CARRIER ASIA CO., LTD. (SINGLE EFFECT HOT WATER TYPE) (SINGLE EFFECT STEAM TYPE) LITHIUM BROMIDE ABSORPTION CHILLER COOLING CAPACITY 527~2321 KW (16JL) 239~2321 KW (16JLR)

(SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

CARRIER ASIA CO., LTD.

(SINGLE EFFECT HOT WATER TYPE)

(SINGLE EFFECT STEAM TYPE)

LITHIUM BROMIDE ABSORPTION CHILLER

COOLING CAPACITY 527~2321 KW (16JL)239~2321 KW (16JLR)

cluk
Stamp
Page 2: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

Standard: 125 /105

: 105 / 95

: 95 / 80

Product specification

Single effect hot water absorption chiller

Absorption product code

Carrier makes the world a better place to live

by creating a comfortable, productive and

healthy environment regardless of climate.

It is our mission is to be customer’s first choice

for air conditioning, heating and refrigeration

solutions everywhere around the world.

Features/Benefits

Single Effect Cooling Cycle

Heat Source and Usage

Physical & Performance Data

Overall Dimension

Foundation Dimension

Thermal Insulation

Hoisting

Specification Scope

Wiring Diagram

Standard Tubing Flow

Water Quality Control

Great Hall of the People, Beijing, China

Kremlin, Moscow, Russia

White House, Washington, USA

Imperial Palace, Tokyo, Japan

Product specification

Single effect steam absorption chiller

Absorption product code

Inlet/outlet temperature of operating hot water

1

2

2

3

7

8

9

10

11

12

14

16

Page 3: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

Features / Benefits Features / Benefits

Environmentally Friendly ChillerUsing water and lithium bromide which are natural as refrigerant medium, no CFCs; Few moving parts enable quiet and vibration-free operation.

Cost-effective cooling alternative-energy chillerThe 16JL/JLR offers an alternative to avoid the high operating costs associated with electric-driven chillers. Fired by low pressure steam or hot water or waste heat, the 16JL/JLR not only reduces or eliminates elect-ric demand and/or reduce charges, but also allows the owner to take advantage of rebates and incentive programs offered by many utility companies.

Superior part load, low cooling water temperature (15°C) operation The standard concentration control system allows stable, part load operation at cooling water temperatures as low as 15°C without a cooling tower bypass with Carrier unique refrigerant management system (US patent: US6,260,364-B1), it has a continuous operating range from 100% to10% of machine capacity.

Automatic motorless purge system extends machine life, ensures optimum efficiency and performanceThe Carrier motorless purge system protects against the potential hazards caused by non-condensable gas produced continuously during machine operation, ensures long machine life and efficient operation.

Anti-crystallization controls maintain proper solution concentrationThe 16JL/JLR automatically limits solution concentration in several ways to avoid both crystallization and over-dilution to provide dependable, trouble-free operation.

Leak-proof hermetic pumps cut maintenance costsCarrier’s proven solution and refrigerant pumps are leak-proof, completely self-contained, and hermetically sealed. The hermetic design eliminates the need for a separate, complicated, and possibly leak-prone seal water system, while providing leak tightness and longer machine life.

Superior corrosion protectionThe 16JL/JLR incorporates a highly effective corrosion inhibitor to provide an extra margin of protection against internal corrosion.

Rugged machine constructionNon-clogging, corrosion-proof spray nozzles ensure against both corrosion and possible blockage for continuous, reliable operation. The 16JL/JLR is built to withstand the most rigorous duty, whether it is used for comfort cooling or light process applications.

Single point electrical connectionAll unitmounted electrical items are factory-wired to the chiller control center and require only a single point electrical connection to the machine from the building’s electrical service.

Page 4: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

Single Effect Cooling Cycle

condenser

generator

cooling water outlet

steam/hot water control valve

overflow tube

evaporator

coolingwater inlet

absorber

heat exchanger

liquidlevelswitch

chilled water

solution pump refrigerant pump

dilute lithium bromide solution

concentrated lithium bromide solution steam

chilled water cooling water refrigerant

The 16JL/JLR consists of evaporator, absorber, condenser, generator, solution heat exchanger, solution pump,

refrigerant pump, control system and other auxiliary system, etc.The operating principle of the chiller is: In highly

vacuum state, refrigerant water evaporate at a low temperature (4.4°C), which cool down chilled water circulating

in evaporator tube.

