C

OV

IN

A, C

AL

IF

OR

NIA

9

17

92

RU

TH

R

IC

HA

RD

F

OO

D C

EN

TE

R

RO

WL

AN

D U

NIF

IE

D S

CH

OO

L D

IS

TR

IC

T

Page 2: SINGLE LINE DIAGRAM LEGEND SHEET DESCRIPTION SCALE …

1.01 DESCRIPTION

PART 1 - GENERAL

1.02 JOB CONDITIONS

1.05 MAINTENANCE MANUALS AND AS-BUILT DRAWINGS

PART 2 - PRODUCTS

2.01 GENERAL

1.04 SUBMITTALS

PART 4 - OTHER APPLICABLE SPECIFICATIONS

1.03 PRODUCT DELIVERY, STORAGE, AND HANDLING

2.02 MATERIALS

PART 3 - EXECUTION

3.01 INSTALLATION

E-1.0

ELECTRICAL

SPECIFICATIONS

Q U A L I T Y A N D E X E L L E N C E

I N E N G I N E E R I N G A N D

D E S I G N S O L U T I O N S

1 8 6 7 2 F L O R I D A S T R E E T , U N I T 2 0 1 A

H U N T I N G T O N B E A C H , C A 9 2 6 4 8

P H O N E : 7 1 4 - 8 4 7 - 1 1 0 2

F A X : 7 1 4 - 2 4 2 - 9 4 9 9

ST

EA

M S

YS

TE

M B

OIL

ER

RE

PL

AC

EM

EN

T P

RO

JE

CT

40

32

S

. E

LL

ES

FO

RD

A

VE

NU

E

WE

ST

C

OV

IN

A, C

AL

IF

OR

NIA

9

17

92

RU

TH

R

IC

HA

RD

F

OO

D C

EN

TE

R

RO

WL

AN

D U

NIF

IE

D S

CH

OO

L D

IS

TR

IC

T

Page 3: SINGLE LINE DIAGRAM LEGEND SHEET DESCRIPTION SCALE …

(E)BT-1

ST-1

TMV-1

RCP-1

(E)HW-1

(E)RCP-2

B-1

CT-1

M

(E)BFP

(E)METER

(E)FS

(E)FS

M

(E)RCP

(E)BRINE

TANK

SOFTNER

TANKS

ST-2

Q U A L I T Y A N D E X E L L E N C E

I N E N G I N E E R I N G A N D

D E S I G N S O L U T I O N S

1 8 6 7 2 F L O R I D A S T R E E T , U N I T 2 0 1 A

H U N T I N G T O N B E A C H , C A 9 2 6 4 8

P H O N E : 7 1 4 - 8 4 7 - 1 1 0 2

F A X : 7 1 4 - 2 4 2 - 9 4 9 9

ST

EA

M S

YS

TE

M B

OIL

ER

RE

PL

AC

EM

EN

T P

RO

JE

CT

4032 S

. E

LL

ES

FO

RD

A

VE

NU

E

WE

ST

C

OV

IN

A, C

AL

IF

OR

NIA

91792

RU

TH

R

IC

HA

RD

F

OO

D C

EN

TE

R

RO

WL

AN

D U

NIF

IE

D S

CH

OO

L D

IS

TR

IC

T

E-2.0

ELECTRICAL

POWER PLAN AND

PANEL SCHEDULE

1

ELECTRICAL POWER PLAN

1/2"=1'-0"

2

ELECTRICAL PANEL SCHEDULE

NTS