Refrigerant vapor generated in evaporator is absorbed by lithium bromide solution in absorber, which makes the

solution become dilute. Such dilute solution is fed into heat exchanger by solution pump, where the temperature

rises. After that, it enters generator, in which it is further heated and concentrated by steam or hot water. The

concentrated solution returns to the absorber after passing through heat exchanger for repeated use.In absorber

and evaporator, lithium bromide solution and refrig-erant water spray onto tubes of the heat exchangers to enhance

heat exchange effect.

Single Effect Cooling Cycle

Heat Source and Usage

Operating steam: gauge pressure 0.04~0.098MPa

(pressure after steam valve).

Operating hot water: Max. temperature 130 ,

Min. temperature 85 .

Heat Source and Usage

Page 5: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

oC

oC

1.The above cooling capacity is based on the following conditions: inlet/outlet temperature of chilled water: 12 /7 , cooling water: 32 /40 , operating steam pressure: 0.098Mpa, fouling factor (both chilled water and cooling water): 0.086m2. /kW. 2.Maximum waterside pressure of chilled water and cooling: 0.8MPa3.For the performance data under non-standard condition, please contact of Carrier Co. or its representative office. 4.This device could also be shipped in two pieces, please contact of Carrier Co. or its representative office for more details.

Physical & Performance Data

Steam pressure:

Chilled w

aterC

ooling water

Steam

Electric

Dim

ensionW

eight

16JL

USRt

104kcal/h

kW

m3/h

mH2O

kPa

A(mm)

m3/h

mH2O

kPa

A(mm)

Mpa

kg/h

A(mm)

A(mm)

V

kW

kW

kVA

mm

mm

mm

ton

ton

Model

Capacity

Inlet/Outlet Temp

Flow Rate

Pressure Drop

Pass No.

Pass No.

Connection Size

Inlet/Outlet Temp

Flow Rate

Pressure Drop

Connection Size

Absorber

Condenser

Inlet Pressure

Consumption

Steam Pipe Size

Drain Pipe Size

Power Supply

Refrigerant Pump

Solution Pump

Capacity

Length

Width

Height

Net Weight

Operating Weight

011

150

45

527.4

91

8.8

86.2

100

3

136

6.9

67.6

125

2

1

1146

125

40

0.4

2.6

4.5

3672

1417

2300

4

5.5

3Ø-380V-50Hz

12/7

32/40

0.098

013

180

54

632.88

109

9.5

93.1

100

3

163

8.1

79.4

125

2

1

1375.2

125

40

0.4

2.6

4.5

3672

1417

2300

4.3

6

015

210

64

738

127

8.9

87.2

125

3

190

5.6

54.9

150

2

1

1604

125

40

0.4

2.6

4.5

3724

1512

2573

6.0

8.1

018

240

73

844

145

9.0

88.2

125

3

217

6.4

62.7

150

2

1

1834

125

40

0.4

2.6

4.5

3724

1512

2573

6.5

8.5

021

280

85

984

169

6.0

58.8

150

2

253

8.2

80.4

200

2

1

2139

150

50

0.4

3.7

6.2

4777

1553

2639

7.5

10.5

024

330

100

1160

200

6.3

61.7

150

2

299

8.8

86.2

200

2

1

2521

150

50

0.4

3.7

6.2

4777

1553

2639

8.0

11.0

027

360

109

1266

218

6.2

60.8

150

2

326

9.7

95.1

200

2

1

2750

150

50

0.8

3.7

6.8

4854

1629

2904

9.0

12.5

030

400

121

1406

242

6.2

60.8

150

2

362

10.2

100.0

200

2

1

3056

150

50

0.8

3.7

6.8

4854

1629

2904

9.5

13.5

034

450

136

1582

272

6.2

60.8

200

2

407

8.8

86.2

250

2

1

3438

200

65

0.8

3.7

6.8

4875

1759

3106

10.5

14.5

038

500

151

1758

302

6.3

61.7

200

2

453

9.2

90.2

250

2

1

3820

200

65

0.8

3.7

6.8

4875

1759

3106

11.0

15.0

047

600

181

2110

363

7.2

70.6

200

2

543

7.3

71.5

300

2

1

4584

200

65

1.5

3.7

7.8

5640

2004

3464

16.0

21.0

052

660

200

2321

399

9.2

90.2

200

2

597

9.4

92.1

300

2

1

5042

200

65

1.5

3.7

7.8

6142

2004

3464

17.0

22.0

Physical & Performance Data

Page 6: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

1.The above cooling capacity is based on the following conditions: inlet/outlet temperature of chilled water: 12 /7 , cooling water: 32 /40 , inlet/outlet temperature of hot water:125 /105 , fouling factor (both chilled water and cooling water): 0.086m2. /kW. 2.Maximum waterside pressure of chilled water and cooling: 0.8MPa.3.For the performance data under non-standard condition, please contact of Carrier Co. or its representative office.4.This device could also be shipped in two pieces, please contact of Carrier Co. or its representative office for more details.

oC

oC

oC

Chilled w

aterC

ooling water

Hot W

aterE

lectricD

imension

Weight

16JL

USRt

104kcal/h

kW

m3/h

mH2O

kPa

A(mm)

m3/h

mH2O

kPa

A(mm)

m3/h

mH2O

kPa

A(mm)

V

kW

kW

kVA

mm

mm

mm

ton

ton

Model

Capacity

Inlet/Outlet Temp

Flow Rate

Pressure Drop

Pass No.

Pass No.

Connection Size

Inlet/Outlet Temp

Flow Rate

Pressure Drop

Pass No.

Connection Size

Inlet/Outlet Temp

Flow Rate

Pressure Drop

Connection Size

Absorber

Condenser

Power Supply

Refrigerant Pump

Solution Pump

Capacity

Length

Width

Height

Net Weight

Operating Weight

011

150

45

527

91

8.8

86.2

100

3

136

6.9

67.6

125

2

1

32

4.2

41.0

80

2

0.4

2.6

4.5

3672

1417

2300

4

5.5

3Ø-380V-50Hz

12/7

32/40

125/105

013

180

54

633

109

9.5

93.1

100

3

163

8.1

79.4

125

2

1

38

5.3

51.6

80

2

0.4

2.6

4.5

3672

1417

2300

4.3

6

015

210

64

738

127

8.9

87.2

125

3

190

5.6

54.9

150

2

1

44

9.6

94

80

4

0.4

2.6

4.5

3724

1512

2573

6.0

8.1

018

240

73

844

145

9.0

88.2

125

3

217

6.4

62.7

150

2

1

50

9.3

92

80

4

0.4

2.6

4.5

3724

1512

2573

6.5

8.5

021

280

85

984

169

6.0

58.8

150

2

253

8.2

80.4

200

2

1

59

6.4

63

100

3

0.4

3.7

6.15

4777

1553

2639

7.5

10.5

024

330

100

1160

200

6.3

61.7

150

2

299

8.8

86.2

200

2

1

69

7.3

71

100

3

0.4

3.7

6.15

4777

1553

2639

8.0

11.0

027

360

109

1266

218

6.2

60.8

150

2

326

9.7

95.1

200

2

1

76

7.1

70

100

3

0.8

3.7

6.75

4854

1629

2904

9.0

12.5

030

400

121

1406

242

6.2

60.8

150

2

362

10.2

100.0

200

2

1

84

6.9

67

100

3

0.8

3.7

6.75

4854

1629

2904

9.5

13.5

034

450

136

1582

272

6.2

60.8

200

2

407

8.8

86.2

250

2

1

95

5.7

56

125

3

0.8

3.7

6.75

4875

1759

3106

10.5

14.5

038

500

151

1758

302

6.3

61.7

200

2

453

9.2

90.2

250

2

1

105

5.9

57

125

3

0.8

3.7

6.75

4875

1759

3106

11.0

15.0

047

600

181

2110

363

7.2

70.6

200

2

543

7.3

71.5

300

2

1

126

7.8

77

125

3

1.5

3.7

7.8

5640

2004

3464

16.0

21.0

052

660

200

2321

399

9.2

90.2

200

2

597

9.4

92.1

300

2

1

139

9.5

93

125

3

1.5

3.7

7.8

6142

2004

3464

17.0

22.0

Physical & Performance Data Physical & Performance Data

Hot water temperature (inlet/outlet): / )

Page 7: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

oC

oC

oC

Chilled w

aterC

ooling water

Hot W

aterE

lectricD

imension

Weight

16JL

USRt

104kcal/h

kW

m3/h

mH2O

kPa

A(mm)

m3/h

mH2O

kPa

A(mm)

m3/h

mH2O

kPa

A(mm)

V

kW

kW

kVA

mm

mm

mm

ton

ton

Model

Capacity

Inlet/Outlet Temp

Flow Rate

Pressure Drop

Pass No.

Pass No.

Connection Size

Inlet/Outlet Temp

Flow Rate

Pressure Drop

Pass No.

Connection Size

Inlet/Outlet Temp

Flow Rate

Pressure Drop

Connection Size

Absorber

Condenser

Power Supply

Refrigerant Pump

Solution Pump

Capacity

Length

Width

Height

Net Weight

Operating Weight

011A

138

42

485

83

7.4

73.0

100

3

126

6.0

59

125

2

1

58

6.9

68

100

3

0.4

2.6

4.5

3672

1417

2300

4

5.5

3Ø-380V-50Hz

12/7

32/40

105/95

013A

166

50

582

100

8.0

78.8

100

3

151

6.9

68

125

2

1

70

7.4

73

100

3

0.4

2.6

4.5

3672

1417

2300

4.3

6

015A

193

58

679

117

7.5

73.8

125

3

176

4.8

47

150

2

1

82

13.6

133

100

3

0.4

2.6

4.5

3724

1512

2573

6

8.1

018A

221

67

776

134

7.6

74.7

125

3

201

5.5

54

150

2

1

93

13.2

129

100

3

0.4

2.6

4.5

3724

1512

2573

6.5

8.5

021A

258

78

906

156

5.1

49.8

150

2

234

7.0

69

200

2

1

109

6.5

64

125

2

0.4

3.7

6.15

4777

1553

2639

7.5

10.5

024A

304

92

1067

184

5.3

52.3

150

2

276

7.5

74

200

2

1

128

7.4

72

125

2

0.4

3.7

6.15

4777

1553

2639

8

11

027A

331

100

1164

200

5.2

51.4

150

2

301

8.3

81

200

2

1

140

7.3

71

125

2

0.8

3.7

6.75

4854

1629

2904

9

12.5

030A

368

111

1294

223

5.2

51.4

150

2

335

8.7

86

200

2

1

156

7.0

69

125

2

0.8

3.7

6.75

4854

1629

2904

9.5

13.5

034A

414

125

1456

250

5.2

51.4

200

2

377

7.5

74

250

2

1

175

5.8

57

150

2

0.8

3.7

6.75

4875

1759

3106

10.5

14.5

038A

460

139

1617

278

5.3

52.3

200

2

419

7.9

77

250

2

1

195

6.0

58

150

2

0.8

3.7

6.75

4875

1759

3106

11

15

047A

552

167

1941

334

6.1

59.7

200

2

502

6.2

61

300

2

1

233

8.0

78

200

2

1.5

3.7

7.8

5640

2004

3464

16

21

052A

607

184

2135

367

7.8

76.3

200

2

553

8.0

79

300

2

1

257

9.7

95

200

2

1.5

3.7

7.8

6142

2004

3464

17

22

Physical & Performance Data Physical & Performance Data

Hot water temperature (inlet/outlet): / )

1.The above cooling capacity is based on the following conditions: inlet/outlet temperature of chilled water: 12 /7 , cooling water: 32 /40 , inlet/outlet temperature of hot water:105 /95 , fouling factor (both chilled water and cooling water): 0.086m2. /kW. 2.Maximum waterside pressure of chilled water and cooling: 0.8MPa.3.For the performance data under non-standard condition, please contact of Carrier Co. or its representative office.4.This device could also be shipped in two pieces, please contact of Carrier Co. or its representative office for more details.

Page 8: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

Hot water temperature (inlet/outlet): / )

oC

oC

oC

Chilled w

aterC

ooling water

Hot W

aterE

lectricD

imension

Weight

16JL

USRt

104kcal/h

kW

m3/h

mH2O

kPa

A(mm)

m3/h

mH2O

kPa

A(mm)

m3/h

mH2O

kPa

A(mm)

V

kW

kW

kVA

mm

mm

mm

ton

ton

Model

Capacity

Inlet/Outlet Temp

Flow Rate

Pressure Drop

Pass No.

Pass No.

Connection Size

Inlet/Outlet Temp

Flow Rate

Pressure Drop

Pass No.

Connection Size

Inlet/Outlet Temp

Flow Rate

Pressure Drop

Connection Size

Absorber

Condenser

Power Supply

Refrigerant Pump

Solution Pump

Capacity

Length

Width

Height

Net Weight

Operating Weight

011B

75

23

264

12/7

45

5.9

57.8

80

4

71

10.2

100

100

4

2

95/80

23

2.6

26

65

4

3Ø-380V-50Hz

0.4

2.6

4.5

3672

1417

2300

4

5.5

3Ø-380V-50Hz

12/7

32/40

105/95

013B

90

27

316

54

6.5

63.7

80

4

85

10.5

103

100

4

2

27

2.6

26

65

4

0.4

2.6

4.5

3672

1417

2300

4.3

6

015B

105

32

369

64

5.60

54.9

100

4

32/40

99

7.8

76

125

4

2

32

4.8

47

80

4

0.4

2.6

4.5

3724

1512

2573

6

8.1

018B

120

36

422

73

5.80

56.8

100

4

113

7.9

77

125

4

2

36

4.7

46

80

4

0.4

2.6

4.5

3724

1512

2573

6.5

8.5

021B

140

42

492

85

11.30

110.7

125

4

132

9.6

94

150

3

2

42

7.8

77

100

4

0.4

3.7

6.15

4777

1553

2639

7.5

10.5

024B

165

50

580

100

11.50

112.7

125

4

156

9.9

97

150

3

2

50

8.9

87

100

4

0.4

3.7

6.15

4777

1553

2639

8

11

027B

180

54

633

109

11.20

109.8

125

4

170

10.4

102

150

3

2

54

8.7

86

100

4

0.8

3.7

6.75

4854

1629

2904

9

12.5

030B

200

60

703

121

10.90

106.8

125

4

189

10.5

103

150

3

2

60

8.4

83

100

4

0.8

3.7

6.75

4854

1629

2904

9.5

13.5

034B

225

68

791

136

11.90

116.6

150

4

212

10.1

99

200

3

2

68

7.0

69

100

4

0.8

3.7

6.75

4875

1759

3106

10.5

14.5

038B

250

76

879

151

11.90

116.6

150

4

236

10.2

100

200

3

2

76

7.2

70

100

4

0.8

3.7

6.75

4875

1759

3106

11

15

047B

300

91

1055

181

6.10

59.8

150

3

283

7.5

74

200

3

2

91

9.6

94

125

4

1.5

3.7

7.8

5640

2004

3464

16

21

052B

330

100

1160

200

7.90

77.4

150

3

312

9.7

95

200

3

2

100

11.6

114

125

4

1.5

3.7

7.8

6142

2004

3464

17

22

Physical & Performance Data Physical & Performance Data

1.The above cooling capacity is based on the following conditions: inlet/outlet temperature of chilled water: 12 /7 , cooling water: 32 /40 , inlet/outlet temperature of hot water:95 /80 , fouling factor (both chilled water and cooling water): 0.086m2. /kW. 2.Maximum waterside pressure of chilled water and cooling: 0.8MPa.3.For the performance data under non-standard condition, please contact of Carrier Co. or its representative office.4.This device could also be shipped in two pieces, please contact of Carrier Co. or its representative office for more details.

Page 9: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

Note:

1. cooling water inlet, steam inlet, hot water inlet shall be located at the front left side.

2. Standard chilled water inlet is located at the left side. Right inlet is optional.

3. Minimum space around chiller shall be

“L”m from the chiller in length direction

0.2m from the top of the chiller

1m from the front side of the chiller (beside the control panel)

0.5m from other parts of the chiller

Overall Dimension Overall Dimension

hot water/steam inlet

cooling water outlet

two flow pathshot water/steam outlet

two flow pathschilled wateroutlet

chilled water inlet

two flow pathschilled water outlet

three flow paths

three flow paths

hot water/steam outlet

chilled water outlet

cooling water inlet

16JL / JLR011~052

16JL/JLR

L

W

H

A

G

C

D

I

O

N

E

I

P

K

B

J

M

011013

3672

1417

2300

1453

743

1625

1636

828

750

1978

1635

828

1392

1033

1635

836

1850

015018

3724

1512

2573

1456

804

1914

1672

1016

751

2346

1734

1016

1503

1108

1893

988

1950

021024

027030

034038 047 052

(mm)

Length Width H

eightC

ooling Water

Chilled W

aterS

team(H

ot Water)

Position

4777

1553

2639

1896

990

2178

2187

1080

710

2352

2196

1080

1500

1174

2141

1082

1950

4854

1629

2904

1899

1300

2203

2214

1410

825

2627

2253

1410

1684

1320

2156

1375

2200

4875

1759

3106

1899

1100

2206

2229

1308

845

2816

2206

1308

1806

1358

2154

1305

2300

5640

2004

3464

2174

1600

2526

2554

1729

770

3147

2522

1729

1910

1424

2442

1748

2468

6142

2004

3464

2423

1600

2763

2803

1729

770

3147

2787

1729

1910

1424

2691

1748

2468

Page 10: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

16JL/JLR011/013

16JL/JLR015/018

16JL/JLR021/024

16JL/JLR027/030

16JL/JLR034/038

16JL/JLR047

16JL/JLR052

A B C D E F G H I J K

(mm)

Foundation Dimension

Tube cleaning length

Note: See detail figure A

4-M20foundationbolt

Drain

Embedded cable conduit

Drains are set at periphery of the chiller

Detail Figure A

Technical requirements: 1. Foundation load bearing capacity of the chiller is designed subject to weight load of the chiller. 2. Foundation levelness is controlled within 1/1000. 3. Square holes in foundation are used to fix foundation bolts. After the chiller is positioned in place, mortar is poured along the slope at one side of the square hole to fix foundation bolts.4. Shaded portion and square hole represents base corner and foundation bolt hole of the chiller respectively. 5. Space for tube drawing lengthwise may be set at the other side of the chiller. 6. Values in brackets are reference values.

Model

Foundation Dimension

2906

2918

3792

3798

3798

4348

4846

3500

3500

4500

4500

4500

4700

5700

150

150

300

300

300

300

300

1277

1280

1646

1649

1649

1924

2173

350

350

500

500

500

500

500

2628

2634

3292

3298

3298

3848

4346

520

600

700

900

900

1000

1000

420

500

600

800

800

900

900

371.5

450

495

650

550

800

800

671.5

750

795

750

650

800

800

3328

3334

4292

4298

4298

4848

5346

Page 11: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

Note:

Material request for high temperature area: glass fibre, asbestos or other similar.

Material request for low temperature area: cellular polyethylene or other similar.

Note: After installation and commissioning is completed, thermal insulation shall be made for the chiller to reduce energy loss, improve operating environment and achieve a longer service life. Thermal insulating material shall not be inflammable, water absorbent or air permeable. Thermal insulation for water box shall facilitate opening/closing of water header during maintenance of tube.

(m2)

011/013

10.3

6.3

015/018

11.5

7

021/024

13.6

8.8

027/030

15.9

9.3

034/038

17.2

10.9

047

21.4

17.2

052

23.6

17.5

Thermal Insulation

50mm thick thermal insulating material: water box and water header of generator

25mm thick thermal insulating material: steam condensate tube, steam condensate heat exchanger

20mm thick thermal insulating material: evaporator body, tube plate of evaporator

10mm thick thermal insulating material: water header of evaporator, refrigerant pump piping

Control panel and motors of solution pump and refrigerant pump do not require thermal insulation. Joint of the thermal insulating material shall be sealed with tape to avoid dampness.Bond should be used in installation of thermal insulation . Welding is strictly prohibited.Thickness and area of insulating material is shown in the following table.

Thermal insulation area

Area

High temp area

Low temp area

Thermal Insulation

High temperature area:

Low temperature area:

Page 12: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

HoistingHoisting

Single piece installation

Two-piece installation

Note: In actual situation, please conduct hoisting according

to the hoisting marks adhered to the chiller

Model 021

Length mm 4777

Width mm 1553

Single

piece

Height mm 2639

Shipping weight t 7.5 8

Operating weight t

011

3672

1417

2300

4

5.5

013

4.3

6

015

3724

1512

2573

6

8.1

018

6.5

8.5 10.5

024

11

027

4854

1629

2904

9

12.5

030

9.5

13.5

034

4875

1759

3106

10.5

14.5

038

11

15

047

5640

2004

3464

16

21

052

6142

2004

3464

17

22

Page 13: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

Specification Scope

Standard Option

Flow Rate ARI, GB & JIS(0.605m3/h.RT) Standard 50 ~ 120% Flow Rate

Ent/Lev Temperature 12 /7 or 54F/44F Leav. Temperature=5~15

Fouling Factor < 0.086 m2. /kW > 0.086 m2. /kW

Max Pressure 10 barG (1.0Mpa) 16 or 20 bar

Water Quality Fresh Water Sea Water or Brine(Ethyleneglycol)

Flow Rate ARI, GB & JIS Standard 50 ~ 120% Flow Rate

Ent/Lev Temperature 32 /40 15 ~ 35 (Pls contact to Carrier if any special requirements)

Fouling Factor < 0.086 m2. /kW > 0.086 m2. /kW

Max Pressure 10 barG (1.0Mpa) 16 or 20 bar

Water Quality Fresh Water Sea Water or Brine(Ethyleneglycol)

Flow Rate See a Physical & Performance data sheet 50 ~ 120% Flow Rate

Steam Pressure 1.0 barG (0.98Mpa)

Hot Water Temperature See a Physical & Performance data sheet

Fouling Factor Below 0.086 m2. /kW Above 0.086 m2. /kW

Max Pressure 10 barG (1.0Mpa) 16 or 20 bar

Power Supply Voltage x Hz x Ph 380V x 50Hz x 3Ph 220V, 400V, 440V, 460V / 60Hz

Control Panel Type PLC Weather Proof or Explosion Type

Type Electric Actuator Auto-Spring Return or Pneumatic Actuator

Control Signal 4 - 20mA 0 - 10dV

Capacity Range 10 - 100%

Low Chilled Water Temperature Switch

Low Chilled Water Flow Switch Cooling Water Flow, Flow Switch

High Temperature Switch @Generator

High motor Temp. and Current of Sol. & Ref. Pump

Painting Color Carrier Green Gary Pls contact to Carrier if any special requirement

Auto-Purging

Purge Chamber, Vacuum Pump and Manometer Pd-Cell

Heat Transfer Tube Copper Nickel(90:10 & 70:30)

A/C & E Titanium for Sea Water

Code GB Standard CE, UL or PED, ASME (pls contact to Carrier)

Shipping 1-Piece 2-Piece

Thermal insulation Job Site Factory Insulation

Safety Device

Copper Tube

Chilled Water

Cooling Water

Item

Steam or Hot WaterPls contact to Carrier if any special requirement

Purge System

Control Valve

, 85F/104F

Specification Scope

Page 14: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

Wiring DiagramWiring Diagram

Page 15: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

Wiring DiagramWiring Diagram

Page 16: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

1.Equipment supplied by Carrier is within the scope of “ ” in flow chart.

2.Please fit thermometer and pressure gauge at inlet/outlet of water tube where it is convenient to observe.

3.Each chiller shall be configured with independent chilled water pump and cooling water pump.

4.Positions of chilled water pump and cooling water pump and expansion tank shall take account of water level difference and static pressure to ensure

the gauge pressure of the chiller does not exceed 0.8MPa.

5.Chilled water and cooling water flow shall meet the specification. It is also allowed to install a flow meter on chilled water tube for the convenience of

operation control.

6.If cooling water inlet temperature tends to decrease to below 15 , a bypass valve shall be installed at the place where it is indicated with dashed line

to maintain such temperature higher than 15 .

7.If steam pressure (gauge pressure) exceeds 0.098MPa (inlet pressure of the chiller), a relief valve shall be installed at the place indicated in the figure.

vapor bleed valve vapor bleed valverelief valve

steam

steam block drain valve

steam control valve

condenser

generatordrain

absorber evaporator

cooling tower

drain valvemakeup water

bypass valve

vapor bleed valve

expansion tank

air conditioner

filterover 10 meshes/inch

chilled water pump

drain

drain

drain

filterover 10 meshes/inch

Legend Thermometer

Pressure gauge

Valve

chiller

boiler drainedwater tank

steam trap

Description of standard tubing flow:

chilled water pump

Standard Tubing FlowStandard Tubing Flow

Page 17: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

Standard Tubing FlowStandard Tubing Flow

8.A steam control valve shall be installed in front of 16JL chiller (such steam valve is supplied by Carrier ). Pressure gauges with a range of 0~0.2MPa

shall be installed in front of and behind steam control valve respectively. To facilitate detection and maintenance, it is recommended to install bypass

line fitted with manual valve at the place of steam control valve.

9.A hot water control valve shall be installed in front of 16JLR chiller (such hot water valve is supplied by Carrier ). Pressure gauges with a range of

0~0.8MPa shall be installed in front of and behind hot water control valve respectively. To facilitate detection and maintenance, it is recommended to

install bypass line fitted with manual valve at the place of hot water control valve.

10.If temperature of steam or hot water exceeds 130°C, measures shall be taken to reduce the temperature.

11.Flange of chilled water, cooling water and steam (or hot water ) tube (single piece) connected with the chiller shall be supplied by Carrier Flange

connected with the field piping shall be provide by customer.

Description of standard tubing flow:

vapor bleed valve vapor bleed valve

drain

cooling tower

drain valvemakeup water

bypass valve

vapor bleed valve

expansion tank

air conditioner

drain

drain

drain

hot water pump filterover 10 meshes/inch

chiller

Legend Thermometer

Pressure gauge

Valve

hot water control valve

condenser

generator

absorber evaporator

filterover 10 meshes/inch

chilled water pump

chilled water pump

Page 18: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

Water quality control is a key point of maintenance for chiller. Problem such as dirt, sludge or corrosion may occur

due to poor water quality. In addition, water quality of the same source will change along with time change (refer to the

following table). For example, when cooling water flows through cooling tower, water content may be lost and evapora-

ted into atmosphere. Cooling water gradually becomes concentrated and deteriorated. Cooling water quality degradat-

ion may cause corrosion and scaling, which will lead to attenuation of refrigeration capacity of chiller and failures, such

as corrosion of heat transfer tube. Therefore, water quality shall be controlled properly, such as setting drainage facility

and adding water on a regular basis. Better effect will be obtained if appropriate water treatment additive is available.

The following table shows relevant water quality benchmarks for chiller for reference.

Note: “ ” mark in the column indicates relevant factor prone to corrosion or scale

Chlorine ion

Quality benchmarks for chilled water, cooling water and makeup water

Item

Cooling water systemChilled water system Trend

Circulation type Direct flow

Makeup water Circulating water Makeup water Direct flow water

Cannot be detected

ScaleCorrosion

Benchm

ark itemR

eference item

Conductivity

Sulfate ion

Acidconsumption

Full hardness

Calcium carbonate hardnessIon state silicon dioxide

Iron

Copper

Sulfur ion

Ammonium ion

Residual chlorine

Free carbon

Stability index

Water Quality ControlWater Quality Control

Page 19: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

Quality benchmarks for chilled water, cooling water and makeup water

Conductivity

ItemTrend

Benchm

ark itemR

eference item

Corrosion ScaleHot water Makeup water

Iron

Copper

Sulfur ion

Ammonium ion

Residual chlorine

Free carbon

Stability index

Chlorine ion

Sulfate ion

Acid consumption

Full hardness

Calcium carbonate hardness

Ion state silicon dioxide

Water Quality ControlWater Quality Control

Note: “ ” mark in the column indicates relevant factor prone to corrosion or scale

Page 20: (SINGLE EFFECT STEAM TYPE) (SINGLE EFFECT HOT ... - CARRIER

T-16JL/R-0710-01(E)-CHK

cluk